HomeMy WebLinkAboutBUILDING PLAN PAGE 1-13Project:
�M` uT�N�G`
PLAN
KEY NOTES
O INTERMATIC DIGITAL TIMER SWITCH "EI600
LIGHTING PLAN
ISSUED FOR PERMIT 02-09-16
KAMM CONSULTING PROJECT #: 2015-0844 ••iaO��i t.AN�g ��j'''
PROJECT MANAGER: DUANE MILLAR •'
1408 0r*ge Ye]iL; • • aS ' /y 4�
A NLA IL A Fort Pierce. Florida 34950 F 2 sn
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A, 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beech, FL 32960
Te1.772.7942929
Faz.772.562.8600
License No. AA0002238
w donadio-smh.com
Consultant:
Drawing Title:
Reference North
77, FILE COPY
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
F�BII:a�'7
Cert. No.: 12,456
Date Signed: E 2 e 1
Project:
SEE ARCHITECTS DRAWINGS FOR
ADDITIONAL ELECTRICAL LOCATIONS,
ELECTRICAL CONTRACTOR TO PROVIDE
CONDUIT, J BOXES AND STUB —INS FOR ALL
DATA LINES TO AND FROM COMPUTERS, P.O,S,
SYSTEM AND PRINTERS. PLEASE VERIFY
ELECTRICAL REQUIREMENTS FROM P,O,S,
PROVIDER,
G.C. TO CONTACT RTG 4 WEEKS PRIOR TO
INSTALL. 11
EXIT SIGNAGE AND LIGHTING TO BE
PROVIDED BY ELECTRICAL CONTRACTOR
ELECTRICAL CONTRACTOR TO INSTALL
CONVENIENCE OUTLETS IN OFFICE AND
OTHER OWNER AND ARCHITECT SPECIFIED
AREAS,
B-26
WIRE THROUGH PHOTOCELL AND TIME CLOCK
ELECTRICAL ROUGH —IN NOTESi
1, THIS PLAN IS INTENDED TO SHOW FOOD SERVICE EQUIPMENT ELECTRICAL
REQUIREMENTS AND ROUGH —IN HEIGHTS ONLY, VERIFY W/ ARCHITECT AND/OR OWNER
FOR ANY ELECTRICAL CONNECTIONS FOR EQUIPMENT NOT SHOWN OR SUPPLIED BY
F,S,E,C
2, ALL DIMENSIONS ARE TAKEN FROM FINISHED FLOORS AND FINISHED WALLS OR AS
NOTED ON PLAN TO CENTERLINE OF JUNCTION BOX OR OUTLET. FOR ALL STUB —UPS AT
4' A.F.F. MAXIMUM HEIGHT TO TOP OF J—BOX IS TO BE 5 1/2' A.F.F.
3, ALL ROUGH—IN'S SHOWN AT WALL LOCATIONS ARE TO BE LOCATED WITHIN INTERIOR
OF WALL. COORDINATE WITH ARCHITECTURAL PLANS FOR ADDITIONAL FLOOR PLAN.
BUILDING ELECTRICAL REQUIREMENTS.
4, ELECTRICAL CONTRACTOR IS REQUIRED TO FURNISH AND INSTALL ALL ELECTRICAL
COMPONENTS NECESSARY TO PROVIDE SERVICE TO LOCATIONS AND EQUIPMENT AS
SHOWN ON THIS SHEET UNLESS NOTED OTHERWISE. ELECTRICAL CONTRACTOR IS ALSO
RESPONSIBLE FOR MAKING FINAL CONNECTIONS TO EQUIPMENT AND FITTINGS SUPPLIED
AND INSTALLED BY FSEC. ALL DISCONNECTS OR LOCK —OUT DEVICES, STARTERS, ETC.
TO MEET N.E.C. AND O,S,H,A, STANDARDS.
5, ALL WORK, RELATING TO THE INSTALLATION AND HOOKUP OF THE SPECIFIED
EQUIPMENT, IS TO BE PERFORMED IN FULL ACCORDANCE WITH APPLICABLE LOCAL,
CITY, COUNTY, STATE AND FEDERAL CODES AND ALL OTHER GOVERNMENTAL
REGULATORY REQUIREMENTS.
6, ELECTRICAL BOXES AND CONDUIT TO BE IN WALLS, SURFACE MOUNTED WORK IS NOT
ACCEPTABLE, WHERE EXPOSED WORK IS UNAVOIDABLE, ALL ELECTRICAL CONDUIT/FLEX
MUST BE FASTENED A MINIMUM OF 6' A.F.F. TO ALLOW FOR FLOOR CLEANING,
7, ELECTRICAL CONTRACTOR TO BRANCH TO CONNECTION WHERE REQUIRED AND TO
CONNECT ALL ELECTRICAL EQUIPMENT AND FIXTURES. ALSO DO ANY INTERNAL WIRING
REQUIRED IN THE FIXTURES INCLUDING INTER —WIRING TO APPLIANCES AS REQUIRED BY
THE SPECIFICATIONS AND/ OR DRAWINGS.
8. ALL ELECTRICAL OUTLET COVER PLATES ARE TO BE STAINLESS STEEL. THOSE
REQUIRED IN BUILDING STRUCTURE ARE TO BE FURNISHED BY THE ELECTRICIAN,
WITH RECEPTACLE. ALL MAIN BREAKER PANELS AND DISCONNECT SWITCHES REQUIRED
BY OTHER ELECTRICAL DRAWINGS ARE TO BE FURNISHED AND INSTALLED BY THE
ELECTRICAL CONTRACTOR AT TIME OF INSTALLATION.
9. VERIFY WITH ARCHITECT OR OWNER'S REPRESENTATIVE, FINAL EQUIPMENT
REQUIREMENTS AND/OR ADDITIONAL WORK TO BE DONE, INCLUDING SUCH ITEMS AS
GENERAL PURPOSE OUTLETS, NON FOOD SERVICE ITEMS, & OWNER SUPPLIED
EQUIPMENT BEFORE ORDERING MATERIAL. REVISIONS TO EQUIPMENT OR PERFORMANCE
EQUIPMENT SCHEDULE
ELECTRICAL SCHEDULE
VOLTS/
PHASE
AMPS
WATTS
P
H..
CONNECTION
"TYPE
ROUGH -IN
HIEGHT
REMARKS
NOEM
QTY
EQUIPMENT CATEGORY
REMARKS
1A
1
WALK—IN COOLER/FREEZER COMBO UNIT
EXISTING] NO WORK REQUIRED
1B
LOT
WALK—IN COOLER REFRIGERATION
EXISTING] NO WORK REQUIRED
9
1
WATER HEATER
VERIFY REQUIREMENTS & LOCATION W/SUPPLIER
10
1
SURVEILLANCE SYSTEM
BY OTHERS
120V/1
8.0
QUAD
78'
VERIFY REQUIREMENTS W/SUPPLIER
21
1
ICE MAKER W/BIN
208-230V/1
12.2
JB
72'
E.C. TO HARDWIRE TO TERMINAL AS REQUIRED
25
1
MICROWAVE
120V/1
13.0
1550
DR
24'
NEMA 5-15
27
2
MICROWAVE CONVECTION OVEN
208-240V/1
27,4
5700
SR
46'
NEMA 6-30j WIRE FOR SECOND FUTURE OVEN
28
1
RERFIGERATED PREP TABLE, 30 PAN
120V/1
12.0
1/2
DR
18,
NEMA 5-15
29
1
RERFIGERATED PREP TABLE, 30 PAN
120V/1
12.0
1/2
DR
18,
NEMA 5-15
30
1
RERFIGERATED PREP TABLE, 18 PAN
120V/1
7.2
1/5
DR
18,
NEMA 5-15
37
6
BLENDER, BAR TYPE
120V/1
15.0 EA.
3 PEAK
DR
46'
NEMA 5-15j DEDICATED CIRCUIT
52A
2
1 POS TERMINAL
BY OTHERS
120V/1
10.0
DR
18'
NEMA 5-15j DEDICATED CIRCUIT] VER, REQMNTS,
52B
2
POS TERMINAL
BY OTHERS
120V/1
10.0
DR
46'
NEMA 5—I5j DE➢ICATED CIRCUIT] VER, REQMNTS.
53
1
POS SYSTEM — BACK OF HOUSE
BY OTHERS
120V/1
1010
DR
18,
NEMA 5-15j DEDICATED CIRCUIT] VER. REQMNTS.
54A
3
POS PRINTER
BY OTHERS
120V/1
10.0
DR
18'
NEMA 5-15j DEDICATED CIRCUIT] VER, REQMNTS,
54B
4
POS PRINTER
BY OTHERS
120V/1
1010
DR
46'
NEMA 5-151 DEDICATED CIRCUIT] VER. REQMNTS,
55A
2
KDS MONITOR
BY OTHERS
120V/1
1010
DR
60'
NEMA 5-15j DEDICATED CIRCUIT] VER. REQMNTS,
55B
1
KDS MONITOR
BY OTHERS
120V/1
10.0
DR
46'
NEMA 5—I5j DEDICATED CIRCUIT] VER, REQMNTS,
57
2 1
STEAMER, PUMP TYPE
208V/1
15,9
3300
SR
46'
NEMA 6-20
79
1
TROPICAL SMOOTHIE NEON SIGN
120V/1
3.0
DR
REMARKS
FEED FROM ABOVE
80
1
TROPICAL SMOOTHIE CAFE EXTERIOR SIGNAGE
120V/1
VERIFY
JB
VERIFY
G.C. TO VERIFY ORIGINATION OF POWER FOR SIGNAGE
198
3
SCONCE LIGHTING
BY OTHERS
120V/1
0,8 AMPS
JB
102'
E,C, TO HARDWIRE TO LIGHTS AS REQURIED
A
LOT
CONVENIENCE OUTLET
120V/1
15.0 CRT.
DR
46'
NEMA 5-15
B
LOT
CONVENIENCE OUTLET
120V/1
15.0 CRT.
DR
IS'
NEMA 5-15
C
LOT
DATA LINES
EC TO PROVIDE EMPTY CONDUIT & JB FOR DATA AND PHONE LINES. VERIFY LOCATIONS WITH OWNER.
POWER PLAN
1/4'-1'-0-
POWER PLAN
ISSUED FOR PERMIT 02-09-I6
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609171h Street
Vero Beach, FL 32960
Ter772.794.2929
Fax.772.662 8600
License No. AA0002238
w donadio-arch.com
Consultant:
Drawing Title:
Reference North
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
9
ALL DEDICATED CIRCUITS TO HAVE ORANGE RECEPTACLES,
Cent. No.: 12,456
Date Signed: E 3.1
Project:
I
I
I
I
I
VERIFY OFFICE
I
REQUIREMENTS
I
W/OWNER
\
----r—,---------------
LJ
0
e
1-112' GROMMET
HOLE IN COUNTER
-- DUPLEX —---------
R_ECEPTACLE
.............
(ORANGE
I I
r9
u
SAFE (ITEM #11)
It
16 PORT II II I
PATCH
II II I I
CONDOR 3'DIApv�.
II II I I CONDUI'
STUBBED — STUBBE
ABOVE ABOVE
0-------- - CEILING
PHONE FIREWALL
BOX I
INTERNET El
MODEM
D------;iyyLleu J
SURFACE
MOUNTED
PAINTED
PLYWOOD
BACKER
BOARD
1 DESK ELEVATION & SECTION
FS-4
POWER AND CABLING REQUIREMENTS
PATCH PANEL
1
THE 16 PORT PATCH PANEL SHOULD BE MOUNTED
ON THE WALL WITH EACH RJ45 TERMINATION
LABELED TO THE CORRESPONDING LOCATION OF
THE TERMINALS AND PRINTERS ON THE COUNTER
AND PREP AREAS.
2
POWER SHOULD BE 1-QUAD OR 2-DUPLEX
DEDICATED AND ISOLATED GROUND (ORANGE) AC
PLUG(S),
3
THE INTERNET CONNECTION FOR CREDIT CARD
PROCESSING SHOULD BE LOCATED CLOSE TO THE
POS PC. THE INTERNET CONNECTION MUST BE A
STATIC IP ADDRESS, (OFFICE AREA)
COUNTER AREA
1
AT EACH COUNTER POS TERMINAL LOCATION, CAT 5
CABLES MUST BE TERMINATED WITH RJ45
CONNECTORS WITH 2 X 2 JUNCTION BOX WITH
2
DOUBLE RUN OF CAT 5 CABLE FOR EACH TERMINAL
3
AT EACH COUNTER POS TERMINAL, DEDICATED AND
ISOLATED GROUND (ORANGE) DUPLEX AC PLUG FOR
TERMINAL AND PRINTER.
PRINTERS AND KITCHEN DISPLAYS
1
AT EACH COUNTER POS TERMINAL LOCATION, CAT 5
CABLES MUST BE TERMINATED WITH RJ45
CONNECTORS WITH 2 X 2 JUNCTION BOX WITH
2
SINGLE RUN OF CAT 5 CABLE FOR EACH PRINTER
AND KITCHEN DISPLAY.
IMPORTANT - SINGLE POS TERMINAL LOCATIONS
WITH 2 REMOTE PRINTERS MUST HAVE 2 CAT 5
CABLES RUNS FROM EACH KITCHEN PRINTER TO
THE PATCH PANEL IN THE ❑FFICE IN ORDER TO
DRIVE BOTH PRINTERS.
REVS W/
P.O.S.
OWNER TO
COORDINATE WITH
MICROS & RTG FOR
ALL KIDS AND
PRINTER LOCATIONS!
PL*S 1/
BE BY
AND
INSTALLED
.
r•
G.C. TO CONTACT
RTG 4 WEEKS
PRIOR TO INSTALL
SPEAKER LOCATIONS
NO.
ITEM DESCRIPTION
MUZAK, MOOD MEDIA — PREFERRED VENDOR — 3
SPEAKERS
1
NEAR THE SMOOTHIE BAR BETWEEN BAR AND FRON
2
NEAR THE COMMUNITY TABLE
3
NEAR THE BANQUETTE
SPEAKERS NOT LOCATED NEAR CEILING FANS &
F_
PUS AREA
T-STAT LOCATIONS
NO.
ITEM DESCRIPTION
T—STAT PREFERRED LOCATIONS
1
NEAR THE RESTROOM CORRIDOR
2
NEAR THE WATER HEATER MOP SINK AREA
VIDEO SURVEILLANCE LOCATIONS
NO.
ITEM DESCRIPTION
MIN. RECOMMENDED SURVEILLANCE, (4 CAMERA
1
MANAGERS STATION/SAFE
2
POS AREA
3
BACK DOOR
4
MAIN ENTRY
PREFERRED SURVEILLANCE (8 CAMERA SYSTEM)
5
SMOOTHIE MAKE LINE
6
PREP AREA
7
DINING AREA
8
BACK OF HOUSE OR CAFE' SPECIFIC -
PAi1N PAAEL
PATIN PAAEL
WPRI
PATIN PAWL
amna
FOM
LOW VOOL TAU"M PLAN
1/4--1'-0-
EQUIPMENT SCHEDULE
ELECTRICAL SCHEDULE
VOLTS/
PHASE
AMPS
WATTS
H.P.
