HomeMy WebLinkAboutRESPONSE TO PERMIT COMMENTSit y leering solu!icns" StLuc�eCourmr November 18, 2015 Don Bergman Architecture LL Bergman Associates 4362 Gator Trace Lane Ft. Pierce, Florida 34982 772-708-0164c hobieone(a bellsouth.net Re: Becker Househol Project Number 1 5037.00 Permit No.: 150 -0127 Subject: Response to Pe mit Comments RECEIVED NOV 2 3 1015 ENVIRONMENTAL RESOURCES Dear Mr. Bergman: Ingenuity Engineers, Inc., is in receipt of permit comments for the above named project. We have reviewed the comments v ith respect to our disciplines and have the following responses: MECHANICAL: I Comment: Please list approved material for condensation line. Response: Will comply, s e revised sheet M-0.1. Comment: Note 8, Page M2.0 requires "Exposed spiral single wall snap lock paint grip ductwork". Pla s indicated spiral ductwork, not snap lock. Response: Note 8 revise , see revised sheet M2.0. Comment: Please submi hanger detail for exposed ductwork. Response: Will comply, see revised sheet M-4.2. Comment: FCU #2 is rat, d for 1600 CFM. Total on plans adds up to 1800 CFM. Response: Schedule remised to match floor plan cfm. See revised sheet M3.1. PLUMBING: Fv ingenuity engineers, inc. 4798 new broad street. suite 300. oriando. florida 32814 . phone: 407. 398.6007 fax: 407.398.6003 C.A. #26308 Becker Household November 18, 2015 115037.00 Page 2 of 2 Comment: This is an occupan y classification change from residential to assembly and business. Per Secti n 1012.8 of the Florida Existing Building Code, this building now has to meet the requirements of the 2014 Florida Plumbing Code. Response: Will comply, see revised floor plan sheets. Comment: This is an occupancy classification change from residential to assembly and business. Per Sec ion 1010 of the 2014 Florida Existing Building Code, this building now has to meet the requirements of the 2014 Florida Accessibility ode. , Response: Will comply, see r vised floor plan sheets. Comment: Per Section 403. of the 2014 Florida Plumbing Code, this building is now required to have s parate sex restrooms. Response: Will comply, see evised floor plan sheets. Comment: Per Table 403.1 o the 2014 Florida Plumbing Code and Section 211 of the 2014 Florida Accessibi ity, this building is now required to have a Hi-Lo drinking fountain. Response: Will comply, see revised floor plan sheets. Comment: Per Table 403.1 f the 2014 Florida Plumbing Code, this building is ow required to have a service sink. Response: Will comply, see revised floor plan sheets. If there are any additional questions or comments, please feel free to contact us. Sincerely, 4-v- - Brian S. Hessinger, PE, LEED AP Chief Operating Officer RECEIVED NOV 2 3 2015 ENVIRONMENTAL RESOURCES ingenuity engineers, inc. 4798 new broad street. suite 300. orlando. florida 32814 • phone: 407.398.6007 fax: 407.398.6003 C.A. #26308 aB Don Bergman Architecture, LLC. Lic. # AA 26002432 23 lS •. MEMORAND TO St. Lucie C 'unty SUBJECT Permit #1108-0127 Building Dopt St. Lucie County Becker House FROM Don Ber DATE 11.23.15 We are in receipt of Bu responses: 1. Please show in load requirem( II. - R: 2. 3. 4. 5. P.O. Box 13537 Fort Pierce, FL 34979-3537 4362 Gator Trace Lane Fort Pierce, FL 34982 T:772.466.5832 Q 772.708.0164 Please not lev R: Please show c R: Please show c R: Please show/ Snack Bar? Ai R: A sleeping are R: NO. 15-012 Dept. comments and have reviewed them and offer the following )esign Criteria block separate occupancy areas with associated occupancy Its. See revised Dimensional Control Floor Plan, Sheet A-1.0 alteration/change of occupancy in Design Criteria See revised Dimensional Control Floor Plan, Sheet A-1.0, and revised Garage Floor Plan, Sheet A-1.1. iphance with FBC Accessibility for all door widths, new and existing. See revised Dimensional Control Floor Plan and revised Life Safety Floor Plan, sheets A-1.0 and LS-1.0 for minimum clear floor areas at new and existing doors. iphance with FBC Accessibility for all door hardware, new and existing. New and existing door harware shall comply with applicable portions of FBC Accessibility Section 404. scribe use of the Kitchen. Is this a commercial kitchen with any seating? cooking? See revised Dimensional Control Floor Plan, Sheet A-1.0. Room title changed to "Staff Breakroom" to reflect its proposed use. No cooking will occur in this space. a cannot open into a Garage, per FBC R302.5.1. See revised Garage Floor Plan, Sheet A-1.1. RECEIVED NOV 2 3 2015 ENVIRONMENTAL RESOURCES