Loading...
HomeMy WebLinkAboutENGINEERING POOL ENCLOSURE1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". SGANNED 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS BY (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. aq Lucie®untv 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. E WOOD DECK IS P E ENT SE 1/4"X3 1/2" GALV LAG CONCRETE & FOUNDATION DESIGN: 3. WHER R S U - 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE SPECIFIED. REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST APPLICABLE: A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS FOLLOWING COMPONENTS: B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT I. PORTLAND CEMENT TYPE 1 - ASTM C 150 24" O.C. AND 6" FROM ENDS. II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK III. AIR ENTRAINING +/- 1 % - ASTM C 260 SCREW AT 24" O.C. AND 6" FROM ENDS IV. WATER REDUCING AGENT - ASTM C 494 D. WHERE 1'X2" INSTALLED THROUGHOUT AN "OPEN VIEW" V. CLEAN POTABLE WATER SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS VI. OTHER ADMIXTURES NOT PERMITTED MASONRY SPECIFICATIONS: B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD II. WELDED WIRE FABRIC - ASTM A185 HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED C.-CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" ON TYPE M OR S MORTAR. OR MORE THAN 5"-WATER ADDED-AF-T-E-R-BATC.HING IS NOT 2. ALL MORTAR SHALL BE TYPE M OR S. PERMITTED. --3. AL-L-GROU-T-SHALL-BE 2000 PSI MINIMUM AND HAVE D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE MAXIMUM COARSE AGGR GE ATE SIZE-OF-3/8"- - --- - ---- - INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING INCLUDING HOT WHEATHER RECOMMENDATIONS. REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. HEIGHT. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE MISCELLANEOUS: ///// w\ i o ST. LL�C COUI TI RU _ . Dmsioti' ��- RFVLF��'r.D FOR COS LI '. CE :� o o p'; w a RE111E`IVED pY DATE -79l = w o w = (D o z _ U 00 PLANS AND PERNIIT MPST _ Q BE KEPT ON JOB - o ' -O = M Olt NO INSPECTION WILL BE ?NIA E. w rrrrlllllll O Co U a 8 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. FBC. (CATEGORY 2 ROOMS ONLY) 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC BARRIER. (CATEGORY 2 ROOMS ONLY) R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO FROM STRUCTURAL CRACKING, SPALLING & OTHER ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE THE FIELD. VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, GROUT WITH BONDING AGENT. DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED (OR EQUAL) TYP. ALL LOCATIONS. STRUCTURE. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED. EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ RESPONSIBILITIES: NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 1. ALL SITE WORK SHALL BE PERFORMED B`! A LISCENED 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING NOTED. CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. LEGEND: (ALL MAY NOT APPL SCR = SCREEN KP = KICK PLATE PW = PICTURE WINDOW X = HORIZ. SLIDING WINDOW O = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP = SOLID INSULATED PANEL CT = CABLE TIE SG = SUPER GUTTER CS = CLEAR SPAN KB = KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW-SE-C-T-I O 2 x 2: 2"x2"x0.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"x0.044" 2 x 5: 2"x5"x0.050" OPEN BACK SECTIONS 1 x 2: 1 "x2"x0.044" 1 x 3: 1 "x3"0.044" SNAP SECTIONS 2 x 2 SNAP: 2"x2"0.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"4.045" THESE PLANS p NlD taLL PPOPOSED WORK - ARE SUBJECT 10 ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NE058-ARY IN ORDER TO COMPLY WITH AU APpUC_A110 CODBS, C0 NI C U LEh ARC NSISILIT' OF THE, FONT CTOR OF RECORD SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"x6"0.050"4.120" 2 x 7 SMB: 2"x7"0.057"0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"x0.092"4.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICAT IN INCHES. RECEIVE® MAY 16 2018 a WALL HEIGHT PER PLAN --moo O O �m o I I A � 0 `\ \`\ m 9 I A I o I I \ m I I I \ y 6 V2X5SMB 6 2X5SMB N X n w w ] O 2X5SMB y 6 2X5SMB I' O 3X2 02 X -n w won. mo. cn0 Xm: U) .• . Do m�' r-' 2� ao �O X —� 00 cnm c7lo W O w D DZ 0 Z w X N --I / / / / / / / / / / / / / / / I I I I I I I I I I I I 21'-8" 6'-6"---16-6"---� 1X3 i 2X3 TYP. W 2X3 N W W WL W 1X3 W �X3 TYP. 00 " 1 7'-3 4 L? o �yA 2X6SMB 6 a 4 n ,- � O -5 v O co m m o CONTRACTOR: m 0 KRUGER CONSTRUCTION zz zz o CORP. N t -D-I m z � o O No V � w PROJECT ADDRESS: CD CD o BACCI 114 QUEENS BESS CT, D IV m FORT PIERCE, FL 2X6SMB 3X2 TYP. 6'-111" 4 UNDER TRUSS :31UI=��■ i i 12X6SMB 1" 5'-6 1-6-6 2.' 6-6 2"� X w 2 O O� O_ in c C) G) c m X 3X2 TYP. 1X3 TYP. OT O N � � m M W m 2X3 TYP. 13'-0" - I FLORIDA ENGINEERING LLC 4456 TAMIAMI TRAIL, UNIT B14 PORT CHARLOTTE, FLORIDA 33980 (941) 391-5980 www.flengineeringllc.com PROJECT NO. 1807506-2 �Z 0 z R. cn - C n p �% � X o n m ~` < m 0 �m i mo zM rn mD c r- U m 0 -n --n 0 n O G7 5 - UND,�� // < .���\ Q�G •''� GENS'F�cS' ��'% No. 60102 !� " STATE OF :�ir NZ Fs o C aig E. Gunderson, P.E. #60102 CA CERT. #30782 DA lO/lO/2018 WALL HEIGHT PER PLAN--{—^ 0 — •O 3� A \ I T I I I \ I I I 8'-0' 0 0 0 Fo \ 3X2 `� \ \ O X w w \ \ \ 2X5SMB i I I I � I � I � I o NIA I = I I I 2X5SM B � w w w M = I I 2X5SMB N \3X2 O 1-1 3'-0" u " " --6'-10 8--{--6'-10 $--+--6'-10 $ —�---� 1'-11"r 6'-6"—6'-6"� 2X3 I 1X3 1X3 02 N 2X3 N 2X3 O wZ2Xccn � w w w w w p0. 