CONNECTION
TYPE
ROUGH -IN
HIEGHT
REMARKS
ITEM
NO
QTY
EQUIPMENT CATEGORY
REMARKS
1
1
NETWORK WALL PLATE 01
JB
18'
DATA LINE JUNCTION BOX
2
2
NETWORK WALL PLATE 02
JB
60'
DATA LINE JUNCTION BOX
3
2
NETWORK WALL PLATE 03
JB
18'
DATA LINE JUNCTION BOX
4
1
NETWORK WALL PLATE 04
JB
18'
DATA LINE JUNCTION BOX
LOW VOLTAGE PLAN
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 171h Street
Vero Beach, FL 32960
Tel.772.794.2929
Fax.772.562 8600
license No, AA0002238
w .donadio-arch.com
Consultant:
Drawing Title:
Reference North
BILE COPY
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
Cert. No.: 12,456
Date Signed: E4.1
Project:
SCHEDULE OF RELOCATED BRANCH CIRCUIT PANEL "AT
MAIN: 400 AMP 3 POLE MAIN LUG ONLY VOLTAGE: 208/12OV, 30, 4 WIRE
SPEC: EXISTING
MOUNTING: RELOCATED AIC SYMM: EXISTING
DESCRIPTION
WIRE
GND.
COND.
TRIP
CKT.
A PHASE
KVA
B PHASE
KVA
C PHASE
KVA
CKT.
TRIP
COND.
GND.
WIRE
DESCRIPTION
PANEL B
3#1 O
1#6
1-1 2
150
3
1
11.4 -
-
-
-
SPARE
3
11.7 -
-
-
-
SPARE
5
10.9 -
-
-
-
SPARE
RTU-1
3#8
1#10
1
35
3
7
4.0 1.0
-
-
-
SPARE
9
4.0 -
-
-
-
SPARE_
11
4.0 -
P243
-
-
-
SPARE
RTU-2
3#8
1#10
1
35
3
13
4.0 -
-
-
-
SPARE
15
4.0 -
-
-
-
SPARE
17
4.0 0.1
-
-
-
EXISTING COOLER LIGHTS
ROOF RECEPTACLE
12
12
1 2
20
19
0.4 1.0
-
-
-
EXISTING COOLER
SPARE
-
-
-
20
21
- 1.0
SPARE
-
-
-
20
23
- 1.0
SPARE
-
-
-
20
25
- 1.0
26
20
3
-
-
-
EXISTING COOLER
SPARE
-
-
-
20
27
SPARE
-
-
-
20
29
1.0
30
SPARE
-
-
-
20
31
- 1.0
32
20
3
-
-
-
EXISTING COOLER
SPARE
-
-
-
20
33
- 1.0
34
SPARE
-
-
-
20
35
1.0
36
SPARE
-
-
-
20
37
- -
38
20
-
-
-
SPARE
SPARE
-
-
-
20
1 39
- -
40
20
-
-
-
SPARE
SPARE
-
-
-
20
1 41
-
42
20
-
-
-
SPARE
22.3 21.6 18.4 1 KVA PER PHASE
185.8 1 00.0 153.3 1 AMPS PER PHASE
62.3 1 TOTAL KVA
SCHEDULE OF RELOCATED BRANCH CIRCUIT PANEL "B"
MAIN: 200 AMP / 3 POLE MAIN LUG ONLY VOLTAGE: 208/12OV, 30, 4 WIRE
SPEC: EXISTING
MOUNTING: RELOCATED AIC SYMM: EXISTING _
DESCRIPTION
WIRE
GND.
I COND.
TRIP
CKT.
A PHASE I
KVA
B PHASE
KVA
C PHASE
KVA
CKT.
TRIP
COND.
GND.
WIRE
DESCRIPTION
WATER HEATER
2#8
1#10
1
3
1
2.21 1.2
2
20
1 2
12
12
37 BLENDER
3
2.2 1.0
4
20
1 2
12
12
52.53.54 POS
SPARE
-
-
-
20
5
- 1.0
6
20
1 2
12
12
52,53,54 POS
SPARE
-
-
-
20
7
- 1.0
8
20
1 2
12
12
52,53,54 POS
10 SURVEILLANCE
12
12
1 2
20
9
0.2 1.0
10
20
1 2
12
12
52,53.54 POS
21 ICE MAKER
2#12
1#12
1 2
2
11
1.0 1.0
12
20
1 2
12
12
52,53.54 POS
13
1.0 -
14
20
1 2
12
12
52,53,54 POS
SPARE
-
-
-
20
15
- 1.6
16
0
2
1/2-
1#12
2#12
57 STEAMER
25 MICROWAVE
12
12
1 2
20
17
1.2 1.6
18
27 MCROWAVE
2#10
1#10
3 4
3
2
19
2.8 1.6
20
0
1 2
1#12
2#12
57 STEAMER
21
2.8 1.6
22
27 MCROWAVE
2#10
1#10
3 4
3
2
23
2.8 0.2
24
20
1 2
12
12
79 SIGN
25
2.8 0.2
26
20
1 2
12
12
80 SIGN
28 REFRIGERATED TABLE
12
12
1 2
20
27
1.0 1.0
28
20
1 2
12
12
CONVENIENCE OUTLETS
29 REFRIGERATED TABLE
12
12
1 2
20
29
1.0 1.0
30
20
1 2
12fi12
CONVENIENCE
OUTLETS
30 REFRIGERATED TABLE
12
12
1 2
20
31
1.0 1.0
32
20
1 2
12CONVENIENCE
OUTLETS
37 BLENDER
12
12
1 2
20
33
1.2 1.0
34
20
1 2
12LIGHTING
37 BLENDER
12
12
1 2
20
35
1.2 1.0
36
20
1 2
12LIGHTING
37 BLENDER
12
12
12
20
37
1.2 1.0
38
20
1 2
12LIGHTING
37 BLENDER
12
12
i 2
20
39
1.2 1.0
40
20
1 2
12LIGHTING
37 BLENDER
12
12
1 2
20
41
12 1.0
42
20
1 2
12LIGHTING
DEMAND FACTOR
KITCHEN EQUIPMENT O 65% PER NI-C TALBE 220.56
1.2
2.2
2.0
NON KITCHEN
KVA
10.2
9.5
8.9
EQUIPMENT
KVA ® 65%
11.4
11.7
10.9
TOTAL KVA
PER PHASE
95.0
97.5
90.8
AMPS PER PHASE
34.0
1 TOTAL KVA
SCHEDULE OF RELOCATED BRANCH CIRCUIT PANEL "C"
MAIN: 200 AMP 3 POLE MAIN LUG ONLY VOLTAGE: 208/12OV. 30, 4 WIRE
SPEC: EXISTING
MOUNTING: EXISTING AIC SYMM: EXISTING
DESCRIPTION
WIRE
GND.
COND.
TRIP
CKT.
A PHASE
KVA
B PHASEPKVA
KVA
CKT.
TRIP
COND.
GND.
WIRE
DESCRIPTION
RTU-3
3#8
1#10
1
40
3
1
4.2 -
2
20
-
-
-
SPARE
3
4.2 -4
20
-
-
-
SPARE
5
6
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
7
1.0 -
8
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
1.0 -10
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
12
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
1.0 -
14
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
1.0 -
16
20
-
-
-
SPARE
EXISTING CIRCUIT
-
-
-
20
[23
1.0 -
18
20
-
-
-
SPARE I
SPARE
-
-
-
20
- -
20
20
-
-
-
SPARE
SPARE
-
-
-
20
- -
22
20
-
-
-
SPARE
SPARE
-
-
-
20
- -
24
20
-
-
-
SPARE
SPARE
-
-
-
20
- -
26
20
-
-
-
SPARE
SPARE
-
-
-
20
27
- -
28
20
-
-
-
SPARE
SPARE
-
-
-
20
29
- -
30
20
-
-
-
SPARE
SPARE
-
-
-
20
31
- -
32
20
-
-
-
ISPARE
SPARE
-
-
-
20
33
- -
34
20
-
-
-
SPARE
SPARE
-
-
-
20
35
- -
36
20
-
-
-
SPARE
SPARE
38
20
-
-
-
SPARE
SPARE
-
-
-
20
39
- -
40
20
-
-
-
SPARE
SPARE
-
-
-
20
41
- -
42
20
-
-
-
SPARE
6.2 6.2 6.2 KVA PER PHASE
51.6 51.6 51.6 AMPS PER PHASE
18.6 TOTAL KVA
UTILITY COMPANY PAD MOUNTED
SERVICE TRANSFORMER
208/120 VOLT, 30 MY
NEMA 3R
I\ /I
\�
I
I
4-500MCM 4"
16V 3P
NEMA 3R
t#3/0 & 1#2G - 2-1
TENANT SPACE
t
200A 3P I PANEL I I PANEL I I PANEL I
NEMA 313
I I I I I I
Q
I I I I I I
L_ J L_ _J L--_J
WIREWAY
A-1, 3,
ELECTRICAL RISER DIAGRAM
LEGEND
NEW
EXISTING ------
l
RISER DIAGRAM
ISSUED FOR PERMIT 02-09-I6
I"I20JliCT MANAGIF,R: PROS5-08.14
DUANE MILLAR�L ft
1408 Ora ene�D ne:= _ •. '�O'.�
PRINCIPAL
Bradly L Brown Florida License #58232 '40
11.2
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL 32960
Tei.772.794.2929
Fax772.562.8600
License No. AA0002238
w .dcnacio-arch.com
Consultant:
Drawing Title:
Reference North
Drn:
Dwg. File:
MT
Chd:
XREF File:
AJD
Project No.:
Plot File:
2015-63
Sheet No.:
Cert. No.: 12,456
Date Signed: E 5.1
Project:
MECHANICAL NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY
FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE
DRAWINGS, THE FLORIDA BUILDING CODE 2014 AND ALL OTHER APPLICABLE STATE,
COUNTY AND LOCAL ORDINANCES AND THE LATEST ADDITION OF THE FOLLOWING
PUBLICATIONS; SMACNA-85, 92, 95; ASHRAE 15-01, 34-01, 62-04; NFPA 70702, 72-02,
9OA-02, 9OB-02, 91-99, 96-01; ANSI Z10.1-98, Z10.3-98, Z21.8-94, Z21.83-98.
2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER
COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK.
3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES.
4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT WITH "AS —BUILT" DRAWINGS.
5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE [5] COPIES OF MANUFACTURER'S
DRAWINGS FOR EACH PIECE OF EQUIPMENT AND CONTROLS INCLUDED IN CONTRACT.
6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL
BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS.
ALL EQUIPMENT SHALL BE UL OR ETL LISTED.
ALL INSTALLATIONS SHALL COMPLY WITH FMC 2014, CH. 3, GENERAL REGULATIONS. BUILDINGS
LOCATED WITHIN 3.000 FT FROM THE OCEAN SHALL UTILIZE NON—FERROUS MATERIALS FOR
ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC.
7. DUCTWORK:
A. ALL AIR CONDITIONING DUCT WORK SHALL BE OF 1-1/2" (R-6) HEAVY DUTY FOIL
REINFORCED FIBERGLASS WITH MANUFACTURER'S LOGO PRINTED ON VAPOR BARRIER
IL ALL FLEX DUCT SHALL BE RATED CLASS I, UL-181 LISTED WITH METALLIZED INNER AND OUTER FOIL
LINERS, MIN. R-6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 25 FT.
FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER, GRILLE, AND REGISTER EQUAL TO "FLEXFLOW
ELBOW" AS MANUFACTURED BY "THERMAFLEX".
C. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL
WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH
EXTERNAL BLANKET INSULATION R-6 MIN.
ALL METAL EXHAUST, MAKE—UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT
CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R-6 MIN.
THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC.
ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A.
SPECIAL
SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2", 1", 2", 3", 4",
6 AND 10". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE
CLASS SHOWN ON PLANS.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM
OF VAV BOXES.
ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR
ITS PRESSURE CLASS SEALING METHODS.
9. OUTSIDE AIR INTAKES SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL NOT LARGER
THAN 1/2" MESH. O/A INTAKES SHALL NOT BE TAKEN FROM A LOCATION CLOSER THAN 10 FT.
FROM ANY CHIMNEY, VENT OUTLET OR SANITARY SEWER VENT OUTLET, UNLESS SUCH VENT
IS NOT LESS THAN 24 INCHES ABOVE THE OUTSIDE AIR VENT.
OUTSIDE AIR INTAKE VENTS LOCATED ON ROOFS WILL BE PROPERLY MARKED WITH A UNIVERSAL
MARKING "INTAKE", PERMANENTLY ATTACHED PER FMC 2014, SEC. 401.5.1
10. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS.
11. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM
CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS
SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAIRE.
PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON
PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS
TO ENSURE COMPLAINCE WITH FMC 2014, PAR. 601.4 AND PAR. 603.15 FOR BALANCED AIR FLOW.
12. TEMPERATURE CONTROLS/THERMOSTAT:
A. SHALL BE COMBINATION COOLING/HEATING, WITH SYSTEM "COOL —AUTO —
HEAT —OFF" AND FAN "ON —AUTO" SELECTOR SWITCHES. PROVIDE PROGRAMMABLE TYPE AS
RECOMMENDED BY MANUFACTURER, HONEYWELL OR EQUAL. PROVIDE TAMPER PROOF COVERS.
13. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION.
INSTALL THERMOSTAT 48" TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS
FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES
AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION.
WHENEVER THERE ARE MORE THAN ONE SENSOR OR THERMOSTAT, SIDE BY SIDE, THEY SHALL BE
GANGED TOGETHER WITHIN THE SAME COVER PLATE WHEREVER POSSIBLE.
CONTRACTOR SHALL COORDINATE THIS ISSUE WITH ARCHITECT/OWNER PRIOR TO INSTALLATION AND
SHALL BRING ANY DISCREPANCY TO THE ENGINEER'S ATTENTION.
14. REFRIGERANT LINES SHALL BE COPPER, TYPE "L" HARD DRAWN WITH WROUGHT COPPER
BRAZING —JOINT TYPE FITTINGS, USE BRAZING MATERIALS FOR HIGH PRESSURE PIPING
PER AWS A5.8: BCuP SERIES COPPER —PHOSPHORUS ALLOY OR BAg1 SILVER ALLOY.
REFRIGERANT LINES SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.
SOFT COPPER TYPE "M" SHALL BE ALLOWED FOR RISER PIPING INSIDE CHASE TO LIMIT
NUMBER OF JOINTS. COORDINATE WITH ENGINEER FOR PRIOR APPROVAL.
ALL EXPOSED INSULATION SHALL BE PROTECTED WITH UV RESISTANT PAINT OR ALUMIN. SHIELD.
15. ARMAFLEX INSULATION SHALL BE USED FOR SUCTION LINES (1/2" FOR ABOVE 40' F AND
1" FOR BELOW 40' F) PER FLORIDA ENERGY CODE TABLE 4-11 FOR PIPING INSULATION.
FILTER/DRYER AND SIGHT GLASS SHALL BE PROVIDED AT LIQUID LINES.
16. ALL BRANCH TAKE —OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS
WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W/SINGLE FOIL TURNING VANES.
PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE —OFFS.
PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS,
"YOUNG REGULATOR" OR EQUAL.
17. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START—UP,
REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER.
18. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS
FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE.
FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION/TEST
STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION.
DETECTORS SHALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH
ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON
DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND
ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM.
19. PROVIDE TYPE "B" DYNAMIC FIRE DAMPERS WITH SERVICE ACCESS DOORS IN ALL DUCTS AND
OPENINGS PENETRATING FIRE RATED WALLS, MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS,
TENANT SEPARATION, PARTITIONS, FLOOR OR ROOF SLABS AND AT OUTSIDE AIR INTAKES AS
REQUIRED. PROVIDE RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEILING OPENINGS, CEILING
FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEILING ASSEMBLY.
