HomeMy WebLinkAboutBUILDING PLANSI
o
MARTIN COUNTY, FL
11'-8" X 24'=O" SHELTER
M�
t«'>1
EME
NO
SMOI�MG
o a
o
0
0 0
0
0
Building Notes:
- These plans comply w/ Rule 6TG20-3.006 for product
approval
The sealed set of plans are on file in the third
party agency's office as directed by the DBPR
This building has NOT been designed or approved for
placement in High Velocity Hurricane Zones (HVHZ)
This building is subject to review and approval of
the fire inspector on site w/ compliance w/ Ch, 633
Fire Safety Code
The manufacturer's data sheet and the state (DBPR)
nsigria shall be permanently mounted to or about
the electrical panel
This structure has been designed for erection or
installation on a site built permanent foundation and
is not designed to be moved once erected or
installed
Light Frame Construction Identification Placards (on
site or details provided)
SPECIAL CONDITIONS / LIMITATIONS
I. SEPARATION FROM EXISTING STRUCTURES TO BE 10' OR GREATER.
2. THI5 STRUCTURE 15 NOT DESIGNED FOR INSTALLATION IN A
FLOOD HAZARD AREA.
3. THIS STRUCTURE 15 NOT DESIGNED FOR HUMAN OCCUPANCY
EXCEPT FOR SHORT TIME PERIODS FOR EQUIPMENT MAINTENANCE.
4. THERMOBOND WILL NOT BE RESPONSIBLE FOR INSTALLATION OF
ANY SPRINKLER SYSTEM, WHICH MAY BE REQUIRED BY LOCAL
BUILDING OFFICIAL.
S. THERMOBOND WILL NOT BE RESPONSIBLE FOR ANY ANTENNA
INSTALLATION ASSOCIATED WITH THIS BUILDING.
6. THIS BUILDING SHALL NOT BE LOCATED AT A SITE THAT EXCEEDS
THE LISTED DESIGN LOADS.
7. IF BATTERIES W/ AN ELECTROLYTE CAPACITY OF MORE THAN 50
GAL. ARE TO BE INSTALLED IN THIS BUILDING, ONE OF THE
FOLLOWING MUST BE INSTALLED BY OTHERS ON SITE:
a. AN EXHAUST FAN W/ A HYDROGEN LIMIT SWITCH TO LIMIT THE
HYDROGEN TO 1% OF THE TOTAL VOLUME OF THE ROOM.
b. CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE NOT
LE55 THAN I CU.FT. PER MINUTE PER 50.FT. OF FLOOR AREA
OF THE ROOM.
8. THI5 BUILDING IS NOT INTENDED FOR OCCUPANCY. THE LIGHTING
SHOWN IS REQUIRED FOR A SERVICE TECHNICIAN TO FUNCTION
SAFELY.
DESIGN LOADS
OCCUPANCY TYPE (RISK CAT.): IV
FLOOR LIVE LOAD: 300 psF
ROOF DESIGN LOAD (STRENGTH): 150 psf
ROOF DESIGN LOAD (DEFLECTION): 75 psf
Pf - (0.7) * (Ce) * (1) * (Ct) * (Pg)
WIND DESIGN
WIND SPEED: 168 Vult (ASCE 7-10)
EXPOSURE: D
Iw=1.15 a=3Ft
GCpi = t 0.18 (PER ASCE 7)
ENCLOSED BUILDING INTERNAL PRESSURE
EXPOSURE FACTOR
Ce
= 1.0
ZONE
1: P=
+ 24.20
PSF
P=
- 5q.50
PSF
IMPORTANCE FACTOR
Is =
1.15
ZONE
2 P=
+ 24.20
PSF
P=
- 9q.90
PSF
THERMAL FACTOR
Ct =
1.0
ZONE
3: P=
+ 24.20
PSF
P= -
150.30
PSF
GROUND SNOW LOAD
Pg
= 60
ZONE
4: P=
+ 54.50
PSF
P=
- 5q.50
P5F
ZONE
5: P=
+ 54.50
PSF
P=
- 6q.60
P5F
ITEMS TO BE INSTALLED ON SITE AND ARE SUBJECT LOCAL
INSPECTION ;
1, Installation of foundation Tie Down Plates,
2, Installation of door canopy.
3. Installation of 70kw generator,
SHIPPING
INFORMATION:
SEISMIC DESIGN:
COPY
BUILDING DEAD LOAD: 72,000 LBS
SHIPPING HEIGHT: 10'-5 1/8" BUILDING FOOT PRINT: 280 50. FT.
SHIPPING WIDTH: 11'-8" SEISMIC DESIGN CATEGORY: D
SHIPPING LENGTH: 24-0" BA51C SEISMIC -FORCE -RESISTING SYSTEM: INTERMEDIATE PRE -CAST WALL
SHIPPING WEIGHT: 72,000 LBS ANALYSIS PROCEDURE: ELF
ASSUMED SITE CLASS: D
DESIGN SPECTRAL RESPONSE ACCELERATION: 55 ■ 1.50 51 = 0.10
SITE COEFFICIENTS: FA = 1.00 FV = 2.2
DESIGN BASE SHEAR: V = CSW = (0.375) (72,000% = 27000 LBS
W - ESTIMATED WEIGHT WITH EQUIPMENT
le - 15
SCA1>nNE-4
13Y
St Lucie County
sgezk)2
St LUCIE
PLAN R
DATE:
DATE:
PLUMB: _
DATE:
MECH:
DATE
DRAWING INDEX
SHEET
DESCRIPTION
REV
12
REV
=VREV
REV
5
REV
6
Cl
COVER SHEET
C2
MATERIALS L15T
Al
FLOOR PLAN
A2
ELEVATIONS
A3
FOUNDATION
El
ELECTRICAL SCHEMATIC
ELI
ELECTRICAL PANELS
E1.2
ALARM DIAGRAM
E2
GROUNDING LAYOUT
E2.1
GROUNDING DETAILS
E3
WIRE MOLD
E4
ELECTRICAL DIMENSIONS
E5
ELECTRICAL DETAILS
51
FLOOR CASTINGS
52
WALL CASTINGS
52.1
WALL CASTINGS DETAILS
53
ROOF CASTINGS
54
GRO55 SECTION
T1
TRANSPORT CONNECTIONS
T2
INSTALL DETAILS
RELEASE DATES
STATUS
RELEASED TO
BY
DATE
P=PROGRESS F=FINAL R=REVISED PR=PRODUCTION C=CUSTOMER 5=STATE/THIRD PARTY
REVISIONS
REV
DESCRIPTION
BY
DATE
I
_
2
3
4
5
6
7
FLORIDA
OCCUPANT LOAD: I
CONSTRUCTION TYPE: 56
USE GROUP: 52
CODES:
2011 NATIONAL ELECTRIC CODE
2014 FLORIDA STATE BUILDING CODE -BUILDING
2014 FLORIDA STATE BUILDING CODE -MECHANICAL
2014 FLORIDA STATE BUILDING CODE -ENERGY
(EXEMPT FROM FLORIDA ENERGY CODE PER. SEC. 101.4.8.5
FOR EQUIPMENT SHELTERS)
�I FT ° 439 - Model AGE3959G
" e sues i
. dp
FL OW ...9.+m.
STAMPS AND SEALS
Ja��WttM^z
za wZ p
pi
j�0O N
ut~��ZZappu�
of
W
in ^
�'
V/ W
2_
J LL
s
�o O
p N C)
. O
2 60
r
(40
J
LL Ln
Alma
9+
O
V im
LLI
QL
z � z
w
�z
ry
a a
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
C 1
IL
MATERIALS
LIST
ITEM
QTY
UM
DESCRIPTION
MANUFACTURER
MFR PART NUMBER
TBB PART NUMBER
NOTE
i
EA
300A PANELBOARD INTERIOR
SQUARE D
N0421-2C
200-0276
8,12
1
1
EA
300A PANELBOARD MCB KIT
SQUARE D
NQM54LA
200-0467
8
1
EA
MAIN CKT BKR, 2/300A
SQUARE D
LAL26300
200-0598
8
1
EA
300A PANELBOARD BOX
SQUARE D
MH62
200-0464
B
2
1
EA
300A PANELBOARD COVER
SQUARE D
NC62S
200-0465
8
3
2
EA IGROUND
BAR
SQUARE D
PK15GTA
700-0022
6
4
1
EA
CKT BKR, 2/15A
SQUARE D
00216
200-0023
8
5
2
EA
CKT BKR, 1/15A
SQUARE D
Q0115
200-0051
8
6
2
EA
CKT BKR, I/BOA
SQUARE D
00130
200-0054
8
7
2
EA
CKT BKR, 2/50A
SQUARE D
=50
200-0065
8
8
I
EA
CKT BKR, 2/60A
SQUARE D
00260
200-0066
8
q
2
EA
CKT BKR, 2/125A
SQUARE D
Q02125
200-0070
8
10
106
EA JCKT
BKR, 1/20A
SQUARE D
00120
200-0052
8
11
2
EA
200A SUB -PANEL, 1�/3W
SQUARE D
0014ON200
200-0152
8
12
2
EA
SUB -PANEL COVER
SQUARE D
QOC40US
200-0164
8
13
4
EA
GROUND BAR
SQUARE D
PKI8GTA
700-0022
6
14
4
EA
GROUND BAR ISOLATOR KIT
SQUARE D
PKGTAB
200-01g7
8
15
1
EA
CKT BKR ENCLOSURE, 400A WITH NEUTRAL KIT
SQUARE D
LA40OS/4005N
200-0601 200-0346
8,12
I6
I
EA
CKT BKR, 2/300A
SQUARE D
04L2300
200-0602
8
17
1
EA
CKT BKR ENCLOSURE, 100A
SQUARE D
00210OBNS
200-01%
8112
IS
1
EA JCKT
BKR, 2/60A
SQUARE D
00260
200-0066
6
Ig
1
EA
SURGE ARRESTOR, TYPE 2 - MOV, 120/2401 1�/3W
TRAN5TECTOR
DSAPEXIMAX608MM
100-0065
8,12
20
1
EA
SURGE ARRESTOR, TYPE 1 - SAD/MOV, 120/240, Io/3W
TRANSTECTOR
DSAPEXIMAX808
100-0087
8112
21
4
EA
SURGE PROTECTION, 120V MODULE
TRANSTECTOR
12R-ICP120V
100-0181
8
22
5
EA
SURGE PROTECTION, 13V MODULE