1X3 00 1X3 20'-7" 3X2 I I N I X I X w X w I w N w 2X6S M B I 1" I 18'q�2 2 O Fv �X I �w I I I I 10 2X6S M B I _ O i C I w � O C I i --I I 2X6SMB N N I w X i w N I X I w I 3X2 l�. I o0 % X O j\2X3 1X3 -11 >X, � O r� O j X o Oho 2X3 w m UNDER TRUSS -n wo w Fa I -I mo m- ZzX 4t O0 m 0O D —I00 • �W 2 cn� I 1X3 V f- 5'-6 2 --f-7'-5 2 -i 6 Q � m FLORIDA ENGINEERING LLC 4456 TAMIAMI TRAIL, UNIT B14 PORT CHARLOTTE, FLORIDA 33980 (941) 391-5980 www.fiengineeringllc.com 1807506 CA CERT. #30782 IGUND,,,,,, ` No. 60102 cc tr -;3 STATE OF 'O :raig E. Gunderson, P.E. #60102 ATE: 06/27/2018 SELF -MATING OR i 1/8'W'W"4" ANGL _ SNAP SECTION TYP. - 1/8"x2"x2" ANGLE 2 - #12 SMS INTO COLUMN 1"x3" O.B. BASE PLATE-TYP. 0 0 2-1/4" x 1/4" MASONRY ANCHOR 3/8" x 4" TAPCON 0 0 1-1/." MIN. CONC. ANCHOR EMBEDMENT MIN 4" SLAB 3000 PSI 2" MIN. INCREASE DISTANCE CONC. w/FIBERMESH WHEN GREATER THAN 2x4 UPRIGHT IS USED ....... ... w CONC. FOOTING BELOW SIDE VIEW NOTE WHERE PAVERS ARE PRESENT USE 5/16" TAPCON XL (RED HEAD MFG.) MASONRY ANCHORS TO PENETRATE UNDERLYING CONCRETE FOOTING 2-1/4" (MIN.) 2 - #12 SMS 3/8" x 4" TAPCON 2 @ SLAB (BEYOND) 2-1/4" X 1/4" TAPCON 2 @ lx3 BASE 1"x3" BASE PLATE ANCHORED TO CONC w/ 1/4" MASONRY ANCHOR V MAX EACH SIDE OF POST AND 24" O.C. MAX CONC. FOOTING BELOW FRONT VIEW DETAIL "B" - 2"x4" OR LARGER SELF MATING UPRIGHT TO DECK DETAILS SCALE: NTS 2x2x3 ANGLE W/ (3) #14 TEKS EACH SIDE 2x2x125 ANGLE W/ (4) #14x3/4" TEKS EACH SIDE elrel:7rz rIL•\Ito]:�9SUa:l.] 2x2xl/8 ANGLE EAVE RAIL TO POST W/ (6) #14 EA. CLIP 0 0 0 0 0 0 0 BEAM PER PLAN NOTCHED TO RECEIVE COLUMN WITHIN 2X2X.125 ANGLE W/ (4) #14 TEKS COLUMN PER PLANS DETAIL E - UPRIGHT TO BEAM CONNECTION SCALE: NTS BEAM INSTALL BF TO CORNE NOTE' BR HAVE 2" TC FROM COB 1-1/2"x2x.062 RECEIVER CHANNEL W/ (4) #12x3/4" TEKS EACH SIDE (TYP.) (4) #10xl112" SMS INTO SCREW BOSSES )GE MEMBER :Z PURLIN PURLIN MEMBER DETAIL "D" - ROOF BRACING CONNECTION DETAL SCALE: NTS FASTEN TOP OF HEADER TO INTERSECTING 2"x3" MEMBER w/(2) #10 SMS w/1" PENETRATION INTO SCREW BOSS OF 2"x3" MEMBER - TYP. BOTH SIDES I II II II 2"x3" DOOR JAMB TII--11- o I II - 0 II III II II II IIII II II _ ---------------------------------- - II �I - 91 I II u II a it Ii WHEN Z-BAR IS USED - FASTEN II u li Z-BAR TO COUHEADER AT EACH II II CORNER AND 18" O/C II II 2x2x.125 ANGLE W/ (2) #10 SMS INTO COL. & 3/8" x 2" TAPCON THRU BASEPLATE INTO CONCRETE 1-1/2" (MIN.) EMBEDMENT ALTERNATE BASE PLATE CONNECTION ATTACH 2"x3" TO BASE PLATE (INTERNAL) w/(2) #10x2" SMS ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL w/(4) #10X3/4" INTO GIRT OR PURLIN & (4) #14x3/4" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED UPRIGHT, BEAM -SNAP, SELF MATING, OR HOLLOW DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: NTS 2"x2"x.063" - DIM. TO MATCH PURLIN SIZE RECEIVING CHANNEL (4) #12 SMS INTERNAL TO EAVE RAIL (2) #12 EACH SIDE INTO PURLIN 0 EAVE RAIL- 3x2 0 2x2x125ANGLE lX3 OPEN EXTRUSION i UPRIGHT W/ (4) #14�C3/4" TEKS EACH SIDE I i 2x2x1/8 ANGLE EAVE RAIL T POST W/ (6) #14 EA. CLIP ;,v: 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF COLUMN 11/2" PENETRATION INTO UNDERLYING FOOTING DETAIL "F" - DOOR JAMB & HEADER DETAIL "G" - SLOPED PURLIN CONNECTION SCALE: NTS OJ / O 4 r �� # -Z �: '� N LL 6 LLI •co o O O J D N U' en / \ LLI 1p�� R (� d' o 00 J 00 0 J m O) co �- co z Z Q E U 0 0 v U W o - J O ao � W ELL Lo , N w °i c ZO�c' PURLIN W < a) Q Fa- U H O L o � 0-00 Z O U ~ U D U) W LL Z m W O zU U i» W w LLI W n a Ucy U Y OU C) m 00 wUL DESIGN DATE: 3/23/2018 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS BEAM o o o I o o I CLOSE BOTTOM OF BEAM WHEN TRIMMED .044 RECEIVING CHANNEL, FASTEN w/(2) #12 SMS EACH SIDE OF BEAM 2x2x4x1/8" ANGLE EA. SIDE OF BEAT w/(4) #14 TEKS EACH LEG EACH #12 SMS FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION #142" WOOD REW 18" O.C. CORNER POST O 2x2x4 ANGLE W/ (4) #14 TEKS O O SIDE VIEW TOP VIEW DETAIL"H" SCALE: NTS FASTEN GUTTER TO FASCIA w/ #14x2" WOOD SCREW 18" O.C. (2) #12 SMS (2) #14x2" WOOD SCREW EXISTING WOOD FASCIA STRUCTURAL GUTTER 5052-H32 GUSSET NOTE F JI:KLvv l2UHIVl I T INSTALL FASTENERS ALONG PERIMETER OF GUSSET 2X6 AND LESS THAN 3 ROWS OF (4) #14 -BEAM JOINT 3/8" MIN, FROM EDGE. FASTENERS FOR 2X7 AND GREATER 4 ROWS OF(4) #14 MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 'NOTE: FOR SPANS OVER 33' ADD ANOTHER ROW FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 DETAIL "W'GUSSET CONNECTION SCALE: NTS EAVE RAIL 1" x 3" O.B. PATIO SECTION (2) #12 TEKS (TYP.) EA. MEMBER (FOR SPANS OVER 32' USE #14 TEKS) x3x0.05 CE (TYP.) K-BRACE LATERAL "W'-BRACING CONNECTION DETAILS (2) #14 WOOD SCREWS (2) #12 SMS INTO FASCIA 2x2x1/8"ANGLE w/(2) GIRT \ '` #12 SMS EA. LEG SMB o 1 o I \ ili \ ` GIRT 1/8"x2"x4" STRAP (2) #12 SMS INTO BEAM SIDE VIEW STRUCTURAL GUTTER (2) #12 SMS INTO GUTTER 2x2x1/8" ANGLE w/(2) #12 SMS EA. LEG \ GIRT FASCIA (2) #12 SMS (2) GUTTER BRACES EACH w/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA SMB 1/8"x2"x4" STRAP o 0 (2) #12 SMS INTO BEAM GIRT (2) #12 SMS INTO GUTTER STRUCTURAL GUTTER `ALTERNATELY USE 2x2x1/8 ANGLE TOP VIEW DETAIL "L" CORNER CONNECTION SCALE: NTS 6063-T6 ALLOY PLATE (ONE SIDE) OR STRONGER K-BRACE 2 x 3 x 0.050 CHAIR RAIL K-BRACE 2x3x0.050 --- — — ---BRACE-(TYP.)- LATERAL "K"-BRACING CONNECTION DETAILS .050" GUTTER STIFFNER FASTEN TO FASIA W(2) #12x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS r_ x 3 x 0.050 DACE (TYP.) DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE: NTS (2) #12 TEKS (TV EA.-MEMBER-(F( SPANS OVER 32 USE #14 TEKS) co o O c.J :z =(D0 Lli o'z= VO:�J Z � O\ m 00 �iJ V co Zz Q E 0 LL It U O J w — Q � � W < LL_ Lo , r LLI V C� I--- ^ G 0 r COLUMN W Q � o � y_ `i C) O OL o O GIRT (CHAIR RAIL) _j d LL. a WHEN BEAM & PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM & PURLIN w/ 1/8"&W" ANGLE & (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (BEAM TO PURLIN) w/ 1/8"x2"4" ANGLE w/(2) #12 SMS INTO EA. MEMBER (BEAM & PURLIN) N 00 t` 0 W U U 0 O Ln I- O 00 z U LLI O w CL z O U U U) W LL Z m W O U Z � w W W W d W o a _ U � F- otY0 0 QO Y U LLJrn LL Z O O a DESIGN DATE: 3/2312018 REVISION 1: DATE PAGE: REVISION 2: DATE /� 4 SCALE: NTS