PROVIDE LOW —LEAKAGE CLASS DAMPERS FOR ALL SITUATIONS WHERE THE AIRFLOW CFM
HAS TO BE CONTROLLED. VERIFY AND REPLACE AS REQUIRED FOR EXISTING SYSTEMS.
20. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2014, CH. 13, 410.1.ABCD.4
(THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS)
FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS.
THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES
AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE (F) FROM
SUPPLY GRILLES AND EVAPORATORS.
FOR (EXISTING) SMOKE EVACUATION SYSTEMS HVAC CONTRACTOR SHALL PROVIDE A T & B
REPORT PRIOR TO ANY NEW WORK, PROVING THAT THE SMOKE EVACUATION SYSTEM PERFORMS
PER ORIGINAL DESIGN DOCUMENTS AND IS COMPLIANT WITH LOCAL CODE REQUIREMENTS.
21. RUN INSULATED FIRE RATED CONDENSATE DRAINS AS REQUIRED.
22. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50.
23. MECHANICAL EQUIPMENT ON ROOF OR ELEVATED STRUCTURES SHALL COMPLY WITH FBC 2014
PAR. 306.5 IF INSTALLED HIGHER THAN 16 FEET A.F.F.
MECHANICAL EQUIPMENT INSTALLED IN ATTICS SHALL MEET THE REQUIREMENTS OF FBC 2014
PAR. 306.3 IF THE EQUIPMENT CAN NOT BE SERVICED/REMOVED THROUGH REQUIRED OPENING.
MECHANICAL EQUIPMENT SHALL BE PROTECTED WITH MECHANICAL BARRIERS IF EXPOSED TO
MECH. DAMAGE. ALL EQUIPMENT SHALL BE INSTALLED ON 6" CONCRETE PAD AT GRADE LEVELSPECIAL
.
ALL WIND LOAD AND OTHER COMPLIANCE CALCULATIONS AND/OR INSTALLATION DETAILS
FOR ROOF MOUNTED EQUIPMENT AS REQUIRED BY FBC 2014, SEC. 1509, 1522 AND CHAPTER 16,
SHALL BE PROVIDED BY STRUCTURAL ENGINEER/ARCHITECT.
24. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120-208 VOLT PANELS AND MIN. 42"
CLEARANCE IN FRONT OF ANY 240-480 VOLT PANEL. PROVIDE ADEQUATE SIDE CLEARANCE
PER NEC.
25. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ
IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND
STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS.
DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND
INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE
WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL
BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING
EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT.
26. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING,
FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE
A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES.
ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D
SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK.
27. CONTRACTOR TO PROVED COORDINATED SHOP DRAWINGS OF ALL DUCT WORK AND EQUIPMENT.
SHOP DRAWINGS TO COORDINATE WITH FIRE SPRINKLER, ELECTRICAL, AND STRUCTURAL SYSTEMS.
28. NO COMBUSTIBLE MATERIALS ARE ALLOWED IN RETURN AIR PLENUMS OR ABOVE
CEILINGS USED AS RETURN AIR PLENUM. IF SPACE WITH RETURN AIR PLENUM
HAS ANY DECK TO DECK PARTITIONS, AIR TRANSFER DUCTS MUST BE INSTALLED.
WHEN CPVC PIPING IS USED FOR FIRE SPRINKLER SYSTEMS, THE R/A GRILLES LAYOUT SHALL
BE (FIELD) COORDINATED WITH SUCH PIPING SO THAT NO PORTION OF THE GRILLES WILL BE
DIRECTLY BELOW THE CPVC PIPING.
29. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED
TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2" ARMAFLEX INSULATION.
PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN
THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 2014, SEC. 307
SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION
CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS.
30. MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF
(1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS
ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND
AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR
(5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING
NON —OPERATIONAL PERIODS OR AS AGREED WITH OWNER.
MECHANICAL SHEET INDEX
SHEET#
DESMPIM
MO.1
MECHANICAL NOTES, LEGEND & INDEX
MO.2
MECHANICAL SPECIFICATIONS
M2.1
MECHANICAL FLOOR PLAN
M6.1
MECHANICAL SCHEDULES
MECHANICAL LEGEND
❑�
CEILING OR INLINE EXHAUST FAN
®
SUPPLY AIR CEILING DIFFUSER
rI
RETURN AIR CEILING GRILLE
I I
STANDARD SINGLE DUCT VVT BOX
L�
WALL LOUVER / WALL DIFFUSER.
(3'0" SERVICE CLEARANCE)
o
LINEAR DIFFUSER
O
THERMOSTAT
L—
MANUAL VOLUME CONTROL DAMPER
H
HUMIDISTAT
MD
MOTORIZED DAMPER
®
REFRIGERANT SENSOR
SP
STATIC PRESSURE SENSOR
FIRE DAMPER
O
DUCT SMOKE DETECTOR
0-REDUCER
OR INCREASER
DD
\S v
FLEX DUCT
AP — ACCESS PANEL
EXISTING FLEX DUCT
--I
AD — ACCESS DOOR
EXISTING DUCTWORK
VCD
VOLUME CONTROL DAMPER
®UP
SUPPLY & OUTSIDE AIR
MOD
MANUALLY OPERATED DAMPER
SECTION (UP)
ON
SUPPLY & OUTSIDE AIR
HH
SUPPLY AIR
DIFFUSER OR GRILLE DESIGNATION
SECTION (DN)
[21UP
RETURN OR EXHAUST DUCT
RETURN/EXHAUST AIR
DIFFUSER OR GRILLE DESIGNATION
SECTION (UP)
m VARIABLE FREQ. DRIVE CONTROL PANEL
/ DN
RETURN OR EXHAUST DUCT
SECTION (DN)
SUPPLY AIR
O
ROUND UP
RETURN AIR
.Mu/c
DOOR UNDER CUT
SHOE TAP DAMPER
EQUIPMENT TAG
OUTSIDE AIR ROOF TOP UNIT
®
ROOFTOP UNIT
RTU— RTU—
ROOF TOP UNIT
VAV—
VARIABLE VOLUME BOX
SOLENOID VALVE.
EF —
EXHAUST FAN
RE
RELOCATE
NOT ALL SYMBOLS MAY APPLY TO THESE PLANS
HVAC ABBREVIATION LEGEND
AC
AIR CONDITIONING
MCA
MINIMUM CIRCUIT AMPS (FOR WIRE SIZING)
AFF
ABOVE FINISH FLOOR
MOD
MANUALLY OPERATED DAMPER
BDD
BACK DRAFT DAMPER
MOCP
MAXIMUM OVERCURRENT PROTECTION DEVICE AMP
CD
CONDENSATE DRAIN
NC
NOISE CRITERIA
COP
COEFFICIENT OF PERFORMANCE
O/A
OUTSIDE AIR
DB
DRY BULB
OBD
OPOSITE BLADE DAMPER
DIA.
DIAMETER
PD
PRESSURE DROP.
E
EXISTING TO REMAIN
R
EXISTING TO BE RELOCATED
EER
ENERGY EFFICIENCY RATIO
R/A
RETURN AIR
EDH
ELECTRIC DUCT HEATER
RLA
RATED LOAD AMPS.
EF
EXHAUST FAN
SEER
STANDARD ENERGY EFFICIENCY RATIO
ESP
EXTERNAL STATIC PRESSURE
TSP
TOTAL STATIC PRESSURE
F
FILTER
VD
VOLUME CONTROL DAMPER
FD
FIRE DAMPER
VFD
VARIABLE FRECUENCY DRIVE
FLA
FULL LOAD AMPS.
WB
WET BULB
FMS
FLOW MEASURING STATION
IPLV
INTEGRATED PART —LOAD VALUE.
NOTE: NOT
ALL SYMBOLS MAY APPLY TO THESE PLAN.
MECHANICAL NOTES
ISSUED FOR PERMIT
KAMM CONSULTING PROJECT 4. 2015-0844\eA�e``,,�t„�i LA?ik
PROJECT MANAGER: WAKE MILLAR _.` „�N ..........
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 nth street
Vero Beach, FL 32960
Te1.772.794,2929
Fax 772.562.8600
License No. AA0002238
www.donadio-arch.com
Consultant:
Drawing Title:
Reference North
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
Certificriqd3 8f Au t oonl4fion #8189 —
PRINCIPAL ,'TIES OF
Bradly L Brown Florida _icensT- e #58232 ,(. date
Cert. No.: 12,456
Date Signed: M O.1
Project:
SECTION I5WO
MECHANICAL
PART 1 GENERAL
1.1 SUMMARY
A. MATERIALS AND WORKMANSHIP
1. PRODUCTS AND MATERIALS SHALL MEET OR EXCEED THE QUALITY OR REQUIREMENTS SPECIFIED OR SHOWN ON
THE DRAWINGS.
2. PROVIDE PRODUCTS AND MATERIALS, WHICH THE MANUFACTURER HAS CERTIFIED AS APPROPRIATE TO THE
APPLICATIONS SHOWN ON THE DRAWINGS AND SPECIFICATIONS
3, PROVIDE PRODUCTS AND MATERIALS, WHICH ARE SUPPORTED BY CONVENIENT, PARTS AVAILABILITY AND
SERVICING.
4. WORKMANSHIP SHALL BE IN ALL RESPECTS OF THE HIGHEST QUALITY AND ALL CONSTRUCTION SHALL BE DOE
ACCORDING TO THE BEST PRACTICE OF THE TRADE. ALL SYSTEMS SHALL BE MADE COMPLETE AND OPERATIONAL IN
FIRST CLASS WORKING ORDER FURNISH ALL NECESSARY LABOR AND MATERIALS TO CONSTRUCT A COMPLETE
SYSTEM.
5, THE HVAC CONTRACTOR SHALL COORDINATE ALL ELECTRICAL, ATC, AND PLUMBING REQUIREMENTS WITH THOSE
SUBCONTRACTORS.
B. OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY LAW FOR THE COMPLETION OF THE WORK
L COST OF THE REQUIRED PERMITS AND INSPECTIONS SHALL BE PAID BY THE CONTRACTOR THE CONTRACTOR SHALL
OBTAIN AND PAY FOR ALL CERTIFICATES OF APPROVAL, WHICH MUST BE OBTAINED PRIOR TO FINAL ACCEPTANCE
OF THE JOB.
2. ALL MATERIALS AND LABOR FURNISHED BY THE CONTRACTOR SHALL BE IN STRICT ACCORDANCE WITH THE RULES
AND REGULATIONS OF THE STATE AND MUNICIPALITY, UTILITY COPANIES, BUDDING CODE - 2001, NATIONAL
ELECTRIC CODE (NEC) AND THE NATIONAL FIRE PROTECTION ASSOCIATION O FPA).
C. PROVIDE ALL LABOR, MATERIALS, SERVICES, EQUIPMENT, AND APPLIANCES REQUIRED FOR THE FABRICATION
AND INSTALLATION OF MECHANICAL SYSTEMS INCLUDING HEATING, VENTILATING, AIR-CONDITIONING, AND
VARIOUS SYSTEMS AS INDICATED ON THE DESIGN DRAWINGS AND AS OUTLINED IN THESE SPECIFICATIONS
D. EQUIPMENT AND DESIGN O' SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE
SPECIFICATIONS SHALL BE CONSIDERED AS 'SPECIFIED STANDARD' OF QUALITY. SUBSTITUTIONS SHALL BE OT
EQUAL QUALITY.
E. THE ENTIRE SYSTEM AND ALL COMPONENTS LISTED HEREIN SHALL MEET ALL STATE, COUNTY, AND LOCAL CODES
AND ORDINANCES IN EVERY RESPECT. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INSPECTIONS
AND PAY ALL FEES
F. ALL EQUIPMENT, ETC. SHALL BE NEW UNLESS OTHERWISE SPECIFIED, FREE OF DEFECTS AS SHOWN ON THE
DRAWINGS, AND AS INDICATED IN THESE SPECIFICATIONS
G. ALL MATERIALS SHALL BE FABRICATED AND INSTALLED IN A NEAT AND PRO'ESSIONAL MANNER WITH THE
COORDINATION OF ALL INVOLVE TRADES TO AVOID INTERFERENCES AND DELAY BUE TO LACK OF
COORDINATION. NO ALLOWANCES WILL BE MADE FOR REWORK DUE TO C013RDINATION DIFFICULTIES OR
INTERFERENCES BETWEEN INVOLVED TRADES
12 QUALITY ASSURANCE
A. PROVIDE TO THE OWNER WITH THE FOLLOWING PRIOR TO FINAL ACCEPTANCE
1. PARTS LIST FOR EACH PIECE OF EQUIPMENT,
2. ONE BOUND SET OF APPROVED SHOP DRAWINGS.
3. ONE BOUND SET OF OPERATING INSTRUCTIONS AND MAINTENANCE SCHEDULES FOR EACH PIECE
OF EQUIPMENT.
4. COPIES OF ALL WARRANTIES FOR EACH PIECE OF EQUIPMENT.
B. GUARANTEES AND WARRANTIES
L GUARANTEE ALL LABOR AND MATERIAL FURNISHED FOR A PERIOD OF ONE YEAR EXTENDING
FROM THE TIME OF FINAICCEPTANCE OF THE BUILDING, THE GUARANTEE SHALL COVER THE
REPAIR OR REPLACEMENT WITHOUT ADDITIOUL TO THE OWNER FOR ANY DEFECTIVE
MATERIAL OR FAULTY WORKMANSHIP.
2. PROVIDE WARRANTIES FOR EACH PIECE OF MAJOR EQUIPMENT. WARRANTIES SHALL BE INCLUDED
WITH THE OWNER'S FINAL DOCUMENTS
C. TRAINING SERVICES
L THOROUGHLY INSTRUCT THE OWNER'S PERSONNEL DURING NORMAL WORKING FLOURS ON
START-UP AND SHUT-DOWNPROCEDURES, TROUBLESHOOTING PROCEDURES, SERVICING
AND PREVENTATIVE MAINTENANCE SCHEDULESPNBDEDURES. REVIEW WITH THE
OWNER'S PERSONNEL THE DATA CONTAINED IN THE OPERATNMBN7011pNCE
MANUALS. SCHEDULE THE TRAINING WITH THE OWNER, PROVIDE AT LEAST 7-DAYS PRIOR NOTICE
TO ARCHITECT/ENGINEER.
a SYSTEM IDENTIFICATION
L PROVIDE IDENTIFICATION LABELS ON ON NEAR EACH PIECE OF MAJOR EQUIPMENT AND EACH
13PERATIONAL DEVICE AND DISCONNECT. THE LABELS SHALL BE CONSTRUCTED OF
ENGRAVED PLASTIC LAMINATE SIGN OR PLAMMMENT MARKER PERMANENTLY
SECURED TO EQUIPMENT. THE LETTERING SHALL BE A MINIMUNNOI IM FOR
EQUIPMENT NAME AND 3/8 INCH FOR EQUIPMENT INFORMATION.