TRANSTECTOR
D5WPHO3
101-0526
B,12
23
1
EA
ENCLOSURE, 3R, 6 X 6 X 4
HOFFMAN
A6R64NK
300-0172
7
24
3
EA
ENCLOSURE, NI, 6 X 6 X 4
HOFFMAN
ASEGX6XANK
BOO-0173
7
25
2
EA
ENCLOSURE, NI, 12 X 12 X 6
HOFFMAN
ASE12X12XGNK
300-0174
7
26
2
EA INEAT14ERPROOF
GFCI RECEPTACLE
PASS 4 SEYMOUR
2095TRWRl
800-0034
8
27
8
EA IDUPLEX
RECEPTACLE
LEVITON
CR20-1
800-0031
7112
28
3
EA
SINGLE POLE SWITCH
LEVITON
C5120-21
BOO-0058
7
2q
8
EA
48" 32H 2-BULB FLUORESCENT
LITHONIA
58 2 32 120 RE BDP
500-Olg2
7
30
31
1
EA
EMERGENCY/EXIT LIGHT
LITHONIA
LHQM 5 W 3 R
600-0019
7
32
I
EA
LED EXTERIOR LIGHT W/PHOTOCELL
LITHONIA
OLW14
500-0040
2,7
33
2
EA
48,000 BTU HVAG W/5KW HEAT
MARVAIR
AVPA46ACA05ON
Sqq-035q
8
34
2
EA
SUPPLY GRILL
MARVAIR
80676
S99-0026
8
35
2
EA
RETURN GRILL
MARVAIR
80679
899-002q
8
36
1
EA
LEADLAG
MARVAIR
COMMSTAT 3
100-0030
8,12
37
38
1
EA
ENTRY PORT, 4 X 3
MICROFLECT
B1334
Iqq-0085
8
3q
1
EA
GROUND BAR KIT
HARDER
EPK12MOT
200-0116
8
40
3
EA
66 BLOCK W/AMPNENOL CONNECTOR
SIEMON
566M12-5W
050-0022
7112
41
3
EA
AMPHENOL CABLE
ORTRONICS
OR-804025PCO50-IGY
752-0080
7
42
150
EA
BRIDGE CLIP
SIEMON
SAl-55-100
050-0004
7
43
1
EA
DOOR ALARM
SENTROL
1047T
500-0106
7,12
44
1
EA
3070 DOOR, RP OUTSWING (FL4553)
CECODOOR
0q8-1120 d 0%-0120
4
45
1
EA
IDEADBOLT
COMPASS
Oq8-2230
7
46
1
EA
ICORE, 7-PIN, A -TYPE
CENTRAL IN HARDWARE
003-1012
7
47
1
EA
PA55AGE LEVER SET
COMPASS
0%-2110
7
48
I
EA
NRP-SS HINGES, SET OF 3
SOMMER
B55000-N-652
OqB-3110
7
4q
I
EA
MAGNETIC WEATHER STRIPPING (3070)
PEMKO
2815
OqB-3210
7
50
1
EA
36" THRESHOLD
REESE
5205
Oq8-3310
7
51
1
EA
36" NEOPRENE STYLE DOOR SWEEP
REESE
323C
OqB-3410
7
52
1
EA
ANTI -PICK PLATE
LATCH GUARD
LGIOOZ/SF
Oq8-3650
7
53
1
EA
36" THRESHOLD STOP
REESE
095-3311
7
54
1
EA
40" DRIP CAP
COMPASS
Oq8-3610
7
55
I
EA
HYDRAULIC DOOR CLOSER WITH HOLD OPEN
ADVANTAGE
8001
Oq8-3522
7
56
1
EA
13070 DOOR CANOPY
B*T
OqB-3660
2,4
57
1
EA
IOLB CO2 FIRE EXTINGUISHER
KIDDE
PROIOCDM
3qq-0051
2,7
56
1
EA
120LB DRY CHEM FIRE EXTINGUISHER
KIDDE
PP020TCM
Sq9-0067
2,7
5q
I
EA
METAL WALL POCKET
SAFCO
21DIgq
001-2048
7
60
1
EA
EYE WASH
HONEYWELL
GRAINGER# 3ARD6
3q9-0255
7
61
1
EA
FIRST AID KIT
NORTH
GRAINGER# 4EYg2
3qq-0254
7
62
1
EA
NO SMOKING SIGN
BRADY
GRAINGER# 4T676
3qq-0108
7
63
1
EA
ELECTRO EMISSION SIGN
RICHARD TELL ASSOCIATES
TE55CQ# 2037q
3qq-0109
7
64
1
EA
TELCO BOARD, 3' X 4' X 3/4", GRAY
THFRM050ND
753-2191
65
1
EA
POWER FAIL RELAY W/BASE
DAYTON
GRAINGER# 3X740/5X852
100-0034 fi 100-0001
7,12
66
50
FT
24" CABLE LADDER W/HARDWARE
CENTRAL STEEL FABRICATORS
10024
001-2231
7113
67
10
FT
6" CABLE LADDER W/HARDWARE
CENTRAL STEEL FABRICATORS
10006
001-2232
7113
68
1
EA
JAASTE BASKET
TOUGH GUY
GRAINGER# 4PGN2
3qq-Olgq
117
6q
I
EA
IDUST PAN
TOUGH GUY
GRAINGER# IVAJ7
3qq-0054
117
70
1
EA
BROOM
TOUGH GUY
GRAINGER# IVAC2
101-0301
1,7
71
1
EA
UTILITY HOLDER
BATTALION
GRAINGER# 4466
101-0528
7
72
1
EA
4" WIREWAY, IOFT
B-LINE
44120 G NK
300-0037
7
73
2
EA
4" WIREWAY, 4FT
B-LINE
4448 G NK
300-0039
7
74
I
EA
4" WIREWAY, 3FT
B-LINE
4436 G NK
BW-0107
7
75
2
EA
4" WIREWAY END CAP
B-LINE
44 E NK
300-0028
7
76
1 4
1 EA
4" WIREWAY CONNECTER
B-LINE
44 C.
300-0049
7
77
0.1
1 EA
JIOFT WIREMOLD
WIREMOLD
ALA480OB-10
001-2327
8
78
3
EA
18FT WIREMOLD
WIREMOLD
ALA480OB-8
001-2327
8
WIREMOLD END CAP
WIREMOLD
ALA45106
001-2340
8
W1REMOLD BLANK COVER
WIREMOLD
ALA-BL
001-232q
6
WIREMOLD 4 HOLE COVER
WIREMOLD
ALA-BL (SEE E3)
001-232q
8
fffO0
WIREMOLD 2 HOLE COVER
W1REMOLD
ALA-BL (SEE E3)
001-232q
8
WIREMOLD RECEPTACLE
PASS $ SEYMOUR
5358
800-0105
7,12
20 KVA UPS
LIEBERT
A54DONCYHNN8
50-I115UPS
BYPASS SWITCH
ILIEBERT
NMBHW81/202816GI
8,12
MATERIALS LIST
ITEM
QTY
UM
DESCRIPTION
MANUFACTURER
MFR PART NUMBER
TBB PART NUMBER
NOTE
86
1
EA
70 KW GENERATOR
GENERAC
LPV700D
025-0321
6,1
87
1
EA
300A ATS, I0/3W, 240V
GENERAC
GTS STYLE
025-02% E 025-02%
8,12
88
1
EA
SMOKE DETECTOR WITH AUXILIARY RELAY
BRK
7010/RM4
100-0185 # 100-0184
7
Bq
2
EA
125A SUB -PANEL, 10/3W
SQUARE D
Q0124MI25
200-0149
8
qO
2
EA
SUB -PANEL COVER
SQUARE D
QOC24US
200-0161
8
ql
2
EA
GROUND BAR
SQUARE D
PKI5GTA
700-00lq
8
112
2
EA
GROUND BAR ISOLATOR
SQUARE D
PKGTAB
200-01C17
8
93
1
EA
BAIT WIRE SYSTEM
HARDER
MOTOGBALARMKT
001-2257
8
q4
q5
96
q7
98
qq
100
101
102
103
104
105
lob
107
3
EA
GROUND STRAP BARS
108
3
EA
GROUND STRAP COVERS
650-0048
I
IOq
60
EA
RIVETS
110
4
EA
LIFTING LUGS
1
111
4
EA
TIE DOWN PLATES
112
8
EA
TIE DOWN BOLTS
113
B
EA
BLACK PLASTIC BASE PLUGS
114
10
EA
FLOOR TILES
I
115
1 1
1 EA
ITUBE OF BRILLIANT WHITE CAULK
1
116
4
EA
TUBES OF BEIGE DYMONIC CAULK
1
117
1
EA
PINT CAN OF TELECOM BROWN PAINT
1
118
1
EA
PINT CAN OF ELASTOMERIC COURSE PAINT
1
Ilq
25
EA
1/8" SHIMS FOR SHELTER SET
120
25
EA
1/4" SHIMS FOR 514ELTER SET
MATERIAL LIST NOTES:
I, SHIP LOOSE
2. PREINSTALL REMOVE FOR SHIPMENT
3. FABRICATED ITEM
4. PAINT - TELECOM BROWN
5. PAINT - TELECOM GRAY
6. PAINT - COLOR DESIGNATED
7. OR EQUIVALENT
8. NO SUBSTITUTIONS ALLOWED
q. NO PART NUMBER SPECIFIED
10. MAY BE DELIVERED AT SIGHT
11. PROVIDED BY OTHERS
12. LABEL
13. QUANTITY ESTIMATED
STAMPS AND SEALS
No
TwSCa( -Q�Q
,pu Q
Za wZ�o �
��o�c�QCie�ao�g
,J IN
F- nc
w
W
uj
'A
Q
V/
V/
o
J
Q
A�pr
li.
ON
W
F-
X
a
G
r
r
C
w
�
m
z
�z4
ki
w
0..
a
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1(003 -105
SCALE 24X36:
NONE
SKEET:
C 2
_.
00
9'-1 3/4"
WALL D
4'-2" MAX.
20
22
EXT
EXT
66
ff------ in
88
ROW 3
WALL C
24' -0"
78 79 80 81 83 29
ROW 2 ROW 1
`
m
��■L,J■���■Ilfil�
�
ISO
IIII
■
NMI
Elio'
�
:,
■�■��lilll��■__■��II��I
.III■
'■■ ■■�I �IIIIII('=
►� '■IIIIIIII!
�IIIIIIII
��
�••�I•�■III�I■11■Illllrj
II!I■r
'IIII■I��
IIII■I(��
':
:;IIII■
!!lllllll■�
IIIIIIII�
WALL A
FLOOR PLAN
SCALE I/2"=1'-0"
COMMERCIAL POWER:
120/240VAC, 300AMP SINGLE PHASE SERVICE,
CONDUIT RUNS:
I. ALL CONDUIT RUNS TO BE EMT UNLESS STATED OTHERWISE.
2. ALL CONDUIT RUNS TERMINATING AT SERVICE ENTRANCE EQUIPMENT SHALL CONTAIN BONDED
BUSHINGS.
3, WIREWAYS CARRYING 3 OR MORE CURRENT CARRYING CONDUCTORS SHALL BE DERATED PER
TABLE 310-15(5)(3)(o) OF APPLICABLE EDITION OF THE NEC.
4. CONDUIT FILL IS BASED ON CHAPTER 9, APPENDIX C OF THE NEC.
CABLE LADDER:
I. CABLE LADDER IS TO BE 8'-0" A.F.F. AND INSTALLED IN ACCORDANCE WITH ARTICLE 392
OF THE NEC LEVEL TO WITHIN 1/8" IN 10' OR SIMILAR.
