Loading...
HomeMy WebLinkAboutPROPANE TANK SPECIFICATIONSmw i S Ferrellgas STORAGE TANK IS ADEQUATELY ANCHORED TO PREVENT FLOATATION, PROPANEi TANK BUOYANCY �6����� COLLAPSE OR LATERAL MOVEMENT MAX BUOYANCY = p�*g*Vt DURING THE BASE FLOOD EVENT. = 1.94 slug/ft3 * 32.2 ft/s= * 66.84 ft' St LucieCount , 3232 Stuart, FL 34 97y = 4176 LBS ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 54-58, NATIONAL FUEL. GAS CODE NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK AND FLORIDA FUEL GAS CODE 2017. = 4176 LBS — 871 LBS = 3305 LBS TANKS INSTALLED IN TRAFFIC AREAS SHALL BE PROTECTED WITH GALV. STEEL FORCE ON r CABLE = 3305 / 2 = 1653 LBS SCHED. 80 PIPE BOLLARDS (4"0) 6' LONG TENSILE OF r CABLE = 7000 LBS X 3' BURY DEPTH WITH CAP 0 3' O.C. STRENGTH FORCE ON AUGER ANCHOR = 1653 / 2 = 827 LBS Z MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS C7 ' o o L'7 IOUND LEVEL GROUND LEVEL I �I "m I I m, mmil I = w-ml, 11= I 0 _l lul ,I U LP TANK 1 I 1 1" 7x19 GALV. AIRCRAFT CABLE 2 TOTAL (IN POLY. SLEEVE) AUGER ANCHOR, 48" LONG W/ 6"0 HEUX 4 TOTAL GRASS I'�TI I�'"`I I �"•1 I �'11I I I'� I i I i� � .0 � � _ • 1 I (MAX COVER)1 1 LP TANK IXCAVATION ,SIZE: i 1! 121x VWx4.5'D 9LB. ANODE BAG — " 709 GALV. AIRCRAFT CABLE ISSUE DATE: DRAWN: ! STRAPPING BOLT APPROVED: DRAWING NUMBER AUGER ANCHOR, 48" LONG W/ 6"0 HEUX T71 FRONT ELEVATION SCALE 1/4' - 1'-0" LP500