2.1 MATERIALS
A. HANGERS AND SUPPORTS
L PROVIDE ALL NECESSARY DUCTWORK, PIPE SUPPORTS, HANGER RODS, CLAMPS AND
ATTACHMENTS TO PROPERLY SUPPORT DUCTWORK, PIPING AND EQUIPMENT FROM THE
BUILDING STRUCTURE, PROVIDE ANY ANGLE DRONJMTRUT AND SUSPENSION RODS
REQUIRED TO INSTALL EQUIPMENT, PIPING AND DUCTWORK
2. ALL SUPPORTS EXPOSED TO OUTDOORS SHALL BE CLEANED, PRIMED AND PAINTED TO PREVENT
RUSTING. FINISH COLOR TO BE SELECTED BY THE OWNER,
3. THE USE OF BAILING WIRE OR PERFORATED METAL STRAPPING IS NOT ACCEPTABLE FOR
SUPPORTS.
B. AIR-CONDITIONING EQUIPMENT (IF ANY NEW EQUIPMENT IS SHOWN)
L NEW UNITS SHALL BE AIR-TO-AIR ELECTRIC AIR AS SCHEDULED ON THE DESIGN DRAWINGS, UNITS
WITH INTEGRAL ELECTRIC RESISTANCE HEATERS SHALL HAVE A SINGLE -POINT ELECTRIC
CONNECTION. TOTAL COOLING CAPACITY OHTHE UNITS SHALL BE AS SCHEDULED ON
DRAWINGS. UNIT CABINETS SHALL BE CONSTRUCTED OF GALVANIZED STEEL,
BONDERIZED AND COATED WITH BAKED ENAMEL. CABINET INSULATION SHALL COMPLY WITH
LOCAL ENERGY CODE.
2. THE UNITS SHALL CONTAIN HERMETIC COMPRESSORS WITH SERVICE VALVES AND VIBRATION
ISOLATION. UNITS SHALL HAVE DUAL COMPRESSORS AND DUAL REFRIGERATION
CIRCUITS OR CAPACITY REDUCTION STEPS WHERE INDICOEBQUIPMENT
SCHEDULE.
3. THE INDOOR AIR FANS SHALL BE OF THE FORWARD -CURVED CENTRIFUGAL CLASS 1 TYPE. THE
OUTDOOR AIR FANS SHALL BE OF THE PROPELLER TYPE, EACH DIRECTLY DRIVEN BY AN
INHERENTLY PROTECTED MOTOR. MOTOR AND DRIVE TOR13VIDE HIGHER FAN
OUTPUT WHEN JOB REQUIREMENTS EXCEED STANDARD FAN CAPACITY SHALL BE PROVIDER
4. COILING SYSTEM SHALL BE PROTECTED BY, LOSS OF CHARGE PROTECTION, HIGH AND LOW
PRESSURE STAT, COMPRESSOR MOTOR OVERLOADS, AND A TIMING DEVICE WHICH
WILL PROHIBIT THE COMPRESSOR MOTOR FORM BEING SUBJECTED TO A STARTING
CURRENT MORE THAN ONCE EVERY FIVE MINUTES. THREE PHASE UNITBASHALL
PHASE -LOSS PROTECTION. THE UNIT WILL HAVE AN AMBIENT AIR COMPRESSOR LOCKOUT SET AT
55 DEGREES. CONTROLS - PROVIDE WALL MOUNTED, HEAT/COOL ON -OFF -AUTO
THERMOSTAT. SMOKE DETECTORS SHALL BE PROVIDED BY DIVISION 16, INSTALLED BY
DIVISION 15 AND WIRED BY DIVISION 1 60D0. LOCATIONSSRORE DETECTORS ARE
INDICATED W HVAC PLANS
5. PROVIDE AIR CONDITIONING UNIT WITH SUB COOLING COIL AND GAS REHEAT OPTION.
C. AIR DISTRIBUTION EQUIPMENT
1. FURNISH SUPPLY AIR DIFFUSERS AND RETURN AIR GRILLS AS SCHEDULED ON THE DESIGN
DRAWINGS.
1. METAL-AIRE OR PRINCE MAY BE SUBSTITUTED AS AN EQUAL.
2. GRILLS REGISTERS AND DIFFUSERS SHALL BE FURNISHED AS SCHEDULED ON THE DESIGN
DRAWINGS.
A DUCTWORK
L GLASS FIBER DUCT BOARD WITH ANTI -MICROBIAL TREATED INNER LINING, EQUAL TO
'TOUGH -DUCT'. INNER LINING SHALL BE SEALED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS, DUCT BOARD SHALL BE 1-1/2' THICK, R-6.
ALL FIELD JOINTS SHALL BE SEALED WITH GLASS FABRIC AND MASTIC.
2. ADJUSTABLE SPLITTERS AND DAMPERS SHALL BE INSTALLED IN EVERY SPLIT AND BRANCH DUCT
AND SHALL BE PROVIDED WITH LOCKING QUADRANTS ON EXPOSED OR IN
ACCESSIBLE AREAS OF THE DUCT FOR EASE OFOPERATION. ELBOWS OR CHANGES
IN DUCT DIRECTION GREATER THAN 45 DEGREES SHALL BE FITTED WIN MIR
CONSISTING OF CURVED AIRFOIL BLADES OR VANES, WHICH WILL PERMIT THE AIR TO MAKE
ABRUPT TURNS WITHOUT APPRECIABLE TURBULENCE
3. FLEXIBLE DUCTWORK SHALL BE ACOUSTICAL LOW-PRESSURE TYPE WITH INTERIOR LINER, METAL
HELIX, FIBERGLASS INSULATION WITH AN R-VALUE OF 6.0 OR GREATER, AND
COPOLYMER SEAMLESS OUTSIDE SLEEVE. THE ENTIREFLEXIBLE DUCT ASSEMBLY
SHALL BE LISTED IN ACCORDANCE WITH UL-181 CLASS I AIR DUCT MATERIAL FLEXIBLE
DUCTWORK SHALL MEET THE ENERGY EFFICIENCY CODE.
4. ALL EXHAUST DUCTWORK SHALL BE GALVANIZED STEEL.
E. FIRE SAFETY CONTROLS
1. INSTALL SMOKE DETECTOR FURNISHED BY DIVISION 16 IN SUPPLY AND RETURN AIR DUCTS.
DETECTOR SHALL SHUT UNIT OFF WHEN ACTIVATED.
F. VIBRATION ISOLATION
1. ALL BLOWER UNITS AND VIBRATING TYPE EQUIPMENT SHALL BE PROPERLY FITTED `JITH MASON
INDUSTRIES VIBRATION ISOLATION EQUIPMENT SIZED IN ACCORDANCE WITH
EQUIPMENT WEIGHT AND DUTY.
2. PROVIDE FLEXIBLE CONNECTORS AT ALL SUPPLY AND RETURN CONNECTIONS TO AIR
CONDITIONING EQUIPMENT CONSISTING OF HEAVY CANVAS OR NEOPRENE
FABRIC WITH AIRTIGHT SEAMS AND CONNECTIONS TO THE EQUIPMENT.
G. AIR FILTERS
L FILTERS SHALL BE 2' FIBERGLASS MEDIA 303 THROWAWAY TYPE IN A RIGID FRAME WITH A
SUPPORTING MAZE ACROSS BOTH ENTERING AND LEAVING SURFACES. SUPPLY
ONE COMPLETE SET OF FILTERS AFTER OWNER'S FINAL ACCEPTANCE, FARR
30/30 OR EQUAL.
H. ACCESS DOORS
L FURNISH IN DUCTWORK AS INDICATED AND WHEREVER NECESSARY FOR PROPER ACCESS TO ALL
INSTRUMENTS, CONTROLS, FIRE DAMPERS MOTORIZED DAMPERS AND
EQUIPMENT AND FOR CONVENIENT INSPECTION, MAINTENANCE AND
REPLACEMENT OF SAME. SIZE TO BE AMPLE FOR USAGE. OPENINGS TO BE REINFORCED ON
ALL SIDES WITH MATERIAL OR DUCTWORK IN WHICH DOORS ARE INSTALLED.
2. HARDWARE - USE VENT LOCK HARDWARE THROUGHOUT. ALL DOORS TO BE HINGED WITH BRASS
PIN HINGES AND WITH QUICK OPENING LATCHES AS FOLLOWS,
I. REACH -IN DOORS TO BE 18, HIGH,
11. TWO (2) M150 HINGES W/ ONE 890 LATCH,
3. ACCESS DOORS (HARD SURFACES) CONTRACTOR SHALL PROVIDE HINGED ACCESS DOORS (MIR
12"X12') FOR DAMPERS, VALVES, ETC, WHERE FLOORS, WALLS, AND
CEILINGS MUST BE PENETRATED TO ACCESS MECHANICAL SYSTEMS. FINISH
SHALL BE COORDINATED THROUGH THE ARCHITECT OR OWNER'S REPRESENTATIVE TO MATCH
SURROUNDING FINISHES. FIRE RATED ACCESS DOORS IN FIRE RATED WALLS OR CEILINGS SHALL
BEAR A U.L. LABEL FOR FIRE RATING REQUIREMENT.
I. UTILITY FANS
L CONTRACTOR SHALL FURNISH AND INSTALL CENTRIFUGAL FANS OF SIZE AND TYPE CALLED FOR ON
DRAWINGS.
2. FANS SHALL BE RATED AND CONSTRUCTED TO BE CAPABLE OF OPERATING AT STATIC PRESSURES
OF 0.5' ABOVE
J. DOOR AIR CURTAIN (IF NEW EQUIPMENT IS SHOW ON DRAWINGS)
L UNITS SHALL BE FURNISHED IN SINGLE INCREMENTS OF SUFFICIENT STRUCTURAL STRENGTH TO BE
SUPPORTED FROM BOTH ENDS WITHOUT INTERMEDIATE SUPPORT.
MULTIPLE UNITS SHALL NOT BE PERMITTED. UNIT CASING SHALL BE A
MINIMUM OF 18 GAUGE 304 STAINLESS STEEL IN A NUMBER THREE FINISH.
2. GALVANIZED FANS SHALL BE FORWARD CURVED CENTRIFUGAL TYPE, DOUBLE INLET DESIGN, WITH
ZINC PLATED HUBS. TANGENTIAL TYPE BLOWERS AND COUPLING
CONNECTION SHALL NOT BE PERMITTED. INLET SCREEN SHALL BE
PERFORATED STAINLESS STEEL POWDER COATED BLACK.
3. DISCHARGE NOZZLE SHALL BE HIGH EFFICIENCY DISCHARGE PLENUM, DESIGNED SO THAT THE AIR
LEAVES ON A 6 DEGREE PLANE. AIR CURTAIN CREATES A POSITIVE AIR
SEAL WITH DIRECTIONAL AIR FOIL VANE. THE VANE SHALL FACILITATE
DEFLECTION OF AIR STREAM *20 DEGREES. UNIT SHALL HAVE MULTIPLE SPEED MOTORCS) TO
CONTROL AIR COLUMN DOWN FROM MAXIMUM SPEED.
4. ALL AIR CURTAINS SHALL CONSIST OF A STAINLESS STEEL CASING, CENTRIFUGAL FAN, RAISED
STAINLESS STEEL INLET SCREEN, ➢ISCHARGE NOZZLE, MOTOR(S) AND AN
OPTIONAL 1/2 INCH RE CLEANABLE FILTER.
5. MOTORS AT 1/2 HP 1075 RPM EACH SHALL BE HEAVY DUTY TYPE EQUIPPED WITH PERMANENTLY
LUBRICATED, SHIELDED SLEEVE BEARINGS OF EQUAL SIZE AT EACH END
AND DOUBLE EXTENDED SHAFTS REQUIRING NO OUTBOARD BEARINGS.
K. INSULATION
L SHALL BE AS MANUFACTURED BY OWEN-CORNING, MANVILLE, PITTSBURGH CORNING,
ARMSTRONG, OR APPROVED EQUAL INSULATION SUNDRIES AND
ADHESIVES SHALL BE MANUFACTURED BY BENJAMIN FOSTER, CHILDERS,
VIMASCO, OR APPROVED EQUAL.
2. INSULATE ALL SHEET METAL DUCTWORK EXCEPT EXHAUST DUCTWORK EXTERNALLY WITH 2'
THICK (R-6 MINIMUM) MANVILLE R SERIES MICROLITE TYPE-100
INSULATION OR APPROVED EQUAL. INSULATION TO HAVE FSK FACING AND
UL FIRE HAZARD CLASSIFICATION UF, FLAMES SPREAD 25, SMOKE DEVELOPED 30, AND FUEL
CONTRIBUTED 51L INSTALL PER ENERGY EFFICIENCY CODE AND
MANUFACTURER'S RECOMMENDATIONS.
3. C13NTRACT132 SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ADEQUATE AND PROPER
INSULATION AND
L. TESTING
L CONDENSATE DRAINS 'WALL BE TESTED BY TEMPORARILY PLUGGING ALL OUTLETS AND FILLING
THE SYSTEM WITH WATER TO THE LEVEL OF THE HIGHEST VENT STACK.
THE SYSTEM MUST BE INSPECTED AND ALL LEAKS REPAIRED AND THE
TEST REPEATED UNTIL THE WATER LEVEL DOES NOT DECREASE FOR A PERIOD OF 24 HUMS,
2. ADJUST THE AIR-CONDITIONING SYSTEMS, VENTILATING SYSTEMS, FANS, ETC. TO DELIVER NOT
LESS THAN THE REQUIRED AIR QUANTITY WITH QUANTITIES IN
EXCESS TO BE SUBJECT TO THE APPROVAL OF THE ENGINEER IF FOUND
NOT HAVE OBJECTIONABLE EFFECTS SUCH AS NOISE, DRAFTS, OR MOTOR OVERLOADS.
3.1 INSTALLATION
A, ALL LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. INDICATED ON THE DRAWINGS ARE
DIAGRAMMATIC AND SHALL BE F13LLOWED AS CLOSELY AS POSSIBLE TO THE PLANS SUBJECT TO BUILDING
CONSTRUCTION AND INTERFERENCES WITH OTHER TRADES. ALL WORK SHALL BE INSTALLED TO ENSURE
MAXIMUM HEADROOM, BALANCED OPERATION AND SUITABLE AESTHETIC APPEARANCE. CONTRACTOR IS
RESPONSIBLE FOR ANY FIELD MEASUREMENTS REQUIRED TO PROVIDE AN APPROVED AND FUNCTIONAL
INSTALLATION.
B. NOT ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION ARE SHOWN ON THESE DRAWINGS.
REFER TO EQUIPMENT INSTALLATION INSTRUCTIONS, SCHEDULES AND APPLICABLE CODES FOR ADDITIONAL
INFORMATION, INCLUDING REQUIRED CONNECTION LOCATIONS, TYPES AND SIZES.
C. CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ADEQUATE AND PROPER
INSULATION AND MOISTURE -SEAL IN A MANNER THAT WILL PERMANENTLY PREVENT THE ACCUMULATION
OF ANY OBJECTIONABLE MOISTURE ON THE EXTERIOR OF AIR-CONDITIONING DOTS, REFRIGERANT PIPING,
CONDENSATE DRAIN PIPING, AIR DUCTS OR OTHER PARTS OF THE SYSTEM. CONTRACTOR SHALL CORRECT
THE CAUSE OF ANY CONDENSATION AND FULLY REPAIR, WITHOUT COST TO THE OWNER, ANY DAMAGES TO
BUILDING SURFACES, FURNISHINGS OR EQUIPMENT CAUSED BY CONDENSATION FROM THIS SYSTEM FOR
THE FULL PERIOD OF THE GUARANTEE.