GROUNDING:
I. ALL GROUNDING EXCEPT FOR CABLE LADDER TO CONFORM TO ARTICLE 250 OF THE NEC.
2. CABLE LADDER GROUNDING TO CONFORM TO ARTICLE 392.60 OF THE NEC,
GENERAL NOTES:
I. LABEL FACE OF ALL ELECTRICAL EQUIPMENT WITH PHENOLIC LABELS. BLACK WITH WHITE
LETTERS. EXTERNAL BYPASS, TI, SDI, $ LAI. EXCEPTION SHALL BE ALL UPS EQUIPMENT SHALL
HAVE PHENOLIC LABELS RED WITH WHITE LETTERS. EX UPSITPI, UPSI, WIREMOLD RECEPTACLES.
2. CONNECT ALARMS TO UPS WITH A DB25 PIN CONNECTOR.
3, CONNECT CIRCUITS PPI-22 $ PPI-24 TO THE EXTERIOR SURGE PROTECTOR AND LABEL.
4. COIL AND TAG 50' OF ALARM WIRE FOR GENERATOR ALARMS.
S. CONNECT GENERATOR ALARMS TO THE DSWP03 SURGE PROTECTION MODULES.
6. COIL AND TAG 12" OF #10 WIRE FOR CIRCUITS, PPI-2 $ 4.
7. COIL 12" OF ALARM WIRE FOR TOWER LIGHT ALARM. TBI-25 $ 26.
8. COIL 50' OF #18 AWG FOR GENERATOR CONTROL WIRE.
M
WALL B
STAMPS AND SEALS
4�=�mw�zz�d
a�ZQ0rzw3.i�i
a
LO
c
~i co
0
IUD
co
oN
d
v I
O
O O
W CD
O
LO
A
O
w
�
J
�=
Q
Q
cf)
J
J_
a
O
CDW
qqT
ON
O
X
J
O_
LL
r
r
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Wagner
SERIAL NUMBER:
1603-105
SCALE " 2AX36:
NONE
SHEET:
Al
2" OVERHANG
TYP
TEME
NO
SN01(ING
q.
I
Po o
Q
Q
Q
4'-5 7/8" 3'-4 1/4"
24-0" (TYP)
(o" TYP T-8"
FRONT ELEVATION (WALL A)
SCALE: NONE
REAR ELEVATION (WALL C)
5C41-E: NONE
11 O I/All
I" NIPPLE FOR TOWER
LIGHT ALARM
I" NIPPLE FOR TOWER
LIGHT ALARM
I" PVC FOR
BAIT WIRE
(2) 3" PVC FOR
TELCO ENTRY
1" PVC AT 45'
#2 MECHANICAL
LUG (2 PLACES)
Lr14Yi
L�JCi.J
G�J
m
RVAI
L____J
I
RIGHT ELEVATION (WALL B
SCALE: NONE
LEFT ELEVATION (WALL D
SCALE: NONE
EXTERIOR
FINISH SCHEDULE
ITEM
SURFACE
FINISH
PAINT COLOR
ROOF
TROWELED SMOOTH
SEALED, ELASTOMERIC COURSE
TELECOM BROWN
PAINT
WALLS
EXPOSED WASHED
OKITE STAIN (2 COATS)
-
AGGREGATE
DOORS
STEEL, RATED
PAINT
TELECOM BROWN
JOINTS
AS FINISHED
SEALED PER DETAILS SHEET
TEL BROWN
ELEVATION NOTES:
I. SEE MATERIALS LIST FOR SHIPPED LOOSE ITEMS.
2. SEE MATERIALS LIST FOR DOOR HARDWARE.
OR GENERATOR
)R GENERATOR
STAMPS AND SEALS
W Z
�oN��fl�a d
zaEwZ
zF Of
J
LL
�1
C0 m
Lu
■� w
Q � �
z � z
w�za
wry
IL Ll
DATE:
3/8M
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Wagner
SERIAL NUMBER:
1603-10=
SCALE " 24XBG:
NONE
SPEET:
A2
LOOSE SAND OR GRAVEL
BACKFILL NOTES: 15, 16 AND 17
SHIMS (TYP)
(2) #4 REBAR AROUND
PERIMETER WALL
m
#3 STIRRUP AT
IS O.G. AROUND
PERIMETER WALL
SEE NOTE: 9
BUILDING FLOOR SYSTEM
(2) #4 REBAR AROUND
PERIMETER WALL
=I
v'UNDISTURBED OR
COMPACTED SOIL
NOTES: 5 AND 10
(3) #4 REBAR AROUND
PERIMETER WALL BASE
SECTION A -A
SCALE: NONE
TYPICAL EACH WAY SEE NOTES FOR SPECIFIC
INFORMATION ON MATERIALS AND OTHER REQUIREMENTS
#3 STIRRUP AT
18" O.C. AROUND
PERIMETER WALL
(3) #4 REBAR
AROUND
PERIMETER
WALL BASE
SEE NOTE:
L005E SAND OR GRAVEL
BACKFILL OPTIONAL VAPOR
BARRIER SEE NOTE: 16
6"x6" MIN. PERIMETER CHAMFER
SHIMS (TYP)
(2) #4 REBAR AROUND
PERIMETER WALL
GRADE
OI III Plll.1, I.1
z
rn
m
CONCRETE SLAB
-BUILDING FLOOR SYSTEM
(2) #4 REBAR AROUND
PERIMETER WALL
TIE DOWN PLA1
(SEE DETAIL
LI BELOW)
#3 STIRRUP AT
IV' O.C. AROUND UNDISTURBED OR
PERIMETER WALL COMPACTED SOIL
SEE NOTE: 9 NOTES: 5 AND 10
(3) #4 REBAR AROUND
PERIMETER WALL BASE
2 SECTION A -A (OPTIONAL)
SCALE: NONE
TYPICAL EACH WAY SEE NOTES FOR SPECIFIC
INFORMATION ON MATERIALS AND OTHER REQUIREMENTS
A
L A
i
7
A-]
FOUNDATION PLAN
SCALE: 1 /2" =1'-0"
SHIMS TYPICAL (SEE NOTE 12)
A
'_�_WWF 6x6 W2.9 x W2.9 IN
SLAB, WHEN SLAB 15 USED
� sHIMs
#3 STIRRUP AT ANCHOR
18" O.C. AROUND (SUPPLIED BY
PERIMETER WALL OTHERS)
(3) #4 REBAR
AROUND
PERIMETER
WALL BASE
FRONT VIEW
WALL
IFTING TEE
ASSEMBLY
FLOOR
®
3/4" �/ pal
J
,
BOLT
a b
FOUNDATION
3/4" X 3 3/8"
SS ANCHOR
MINIMUM
I" CHAMFER (TYP.)
(3) 1-1/8"
DIAMETER HOLES
NOTES:
1. PRIME AND PAINT THORO PRODUCTS
COCOA, OR AS OTHERWISE SPECIFIED
2. THIS PART TO BE SNIPPED LOOSE WITH
- BUILDING
A
(4) 3/8" X 6" X loll TIE DOWN PLATES
3 TIE DOWN DETAIL
SCALE: 1-1/2" = I'-0"
THIS DRAWING IS NOT FOR CONSTRUCTION SEE NOTE: 13
FOUNDATION NOTES:
I. ALL FOUNDATION WORK BY OTHERS AND SUBJECT TO LOCAL INSPECTION AND APPROVAL.
2. FOUNDATION SURFACE SHALL BE LEVEL TO WITHIN +/- 1/8" PER 10 LINEAL FEET IN ANY
DIRECTION.
3. FOUNDATION SHALL BE SQUARE TO WITHIN +/- 1/4"
4. BASE FOUNDATION WALL FOOTING MUST BE ESTABLISHED A MIN. OF 6" BELOW FROST LINE
AND ON UNDISTURBED SOIL,
5. SOIL BEARING CAPACITY SHALL NOT BE LESS THAN 3000 PSF.
6. CONCRETE STRENGTH SHALL NOT BE LESS THAN 3000 PSI, AS DETERMINED BY ASTM
G31,C39,072, LATEST REVISION.
7, REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, LATEST REVISION,
8. CONCRETE MIX DESIGN, BATCHING AND CONSTRUCTION PRACTICES SHALL CONFORM TO ACI 318,
ACI 305R, ACI 306.1 LATEST REVISIONS.
9. DETAILING, FABRICATION AND PLACEMENT OF REINFORCING STEEL SHALL COMPLY WITH ACI
315, ACI 3181 ACI 306R, AWSDI.4 LATEST REVISIONS, AND WITH CRSI STANDARDS,
10. COMPACTION REQUIREMENTS TO BE DETERMINED BY ENGINEERING ANALYSIS OF SITE SPECIFIC
DATA.
11. TIE DOWN PLATES, IF USED, MUST BE ENTIRELY ABOVE GRADE.
12. SHELTER MUST BE SHIMMED.
13. THIS INFORMATION IS PROVIDED FOR REFERENCE ONLY. FINAL DESIGN BASED ON SITE SPECIFIC
DATA 15 THE RESPONSIBILITY OF THE SITE CONTRACTOR,
14. PROVIDE PROPER DRAINAGE AWAY FROM FOUNDATION AT GRADE,
15. SLAB REINFORCEMENT TO BE LOCATED IN UPPER THIRD OF SLAB.
16. BACKFILL DEPTH REQUIREMENTS TO BE DETERMINED BY ENGINEERING ANALYSIS OF SITE
SPECIFIC DATA (4" MIN.).
17. BACKFILL DEPTH REQUIREMENTS TO BE DETERMINED BY ENGINEERING ANALYSIS OF SITE
SPECIFIC DATA (4" MIN.).
FOUNDATION LOADS:
2. DEAD LOAD:1375 PLF
3. LIVE LOAD: 2700 PLF
STAMPS AND SEALS
Qp[=�
�-mwW Qzz
ZsaZwZ Lp.L
Qoa��-r'Oz �i3 .iYi
za Q=�=
�-zaiw�oao~ r
f- a�
od,NF W Ll2 mF�
zf a
w
W
In J
W
Q cn
J
0 O
® cm
� o0
r
to
44
LL
w
w
■�
�+
m
a
z�zQwz
oQ
wr
C.
Q
DATE:
3/8/1
SALES MANAGER:
D. Brunswic
DRAWN BY:
J. Wagnie
1603-IC
SCALE 2436:
NON
SI IEET:
A3
UTILITY SERVICE WITH
GROUND 120/240 VAC
14/3W 60Hz (BY OTHERS,
SUBJECT TO LOCAL CODES)
SERVICE GROUND BONDED TO
EXTERIOR GROUND RING WHERE
ENTRY PORT 15 BONDED
120/240 vac 10/3W
60Hz 70kW
UPS GROUND CONNECTED FROM
GROUND ON UPS TERMINAL
STRIP TO MASTER GROUND BAR.
ONE -LINE WIRING DIAGRAM
SCALE NONE
NEUTRAL SHALL BE PULLED WHEN
REQUIRED BY UPS MANUFACTURER
UPS GROUND CONNECTED FROM
GROUND ON UPS TERMINAL
STRIP TO MASTER GROUND BAR.
