HomeMy WebLinkAboutPROPANE TANK SPECIFICATIONSmw i S Ferrellgas
STORAGE TANK IS ADEQUATELY
ANCHORED TO PREVENT FLOATATION, PROPANEi TANK BUOYANCY �6�����
COLLAPSE OR LATERAL MOVEMENT MAX BUOYANCY = p�*g*Vt
DURING THE BASE FLOOD EVENT. = 1.94 slug/ft3 * 32.2 ft/s= * 66.84 ft' St LucieCount , 3232 Stuart, FL 34 97y
= 4176 LBS
ALL WORK SHALL BE IN ACCORDANCE WITH
NFPA 54-58, NATIONAL FUEL. GAS CODE NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK
AND FLORIDA FUEL GAS CODE 2017. = 4176 LBS — 871 LBS
= 3305 LBS
TANKS INSTALLED IN TRAFFIC AREAS
SHALL BE PROTECTED WITH GALV. STEEL
FORCE ON r CABLE = 3305 / 2 = 1653 LBS
SCHED. 80 PIPE BOLLARDS (4"0) 6' LONG
TENSILE OF r CABLE = 7000 LBS
X 3' BURY DEPTH WITH CAP 0 3' O.C.
STRENGTH
FORCE ON AUGER ANCHOR = 1653 / 2 = 827 LBS
Z
MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS
C7
'
o
o
L'7
IOUND LEVEL
GROUND LEVEL
I �I "m I I m, mmil
I = w-ml, 11= I
0
_l lul ,I
U
LP TANK
1
I
1
1" 7x19 GALV.
AIRCRAFT CABLE
2 TOTAL (IN POLY.
SLEEVE)
AUGER ANCHOR, 48"
LONG W/ 6"0 HEUX
4 TOTAL
GRASS
I'�TI I�'"`I I �"•1 I �'11I I I'� I i
I i� � .0 � � _
• 1
I (MAX COVER)1
1
LP TANK
IXCAVATION ,SIZE:
i 1! 121x VWx4.5'D
9LB. ANODE BAG —
" 709 GALV.
AIRCRAFT CABLE
ISSUE DATE:
DRAWN:
!
STRAPPING BOLT
APPROVED:
DRAWING NUMBER
AUGER ANCHOR, 48"
LONG W/ 6"0 HEUX
T71
FRONT ELEVATION
SCALE 1/4' - 1'-0"
LP500