D. ALL PENETRATIONS SHALL BE PATCHED AND FINISHED TO MATCH SURROUNDING SURFACES AND FINISHES
ALL EQUIPMENT OR PIPE PENETRATIONS THROUGH WALLS, ROOFS AND FLOORS SHALL BE SLEEVED AND
SEALED SO AS TO BE WATER AND AIRTIGHT.
E. CLEANING TESTING AND ADJUSTING, THE CONTRACTOR, AT HIS EXPENSE, SHALL CLEAN, REPAIR, ADJUST,
CHECK, BALANCE, AND PLACE IN SERVICE THE VARIOUS SYSTEMS HEREIN SPECIFIED WITH THEIR RESPECTIVE
EQUIPMENT, ACCESSORIES AND PIPING. HE SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, AND
TOOLS REQUIRED TO PERFORM TESTS REQUIRED BY THESE SPECIFICATIONS AND BY THE GOVERNING
AUTHORITIES.
F. NO WORK SHALL BE CONCEALED UNTIL PROPERLY INSPECTED AND TESTED.
MECHANICAL
ISSUED FOR PERMIT 02-09-16
KAMM CONSULTING PROJECT#: 2015-0844
PROJECT MANAGER: DUANB MILLAR -�% ARP®LY �NE
PRINCIPAL
Badly L Brown Florida License ti38232
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL 32960
Tol.772.794.2929
Fax.772.562.8600
License No. AA0002238
wwe.donadio-arch.com
Consultant:
Drawing Title:
Reference North
��!LF COPY
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
Cart. No.: 12,456
Date Signed: M ® • 2
Project:
225
MEC�ul-IANI CAL PLAN
1/4'-1--0'
MECHANICAL PLAN
ISSUED FOR PERMIT 02-09-16
KAMM CONSULTING PROJECT #: 2015-08"
PROJECT MANAGER: DUANE MILLAR ..rilti
14" Orange
r�M M Fort Pierce rid 34954
Phone 77
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL32960
791.772.794.2929
Faz.772.562.6600
License No. AA0002238
w .donadio-arch.conn
Consultant:
Drawing Title:
Reference North
i�&FILF CAIJ�Py
Drn: Dwg. File:
MT
Chet: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
PRINCIPAL
Bradly L Brown 1`101 ida License #58232
Cart. No.: 12,456
Date Signed: M2*1
FAN SCHEDULE
SELECTION
DATA
FAN DATA
I MOTOR DATA
GENERAL
DATA
TAG
SERVICE AREA
MANUF.(*)
MODEL
CONFIG.
CFM
ESP ("WG)
SONES
HP
RPM
DRIVE
VOLTAGE
WEIGHT
(LBS)
IMENSIH"
L"xW"x
L"xW" OPENING
CONTROL
ACCESSORIES
EF-1
BATHROOMS
GREENHECK
SP-B70
CEILING
50
.2
1.1
45 WATT
563
DIRECT
120/1/60
10
14X12X8
*
LIGHT INTERLOCK
1-6
(*) APPROVED EQUAL MANUFACTURER: COOK, TWIN -CITY, ACME, PENN
ACCESSORIES
1.
NOTES:
PROVIDE GRILLE COLOR PER ARCH. SPECS
GENERAL FAN NOTES:
2.
PROVIDE BACK DRAFT DAMPER
a.
MOTOR STARTERS, DISCONNECTS (IF NOT FACTORY PROVIDED) AND ALL EQUIPMENT
3.
LOCATE BACK DRAFT DAMPER AT DISCHARGE
NORMAL POWER AND EMERGENCY POWER WIRING
BY ELEC. CONTRACTOR
4.
PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND INTEGRAL
THERMAL OVERLOAD PROTECTION, b.
ALL CONTINUOUS -DUTY MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION
COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ANY PURCHASING.
ACCORDING TO NATIONAL ELECTRICAL CODE PAR.
430-32.
5.
PROVIDE BIRD SCREEN
6.
SUPPORT FROM STRUCTURE COMPLETE WITH VIBRATION
ISOLATORS
C.
FIELD ADJUST OPENINGS WITH STRUCTURE.
OUTSIDETAAIR
CALCULATIONS
(PER 6-1,
ASHRAE 62.1-2014)
AREA SERVED
OR UNIT TAG
NET OCCUPIABLE
AREA SQ.FT.
AREA OUTDOOR
AIR RATE (RA)
CFM/FT" 2
TOTAL NO.
OF PEOPLE
PEOPLE OUTDOOR
AIR RATE (RP)
(
CFM/PERSON
DEFAULT VALUES
TOTAL N0. OF
PEOPLE FROM
DEFAULT VALUES
COMBINED OUTDOOR
AIR RATE
TOTAL CFM
O/A REQUIRED
TOTAL CFM
O/A PROVIDED
NOTES
OCC. DENS. P
1000FT�2 FL. AR•
CFM PERSON
/
RTU-1
KITCHEN
719
0.18
7
7.5
-
-
130+53
183
200
SEE NOTES
RTU-2
DINNING
1 534
0.18
25
7.5
-
-
96+188
284
285
SEE NOTES
RTU-3
OFFICE
1192
0.06
10
5
-
-
72+50
122
160
SEE NOTES
TOTAL
1253.0
-
-
-
-
-
-
589.0
485.0
-
NOTES:
1. CALCULATIONS ARE
BASED ON ESTIMATED MAX. OCUPPANCY
RATES PER ARCHITECTURAL PLANS AND
ASHRAE 62.1-2014.
VENTILATION
RATES PER ASHRAE 62.1-2014.
2, FOR OFFICE AND
OTHER SIMILAR
AREAS CALCULATIONS
ARE
BASED ON CONTINUOUS OCCUPANCY
ROOFTOP A/C EQUIPMENT SCHEDULE
A/C UNIT TAG
RTU-1,2
RTU-3
MANUFACTURER
CARRIER
CARRIER
MODEL
50VL-A36
50VL-A48
TOTAL SENSIBLE CAP. MBH.
24.5
34.3
TOTAL COOLING CAP. MBH.
34.2
47.0
ENT. AIR TEMP D.B./W.B. T
80'/67-
80'/67-
LEAV. AIR TEMP D.B./W.B. 'F
-
-
SUPPLY AIR CFM
1200
1600
OUTSIDE AIR CFM
SEE OA SCHEDULE
160
VOLTAGE
208/30/60
208/30/60
MCA/MOCP
33.5/35.0
35.5/40.0
SEER/EER
14.5/-
14.2/-
OPERATING WEIGHT LBS.
365
439
DIMENSIONS L x W x H (IN.)
48X32X50
48X43X50
REF./LBS.
R-41 OA/-
R-41 OA/-
NOMINAL TONNAGE/STAGES
3/1
4.0/2
FQZ
NO. OF COMPRESSORS
1
1
LIU�
uJ
COMP. R.L.A. EACH
9.0
13.7
ZNO.
OF OUTDOOR FANS
1
1
8
FAN FLA. EACH
1.2
1.2
INDOOR FAN TYPE
FC
FC
FAN E.S.P. (IN. W.G.)
0.5"
1"
ZZ
FAN H.P./B.H.P.
0.75 BHP
1.0 BHP
U
FAN F.L.A.
6.0
7.6
COIL ROWS/FPI
-
-
a-
HEATER TYPE
ELECTRIC
ELECTRIC
HEATER K.W. ® RATED VOLTAGE
7.5 ® 208V/30
7.5 ® 208V/30
NO. OF STEPS
1
1
FILTER TYPE/EFF.
1" THROWAWAY/30%
1" THROWAWAY/30%
NOTES:
1. UNITS SHALL BE "ARI" RATED. APPROVED EQUIVALENT: AAON,
LENNOX, McQUAY, TRANE, YORK
2. PROVIDE FACTORY BUILT ROOFCURB 14"(OR 20" IF NECESSARY) HIGH,
INSTALL UNIT LEVEL WITHIN PRESCRIBED TOLERENCES (SEE DETAIL)
3. PROVIDE COMPRESSOR 5-YEAR WARRANTY
4. PROVIDE SLOPED CONDENSATE DRAIN PAN AND INTERNAL TRAP.
5. -
6. PROVIDE MOTORIZED/MODULATING OUTSIDE AIR DAMPER WITH CO2 SENSOR.
7. PROVIDE SERVICE CLEARANCES PER MFGR'S RECOMMENDATIONS.
8. PROVIDE SINGLE POINT POWER ENTRY.
9. PROVIDE FACTORY MOUNTED FUSED DISCONNECT, COORDINATE PRIOR TO PURCHASING
10. PROVIDE VIBRATION/SOUND ISOLATION CURB.
11. PROVIDE MOTOR OVERLOAD AND THERMAL PROTECTION.
12. PROVIDE MATCHING PROGRAMMABLE THERMOSTAT.
13. PROVIDE ELECTRONIC CONDENSATION CONTROL SYSTEM FOR DRAIN PAN(S).
14. PROVIDE ELECTRIC HEATER WITH MIN. 2 STAGES IF OVER 10 KW CAPACITY.
15. PROVIDE 2 POSITION HOT GAS REHEAT FOR RTU-2.
EL:OO'J'J
CC
TURNING
HANQ`� NU
HANG ALL DUCT PER SMACNA STANDARDS
r AD
CHANNEL STRAP & SADDLE
HVAC DUCT
LOCKING QUADRANT
TO BE EXPOSED -
FLEXIBLE DUCT WITH
INSULATION &
VAPOR BARRIER -
TIE TO
STRUCTURAL
SUPPORTS -
2" WIDE METAL BAND
SUPPORT
SQUARE TO
ROUND
ADAPTER -
SUSPENDED TYPE
CEILING SYSTEM
■rm
DUCT-001
MPER
SEE M6.1 FOR TYPE
RETURN AND EXHAUST DUCT
MOUNTED NOT GRIsLLE CALE DETAIL
GALV. STEEL ROD OR
STRAP SUPPORTS PER
SMACNA STANDARDS
SIDE TAKE -OFF FITTING
WITH DAMPER, BELL MOUTH
OR SHOETAP TYPE (SEE NOTE
MAIN SUPPLY AIR
DUCT, SEE PLANS FOR
TYPE AND INSULATION
\ /
- - J,
11-1/2" X 1-1/2" X 1/8" GALV.
ANGLE OR STRAP PER SMACNA
CONNECT INNER DUCT WITH DRAWBAND
AND SEAL WITH TAPE/MASTIC OUTERDUCT
AT NECK CONNECTION
C PROVIDE THERMAL INSULATION BLANKET
IF INSTALLED IN UNCONDITIONED SPACE
LOUVERED FACE CEILING DIFFUSER
WITH 2' X 2' LAY -IN ALUM. PANEL
NOTE: PROVIDE CABLE CONTROL DAMPER FOR HARD CEILING AREAS.
DETAIL
0 SUPPLY AIR GRILLE SCHEDULE
TAG
MANUF. & MODEL
FACE SIZE
NECK SIZE
MATERIAL
FRAME
FINISH
DAMPER
THROW
NC
CFM
RANGE
NOTES
A
TITUS/ TDCA-AA
2024
SEE SCH.
ALUM.
NOTE #3
WHITE
OBD
4-WAY
MAX. 30
SEE
SCH.
1-6
B
TITUS/ TDCA-AA
12X12
SEE SCH.
ALUM.
NOTE #3
WHITE
OBD
4-WAY
MAX. 30
SEE
SCH.
1-6
(*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B. NAILOR
GENERAL NOTES
1. PROVIDE SPIN -IN COLLAR AT TRUNK TO FLEX DUCT CONNECTION.
2. PROVIDE TYPICAL 4-WAY DIFFUSION, 2-WAY OR 3-WAY ONLY WHERE INDICATED ON PLAN
3. REFER TO ARCHITECT PLANS FOR CEILING TYPE.
FLEX SCHIEDIJLE
4. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL.
5. FLEX DUCT SIZE TO BE SAME AS DIFFUSER NECK SIZE.
60"
50-125 CFM
6. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE.
80"
130-200 CFM
100"
205-330 CFM
CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT/OWNER, 120"
335-450 CFM
PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BULDING
140"
STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL
455-600 CFM
OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO
THE ATTENTION OF ENGINEER.
160"
605-700 CFM
�� RETURN AIR GRILLE SCHEDULE
TAG
MANUF. & MODEL
FACE SIZE
NECK SIZE
MATERIAL
FRAME
FINISH
DAMPER
THROW
NC
1cFM
RANG
NOTES
AA
TITUS/ 350FLF1
24X24
SEE SCH.
ALUM.
NOTE #1
WHITE
OBD
-
MAX. 30
SEE SCH.
2-3
(*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B, NAILOR
GENERAL NOTES
CONTRACTOR SHALL VERIFY WITH ARCHITECT
AND TENANT
OR OWNER, PRIOR TO ANY PURCHASING OR
INSTALLATION,
1. REFER TO ARCHITECT PLANS FOR CEILING TYPE.
A BUILDING STANDARD HAS TO BE FOLLOWED REGARDING
2. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL.
A
A SPECIFIC MODEL OR MANUFACTURER AND
SHALL BRING
3. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN
ANY DISCREPANCY TO THE ATTENTION OF ENGINEER.
UNCONDITIONED SPACE
NECK SIZE CFM RANGE NECK SIZE
CFM RANGE
6X6 0-150 CFM 15X15
0-900 CFM
8X8 0-250 CFM 18X18
0-1350 CFM
10X10 0-400 CFM 22x22
0-2000 CFM
12X12 0-600 CFM
MECHANICAL SCHEDULES
ISSUED FOR PERMIT 02-09-1 r,
KAMM CONSULTING PROJECT #: 2015-0844
PROJECT MANAGER: DUANE MILLAR
1408 Ora ui
Fort Pi r da- ¢q99�j5pp qq��
M M Phone? 2. 5-..1 5 745
nsu u bbro @kax mcon6Ulting, FIT.
Certipc tlg7, ,f t I aahon #81
PI2INC11` 11 @ t7-76�'Z
Bradly LBrown Flaridn License 115823 .9 to
STA
Project:
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 1]Ih Street
Vero Beach. FL 32950
Te1.772. 794.2929
Fax 772.562.8600
License No. AA0002238
www.donadio-arch.com
Consultant:
Drawing Title:
Reference North F,�&R , L' COP)
Drn: Dwg. F
MT
Chd: XREFI
AJD
Project No.: Plot Fil
2015-63
Sheet No.:
Cert. No.: 12,456
Date Signed: M 6. 1
dAL Et4G,r'•
Project:
EQUIPMENT SCHEDULE
MECHANICAL SCHEDULE
ITEM
No
QTY
EQUIPMENT CATEGORY
REMARKS
WATER
HOT COLD
ROUGH -IN
HIEGHT
WASTE
ROUGH -IN
HIEGHT
GAS
ROUGH -IN
HIEGHT
REMARKS
DIRECT
JINDIRECT
SIZE
MBTU
4
1
THREE COMPARTMENT SINK
<3) 1-1/2'
REMARKS
RUN I.W. TO FLOOR SINKI MANIFOLD DRAINS
5
1
PRE -RINSE FAUCET
1/2'
1/2'
22'
7
1
MOP SINK
BY OTHERS
2'
3'
VERIFY REQUIREMENTS W/LOCAL JURISDICTION
8
1
SERVICE FAUCET
1/2'
1/2'
42'
9
1
WATER HEATER
BY G.C.