ONE -LINE DIAGRAM NOTES:
I. ALL GROUNDING TO CONFORM TO ARTICLE 250 OF THE NEC
2. WIREWAYS CARRYING 3 OR MORE CURRENT CARRYING CONDUCTORS SHALL BE DERATED PER
TABLE 310-15(15)(3)(d) OF THE APPLICABLE EDITION OF THE NEC
3. CONDUIT FILL 15 BASED ON CHAPTER q, APPENDIX C OF THE NEC
4. INCLUDE THE NEUTRAL TO GROUND BOND SCREW TO BE DONE ON SITE BY OTHERS.
5. MINIMUM CONDUIT SIZE SHALL BE i" (TRADE SIZE 16)
SCHEMATIC LEGEND
ON SITE BY OTHERS
LUGGED LOAD CENTER ELECTRICAL EQUIPMENT
LOAD CENTER WITH
BREAKER
TRANSFER SWITCH
GENERATOR
H \ F SURGE ARRESTOR
PIG TAIL GROUND
OFF-0
BY —0 �• 3 POSITION SWITCH
NOR— O
CIRCUIT BREAKER
v / F INVERTER
CONVERTER
GROUND
• CONNECTION
STAMPS AND SEALS
�oa�w�w�o
7dgN��o�t��u3pG��
z�aLwZpo��o
t, 0 @
1—izu
Lu
IrmLm
Lo
co
Q 4
z0
Q)
04
O�
CA
L0
�C
co
+� I
CCQ
0 �I
O
r�l c m
W .co
"
a
M/
NN
W
H
�
a
W
W
Q
cl)
V
J
-
O
�
0
-
a
®N
0.
2
co
V
t
w
r
J
w
to
J
LL Lo
A
_ 0)
� M
o
W
--LLI
Lij co
c
z
w z
� Q
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
S{IEET:
E1
PP1 300A, 120/240VAC, 1(p/3W, 60Hz, M.BKR
LOAD
VOLT AMPS
WIREBREAKER
BREAKER
WIRE
VOLT AMPS
LOAD
A
I B
I
ITRIPIP
I
I A
I B
UPS) FEED
8400
1 2 125 1 2 30 1 10
3 4 30 1 10
8 2 50 5 (350 2 8
I 20 g 10
60 2 4
11 12
13 14 15 1 1
12 1 20 15 16 20 1 12
12 2 15 17 18 20 1 12
Ig —40 20 20 1 12
12 1 15 21 22 20 1 12
23 24 20 1 12
25 26
27 28
2g 30
31 32 1
33 34
35 36
I 2 125 37 5 40
WIRE TYPE TO BE THHN UNLESS NOTED
LOAD
OTHERS AS REQUIRED
250
TOWER LIGHT
8400
250
TOWER LIGHT
HVAC #1
3300
3300
HVAC #2
3300
3300
SPARE
60
SURGE ARRESTOR
BLANK
60
BLANK
SPARE
LIGHTS INT It EXT
1110
160
BAIT WIRE
POWER FAIL
120
1260
RECEPTACLES
120
360
RECEPTACLE GFCI
SMOKE DETECTOR
120
120
BLOCK HEATER*
BLANK
120
BATT. CHARGER*
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
UPS2 FEED
8400
BLANK
8400
BLANK
VA PER PHASE
20340
21330
4gg0
4270
VA PER PHASE
+ CALCULATED AT 125%
CONNECTION BY OTHERS
$ GROUND FAULT PROTECTION
FOR CONTINUOUS
BY
25330
25600
TOTAL VA PER PHASE
211
213
AMPS PER PHASE
50.9
TOTAL KVA
234
AMPS X 110%
UPS1TP3 125A,
120/240VAC,
1(p/3W,
60Hz, M.BKR
LOAD
VOLT
AMPS
WIRE
BREAKER
BREAKER
WIRE
VOLT
AMPS
LOAD
A
B
P
TRIP
TRIP
P
A
B
ROW I RECEPT #1
ROW I RECEPT #3
ROW I RECEPT #5
ROW I RECEPT #7
ROW 1 RECEPT #q
ROW I RECEPT #11
ROW I RECEPT #13
ROW 1 RECEPT #15
BLANK
BLANK
BLANK
TELCO RECEPT #1
VA PER PHASE
180
180
80
180
720 1
1
180
180
180
180
80
900 1
12
12
12
12
12
12
12
12
12
I 20 I
1 20 3
I 20 5
1 20 7
1 20 9
1 20 11
1 20 13
1 20 15
17
ig
21
I 20 23
WIRE TYPE TO BE THHN
2 20 1
4 20 1
6 20 I
8 20 1
10 20 1
12 20 1
14 20 1
16 20 1
18
20
22
24 20 1
UNLESS NOTED
12
12
12
12
12
12
12
12
12
1 180
150
150
I80
1
720
1440
12
ROW I RECEPT #2
150
ROW I RECEPT
#4
ROW 1 RECEPT
#6
180
ROW I RECEPT
#8
ROW I RECEPT
#10
160
ROW I RECEPT
#12
ROW I RECEPT
#14
160
ROW I RECEPT
#16
BLANK
BLANK
BLANK
180
TELCO RECEPT
#2
900
VA PER PHASE
1800
TOTAL VA
15
TOTAL AMPS/PHASE
3.2
TOTAL KVA
17
AMPS X 110%
UPS1TP1
200A,
120/240VAC,
1(0/3W,
60Hz, M.BKR
LOAD
VOLT
AMPS
''I I'':
BREAKER
WIRE
VOLT
AMPS
LOAD
A
B
P
ITRIP
ITRIP1
P
I
I A
B
ROW
3 RECEPT #1
180
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
1 20 1
1 1 20 3
1 1 1 20 5
1 20 7
1 1 1 20 g
1 1 20 it
1 20 13
1 20 15
1 20 17
1 20 Ig
1 20 21
1 20 23
1 20 25
1 20 27
1 20 2q
1 20 31
33
35
37
39
WIRE TYPE TO BE THHN
2 20 1
4 20 1
6 20 1
8 20 1
10 20 1
12 20 1
14 20 1
16 20 1
18 20 1
20 20 1
22 20 1
24 20 1
26 20 1
28 20 1
30 20 1
32 20 1
34
36
38
40
UNLESS NOTED
1 12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
1 1&0
ROW 3 RECEPT
#2
ROW 3 RECEPT #3
180
180
ROW 3 RECEPT
#4
ROW 3 RECEPT #5
150
180
ROW 3 RECEPT
#6
ROW 3 RECEPT #7
180
180
ROW 3 RECEPT
#8
ROW 3 RECEPT #q
180
180
ROW 3 RECEPT
#10
ROW 3 RECEPT #11
180
180
ROW 3 RECEPT
#12
ROW 3 RECEPT #13
180
I80
ROW 3 RECEPT
#14
ROW 3 RECEPT #15
180
180
ROW 3 RECEPT
#16
ROW 2 RECEPT #17
180
160
ROW 2 RECEPT
#18
ROW 2 RECEPT #19
180
180
ROW 2 RECEPT
#20
ROW 2 RECEPT #21
180
180
ROW 2 RECEPT
#22
ROW 2 RECEPT #23
180
180
ROW 2 RECEPT
#24
ROW 2 RECEPT #25
180
180
ROW 2 RECEPT
#26
ROW 2 RECEPT #27
180
1130
ROW 2 RECEPT
#25
ROW 2 RECEPT #2q
180
180
ROW 2 RECEPT
#30
ROW 2 RECEPT #31
180
180
ROW 2 RECEPT
#32
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
VA PER PHASE 1
1440 1
1440
1440
VA PER PHASE
K240
2880
TOTAL VA
24
TOTAL AMPS/PHASE
5.8
TOTAL KVA
26
AMPS X 110%
UPS2TP4125A,
120/240VAC,
1(p/3W,
60Hz, M.BKR
LOAD
VOLT
AMPS
WIREBREAKER
BREAKER
WIRE
VOLT
AMPS
LOAD
A
B
P
TRIP
TRIP
P
A
B
ROW I RECEPT #1
ROW 1 RECEPT #3
ROW 1 RECEPT #5
ROW I RECEPT #7
ROW I RECEPT #q
ROW 1 RECEPT #11
RQW 1 RECEPT #13
ROW 1 RECEPT #15
BLANK
BLANK
BLANK
TELCO RECEPT #3
VA PER Fi�ASE
180
180
180
180
720
180
180
180
180
180
900 1
12
12
12
12
12
12
12
12
12
1 20
1 20
1 20
1 20
1 20
1 20
1 2013
i 1 20
I 20
WIRE TYPE
1
3
5
7
q
11
15
17
lg
21
23
TO BE THHN
2 20 1
4 20 1
6 20 1
8 20 1
10 20 1
12 20 1
14 20 1
16 20 1
18
20
22
24 20 1
UNLESS NOTED
12
12
12
12
12
1 12
1 12
12
12
160
ROW 1 RECEPT
#2
150
ROW I RECEPT
#4
180
ROW I RECEPT
#6
160
ROW I RECEPT
#8
180
ROW 1 RECEPT
#10
180
ROW 1 RECEPT
#12
150
ROW I RECEPT
#14
180
RQW I RECEPT
#16
BLANK
BLANK
BLANK
180
TELCO RECEPT
#4
720
900
VA PER PHASE
1440
1800
TOTAL VA
12
15
TOTAL AMPS/PHASE
3.2
TOTAL KVA
17
AMPS X 110%
` UPS2TP2 200A,
120/240VAC,
1(p13W,
60Hz, M.BKR
LOAD
VOLT
AMPS
WIREBREAKER
JBREAKERJNIREJVOLT
AMPS
LOAD
A
B
I
I P
TRIP1
TRIP1
P
I
A
IB
ROW
3 RECEPT #I
180
12
12
12
12
12
12
12
12
12
12
12
12
12
12
1 20 1
1 20 3
1 20 5
1 20 7
1 20 g
1 20 11
1 20 13
1 20 15
1 20 17
1 20 lg
1 20 21
I 20 23
1 20 25
1 20 27
1 20 2q
1 20 31
33
35
37
3g
WIRE TYPE TO BE THHN
2 20 1
4 20 1
6 JO 1
8 20 1
10 20 1
12 20 1
14 20 1
16 20 1
18 20 1
20 20 1
22 20 1
24 20 1
26 20 1
28 20 1
30 20 1
32 20 1
34
36
Be
40
UNLESS NOTED
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
180
ROW 3 RECEPT #2
ROW 3 RECEPT #3
180
180
ROW 3 RECEPT
#4
ROW 3 RECEPT #5
180
180
ROW 3 RECEPT
#6
ROW 3 RECEPT #7
180
180
ROW 3 RECEPT
#8
ROW 3 RECEPT #q
180
ISO
ROW 3 RECEPT
#10
ROW 3 RECEPT #11
180
180
ROW 3 RECEPT
#12
ROW 3 RECEPT #13
180
180
ROW 3 RECEPT
#14
ROW 3 RECEPT #15
150
180
ROW 3 RECEPT
#1(o
ROW 2 RECEPT #17
180
180
ROW 2 RECEPT
#18
ROW 2 RECEPT #19
180
180
ROW 2 RECEPT
#20
ROW 2 RECEPT #21
180112
180
ROW 2 RECEPT
#22
ROW 2 RECEPT #23
I80
ROW 2 RECEPT
#24
ROW 2 RECEPT #25
15012
180
ROW 2 RECEPT
#26
ROW 2 RECEPT #27
I80
ROW 2 RECEPT
#28
ROW 2 RECEPT #29
I80
180
ROW 2 RECEPT
#30
ROW 2 RECEPT #31
180
180
ROW 2 RECEPT
#32
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
VA PER PHASE
1440
1440
1440
VA PER PHASE
K24
2880
TOTAL VA
24
TOTAL AMPS/PHASE
5.8
TOTAL KVA
26
AMPS X 110Y
Arm`
I= rr-
'I 'b
Lo
to 9
�0 ...r� z0
en
O � N
O W to
LO
�co
0 cv
d
U I
0
W o0
cv�
co
0
4
X
W
V)
00
J
W
co
W
Z
2=
a
0®
Q
0
tV
0.
t�
2
J
00
r
W
r
CD
J me
LL n
A
� M
C) W
� m
< z
� z l-Wi 3
d Q
(Y (Y
IL Q
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
E1.1
ALARM NOTES:
L ALL ALARMS TO BE NORMALLY CLOSED.