VERIFY REQUIREMENTS W/LOCAL JURISDICTION
21
1
ICE MAKER W/BIN
1/2'
REMARKS
(2) 3/4'
REMARKS
RUN I.W. TO FLOOR SINKI FILTERED CW FROM #2
P.C. TO RUN CW TO ITEM #21
22
1
WATER FILTER, 3-STAGE
1/2'
84'
24
1
PREP SINK
1/2'
1/2'
22'
1-1/2'
REMARKS
P.C. TO RUN I.W. TO FLOOR SINK
31
1
WORK TABLE W/HAND SINK & DUMP SINK
(2) 1/2'
(2) 1/2'
22'
1-1/2'
1-1/2'
18'
P.C, TO RUN I.W. TO FLOOR SINK
36B
1
FILTERED WATER SPIGOT
1/2'
REMARKS
FILTERED CW FROM #36C
36C
1
WATER FILTER, 2-STAGE
1/2'
22'
P.C. TO RUN CW TO ITEM #36B
38
1
ICE BIN, DROP -IN
1'
REMARKS
C. TO RUN I,W, TO HUB DRAIN
39
1
HAND SINK
1/2'
1/2'
22'
1-1/2'
I8'
57
2
STEAMER
1/2' ■
REMARKS
I I
I
SHUT-OFF TO BE AT 22' A.F.F.
62 1 DRAIN BOARD i 1' REMARKS P.C. TO RUN I.W. TO HUB DRAIN
wG,C, TO TEE CW TO EACH STEAMER USING 1/4' TUBING THRU REGULATOR
PLUMBING EQUIPMENT SCHEDULE
HOT WATER TO FIXTURES (WHERE
APPLICABLE)
COLD WATER SUPPLY
GATE VALVE
9C CHECK VALVE
REF.
No
ITEM DESCRIPTION
MANUFACTURER OR CAT. #
REMARKS
AGF
AIR GAP FITTING
ZURN Z - 1024-4 OR EQUAL
3/4" X 1 1/2"
ET
EXPANSION TANK FOR EWIIWILKINS
WXTP-8 OR EQUAL
2 GAL., 40 PSIG. 200 DEG. MAX.
FS
FLOOR SINK - INSTALLED
WADE W-9140-16-1, 12"X12" OR EQUAL,
PROVIDE INTERNAL STRAINER
FLUSH WITH FINISH FLOOR
NICKEL -BRONZE STRAINER 3/4" GRADE
VACUUM BREAKER
EXPANSION TANK
ELECTRIC WATER HEATER
MOUNTED AS HIGH AS POSSIBLE
ABOVE MOP SINK
EWH
TANK TYPE 50 GAL.
AO SMITH DEL-50D COMMERCIAL TANK TYPE WATER
32" MAX. HEIGHT
WATER HEATER
HEATER LIGHT DUTY ELECTRIC 50 GAL. 12KW.
PRESSURE/TEMPERATURE RELIEF VAL
WHA
WATER HAMMER
PRECISION PLUMBING PRODUCTS TYPE SC OR EQUAL
PROVIDE ACCESS PANELARRESTEIR
1' DIA. GALVANIZED ALL
THREADED ROD, CONNECT TO
FCO
FLOOR CLEAN OUT
ZURN Z1400 OR EQUAL
FLUSH WITH FINISH FLOOR
STRUCTURE ABOVE <4
WCO
WALL CLEAN OUT
ZURN Z1441 OR EQUAL
REQUIRED)
PRV
PRESSURE REDUCING
WATTS SERIES LFN45B LEAD FREE WATER PRESSURE
MAX. WORKING PRESSURE: 400
VALVE
REDUCING VALVE OR EQUAL. CAST COPPER SILICON
PSI (27.6 BAR) ADJUSTABLE
PROVIDE DIELECTRIC UNION
ALLOY BODY CONSTRUCTION, STAINLESS STEEL
REDUCED PRESSURE RANGE: 25
AT HOT AND COLD WATER
INTEGRAL STRAINER, THERMOPLASTIC SEAT AND
TO 75 PSI, STANDARD PRESSURE
CONNECTIONS TO HEATER
CAGE, THERMAL EXPANSION BYPASS AND SEALED
SETTING: 50 PSI
SPRING CAGE
GALVANIZED STEEL DRAIN PAN,
MXV
UNDER SINK
WATTS LFMMV SERIES OR EQUAL; LEAD FREE
UP TO 1" HW & CW ROUGH -IN
(OR HIGH IMPACT PLASTIC PER
THERMOSTATIC MIXING
VALVE SHALL HAVE INTEGRAL
CODE) SIZED TO PROVIDE 2'
VALVE
CHECK STOPS. CONCEAL IN WALL
MINIMUM CLEARANCE ON ALL
SIDES OF WATER HEATER.
RPZ
REDUCED PRESSURE ZONE
WATTS SERIES LF009, LEAD FREE DOUBLE CHECK
eAVITY
LEAD FREE CAST COPPER SILICON
CPREVENTER HECK VALVE
VALVE ASSEMBLY, OR EQUAL
ALLOY TO MAX. WORKING
BACDKUFLOWLE
PRESSURE:2" 175 py�I
1' GALVANIZED ANGLE STEEL
FRAME WITH 16 GA
BFP1
BACK FLOW PREVENTION
WATTS SERIES 9D DUAL CHECK VALVE ASSEMBLY
MIN. WORKING PRESSURE: 25 PSI;
GALVANIZED BOTTOM, SIZE
ASSEMBLY FOR ICE
WITH ATMOSPHERIC PORT, OR EQUAL
MAX. WORKING PRESSURE: 175
TO FIT DRAIN PAN.
MAKER I
PSI
MOP SINK FAUCET 48' ABOVE FLOOR
PLUMBING EQUIPMENT SCHEDULE
REF.
No ITEM DESCRIPTION MANUFACTURER OR CAT. #
HLA WALL HUNG LAVATORY AMERICAN STANDARD 0124.24
- PERFORATED STRAINER WITH 1 1/4" OFFSET TAILPIECE - MCGUIRE 155WC
- CHROME PLATED 3/8" SUPPLY WITH ANGLE STOP AND WROT ESCUTCHEON - MCGUIRE 158WC
- CHROME BRASS P-TRAP, 17 GA. WITH ESCUTCHEON - MCGUIRE 8902
- WALL MOUNTED CARRIER WITH HANGER PLATE, CONCEALED ARMS - ZURN OR JOSAM
- FAUCET WITH AERATOR, 6" HANDLE, .05 GPM FLOW, ON 4" CENTERS - SYMMONS S-20-2-G-FR-W
MOP BASIN - ONE PIECE CONSTRUCTION, 24"X24"X10", FLOOR MOUNTED TYPE FIAT MSB-2424
- FAUCET WITH PAIL HOOK AND HOSE END, VACUUM BREAKER, INTEGRAL STOP FIAT 83-AA
- HOSE AND HOSE BRACKET - FIAT 832-AA
- MOP HANGER, 24" X 3", 18 GA. - FIAT 889-CC
- VINYL BUMPER GUARD - FIAT 889-CC
- SILICON SEALANT - FIAT 833-AA
PROVIDE ESCUTCHEONS AT ALL
WALL PENETRATIONS
EXTEND EMERGENCY DRAIN PAN
DISCHARGE PIPING MINIMUM 1
INCH TO DRAIN INDIRECTLY
INT❑ FLOOR DRAIN
EXTEND TEMPERATURE &
PRESSURE RELIEF DISCHARGE
PIPING FULL SIZE AS
RECOMMENDED BY
MANUFACTURER INDIRECTLY
INT❑ MOP SINK,
MOP SINK
PREFERRED WATER HEATER DIAGRAM
r
NOT TO SCALE
HWC
WATER CLOSET - ADA, VITREOUS CHINA, FLUSH TANK, SIPHON JET, ELONGATED
AMERICAN STANDARD 2108.408 OR
PLUMBING ROUGH -IN NOTES:
BOWL, 12" ROUGHING, FLOOR MOUNTED, WATER SAVER TYPE, SEAT 19" A.F.F.
EQUAL
- WHITE SOLID PLASTIC SEAT, OPEN FRONT, CHECK HINGE
- OLSONITE 95
1. THIS PLAN IS INTENDED TO SHOW FOOD SERVICE EQUIPMENT PLUMBING REQUIREMENTS AND
ROUGH -IN HEIGHTS ONLY. VERIFY W/ ARCHITECT AND/OR OWNER FOR ANY PLUMBING
- CHROME PLATED 3/8" SUPPLY WITH ANGLE STOP AND WROT WITH ESCUTCHMN
MCGUIRE 166
CONNECTIONS FOR EQUIPMENT NOT SHOWN OR SUPPLIED BY F.S.E.0
2. PLUMBING CONTRACTOR SHALL PROVIDE ALL ROUGH -IN AND FINAL CONNECTIONS TO ALL FOOD
SERVICE FACILITIES EQUIPMENT. ALL WORK TO BE IN ACCORDANCE WITH ALL NATIONAL, STATE
AND LOCAL CODES AS REQUIRED.
3. All DIMENSIONS ARE FROM AN ESTABLISHED BUILDING COLUMN LINE OR WALL AS INDICATED
TO CENTERLINE OF ROUGH -IN. IN THE CASE OF EQUIPMENT SUCH AS FAUCETS, & MIXING
VALVES, THE DIMENSION WILL RUN TO THE HALF -WAY POINT BETWEEN HOT AND COLD
WATER ROUGH -INS. CONSULT THE PROJECT CUT -BOOK TO DETERMINE IF ITEM IS 4" OR 8"
ON CENTER.
4. WHEN ROUGH -IN IS OUT OF WALL, THIS INDICATES CONCEALED LINES, DO NOT RUN ANY
EXPOSED LINES WHERE POSSIBLE. ANY AND ALL EXPOSED PIPING OR FITTINGS TO BE
STAINLESS STEEL, CHROME PLATED OR ENCLOSED IN A STAINLESS STEEL CONCEALED,
MOUNTED CHASE, OR AS SPECIFIED BY FOOD SERVICE EQUIPMENT CONTRACTOR.
5. PLUMBING CONTRACTOR IS REQUIRED TO FURNISH AND INSTALL ALL MECHANICAL COMPONENTS
NECESSARY TO PROVIDE SERVICE TO LOCATIONS AND EQUIPMENT AS SHOWN ON THIS SHEE
UNLESS NOTED OTHERWISE. PLUMBING CONTRACTOR IS ALSO RESPONSIBLE FOR MAKING FINAL
CONNECTIONS TO EQUIPMENT AND FITTINGS SUPPLIED AND INSTALLED BY FSEC.
6. PLUMBING CONTRACTOR TO HANG ALL HAND SINKS, AND MOUNT ALL DISPOSERS, FAUCETS,
BASKET DRAINS, LEVER DRAINS, TO/ON KITCHEN EQUIPMENT WITH FINAL CONNECTION TO
ROUGH-IN(S) AFTER EQUIPMENT IS SET IN PLACE.
7. ALL DRAIN LINES TO BE TRAPPED. SUPPLY ALL INDIRECT WASTE LINES WITH A TRAP AND AN
AIR GAP AT FLOOR RECEPTACLE. (AIR GAP TO BE A MINIMUM OF TWO TIMES THE DIA. OF
THE WASTE LINE. VERIFY WITH LOCAL CODE) VERIFY WITH LOCAL CODES IF WASTES SHOULD
BE DIRECT OR INDIRECT. VERIFY IF CLEAN WATER WASTES ARE REQ'D TO EMPTY INTO STORM
SEWERS.
8. GENERAL WATER PRESSURE IN KITCHEN AREA IS NOT TO EXCEED 50 PSI. PLUMBING
CONTRACTOR SHALL FURNISH AND INSTALL PRESSURE REDUCING VALVES, FLOW CONTROLS,
BACK FLOW PREVENTION, WATER HAMMER ARRESTORS, GATE VALVES, FOR WATER
CONNECTIONS AS REQUIRED PER LOCAL CODES.
9. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL WATER HAMMER ARRESTORS AND PRESSURE
REDUCING VALVES (PRV) IN LINE BEFORE ALL SOLENOID VALVES, IE: AT DISHMACHINE,
DISPOSER(S), ICE MAKER(S), STEAMER(S), ETC.
PLUMBING NOTES
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH FBC 2014,
APPLICABLE LOCAL CODES, RULES AND ORDINANCES.
2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
HIMSELF WITH ALL EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL
EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE
A PART OF THIS CONTRACT.
5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURA11ON OF THE WORK.
6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND
TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO
BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR
ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES.
7. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
8. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER/ARCHITECT
PRIOR TO BEGINNING CONSTRUCTION.
9. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES
PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES.
10. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE "L" COPPER.
COORDINATE WITH LOCAL JURISDICTION FOR ADDITIONAL REQUIREMENTS.
PROVIDE ALTERNATE FOR CPVC PIPING EQUAL TO BFGOODRICH "FLOWGUARD GOLD" FOR WATER
KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS. CONTRACTOR SHALL PERFORM A
WATER TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLATION
AND SHALL SUBMIT TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL.
11. SOIL, WASTE, VENT AND RAINWATER PIPING SHALL BE CAST IRON OR PVC, WHERE CODE ALLOWS.
PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS.
12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY
MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR
TO INSTALLATION.
13.FURNISH AND INSTALL APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING
FIXTURES, SIZED AND LOCATED PER MANUF.'S INSTALLATION INSTRUCTIONS AND WH-PDI 201.
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND
EQUIPMENT CONNECTIONS.
15.ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL.
16.ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR
SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS
AS PART OF THE PLUMBER'S WORK.
17. PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM
DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE BY
OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE
AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLA11ON
WHICH MAY HAVE BEEN DAMAGED.
18. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER
ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND
MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED.
19.PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS FINISH TO MATCH FIXTURE TRIM.
20.NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES
WHERE USED AS RETURN AIR PLENUMS.
21. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR
EQUIPMENT ROOMS.
22.ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM
LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER/OPERATOR.
23. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH ARMAFLEX INSULATION
PER TABLE 4-11 F.B.C. 2014 WHERE USED IN A RETURN AIR PLENUM. PVC PIPING WITH
ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES.
SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING.
24. CONDENSATE LINES SHALL NOT DRAIN ON THE ROOFING SYSTEM OR ANY OF ITS COMPONENTS
AND CONDENSATE LINES NEED NOT COMPLY WITH MIN. CLEARANCE REQUIREMENTS
PER FBC 2014, PAR. 1522.3.5
25. PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL
SHUT-OFF.
26. PROVIDE TRAP PRIMER FOR ALL FLOOR DRAINS, FLOOR SINKS, AND HUB DRAINS SHOWN ON PLANS. IF
SPECIFICATION IS NOT PROVIDED, SUPPLY PRECISION PLUMBING PRODUCTS MODEL #PR-500.
INSTALL PER MANUFACTURES RECOMMENDATIONS.
27. WATER PIPING INSULATION SHALL BE ARMAFLEX OR EQUAL INSTALLED IN ACCORDANCE
WITH MANUFACTURERS INSTRUCTIONS FOR ALL HOT WATER PIPING. WHERE DOMESTIC
WATER TEMPERATURES CAN CAUSE SWEATING ALL COLD WATER PIPING SHALL BE INSULATED
WITH ARMAFLEX INSULATION, THICKNESS AS PER TABLE 4-11 OF FLORIDA ENERGY CODE.
28•STUDOR MINI/MAXI AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO
VENT PIPING THRU ROOF WHERE ACCEPTABLE BY THE PLUMBING OFFICIAL AND LOCAL
CODES. INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS.
29. ALL HORIZONTAL RAINWATER PIPING THE RECEIVES CONDENSATE DISCHARGE FROM AIR
CONDITIONING EQUIPMENT SHALL BE INSULATED WITH 1" THK. ARMAFLEX.
30. PLUMBING PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, FIRE SPRINKLER, STRUCTURAL AND CIVIL PLANS AND
SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. PIPING MODIFICATIONS SUCH AS OFFSETS, BENDS,
TRANSITIONS, AND SIZES SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL
SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
CHANGES IN PIPE SIZES AND ROUTING SHALL BE REQUIRED BY THE CONTRACTOR TO AVOID CONFLICTS
AND TO ADAPT TO EXISTING FIELD CONDITIONS PROVIDED THAT INSTALLATION MEETS ALL
APPLICABLE CODES.
31. SUPPLY TRAP PRIMER FOR ALL FLOOR DRAINS, FLOOR SINKS, HUB DRAINS, ETC. SHOWN ON PLANS.
32.CONTRACTOR TO FIELD VERIFY ALL SUPPLY PRESSURE REQUIREMENTS AND LIMITATIONS. PROVIDE
PRESSURE REDUCING VALVE IF REQUIRED.
33. ANY REFERENCE OR APPLICATION OF DENTAL COMPRESSED AIR AS NOTED ON THIS PLAN IS NOT
USED OR INTENDED FOR LIFE-SUPPORT PURPOSES SUCH AS RESPIRATORS, IPPB MACHINES,
ANALGESIA, ANESTHESIA, ETC. THE ONLY USE IS AS INCIDENTAL AIR DISCHARGE INTO THE ORAL
CAVITY AND NOT A PRIMARY OR SECONDARY SOURCE OF AIR TO SUSTAIN LIFE.
PLUMBING CONTRACTOR TO VERIFY THAT FLOG
SINKS/FLOOR DRAINS & WASTES CONFORM TO
LOCAL CODES
DIRECT ALL INDIRECT WASTES INTO FLOOR
SINKS/FFD'S PER LOCAL CODES.
SEE ARCHITECTS DRAWINGS FOR ADDITIONAL
FLOOR DRAIN LOCATIONS.
PLUMBING SHEET INDEX
SHEET#
DESCRIPTION
POA
PLUMBING NOTES, LEGENDS, AND DETAILS
PO.2
PLUMBING SPECIFICATIONS
P2.1
SANITARY PLAN
P3.1
DOMESTIC WATER PLAN
P5.1
PLUMBING ISOMETRICS
PLUMBING LEGEND
CO
CLEAN OUT
S-- i
SANITARY SEWER PIPING
S.O.V.
SHUT-OFF VALVE
- - - S
VENT PIPING
COTC
CLEAN OUT TO GRADE
S- - -S
DOMESTIC COLD WATER PIPING
FS
FLOOR SINK
- - ---5
HOT WATER PIPING (110')
CW
DOMESTIC COLD WATER
HOT WATER PIPING (140')
HW
DOMESTIC HOT WATER----5
HOT WATER RECIRCULATING PIPING
HWR
DOMESTIC HOT WATER RECIRCULATING
CD 5
CONDENSATE PIPING
HB
HOSE BIBB
CA 5
COMPRESSED AIR PIPING
VTR
VENT THRU ROOF
S-T&P-S
TEMPERATURE AND PRESSURE RELIEF
GATE VALVE
S-SD- 4
STORM DRAIN PIPING
poQ
GLOBE VALVE
S- G --j
GAS PIPING
N
CHECK VALVE
S_C-S
PIPE RISE UP
GAS SOLENOID VALVE
PIPE DOWN OR DROP
GAS COCK
CAPPED END OF PIPE
4"
WATER HAMMER ARRESTER (PDI No.)
POINT OF CONNECTION
® FD
FLOOR DRAIN
-J
P-TRAP
PROVIDE TEST TEE
WITH SCREWED COUNTER-
SUNK ABS PLASTIC PLUG:
TAPERED -THREAD WITH
TFE JOINT COMPOUND. -
WHERE CLEANOUT TEE
IS CONCEALED IN A
CHASE OR PARTITION,
PROVIDE A ROUND 18
GAUGE STAINLESS STEEL
COVER WITH BEVELED
EDGES AND FLATHEAD
MACHINE SCREW.
CONCRETE
FLOOR
SLAB
COLUMN OR PARTITION
AS SHOWN ON FLOOR PLAN
CLEANOUT FACE SHALL
BE WITHIN 4" OF WALL
SURFACE. PROVIDE
PIPE EXTENSION IF REQUIRED.
NOTE:
PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES
NOT SERVED WITH A FLOOR CLEANOUT: LOCATE ABOVE FIXTURE FLOOD RIM
WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR OTHER WCO REQUIREMENTS.
WALL CLEANOUT DETAIL
NOT TO SCALE
SHOCK ARRESTOR SCHEDULE
P.D.I. DESIGNATION
MANUF. & MODEL
FIXTURE UNITS
CONNECTION
A
SIOUX CHIEF 652-A
1-11
1/2"
B
SIOUX CHIEF 653-B
12-32
3/4"
C
SIOUX CHIEF 654-C
33-60
1"
SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO
ACCESS DOOR REQUIRED. CONFORMS TO ANSI/ASSE 1010 STANDARDS.
SLOPE OF HORIZ. DRAINAGE PIPE
SIZE (inches)
MINIMUM SLOPE (inch per foot)
2-1/2 or less
1/4
3to6
1/8
8 or larger
1/16
TABLE 704.1 OF THE FLORIDA PLUMBING CODE 2014
PLUMBING NOTES
PERMIT
KAMM CONSULTINt.; PROJECT #:
2015-0844
PROJECT MANAGER: DUANE MILLAR
1408 Oran
e IL,
IL,
Fort Piercge
e..
PRINCIPAL
Bradly L Brown PI=& License #58232 m
02-09-16
4v.j��rQ
� e
fng.coln
f%t&W) 89 ;
i <%r
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beech, FL 32960
Te1.772.794.2929
Fax.772.562.8600
License No. AA0002238
w .donedio-erch.com
Consultant:
Drawing Title:
Y�`s
;1 i a
Reference North
Drn:
Dwg. File:
MT
Chd:
XREF File:
AJD
Project No.:
Plot File:
2015-63
Sheet No.:
Cert. No.: 12,456
Date Signed: P O 0 1
Project:
SECTION 10800
TOILET ACCESSORIES
PART 1 GENERAL
1.1 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS,
WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED
INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
PART 2 PRODUCTS
2.1 MATERIALS
A. TOILET AND BATH ACCESSORIES:
1. ACCESSORY: PAPER TOWEL DISPENSERS.
2. ACCESSORY: TOILET TISSUE DISPENSERS, SINGLE ROLL.
3. ACCESSORY: WASTE RECEPTACLES.
4. ACCESSORY: GRAB BARS.
S. ACCESSORY: WALL MIRROR
6. ACCESSORY: SOAP DISPENSERS, WALL MOUNTED.
7. ACCESSORY: MOP AND BROOM HOLDERS.
B. ACCEPTABLE MANUFACTURERS:
1. AVAILABLE MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, MANUFACTURERS OFFERING
TOILET ACCESSORIES THAT MAY BE INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
A. A. & J. WASHROOM ACCESSORIES.
B. BOBRICK WASHROOM EQUIP., INC.
C. BRADLEY CORPORATION.
D. MCKINNEY/PARKER.
C. MATERIALS, GENERAL:
1. STAINLESS STEEL: AISI TYPE 302/304, WITH POLISHED NO. 4 FINISH, 22 GAGE MINIMUM, UNLESS OTHERWISE
INDICATED.
2. BRASS: LEADED AND UNLEADED, FLAT PRODUCTS, ASTM B19; RODS, SHAPES, FORGINGS, AND FLAT PRODUCTS
WITH FINISHED EDGES, ASTM B36; CASTINGS, ASTM B 30
3. SHEET STEEL: COLD -ROLLED, COMMERCIAL QUALITY ASTM A 366, 20-GAGE MINIMUM, UNLESS OTHERWISE
INDICATED. PREPARATION AND METAL PRETREATMENT AS REQUIRED FOR APPLIED FINISH.
4. GALVANIZED STEEL SHEET: ASTM A 527, G60.
5. CHROMIUM PLATING: NICKEL AND CHROMIUM ELECTRO-DEPOSITED ON BASE METAL, ASTM B456, TYPE
6. BAKED ENAMEL FINISH: FACTORY -APPLIED, GLOSS WHITE, BAKED ACRYLIC ENAMEL COATING.
7. MIRROR GLASS: ASTM C 1036, TYPE 1, QUALITY Q2, 1/4" THICK, (0.23-INCH), WITH SILVERING,
ELECTRO-PLATED COPPER COATING, AND PROTECTIVE ORGANIC COATING.
8. GALVANIZED STEEL MOUNTING DEVICES: ASTM A 153, HOT -DIP GALVANIZED AFTER FABRICATION.
9. FASTENERS: SCREWS, BOLTS, AND OTHER DEVICES OF SAME MATERIAL AS ACCESSORY UNIT OR OF GALVANIZED
STEEL WHERE CONCEALED.
D. SANITARY NAPKIN DISPOSALS:
1. SURFACE MOUNTED SATIN STAINLESS STEEL, WITH SELF -CLOSING DOOR AND TUMBLER LOCK RETENTION OF THE
RECEPTACLE.
A. PROVIDE DISPOSABLE LINERS, (BOBRICK 353-12) MINIMUM QUANTITY OF TWELVE PER EACH UNIT.
E. TOILET TISSUE DISPENSER:
1. SURFACE MOUNTED DOUBLE ROLL TOILETTISSUE HOLDER OF SATIN FINISH STAINLESS STEEL,. 1/8INCH WALL
THICKNESS, AT EACH WATER CLOSET.
F. 2.06 GRAB BARS
1. STAINLESS STEEL TYPE 304 SATIN FINISHES WITH WALL THICKNESS NOT LESS THAN 18 GAGE AND AS FOLLOWS:
a. MOUNTING:EXPOSED,MANUFACTURER'S STANDARD I/81NCH THICK FLANGES AND VANDAL RESISTANT
ANCHORAGES.
B. CLEARANCE: 1-1/2" CLEARANCE BETWEEN WALL SURFACE AND INSIDE FACE OF BAR.
C. GRIPPING SURFACES: SMOOTH, SATIN FINISH.
D. MEDIUM -DUTY SIZE: OUTSIDE DIAMETER OF 1-1/4".
E. LENGTHS AND SHAPES AS INDICATED ON THE DRAWINGS, CAPABLE OF SUPPORTING 250 I.B. CONCENTRATED LOAD
IN ANY DIRECTION, PER ASTM F446.
G. LIQUID SOAP DISPENSER: (PUBLIC)
1.TYPE-304, SATIN FINISH STAINLESS STEEL, 40 FL. OZ. CAPACITY. CONCEALED WALL FASTENING SHALL BE
VDAL-RESISTANT WITH UNBREAKABLE REFILL WINDOW.
2. VALVE OPERATES WITH LESS THAN 5 LES. OF FORCE.
H. WALL MIRRORS:
1. STAINLESS STEEL CHANNEL FRAME MIRROR: ONE PIECE TYPE 304 CHANNEL FRAME 3/41NCH X 3/4 INCH, SATIN
FINISH WITH MITERED CORNERS, WELDED, GROUND AND POLISHED SMOOTH.
2. FLOAT/PLATE GLASS MIRROR, 1/41NCH THICK, PLATED, MIRROR.
3. MOUNTING: INSTALL ON CONCEALED WALL HANGER AND LOCK IN PLACE WITH THEFT -RESISTANT SCREWS.
4. SIZES AS INDICATED.
I. PAPER TOWEL DISPENSER:
1. SURFACE -MOUNTED TOWEL DISPENSERS: FABRICATE OF STAINLESS STEEL WITH HINGED FRONT EQUIPPED
WITH TUMBLER LOCKSET. PROVIDE PIERCED SLOTS AT SIDES AS REFILL INDICATORS.
2. CAPACITY: NOT LESS THAN EITHER 300 C-FOLD OR 400 MULTIFOLD PAPER TOWELS WITHOUT SPECIAL ADAPTERS.
3. SURFACE MOUNT STAINLESS SHELF: SATIN FINISH S.S. WITH BRACKETS.
PART 3 EXECUTION
3.1 INSTALLATION
A. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED
SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH
UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS.
B. RESTORE DAMAGED FINISHES AND TEST FOR PROPER OPERATION. CLEAN AND PROTECT WORK FROM DAMAGE.
SECTION 15100
PLUMBING
PART1 GENERAL
1.1 SUMMARY
A. WORK SHALL INCLUDE BUT NOT BE LIMITEDTOTHE FOLLOWING: PROVIDE ALL LABOR, MATERIALS, SERVICES,
EQUIPMENT AND APPLIANCES REQUIRED FOR THE FABRICATION AND INSTALLATION OF THE PLUMBING
SYSTEM, AS INDICATED ON THE DESIGN DRAWINGS AND AS OUTLINED IN THESE SPECIFICATIONS.
B. EQUIPMENTAND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE
SPECIFICATIONS SHALL BE CONSIDERED AS "SPECIFIED STANDARD" QUALITY. SUBSTITUTIONS SHALL BE EQUAL
QUALITY.
C. THE ENTIRE SYSTEM AND ALL COMPONENTS LISTED HEREIN SHALL MEETALL STATE, COUNTY AND LOCAL CODES
AND ORDINANCES IN EVERY RESPECT. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INSPECTIONS
AND PAY ALL FEES
D. ALL EQUIPMENT,ETC., SHALL BE NEW UNLESS OTHERWISE NOTED, AND AS SPECIFIED FREE OF DEFECTS AS
SHOWN ON THE DRAWINGS AND AS INDICATED IN THESE SPECIFICATIONS. ALL ELECTRICAL POWERED
EQUIPMENT SHALL BE U.L. OR E.T.L. LISTED.
E. ALL MATERIALS SHALL BE FABRICATED AND INSTALLED IN A NEAT AND PROFESSIONAL MANNER WITH THE
COORDINATION OF ALL INVOLVED TRADES TO AVOID INTERFERENCES AND DELAY DUE TO LACK OF
COORDINATION, NO ALLOWANCES WILL BE MADE FOR REWORK DUE 1'O COORDINATION DIFFICULTIES OR
INTERFERENCES BETWEEN INVOLVED TRADES.
F. OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY LAW FOR THE COMPLETIONS OF THE WORK. COST OF
THE REQUIRED PERMITS AND INSPECTIONS SHALL BE PAID BY THE CONTRACTOR. THE CONTRACTOR SHALL
OBTAIN AND PAY FOR ALL CERTIFICATES OF APPROVAL, WHICH MUST BE OBTAINED PRIOR TO FINAL
ACCEPTANCE OF THE JOB. ALL MATERIALS AND LABOR FURNISHED BY THE CONTRACTOR SHALL BE IN STRICT
ACCORDANCE WITH THE RULES AND REGULATIONS OF THE STATE AND MUNICIPALITY, UTILITY COMPANIES,
FLORIDA BUILDING CODE PLUMBING- 2004, NATIONAL ELECTRIC CODE (NEC) AND THE NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA).