2. UNSHIELDED SINGLE TWISTED PAIR WIRE IN STANDARD.
TO TBG IN BYPASS
ALARM BLOCK #1
(NC -RED)
ALARM BLOCK #2
ALARM BLOCK #3
TO TBG IN BYPASS
BRIDGE CLIP
(TYP)
(C-BLK)
RED
1
0 0
0
0
1
0 0 0
0
DOOR ALARM
DAl-NC
2
2
GEN PRE HIGH COOLANTS(
GP#CT5-NC
2
C
#22 SOLID
DAI-C
WHITE
0 o
WHITE
0 0 0
o
TEMP SHUTDOWN l
GPNCTS-C
0 0 0
o
3
o 0 0
o
RED
3
o
#22 SOLID
3
0 0 0
0 C
DOOR ALARM GEN ROOM
ff
1 DA2-NC
4
UPS2 RUN J
r UPSI 12-NC
4
GEN LOW COOLANT 1
GLCTW-NC
#22 SOLID
l DA2-C
0 0 0
0
o
#22 SOLID l
UPSI 14-C WHITE
o
TEMP WARNING 1
GI-C
4
0 0 0
0
o C
5
5
#22 SOLID
5
[
RED
O
RED
O 0
RED
0 0
SMOKE DETECTOR
r
1 DI -NC
6
UP52 BYPASS J
r UPSI 12-NC
6
E�jGEN
LOW COOLANT LEVEL
GLTL-NC
6
tt22 SOLID
l DI-C
WHITE
� �
tt22 SOLID
1 UPSI 17-C WHITE
O �
tt22 SOLID
GLTL-C WHITE
o 0
�-1
7
�] O �
o
RED
7
� �
RED
7
O 0
[
FIRE PANEL TROUBLE
NPT-NC
{
$
UP52 POWER FAIL
{
UPSI I2-NC
6
GEN COOL TEMP FAIL
{
GCTSF-NC
8
tt22 SOLID
NPT-C
O 0 O
O
tt22 SOLID
UP51 II-C WHITE
tt22 SOLID
GCTSF-C WHITE
0
RED
9
� O
RED
9
0 O
RED
9
O O
� r
L
HIGH/LOW TEMP
r
J NTA-NC
10
UPS2 FAIL J
UPSI 12-NC
10
GEN HIGH BATT VOLTAGE
GNBVW-NC
10
tt22 SOLID
l PTA-C
WHITE
0 0
tt22 SOLID l
UPSI 14-C NHITE
=
#22 SOLID
GLBVW-G NHITE
0 0
11
� 0 0
o
RED
11
0 O
RED
11
0 0
�
HIGH/LOW HUMIDITY
PHA -NC
12
UP52 LOW BATTERY
UPSI 12-NC
12
GEN LOW BATT VOLTAGE
{
GLBVW-NC
12
tt22 SOLID
HHA-C
0
tt22 SOLID
UPSI 17-C NHITE
#22 SOLID
GLBVW-C WHITE
O O
�E
RED
13
0 0
RED
13
� �
0
13
� � �
0
O [
AC POWER FAIL
J PFA-NC
14
UPS2 SUMMARY
{
UPSI 12-NC
14
GEN #22HSOLID {
GNF-NC
14
C
#22 SOLID
l PFA-C
WHITE
#22 SOLID
UPSI 11-C WHITE
GNF-C
O O
O
0 o
RED
15
0 0
15
0 0 0
o C
SURGE ARRESTOR #2
J LA2-NC
GEN RUN J
GRN-NC
16
GEN LOW FUEL SHUT
GLFS-NC
16
[
tt22 SOLID
1 LA2-00
o
tt22 SOLID l
GRN-C WHITE
0 0
tt22 SOLID
GLFS-C
0 0 0
o
0 o
RED
17
o a
RED
17
0 0
C
#VAC FAIL
1 NVAC LO-NC
GEN FAIL
GFL-NC
18
GEN LOW FUEL
{
GLF-NC
18
C
tt22 SOLID
1 NVAC LO-00
o
tt22 SOLID
GFL-C WHITE
0 0
tt22 SOLID
GLF-C WHITE
0 0
123
0 0
o
RED
19
0 0
19
O
[
IST ALARM
JFIRE 5YS-NC
GEN DISABLE
{
GDA-NC
20
GEN DL/##22TSOLID
O
GGDLFTINC
20
[
#22 SOLID
l FIRE SYS-00
0
0
tt22 SOLID
GDA-C WHITE
0 o
IDI
o
0 0
o
21
0 0 0
o
21
0 0 0
o
GEN ROOM IST ALARM
i(FIRE SYS-NC
GEN OVERSPEED
{
GOS-NC
22
GEN DL/LP TANK 2
{
GDLFT2-NC
22
C
#22 SOLID
l FIRE SYS-C
0 0
0
#22 SOLID
GOS-G
0 0 0
0
#22 SOLID
GDLFT2-C
0 0 o
a
0 0
0
23
0 0 0
0
23
0 0 0
o
RF LN DEHYDRATOR
(DENYDTR-NC
24
GEN UNDERSPEED
GUS-NC
24
GEN DL/LP TANK 3 j
GDLFT3-NC
24
C
tt22 SOLID
SOLID
l DENYDTR-C
O O O
0
tt22 SOLID
GUS-C
0 0 0
0
1
tt22 SOLID ll
GDLFT3-C
0 0 0
0
RED
25
0 0
25
0 0 0
0
25
0 0 0
o C
TOWER LIGHT FAIL
r
J TWR LGT-NC
26
GEN OVERCRANK J
GOG-NC
26
r
GEN DL/LP TANK 4 J
GDLFT4-NC
26
C
tt22 SOLID
1 TWR LGT-C
WHITE
O O
#22 SOLID l
GOC-G
tt22 SOLID t
GDLFT4-C
O O
O
RED
27
0
0
0 0
0
0
7
O
L_
SURGE ARRESTOR #IJ
LAI-NC
28
GEN RPM SENSOR LOSS 1
GRSL-NC
28
GEN REMOTE START
GRS-NC
28
[
tt22 SOLID
l LAI-C
WHITE
o
0
tt22 SOLID l
GRSL-G
0 0
0
0
tt22 SOLID
GRS-C
o
0
�
RED
29
O O
29
O O �
O
29
O O O
O C
GROUND BAR THEFT
J GND-NC
30
GEN OVER VOLTAGE J
GOV-NC
30
GEN REMOTE STOP f
GRSP-NC
30
C
#22 SOLID
l GND-C
W#ITF
0
#22 SOLID l(
GOV-C
#22 SOLID
GRSP-C
0 0
o
31
0 0 0
O O
O
32
GEN UNDER VOLTAGE)
GUV-NC
31
r
GEN HIGH TEMPI
GHT-NC
31
C
0 0 0
0
o
#22 SOLID 1
GUV-G
O
#22 SOLID 1
GNT-C
O 0
O
33
O O O
O
33
33
O O
O C
TO TBG IN BYPASS
GEN OVER FREQ
GOF-NC
(NC -RED)
34
O O
O
#22 SOLID {
GOF-C
34
O O 0
0
34
O O O
O C
TO TBG IN BYPASS
35
35
35
(G-BLK)
36
0 0 0
o
GEN UNDER FREQ
{
GUF-NC
36
0 0 0
o
ATE, NORMAL POWER
{
TBI-I-NC RED
36
0 0
0 0
o
#22 SOLID
GUF-C
0 0 0
0
#22 SOLID
TB1-3-C WHITE
0 0
37
0
0
37
0 0 0
o
RED
37
0 o
C
GEN LOW OIL PRES
{
GLOP -NC
38
ATS STANDBY POWER
{
TBI-G-NC
38
TB #15
WHITE
E39
0 0 0
o
tt22 SOLID
GLOP-C
O O
O
#22 SOLID
TBI-B-C WHITE
o
RED
0
39
0 0 o
o
39
o 0
0 E
UPSI RUN1
r UP51 12-NC
41
GEN HIGH OIL PRES
{
CHOP -NC
40
ATS REMOTE START
{
RS-NC
41
0
#22 SOLID
l UPSI 14-C
WHITE
0
#22 SOLID
GHOP-C
o a o
o
tt22 SOLID
PS-C
0 o a
o
RED
41
o
41
0 0 0
o
41
0 o
o [
UPSI BYPASS
� UPSI 12-NC
42
GEN OIL PRES FAIL �
GOPF-NC
42
r
TRANSFER COMPLETE 1
75I-2-NC
42
C
#22 SOLID
UPSI 17-C
NHITE
0 0
#22 SOLID
GOPF-G
o
o
tt22 SOLID l
TBI-4-C
o O
O
RED
43
0 0
43
0 0 0
0
43
o 0 0
0 [
UPSI POWER FAIL
1 UPSI 12-NC
44
f
GEN OIL TEMP FAIL J
GOTF-NC
44
E
#22 SOLID
l UPSI II-C
NHITE
0 o
tt22 SOLID l
GOTF-C4
0 0 0
0
0 0 0
o
RED
45
45
0 0 0
0
45
0 0 0
o C
UPSI FAIL
UPSI 12-NC
GEN PRE HIGH OIL
GPNOPW-NC
#22 SOLID
f UPSI 14-C
WHITE
Al0
0
PRESSURE WARNING
GP#OPW-C
46
0 0 0
0
0
46
0 0 0
0
0 C
RED
0 o
tt22 SOLID
47
0 o a
o
47
0 0 0
0
UPSI LOW BATTERY
UP51 12-NG
GEN PRE HIGH OIL
GPNOTW-NC
422 SOLID
f UPSI I7-C
NHITEO
O
TEMP WARNING
GPHOTW-G
48O
O
O
48
[
V
tt22 SOLID
49
49RED�
O
� O 0
�UPSI
SUMMARY
f UPSII2-NC
GEN START INHIBIT1
GSIOP-NC[#22
50
50
SOLID
UP51 II-CWHITE
0
OIL PRESSURE i
GSIOP-C
O O O
O
O 0 0
O
#22 SOLID
CONNECTOR
CONNECTOR
CONNECTOR
AT
BLOCK
AT
BLOCK
AT
BLOCK
STAIYPS AND SEALS
ALARM BLOCKS
SCALE: NONE
a�=�mW�'ZQ
Zmi 9i w3�i
aQazapp[�
�-ZaEwZpO� ~
zwaqtyu�_ Foal
Wi
Z F iv
w
W
W
Q
J
U)
Q
Do
ON
Q
O
�
^
�
J
Q
r
r
W
J
LL
'O
V
•� w
w C0
CID
Q � �
z Z
L
O Q
CL Ca
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Wagner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
El m2
CONNECT EQUIPMENT GROUND TO GROUND
BAR HERE TO THIS LOCATION ONLY
Al id
SERVICE GROUND
COIL EXIT
INSTALL GBKI4 TO SIDE OF ENCLOSURE WITH #10 BOLTS AND
NUTS. (REMOVE PAINT AND USE NO-OX) GROUND EACH DSWPH03
TO GBKI4. CONNECT #2 TO THE ENCLOSURE WITH 2-HOLE LUG
(PLACE #2 AS CLOSE AS POSSIBLE TO THE #10 BOLTS) AND
RUN AS SHOWN TO THE MGB AND CONNECT WITH A 2-HOLE LUG.
❑ ❑ ®0
O
❑ ❑
a
E
101
#2 GREEN TO UPS
TERMINAL STRIP
WALL D
4'-I"
—T
I' -8"
lr�
CONNECT CABLE LADDER TO GROUND
BAR MERE TO THIS LOCATION ONLY
ROW 3
WALL C
3'-0"
ROW 2 ROW I
M
�
®I I® ®I
I — II 11 p II 11 11 U II
loom
11
�MISM MOM!�
I u u e
I)
c
N
N
B �
11 �
O C
N N
c
w
L J FolI �I
❑ ' lIX3> I I II
WALL A
GROUNDING LAYOUT
SCALE 1/2"=1'-0"
CABLE LADDER:
L CABLE LADDER IS TO BE 8'-0" A.F.F. AND INSTALLED IN ACCORDANCE WITH ARTICLE 392
OF THE NEC LEVEL TO WITHIN 1/8" IN 10' OR SIMILAR.
GROUNDING:
I. ALL GROUNDING EXCEPT FOR CABLE LADDER TO CONFORM TO ARTICLE 250 OF THE NEC.
2. CABLE LADDER GROUNDING TO CONFORM TO ARTICLE 392.60 OF THE NEC.
#2 BARE STRANDED COPPER IPGB ON 4" PANDUIT
STANDOFFS EVERY 24" (PRT. #PP2S-5I0-C), CONNECTED
TO MASTER GROUND BAR. ALL CONNECTIONS SHALL BE
MADE WITH BURNDY COMPRESSION FITTINGS AND ALL
BENDS SHALL BE 8" MIN. RADIUS.
WALL B
v
ww p?
z W W Z W Z
w eQoE>-op[Qz
a z=�
w
NQ�a�uEa�� y}C'
0.'VUOQ3j
zF
LL
F
W
W
J
—
C
a�
-
J
-
C
0
o
2
C
ON
�X
O-
2
oo
—
C
r
c:
J
LL
TE:
3/8/1�
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Wagner
SERIAL NUMBER:
1603-10y
SCALE 24X36:
NONE
SHEET:
E2
INSULATOR
CEILING
® THREADED ROD \
CABLE LADDER
(8) 1/2" FLAT WASHER
(8) 1/2" LOCK WASHER
(8) 1/2"-11 NUT
BRACKET, HANGER, PLATE
WITH 129/32" SLOT
LADDER INSTALLATION DETAIL
SCALE: NONE
EXTENSION BARS
THROUGH WALL
WALL MOUNTING
BRACKET
0
0
19,
0
p
0
0
0
0
0
B,
O
O00�
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 0
0
0
0
0
0
®
0
0
0
® 0
0
GROUND BAR
INTERIOR GROUND BAR DETAIL
SCALE: NONE
1/4"-20
2 HOLE LUG HEX BOLT
#6 GREEN �I/4" FLAT
WASHER
PRIMARY GROUND" �`�-1/4" LOCK
BAR/METAL WASHER
ENCLOSURE
LOCK NUT
HEX BOLT
-LOCK WASHER
I. SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS,
2. BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT.
3. APPLY ANTI -OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN
EXCESS COMPOUND.
4. ONLY ONE LUG PER SET OF BOLTS.
GROUNDING CONNECTION
SCALE: NONE
3/4" PVC FOR
GROUND ACCESS
I PVC CAST IN WALL
450 PVC NIPPLE DETAIL
SCALE: NONE
(INSTALLED ON SITE)
EXTERIOR GROUND BAR DETAIL
SCALE: NONE
CABLE LADDEP
CORNER
HOLE LUG
#6 GREEN
1/4"
55, 1/4"-20
TO MGB
#6 GRE
GROUN
#6 GRE
RACK
TO Ml
EQUIPME
GROUND B
#6 GREEN
GROUND B
(TYI
EXAMPLE 1 EXAMPLE 2
I. IF RACK HAS A GROUND BUS BAR (EXAMPLE 1 8 2) ALL EQUIPMENT GROUNDS SHALL
BE CONNECTED TO THE EQUIPMENT BUS BAR VIA #/n GRN. A #2 GRN SHALL THEN BE
TAKEN FROM THE GROUND BUS BAR TO THE EQUIPMENT GROUND BUS CONDUCTOR.
2. ALL EQUIPMENT GROUND SPLICES SHALL BE TAPED WITH GREEN TAPE.
EQUIPMENT GROUNDING ELEVATION EXAMPLE
REFER TO ONLY WHEN EQUIPMENT IS INSTALLED. VIEWED FROM REAR OF EQUIPMENT
SCALE: NONE
GROUND
USE WHITE BASE AS TEMPLATE t DRILL 1/4" HOLES
6"O.C. STAGGERED FROM LEFT TO RIGHT AND SECURE
DURO-LAST VINYL BASE WITH 1/4"XI-1/4" NYLON ANCHOR
4 VINYL BASE DURO-LAST #1571 (WHITE)
FASTEN WITH NYLON DRIVE RIVETS
BOLT (NO METAL TO BE USED)
K WASHER 2" GROUND STRAP
BROWN VINYL COVER
DURO-LAST #1572 (TAN)
GROUND RING (REFER TO
MANUFACTURERS
INSTALLATION INSTRUCTIONS)
a`.
d BUS
BASE It COVER SHALL
EXTEND G" BELOW
GRADE, CUT OFF EXCESS
GROUND BAR/STRAP/COVER DETAIL
SCALE: NONE
TO IPGB RING
11 METAL DOOR FRAME
551 1/4"-20 BOLT II
WITH FLAT WASHER 2 HOLE LUG G 2" REF.
T ItB 54205
ACROSS EVERY LADDER TO LADDER
CONNECTION
CABLE LADDER BOND DETAIL
SC:` -LE: NONE
DOOR
1/4" X I" BOLT t
1/4" FLAT WASHER
HINGE LINE DOOR BONDING
STRAP
r%e%f%o Qf1Al1'liRlf_ 11CTA ll
SCALE: NONE
"C" TAP
YC2C4
1/B" MIN.
1/4" MAX.
8" RADIUS ALL AXES
#2 STRANDED
NON -JACKETED
GREEN
TO GROUND ITEM--
IPGB RING GROUND TAP
SCALE: NONE
VTrl_T ]gawVDIRT
NEWTON BRACKET 2105
LOCATE ON CABLE
LADDER EVERY 18"
#2 STRANDED GREEN SECURE
TO BRACKET WITH TY-WRAPS
NEWTON BRACKET GROUND
SCALE: NONE
BRACKET PANDUIT
PP25--510-C
TY-RAP Tt5
#10 X 1-1/2" HHW
PLATED SHEET
METAL SCREW
#2 STRANDED'
NON -JACKETED
(2) TY-RAP T48 TY24M
FEED ONE OVER AND
ONE UNDER
IPGB GROUND INSTALLATION
SCALE: NONE
GROUNDING NOTES:
I. USE NO-OX AT ALL GROUND TERMINATIONS.
2. IN PLACES WHERE THE GROUND BUS WIRE IS LESS THAN 2" FROM METALLIC OBJECTS AND NOT
BONDED, NEATLY TAPE THE SECTION WITH GREEN TAPE. WHERE NECESSARY, REMOVE THE TIE
WRAPS (AND RE -INSTALL AFTER TAPING) AND TAPE C-TAPS FIRST AND THEN TAPE PAST
THEM IN A CONTINUOUS WRAP.
3. PLACE HEAT SHRINK TUBING ON GROUND BAR PIGTAILS THAT GROSS WALL MOUNTED CONDUIT.
4. ALL DOORS TO BE GROUNDED TO THEIR FRAMES WITH WELDING WIRE. USE #2 GAUGE WELDING
WIRE AND STANDARD BURNDY TWO -HOLE LUGS. PLACE A 2" BAND OF GREEN TAPE AT EACH END
OF THE JUMPER.
5. INTERIOR PERIMETER GROUND BUS (IPGB): #2 BARE STRANDED COPPER AROUND INSIDE
PERIMETER OF BUILDING WITH EACH END LUGGED TO THE GROUND BAR.
6. BONDING JUMPERS: #6 GREEN STRANDED INSULATED WIRE FROM METALLIC EQUIPMENT TO IPGB
AND ACROSS LADDER RACK SPLICES/CROSSES/TEES,
7. EQUIPMENT GROUND BUS: #2 GREEN RAN OUTSIDE EACH RUN OF CABLE LADDER WITH NEWTON
CLIPS (#2106G).
"G" TAP #2 STRANDED
YC2C2—\ GREEN
„ #2 STRANDED
1/8 MIN GREEN
1/4" MAX.