1.2 QUALITY ASSURANCE
A. MATERIALS AND WORKMANSHIP:
a.PRODUCTS AND MATERIALS SHALL MEET OR EXCEED THE QUALITY OR REQUIREMENTS SPECIFIED OR SHOWN ON
THE DRAWINGS.
b.PROVIDE PRODUCTS AND MATERIALS, WHICH THE MANUFACTURER HAS CERTIFIED AS APPROPRIATE TO THE
APPLICATIONS SHOWN ON THE DRAWINGS AND SPECIFICATIONS.
c.PROVIDE PRODUCTS AND MATERIALS, WHICH ARE SUPPORTED BY CONVENIENT, PARTS AVAILABILITY AND
SERVICING.
d. WORKMANSHIP SHALL BE IN ALL RESPECTS OF THE HIGHEST QUALITY AND ALL CONSTRUCTION SHALL BE
DONE ACCORDING TO THE BEST PRACTICE OF THE TRADE. ALL SYSTEMS SHALL BE MADE COMPLETE AND
OPERATIONAL IN FIRST CLASS WORKING ORDER. FURNISH ALL NECESSARY LABOR AND MATERIALS TO CONSTRUCT
COMPLETE SYSTEM.:
b.
B. PROVIDETHE OWNER WITH THE FOLLOWING PRIORTO FINAL ACCEPTANCE:
a.PARTS LIST FOR EACH PIECE OF EQUIPMENT.
b.ONE BOUND SET OF APPROVED SHOP DRAWINGS.
c.ONE BOUND SET OF OPERATING INSTRUCTIONS AND MAINTENANCE SCHEDULES FOR EACH PIECE OF EQUIPMENT:
d.COPIES OF ALL WARRANTIES FOR EACH PIECE OF EQUIPMENT.
C. GUARANTEES AND WARRANTIES:
a.GUARANTEE ALL LABOR AND MATERIAL FURNISHED FOR A PERIOD OF ONE YEAR EXTENDING FROM THE TIME OF FINAL
ACCEPTANCE OF THE BUILDING. THE GUARANTEE SHALL COVER THE REPAIR OR REPLACEMENT WITHOUT ADDITIONAL COST TO
THE OWNER FOR ANY DEFECTIVE MATERIAL OR FAULTY WORKMANSHIP.
b.PROVIDE WARRANTIES FOR EACH PIECE OF MAJOR EQUIPMENT. WARRANTIES SHALL BE INCLUDED WITH THE OWNER'S
FINAL DOCUMENTS.
PART 2 PRODUCTS
2.1 MATERIALS
A. ACCESS PANEL:
a.CONTRACTOR SHALL PROVIDE HINGED ACCESS DOORS (MIN. 12"X12") FOR VALVES, ETC. WHERE FLOORS, WALLS AND CEILING
MUST BE PENETRATED TO ACCESS MECHANICAL SYSTEMS. FINISH SHALL BE COORDINATED THROUGH THE ARCHITECT TO MATCH
SURROUNDING FINISHES.
B. CLEANING, TESTING AND ADJUSTING:
a.THE CONTRACTOR, AT HIS EXPENSE, SHALL CLEAN, REPAIR, ADJUST, CHECK, A. BALANCE, AND PLACE IN SERVICE THE VARIOUS
SYSTEMS HEREIN SPECIFIED WITH THEIR RESPECTIVE EQUIPMENT, ACCESSORIES AND PIPING. THE CONTRACTOR SHALL FURNISH
ALL LABOR, MATERIALS,. EQUIPMENT, AND TOOLS REQUIRED TO PERFORM TESTS REQUIRED BY THESE SPECIFICATIONS AND BY
THE GOVERNING AUTHORITIES.
b.NO WORK SHALL BE COVERED OR CONCEALED UNTIL PROPERLY INSPECTED B. AND TESTED,
c. ALL DOMESTIC WATER PIPING SYSTEMS SHALL BE TESTED FOR ABSOLUTE C. TIGHTNESS BY SUBJECTING THE SYSTEM TO A
HYDROSTATIC PRESSURE OF 150 PSI GAUGE OR 50 PSI OVER WORKING PRESSURE, WHICHEVER IS GREATER FOR A PERIOD OF
NOT LESS THAN EIGHT (8) HOURS. ALL LEAKS SHALL BE REPAIRED AND THE HYDROSTATIC TESTREAPPLIED UNTIL, FOR AN EIGHT
(8) HOUR PERIOD, NO LEAKS CAN BE FOUND WHILE THE SYSTEM IS SUBJECT TO THE TEST PRESSURE, SOIL PIPE AND
CONDENSATE DRAINS SHALL BE TESTED BY TEMPORARILY PLUGGING ALL OUTLETS AND FILLING THE SYSTEM WITH WATER TO
THE LEVEL OF THE HIGHEST VENT STACK, THE SYSTEM MUST BE INSPECTED AND ALL LEAKS REPAIRED AND THE TEST REPEATED
UNTIL THE WATER LEVEL DOES NOT DECREASE FOR A PERIOD OF 24 HOURS.
C. HANGERS AND SUPPORTS:
a.PROVIDE ALL NECESSARY, PIPE SUPPORTS, HANGERS, RODS, CLAMPS AND ATTACHMENTS TO PROPERLY INSTALL AND
SUPPORT PIPING AND EQUIPMENT FROM THE BUILDING STRUCTURE.
b.PROVIDE ANY ANGLE IRON OR UNISTRUT AND SUSPENSION RODS REQUIRED TO INSTALL EQUIPMENT AND PIPING.
D. WATER SUPPLY SYSTEMS:
a.EXTEND WATER SERVICE AS INDICATED ON DESIGN DRAWINGS, PROVIDE SHOCK ABSORBERS AND VACUUM BREAKERS WHERE
REQUIRED.
b.PIPE AND FITTINGS:
I. ABOVEGROUND - SCHEDULE 40 CPVC.
II. BELOW GROUND- SCHEDULE 80 CPVC.
c.CHLORINAT10N: BEFORE BEING PLACED IN SERVICE ALL WATER DISTRIBUTION. SYSTEMS SHALL BE STERILIZED WITH CHLORINE
IN ACCORDANCE WITH FPC 610.1 STANDARD PROCEDURE FOR DISINFECTING POTABLE WATER PIPING.
dJNSULATION: INSULATE ALL HOT WATER LINES WITH 1" OF INSULATION HAVING A CONDUCTIVITY NOT EXCEEDING 0.27
BTU PER INCH.
IJ. CONNECTIONS TO MISCELLANEOUS EQUIPMENT:
a.ROUGH-IN AND CONNECT WATER, WASTE, AND VENT TO COMPLETE THE INSTALLATION OF EQUIPMENT LISTED ON THE
DRAWINGS.
b.PLUMBING FIXTURES SHALL BE PROVIDED COMPLETE AS SHOWN ON THE DRAWINGS WITH ALL REQUIRED SUPPLY,
WASTE, SOIL, AND VENT CONNECTIONS, TOGETHER WITH ALL FITTINGS, SUPPORTS, FASTENING DEVICES, COCKS, VALVES, AND
TRAPS.
c. ALL FIXTURES SHALL HAVE STOP VALVES ON ALL WATER CONNECTIONS, ALL EXPOSED METALTRIM ON ALL FIXTURES SHALL BE
POLISHED CHROMIUM PLATED. ALL EXPOSED PIPES EXTENDING FROM WALL SHALL HAVE CHROMIUM PLATED BRASS
ESCUTCHEON MOUNTED AGAINST WALL. EXPOSED PVC PIPING AND P-TRAPS ARE UNACCEPTABLE.
d.THE PLUMBING FIXTURES SHALL BE ROUGHED -IN ACCORDANCE WITH MANUFACTURER'S "ROUGH -IN INFORMATION".
PROVISIONS FOR MOUNTING WALL FIXTURES SHALL BE MADE WHILE THE WALL 15 BEING BUILT.
F. DRAINAGE SYSTEM:
a.PIPE SLOPE:
I. 2-1/2 INCH DIAMETER AND LESS SHALL BE INSTALLED WITH A FALL OF NOT LESSTHAN 1141NCH PER FOOT.
II. 31NCH DIAMETER OR LARGER SHALL BE INSTALLED WITH A FALL NOT LESS 2. THAN 1/81NCH PER FOOT.
G. PIPE AND FITTINGS:
a.DRAIN, WASTE AND VENT PIPING FOR THIS PROJECT SHALL BE SCHEDULE 40 PVC TYPE DWV.
b. PROVIDE CLEANOUTS EVERY 75 FEET, AT CHANGES IN DIRECTION, AT BASE OF DOWN SPOUTS AND AT BASE
OF SOIL AND WASTE STACKS.
PART 3 EXECUTION
3.1 INSTALLATION
A. ALL LOCATIONS OF EQUIPMENT,PIPING,ETC. INDICATED ON THE DRAWINGS ARE DIAGRAMMATIC AND SHALL BE
FOLLOWED AS CLOSELY AS POSSIBLE TO THE PLANS, SUBJECT TO BUILDING CONSTRUCTION AND INTERFERENCES WITH
OTHER TRADES. ALL WORK SHALL BE INSTALLED TO ENSURE MAXIMUM HEADROOM, BALANCED OPERATION AND
SUITABLE AESTHETIC APPEARANCE. CONTRACTOR IS RESPONSIBLE FOR ANY FIELD MEASUREMENTS REQUIREDTO PROVIDE
AN APPROVED AND FUNCTIONAL INSTALLATION.
B. NOT ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION ARE SHOWN ON THESE DRAWINGS. REFER TO
EQUIPMENT INSTALLATION INSTRUCTIONS, SCHEDULES AND APPLICABLE CODES FOR ADDITIONAL INFORMATION,
INCLUDING REQUIRED CONNECTION LOCATIONS, TYPES AND SIZES,
C. PROVIDE ISOLATION VALVES AND UNIONS AT ALL EQUIPMENT AND AS INDICATED ON DRAWINGS.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ADEQUATE AND PROPER INSULATION AND
MOISTURE -SEAL IN A MANNER THAT WILL PERMANENTLY PREVENT THE ACCUMULATION OF ANY OBJECTIONABLE
MOISTURE ON THE EXTERIOR OF CONDENSATE DRAIN. PIPING, OR OTHER PARTS OF THE SYSTEM. THE CONTRACTOR SHALL
CORRECT THE CAUSE OF ANY CONDENSATION AND FULLY REPAIR, WITHOUT COST THE OWNER, ANY DAMAGES TO
BUILDING SURFACES, FURNISHINGS OR EQUIPMENT CAUSED BY CONDENSATION FROM THIS SYSTEM, FOR THE FULL
PERIOD OF THE GUARANTEE.
E. PERFORM ALL WORK NECESSARY TO PREPARE THE STRUCTURE FOR THE INSTALLATION OF THE WORK.
F. ALL HOLES, OPENINGS AND DAMAGED MATERIALS CREATED DURING CONSTRUCTION SHALL BE REPAIRED AND FINISHED
BY EXPERIENCED WORKMEN. PROVIDE ALL ROOF, WALL AND FLOOR PENETRATIONS REQUIRED TO COMPLETE
INSTALLATION OR WORK (MAINTAIN FIRE RATING OF EXISTING STRUCTURE). ALL PENETRATIONS SHALL BE PATCHED AND
FINISHED TO MATCH SURROUNDING SURFACES AND FINISHES. ALL EQUIPMENT OR PIPE PENETRATIONS THROUGH WALL,
ROOF AND FLOORS SHALL BE SLEEVED AND SEALED SO AS TO BE WATER AND AIR TIGHT.
PLUMBING
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL 32960
Te1.772.794.2929
Pea.772.562.8600
License No. AA0002238
w .donadioarch.com
Consultant:
Drawing Title:
F 4
10: <, CC�p
Reference North
AL
77
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
Cart. No.: 12,456
Date Signed: P O 2
Project:
KEY NOTES
Oj TIE NEW SANITARY LINE TO EXISTING IN AREA.
CONTRACTOR TO FIELD VERIFY LOCATION AND
SIZE PRIOR TO CONSTRUCTION.
OTIE NEW GREASE WASTE LINE TO EXISTING
GREASE TRAP IN AREA. CONTRACTOR TO FIELD
VERIFY LOCATION AND SIZE PRIOR TO
CONSTRUCTION.
O1-1/4" CONDENSATE LINE. TIE TO NEAREST
MEANS OF ROOF DRAINAGE.
SANITARY PLAN
SAMTQFR--'�Y PLAN
1/4'-1'-0'
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL 32960
Te1.772.794.2929
Fax.772562.8600
License No. AA0002238
w. Aonario-arch.com
Consultant:
Drawing Title:
Reference North
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
Cert. No.: 12,456
Date Signed: P 2.1
Project:
DD OMM C STM WATER PLAN
1/,V-1'-o•
KEY NOTES
OTIE NEW DOMESTIC LINE TO EXISTING IN AREA.
CONTRACTOR TO FIELD VERIFY LOCATION AND
SIZE PRIOR TO CONSTRUCTION.
DOMESTIC WATER PLAN
ISSUED FOR PERMIT 02-09-I6
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
609 17th Street
Vero Beach, FL 32960
Te1.772.794,2929
Fan.772.562.8600
License No. AA0002238
w .donadio-arch.com
Consultant:
Drawing Title:
:emu. ..i",
' ReferenceNortl
I t
Drn: Dwg. File:
MT
Chd: XREF File:
AJ D
Project No.: Plot File:
2015-63
Sheet No.:
Cart. No.: 12,456
Date Signed: Mel
Project:
(31 UEA8E VV ! I TE
H\1`DJ-0METMC PLAN
N.T.S.
2- —
SAMTARY
MOMETMC PLAN
N.T.S.
` \ 2
• ii�� tIZP I II II t/2P ���+// " ,%' \
1� �\ \ I I ti P
Illiii I I I 1 3�ar
`\` \ 31 I s1 DD/� � � ✓ 1 I
36 �777 I'O
DD 0ME"EJ-3T�C" I��/i A T E R
D�0METG'�C PLAN
N.T.S.
KEY NOTES
O1 TIE NEW SANITARY LINE TO EXISTING IN AREA.
CONTRACTOR TO FIELD VERIFY LOCATION AND
SIZE PRIOR TO CONSTRUCTION.
OTIE NEW DOMESTIC LINE TO EXISTING IN AREA.
CONTRACTOR TO FIELD VERIFY LOCATION AND
SIZE PRIOR TO CONSTRUCTION.
O3 TIE NEW GREASE WASTE TO EXISTING IN AREA.
CONTRACTOR TO FIELD VERIFY LOCATION AND
SIZE PRIOR TO CONSTRUCTION.
SANITARY ISOMETRIC
Proposed
Improvements
for
Tropical
Smoothie
Cafe
ST. LUCIE COUNTY,
Key Plan: FLORIDA
Issues:
No.: Date: Description:
A. 02.09.16 PERMIT ISSUE
Architect:
DONADIO
& Associates, Architects P.A.
60917th Street
Vem Beach, FL 32960
Tat 772.794 2929
Fax.772.562.8600
License No. AA0002238
www.donadio-arch.com
Consultant:
)rawing Title:
Reference North
Drn: Dwg. File:
MT
Chd: XREF File:
AJD
Project No.: Plot File:
2015-63
Sheet No.:
art. No.: 12,456
ate Signed: P5.1