8" RADIUS ALL AXES
EQUIPMENT GROUND TAP
SCALE: NONE
STAMPS AND SEALS
u w z
os'd wr8 °�
}�F f�l w
F
mnftn�_@Q S
'imp
t o
zo
ca
�z
A4 c
®w
ftS d
Qr' 0
J� cv
� I
co
0 �+
U I
O
O O
rTl G CD
WGo
� q
a
�
W
J
v+ W
P
o
aco
O
Z
O N
z
F
OX
00
0
ce
P
r
DATE:
3/5/16
SALES [MANAGER:
D. Brunswick
DRAWN BY:
J. Wa ner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
Ell
k
uw.w
5/32" DIA. l ��
(TYP 8 PLACES)
11A. NOLE
(TYP 4 PLACES)
WIREMOLD SIMPLEX COVER
SCALE: NONE
2 EACH REQUIRED
5/32" DIA. ,, 1_
(TYP 8 PLACES)
_ _.A. HOLE
(TYP 4 PLACES)
WIREMOLD SIMPLEX COVER
SCALE: NONE
EMT CONNECTOR
EMT CONDUIT �
RIGID COUPLING
CABLE LADDER J
90° LIQUIDTITE CONNECTOR
STRAIGHT LIQUIDTITE
CONNECTOR
CEILING
�— LIQUIDTITE
CONDUIT
WIREMOLD
4 WIREMOLD CONNECTION
SCALE: NONE
(DO NOT RUN CONDUITS THROUGH CABLE LADDER)
(CONDUIT SHALL LINE-UP WITH BLANK COVER PLATE)
REAR WALL
�TOP TOP —
CEILING
3"x3"xl/4" ALUMINUM
ANGLE
114" BOLT AND NUT
)R (USE 2 EACH
EMOLD RUN)
WIREMOLD
WIREMOLD INSTALLATION DETAIL
SCALE: NONE
INSULATORS SHALL BE PLACED AS
CLOSE TO CABLE LADDER AS POSSIBLE
CIRCUIT #I
CIRCUIT #17 CIRCUIT
CIRCUIT #2
CIRCUIT #I8 CIRCUIT
CIRCUIT #3
CIRCUIT #Iq CIRCUIT
CIRCUIT #4
CIRCUIT #20 CIRCUIT
CIRCUIT #1 CIRCUIT #17
CIRCUIT #2 CIRCUIT #18
CIRCUIT #3 CIRCUIT #lq
CIRCUIT #4 CIRCUIT #20
CIRCUIT #5
CIRCUIT #21 CIRCUIT
CIRCUIT #6
CIRCUIT #22 CIRCUIT
CIRCUIT #7
CIRCUIT #23 CIRCUIT
CIRCUIT #84
CIRCUIT #24 CIRCUIT
—STOP
IT #1
IT #2
IT #3
IT #4
24 EACH REQUIRED
CIRCUIT #q
CIRCUIT #10
CIRCUIT #5
CIRGUIT #6
CIRCUIT #7
CIRGUIT #8
CIRCUIT #21
CIRCUIT #22
CIRCUIT #23
CIRCUIT #24
CIRCUIT 325
CIRCUIT #26
CIRCUIT #q
CIRCUIT #10
CIRCUIT #5
CIRCUIT #6
CIRCUIT #7
CIRCUIT #8
CIRCUIT #11
CIRCUIT #27
CIRCUIT #11
CIRCUIT #12
CIRCUIT #28
CIRCUIT #12
CIRCUIT #q
CIRCUIT #25
CIRCUIT #q
CIRCUIT #10
CIRCUIT #26
CIRCUIT #10
CIRCUIT #11
CIRCUIT #27
CIRCUIT #II
CIRCUIT #12
CIRCUIT #28
CIRCUIT #12
CIRCUIT #13
CIRCUIT #29
CIRCUIT #13
CIRCUIT #14
CIRCUIT #3
CIRCUIT #14
GROUND TO BE PLACED TOWARD THE TOP
CIRCUIT #15
CIRCUIT #31
CIRCUIT #15
(TOP HALF OF WIREMOLD)
CIRCUIT #16
CIRCUIT #32
CIRCUIT #16
WIREMOLD COVER SHALL BE LABELED
CIRCUIT #13
CIRCUIT #2q
CIRCUIT #13
WITH THE PANEL # IN THE CENTER,
/uPSITPI
CIRCUIT #14
CIRCUIT #30
CIRCUIT #14
AND THE CIRCUIT # UNDER EACH
CIRCUIT #15
CIRCUIT #31
CIRCUIT #15
RECEPTACLE AS SHOWN BELOW:
CIRCUIT #16
CIRCUIT #32
CIRCUIT #16
UPSITPI
UPS2TP2
UPS2TP2
UPSITPI
UPSITP3
UPS2TP4
/a
ea la la
ROW 3
ROW 2
ROW I
0
0 0 0
o
Oa
a o 0
Da Oa Oa
0 0 0
0
0 0 0
CKT #1
GKT #2 CKT #3 CKT #4
GROUND TO BE PLACED TOWARD THE BOTTOM
WIREMOLD
CIRCUIT LOCATION
(BOTTOM HALF OF WIREMOLD)
SCALE: NONE
SIMPLEX RECEPTACLE _ORIENTATION
SCALE: NONE
RECEPTACLES TO BE PLACED ON REAR SIDE OF EQUIPMENT.
UPS] CIRCUITS TO BE ON TOP HALF OF WIREMOLD.
UPS2 CIRCUITS TO BE ON BOTTOM HALF OF WIREMOLD.
STAMPS AND SEALS
Lo 'Cf
co 00
4
z0
OQ ��
®�
� O>
O
Lo
q �
0�I
O
CX? co
W co
Lo N
w
W
m
J
ui
Q
to
J
0
J
O®
�
®N
bo
1
r
r
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
E 3
)IL 50' OF GENERATOR
)NTROL AND ALARM
RES
WALL D
Al
4'-2" MAX.
lk
F
WALL C
vi u
■il�■i�����ll��
11
11
11
I
:,
NMI
IWO
■
� ■
�
1
■I/!
�I!�
III
I
I�
�
�
■■■1�1�-
;��
■III,
mol■L,J■���■Ilril�■�■�■�1Ilrml
Emmillmilim
:
■■ ■■��
■iillilfl-
� �■IIIIIII!�
■ I �IIIIIIII
-i
������1■III■�■����Illlrl
��III■I-
IIII■Ir��
�,I
I r
,
j�
11
1
.;III!■
!!lllllll■�
IIIIIIII■
I I 111
III■r'I
1
11
—._�.
unui���innn��■�ni�lll���
WALL A
ELECTRICAL DIMENSIONS
SCALE 1/211=1'-0"
COMMERCIAL POWER:
I 120/240VAC, 300AMP SINGLE PHASE SERVICE. I
CONDUIT RUNS:
I. ALL CONDUIT RUNS TO BE EMT UNLESS STATED OTHERWISE.
2. ALL CONDUIT RUNS TERMINATING AT SERVICE ENTRANCE EQUIPMENT SHALL CONTAIN BONDED
BUSHINGS.
3. NIRENAYS CARRYING 3 OR MORE CURRENT CARRYING CONDUCTORS SHALL BE DEBATED PER
TABLE 310-15(B)(3)(o) OF APPLICABLE EDITION OF THE NEC.
4. CONDUIT FILL IS BASED ON CHAPTER 9, APPENDIX C OF THE NEC.
WALL B
STAMPS AND SEALS
�zl-=mNWWDWD
Ou GrI
-Z DxaDO�Nw
z � ozw
8a i ax�
�a"BQ�WZ !-
Hwya 0 aw�
Ng� yZjzUQ
~ wo D-<,
Z� a
�j O
�./ .Q
zo
O� 0
�co
0
U I
0
00
W c\? co
0
0
10
Z
w
O
J
(J)
Z
�
=
W
aco
J
-
p
00
Q
ON
H
XU
2
0
U
w
W
J
W
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603 -105
SCALE 24X36:
NONE
SHEET:
E4
v
a
COIL 50' OF
ALARM WIRE
TO TB6 IN BYPASS
(C-BLK)
DSWPH03 MODULE
SCALE: NONE
TO TB6 IN BYPASS
(NC -RED)
TBI
TO TERMINAL
BOARD
LI
L2
120V SURGE PROTECTOR MODULE
SCALE: NONE
TO T66
IN BYPASS
(C-BLK)
WNITE/GREEN
TO T66 IN
(NC -RED)
2 a
BYPASS
TBI
o o
a
5
3
o
r�
UPSI
12-NC
l
l UPSI
RUN
4
UPSI
14-C
J #22
SOLID
7
GREEN/WNITE
0
0
UPSI
12-NC
1 UPSI
BYPASS
JUMPER s
o 0
0
UPSI
17-C
J #22
SOLID
W41TE/BROWN
7
0 0
0
UP51
12-NC
UPSI
POWER FAIL
18
BROWN/WHITE
EV
0 0
0
UPSI
II-C
#22
SOLID
1q
WNITEBLUE
9
0 o
p
UPSI
12-NC
l
L UP51
FAIL
10
UP51
14-G
J #22
SOLID
21
GRAY/WNITE
ORANGE/WNITE
19
UPSI
12-NC
UP51
LOW BATTERY
p
12
UPS
17-C
#22
SOLID
9
WHITE/ORANGE
0 0
BLUE/WHITE
13
0 0
0
UPSI
12-NC
UP51
SUMMARY
6
WNITE/GRAY
14
UPSI
ll-C
#22
SOLID
UPS1 ALARM CONNECTIONS
SCALE: NONE
NOTE:
I. LEIBERT 20kVA UPS 25-PIN INTERFACE CABLE CONNECTION
DAI
DOOR
ra� ''�ALARM
HTA
HIGH
TEMP
ALARM
SERI ES
ALARM
LOW
TEMP
ALARM
150I4
LOW
° HUMIDITY
ALARM
NIGH
° HUMIDITY
ALARM
DI
SMOKE
[ q-- I ALARM
MISC. DIAGRAMS
SCALE: NONE
ALARM
UP52
12-NC
} UPS2 RUN
UP52
14-C
#22 SOLID
UPS2
12-NC
l
LUPS2 BYPASS
UP52
17-C
J #22 SOLID
UP52
12-NC
UPS2 POKER FAIL
UPS2
Il-C
J SOLID
UP52
12-NC
l#22
L UP52 FAIL
UP52
14-C
J #22 50LID
UPS2
12-NC
UP52 LOW BATTERY
UPS2
17-C
#22 SOLID
UP52
12-NC
UPS2 SUMMARY
UPS
II-C
#22 SOLID
UPS2 ALARM_CON_NEC_TIONS
SCALE: NONE
NOTE:
I. LEIBERT 20kVA UPS 25-PIN INTERFACE CABLE CONNECTION
LAI
PRIMARY SECONDARY
SUPPRS50R SUPPRESSOR
C NO NC C NO NC
u
C NC
NOT USED NOT USED
LA2
PRIMARY SECONDARY
SUPPRESOR SUPPRESSOR
C NO NC C NO NC
u
C NC
NOT USED NOT USED
ONE -LINE WIRING DIAGRAM
SCALE: NONE
NO -L -BLACK
C WHITE USE 3/22 AWG SOLID WIRE
NC RED
(NON-SHEILDED)
ALARM WIRE COLOR CODE
SCALE: NONE
SWITCH
CIRCUIT \_��
BREACKER ff
PHOTO CELL LIGHT
EXTERIOR LIGHT CIRCUIT
SCALE: NONE
CIRCUIT
BREAKER
POWER
FAIL
ALARM
POWER FAIL DIAGRAM
SCALE: NONE
HVAG-1 FAIL HVAC-2 FAIL
ALARM ALARM
NC NC
0 0
c c
HVAC_FA_I_L DIAGRAM
SCALE. NONE
STAMPS AND SEALS
Q �NOul z
Zi 1-taW W
=a�ZE 4
o
J
ui
In
/Q
NV
V
W
J
W
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Na ner
SERIAL NUMBER:
1603-105
SCALE 24X3G:
NONE
SHEET:
E5
3/81, "
TOP VIEW
C�
REAR VIEW
3/4" DIAMETER
m
5
n
3/4"-10 FERRULE
(2) PLACES EACH (2) PER
FERRULE, MIN. INTERIOR LIFT
DEVICE
3 1/2"
HOLD
3/4" DIAMETER
(TYP)
SIDE VIEW
LIFT DEVICE NOTES:
I. FLOOR AREA < 240 50. FT. 4 INTERIOR LIFT
DEVICE PER FLOOR
2. FLOOR AREA > 240 50. FT, 8 INTERIOR LIFT
DEVICE PER LOAD
INTERIOR LIFT -DEVICE
SCALE: 1-1/2" = 1'-0"
FLOOR LAYOUT
SCALE:
INTERIOR LIFT DEVICE SEE DETAIL THIS SHEET
#4 BAR GR. 60
3 SIDES #4 GR. 60 HOOK BAR
3/16"
A ° T
° 4 " ° m
� ;::::ri - %
1/2" x 5/16" STEEL ANGLE
m
SIDE VIEW
TOP VIEW
FLOOR INTERIOR LIFT DEVICE DETAIL
SCALE: 1-1/2" = 1'-0"
#4 GR 60 REBAR WITHIN I" OF
TOP SURFACE OF FLOOR
SEE INTERIOR LIFT DEVICE DETAIL
PERIMETER ANGLE
DOOR EMBED PLATE (TYP)
DETAIL FOR DOOR LOCATION
SCALE: 1-1/2" = 1'-0"
THIS DETAIL APPLIES ONLY WHEN LIFT
POINT 15 UNDER DOOR OPENING
`NTERIOR LIFT DEVICE
SEE DETAIL THIS SHEET
/ �3" MIN RADIUS
4
DO NOT SPLICE
WITHIN 24" EA.
SIDE OF LIFT
DEVICE
E a
OVERLAP 36" MIN.
n MID FLOOR CROSS TIE
SCALE: NONE
INTERIOR LIFT DEVICE
SEE DETAIL THIS SHEET
3" MIN RADIUS
OVERLAP 36" MIN.
END FLOOR CROSS TIE
5 SCALE NONE
ONE PER LIFT DEVICE PAIR REBAR: #4 GR 60.
3AR AT
JRS
#4 60 GkAur KCDAK A I i= v- .
TYPICAL FLOOR REBAR LAYOUT
SCALE; NONE
REBAR NOTES:
SHORT (TENSION) DIRECTION I" FROM BOTTOM OF CASTING BED
• LONG (TENSION) DIRECTION 1-3/4" OR JUST ABOVE TENSION REBAR
CASTING DETAIL NOTES:
REINFORCING BAR:
• REINFORCING BAR TO BE ASTM A615, LATEST REVISION, PLAIN BILLET STEEL
• REINFORCING BAR GRADE 60 OR HIGHER IS NOT PERMITTED FOR EMBED PLATE EXTENSIONS.
• REINFORCING BAR FOR SLAB STRENGTH AND T*S TO BE ASTM A615 GRADE 60.
• LIGHT RUST ACCEPTABLE PER ASTM A615, SECTION 12, SCALING AND PITTING NOT
PERMITTED.
• REINFORCING BAR BEND RADII SHALL NOT BE LE55 THAN SIX BAR DIAMETERS.
• LOCATION AND FORMING TOLERANCES: +/- 1/8"
• MAXIMUM CONCRETE COVER BETWEEN CASTING BED AND PRIMARY SLAB STRENGTH
REINFORCING BAR SHALL NOT EXCEED V.
• TRANSVERSE REINFORCING BARS (PRIMARY STRUCTURAL REBAR) SHALL NOT BE SPLICED.
• LONGITUDINAL REINFORCING BARS (Tt5 REBAR) MAY BE SPLICED - AT MOST EVERY 48" WITH
A MINIMUM OVERLAP OF 18"
WELDING:
• WELDING PRACTICE FOR REINFORCING BAR TO CONFORM TO AWS DIA, LATEST EDITION
• WELDING PRACTICE FOR STRUCTURAL STEEL TO CONFORM TO AWS DI.1, LATEST EDITION
• DO NOT WELD REINFORCING BAR WITHIN THREE BAR DIAMETERS OF A BEND.
• DO NOT WELD GRADE 60 REINFORCING BAR.
• GRADE 40 REINFORCING BAR REQUIRED TO BE WIRE TIED CONNECTIONS ONLY.
• CONTINUOUS ELECTRODES TO CONFORM TO AW5 A5.15 OR AW5 A5.20, LATEST EDITION.
• OTHER ELECTRODES TO CONFORM TO APPLICABLE AW5 STANDARDS.
OTHER MATERIALS
• PLATE AND ANGLE TO BE ASTM A36 Fy = 36 KSI (MIN)
• HEADED STUDS TO CONFORM TO ASTM AI08 AND AWS D1J. HIGH STRENGTH STEEL 15 NOT
PERMITTED.
• HOLES MUST BE DRILLED AND REAMED OR PUNCHED. PLASMA CUTTING OR TORCHING IS NOT
PERMITTED.
• FLOOR -WALL CONNECTION PLATES ARE NOT TO BE SPACED MORE THAN 3' APART.
• WELD PLATE HP-11 MAXIMUM SPACING 3'-0" ON LONG WALLS.
CASTING LEGEND
LIFTING FERRULE WELD CLIP
FLOOR WELD CLIP
0 STANDARD WELD CLIP
® EXTERIOR LIFTING DEVICE
• ROOF LIFTING PIN
CASTING TOLERANCES
WALL PANELS
(SEE NOTE I)
TOLERANCE
FLOOR PANELS
TOLERANCES
LENGTH
+/- 1/8
LEVEL
+/- 1/8"
WIDTH
+/- I/8
SQUARE
+/- 1/8"
DEPTH
+/- 1/8
VERTICAL WARP
+/- 1/8"
EDGE SWEEP
+/- 3/8"
EMBED PLATE POSITION
+/- 1/4
EMBED PLATE TIP/FLUSH
+/- 1/8
PENETRATION LOCATION
(SEE NOTE 3)
I/8
BOWING
+/- 1/4
WARPING
+/- 114 IN 10' LEAST
DIMENSION, MAX.
SQUARE (SEE NOTE 2)
+/- 1/8
NOTES:
I. MAXIMUM DEVIATION OVER PANEL
2. MAXIMUM DIFFERENCE IN DIAGONAL DIMENSIONS
3. UNLESS NOTED OTHERWISE
STAMPS AND SEALS
ww Z _
aQa�mw�Q Q
�r -I!
aQ wz��oat
Z���p���
No—Nf-Z �zm
on o�u
Q
§u -
z F- a
A`
\�' N O
Lo
d0 O
zo
&�
co
®w 0
O)
Lo
Lo
cq
41 1
O co
0
O O
W c co
co
W
v,
LITJ
F-
Q
'i'^^
v♦
J
Q
®
®
♦
,V
O
CV
p
X
®
O
co
LL
1
f
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY
J. Na ner
SERIAL NUrIBER:
1603-105
SCALE ' 24X36:
NONE
SHEET:
si
4
W
WALL A LAYOUT
SCALE: 3/8"=1'-0"
WALL C LAYOUT
SCALE:
2'-7° v I, 1'-2
c
m
v
(4) 1 1/2" PVC
2X4 BLOCKOUT
r ,
c P
r ,
PVC
1'-4" 3'-0" TYP 2'-6 I/4" � SIESMIC PLATE
5 _10 SEE STUD TABLE
THIS PAGE
WALL B LAYOUT
SCALE:
4'-0" TYP v 11-
WALL D LAYOUT
SCALE:
:SMIC PLATE
E STUD TABLE
IS PAGE
CASTING LEGEND
LIFTING FERRULE WELD CLIP
FLOOR WELD CLIP
[] STANDARD WELD CLIP
® EXTERIOR LIFTING DEVICE
• ROOF LIFTING PIN
STUD TABLE
SHELTER
SHELTER WIDTH (FEET)
LENGTH
(FEET)
8'
10'
12'
13'
14'
NUMBER OF STUDS
8'
6
6
5
5
5
9'
7
6
6
6
5
10,
7
7
6
6
6
11'
8
7
6
6
6
12'
8
7
7
7
6
13'
q
8
7
7
7
14'
9
8
a
7
7
15'
10
q
8
8
7
16'
10
q
8
8
8
17'
11
q
q
8
8
18,
11
10
9
q
q
19,
II
10
q
q
9
20'
12
11
10
q
q
21'
12
11
10
10
10
22'
13
II
1 II
10
10
23'
13
12
1 II
II
10
24'
14
12
1 11
II
II
25'
14
13
12
11
II
26'
15
13
12
12
11
27'
15
14
12
12
12
28'
16
14
13
12
12
29'
16
14
13
13
12
30'
17
15
14
13
13
31'
17
15
14
13
1 13
32'
IS
16
14
14
13
33'
18
16
15
14
14
34'
19
16
15
14
14
36'
Iq
17
15
15
14
36'
20
17
16
15
15
37'
20
18
6
16
15
38'
21
18
16
16
15
39'
21
IS
1 17
16
16
40'
21
Iq
1 17
17
16
EXTERIOR
FINISH SCHEDULE
ITEM
SURFACE
FINISH
PAINT COLOR
ROOF
TROWELED SMOOTH
SEALED, ELASTOMERIC COURSE
PAINT
TELECOM BROWN
WALLS
EXPOSED WASHED
AGGREGATE
OKITE STAIN (2 COATS)
-
DOORS
STEEL, RATED
PAINT
TELECOM BROWN
JOINTS
AS FINISHED
SEALED PER 'DETAILS SHEET
TELECOM BROWN
CASTING TOLERANCES
WALL PANELS
(SEE NOTE 1)
TOLERANCE
FLOOR PANELS
TOLERANCES
LENGTH
+/- 1/8
LEVEL
WIDTH
+/- 1/8
SQUARE
DEPTH
+/- 1/8
VERTICAL WARP
EDGE SWEEP
EMBED PLATE POSITION
+/- 1/4
EMBED PLATE TIP/FLUSH
+/- 1/8
PENETRATION LOCATION
(SEE NOTE 3)
+/- 1/8
BOWING
+/- 1/4
WARPING
+/- 1/4 IN 10' LEAST
DIMENSION, MAX.
SQUARE (SEE NOTE 2)
+/- 1/8
NOTES:
1. MAXIMUM DEVIATION OVER PANEL
2. MAXIMUM DIFFERENCE IN DIAGONAL DIMENSIONS
3. UNLESS NOTED OTHERWISE
STAMPS AND SEALS
AAmmank
Lo
Lb
0
rVr1 .Q
zo
cd
O j
p
~� c
OwLO
O �
�cli
+� I
A co
0 cv
d
U I
00
W GmGo
w
w
co
pA
w
z
Z
cl)
�
Q
o®
v
®
N
J
Q
®
�
b
r
r
DATE:
3/8/16
SALES MANAGER:
D. Brunswick
DRAWN BY:
J. Wagner
SERIAL NUMBER:
1603-105
SCALE 24X36:
NONE
SHEET:
S 2
a