HomeMy WebLinkAboutPROPOSED EXPANSION PAGE 1-5Project: MECHANICAL NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE DRAWINGS, THE FLORIDA BUILDING CODE 2010 AND ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL ORDINANCES AND THE LATEST ADDITION OF THE FOLLOWING PUBLICATIONS; SMACNA-85, 92, 95; ASHRAE 15-01, 34-01, 62-04; NFPA 70-02, 72-02, 90A-02, 90B-02, 91-99, 96-01; ANSI Z10.1-98, Z10.3-98, Z21.8-94, Z21.83-98. 2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK. 3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES. 4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT WITH "AS -BUILT" DRAWINGS. 5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE [5] COPIES OF MANUFACTURER'S DRAWINGS FOR EACH PIECE OF EQUIPMENT AND CONTROLS INCLUDED IN CONTRACT. 6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS. ALL EQUIPMENT SHALL BE UL OR ETL LISTED. ALL INSTALLATIONS SHALL COMPLY WITH FMC 2010, CH. 3, GENERAL REGULATIONS. BUILDINGS LOCATED WITHIN 3,000 FT FROM THE OCEAN SHALL UTILIZE NON-FERROUS MATERIALS FOR ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC. 7. DUCTWORK: A, ALL AIR CONDITIONING DUCT WORK SHALL BE OF 1-1/2" (R-6) HEAVY DUTY FOIL REINFORCED FIBERGLASS WITH MANUFACTURER'S LOGO PRINTED ON VAPOR BARRIER a. ALL FLEX DUCT SHALL BE RATED CLASS I, UL-181 LISTED WITH METALLIZED INNER AND OUTER FOIL LINERS, MIN. R-6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 25 FT. FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER, GRILLE, AND REGISTER EQUAL TO "FLEXFLOW ELBOW" AS MANUFACTURED BY "THERMAFLEX". C. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH EXTERNAL BLANKET INSULATION R-6 MIN. ALL METAL EXHAUST, MAKE-UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R-6 MIN. THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC. ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A. SPECIAL SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2", 1", 2", 3", 4", 6", AND 10". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE CLASS SHOWN ON PLANS. WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY. WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM OF VAV BOXES. ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR ITS PRESSURE CLASS SEALING METHODS. 9. OUTSIDE AIR INTAKES SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL NOT LARGER THAN 1/2" MESH. O/A INTAKES SHALL NOT BE TAKEN FROM A LOCATION CLOSER THAN 10 FT. FROM ANY CHIMNEY, VENT OUTLET OR SANITARY SEWER VENT OUTLET, UNLESS SUCH VENT IS NOT LESS THAN 24 INCHES ABOVE THE OUTSIDE AIR VENT. OUTSIDE AIR INTAKE VENTS LOCATED ON ROOFS WILL BE PROPERLY MARKED WITH A UNIVERSAL MARKING "INTAKE", PERMANENTLY ATTACHED PER FMC 2010, SEC. 401.5.1 10. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS. 11. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAIRE. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS TO ENSURE COMPLAINCE WITH FMC 2010, PAR. 601.4 AND PAR. 603.15 FOR BALANCED AIR FLOW. 12. TEMPERATURE CONTROLS/THERMOSTAT: A. SHALL BE COMBINATION COOLING/HEATING, WITH SYSTEM "COOL -AUTO - HEAT -OFF" AND FAN "ON -AUTO" SELECTOR SWITCHES. PROVIDE PROGRAMMABLE TYPE AS RECOMMENDED BY MANUFACTURER, HONEYWELL OR EQUAL. PROVIDE TAMPER PROOF COVERS. 13. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION. INSTALL THERMOSTAT 48" TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE. MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION. WHENEVER THERE ARE MORE THAN ONE SENSOR OR THERMOSTAT, SIDE BY SIDE, THEY SHALL BE GANGED TOGETHER WITHIN THE SAME COVER PLATE WHEREVER POSSIBLE. CONTRACTOR SHALL COORDINATE THIS ISSUE WITH ARCHITECT/OWNER PRIOR TO INSTALLATION AND SHALL BRING ANY DISCREPANCY TO THE ENGINEER'S ATTENTION. 14. REFRIGERANT LINES SHALL BE COPPER, TYPE "L" HARD DRAWN WITH WROUGHT COPPER BRAZING -JOINT TYPE FITTINGS, USE BRAZING MATERIALS FOR HIGH PRESSURE PIPING PER AWS A5.8: BCuP SERIES COPPER -PHOSPHORUS ALLOY OR BAgt SILVER ALLOY. REFRIGERANT LINES SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS. SOFT COPPER TYPE "M" SHALL BE ALLOWED FOR RISER PIPING INSIDE CHASE TO LIMIT NUMBER OF JOINTS. COORDINATE WITH ENGINEER FOR PRIOR APPROVAL. ALL EXPOSED INSULATION SHALL BE PROTECTED WITH UV RESISTANT PAINT OR ALUMIN. SHIELD. 15. ARMAFLEX INSULATION SHALL BE USED FOR SUCTION LINES (1/2" FOR ABOVE 40' F AND 1" FOR BELOW 40' F) PER FLORIDA ENERGY CODE TABLE 4-11 FOR PIPING INSULATION. FILTER/DRYER AND SIGHT GLASS SHALL BE PROVIDED AT LIQUID LINES. 16. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W/SINGLE FOIL TURNING VANES. PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS. PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS, "YOUNG REGULATOR" OR EQUAL. 17. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START-UP, REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER. 18. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE. FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION/TEST STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION. DETECTORS SHALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM. 19. PROVIDE TYPE "B" DYNAMIC FIRE DAMPERS WITH SERVICE ACCESS DOORS IN ALL DUCTS AND OPENINGS PENETRATING FIRE RATED WALLS, MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, TENANT SEPARATION, PARTITIONS, FLOOR OR ROOF SLABS AND AT OUTSIDE AIR INTAKES AS REQUIRED. PROVIDE RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEILING OPENINGS, CEILING FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEILING ASSEMBLY. PROVIDE LOW -LEAKAGE CLASS DAMPERS FOR ALL SITUATIONS WHERE THE AIRFLOW CFM HAS TO BE CONTROLLED. VERIFY AND REPLACE AS REQUIRED FOR EXISTING SYSTEMS. 20. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2010, CH. 13, 410.1.ABCD.4 (THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS) FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS. THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE ('F) FROM SUPPLY GRILLES AND EVAPORATORS. FOR (EXISTING) SMOKE EVACUATION SYSTEMS HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PRIOR TO ANY NEW WORK, PROVING THAT THE SMOKE EVACUATION SYSTEM PERFORMS PER ORIGINAL DESIGN DOCUMENTS AND IS COMPLIANT WITH LOCAL CODE REQUIREMENTS. 21. RUN INSULATED FIRE RATED CONDENSATE DRAINS AS REQUIRED. 22. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50. 23. MECHANICAL EQUIPMENT ON ROOF OR ELEVATED STRUCTURES SHALL COMPLY WITH FBC 2010 PAR. 306.5 IF INSTALLED HIGHER THAN 16 FEET A.F.F. MECHANICAL EQUIPMENT INSTALLED IN ATTICS SHALL MEET THE REQUIREMENTS OF FBC 2010 PAR. 306.3 IF THE EQUIPMENT CAN NOT BE SERVICED/REMOVED THROUGH REQUIRED OPENING. MECHANICAL EQUIPMENT SHALL BE PROTECTED WITH MECHANICAL BARRIERS IF EXPOSED TO MECH. DAMAGE. ALL EQUIPMENT SHALL BE INSTALLED ON 6" CONCRETE PAD AT GRADE LEVEL . BEWALN4IF2 ALL WIND LOAD AND OTHER COMPLIANCE CALCULATIONS AND/OR INSTALLATION DETAILS FOR ROOF MOUNTED EQUIPMENT AS REQUIRED BY FBC 2010, SEC. 1509, 1522 AND CHAPTER 16, SHALL BE PROVIDED BY STRUCTURAL ENGINEER/ARCHITECT. 24. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120-208 VOLT PANELS AND MIN. 42" CLEARANCE IN FRONT OF ANY 240-480 VOLT PANEL. PROVIDE ADEQUATE SIDE CLEARANCE PER NEC. 25. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO HE READ IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT. 26. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES. ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK. 27. NO COMBUSTIBLE MATERIALS ARE ALLOWED IN RETURN AIR PLENUMS OR ABOVE CEILINGS USED AS RETURN AIR PLENUM. IF SPACE WITH RETURN AIR PLENUM HAS ANY DECK TO DECK PARTITIONS, AIR TRANSFER DUCTS MUST BE INSTALLED. WHEN CPVC PIPING IS USED FOR FIRE SPRINKLER SYSTEMS, THE R/A GRILLES LAYOUT SHALL BE (FIELD) COORDINATED WITH SUCH PIPING SO THAT NO PORTION OF THE GRILLES WILL BE DIRECTLY BELOW THE CPVC PIPING. 28. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2" ARMAFLEX INSULATION. PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 2010, SEC. 307 SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS. 29. MANUFACTURER'S WARRANTY. CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF (1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR (5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING NON -OPERATIONAL PERIODS OR AS AGREED WITH OWNER. MECHANICAL SHEET INDEX SFEErt MSCPoP110N MO.1 MECHANICAL NOTES, LEGEND & INDEX M2.1 MECHANICAL FLOOR PLAN M6.1 MECHANICAL SCHEDULES MECHANICAL LEGEND EF CEILING OR INLINE EXHAUST FAN ® SUPPLY AIR CEILING DIFFUSER r� RETURN AIR CEILING GRILLE I STANDARD SINGLE DUCT VVT BOX WALL LOUVER / WALL DIFFUSER. (3'0" SERVICE CLEARANCE) a LINEAR DIFFUSER Q THERMOSTAT L-- MANUAL VOLUME CONTROL DAMPER OH HUMIDISTAT MD MOTORIZED DAMPER ® REFRIGERANT SENSOR `� FIRE DAMPER SP STATIC PRESSURE SENSOR (Zoo DUCT SMOKE DETECTOR REDUCER OR INCREASER /"� S, "5 ' FLEX DUCT �•� E.;,I AP -ACCESS PANEL EXISTING FLEX DUCT -t----- -- AD - ACCESS DOOR ee sr EXISTING DUCTWORK ®UP SUPPLY & OUTSIDE AIR SECTION (UP) j a SUPPLY & OUTSIDE AIR DN SECTION (DN) UP RETURN OR EXHAUST DUCT SECTION (UP) i ON RETURN OR EXHAUST DUCT SECTION (DN) ® ROUND UP SHOE TAP DAMPER I„1M ROOFTOP A SOLENOID VALVE. RE RELOCATE VCD VOLUME CONTROL DAMPER MOD MANUALLY OPERATED DAMPER Tnc SUPPLY AIR o DIFFUSER OR GRILLE DESIGNATION 0 RETURN/EXHAUST AIR DIFFUSER OR GRILLE DESIGNATION ® VARIABLE FREQ. DRIVE CONTROL PANEL SUPPLY AIR RETURN AIR -Mu/c DOOR UNDER CUT TNo EQUIPMENT TAG OARTU- OUTSIDE AIR ROOF TOP UNIT RTU- ROOF TOP UNIT VAV- VARIABLE VOLUME BOX EF - EXHAUST FAN I NOT ALL SYMBOLS MAY APPLY TO THESE PLANS I HVAC ABBREVIATION LEGEND AC AIR CONDITIONING AFF ABOVE FINISH FLOOR BDD BACK DRAFT DAMPER CD CONDENSATE DRAIN COP COEFFICIENT OF PERFORMANCE DB DRY BULB DIA. DIAMETER E EXISTING TO REMAIN EER ENERGY EFFICIENCY RATIO EDH ELECTRIC DUCT HEATER EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE F FILTER FD FIRE DAMPER FLA FULL LOAD AMPS. FMS FLOW MEASURING STATION IPLV INTEGRATED PART -LOAD VALUE. MCA MINIMUM CIRCUIT AMPS (FOR WIRE SIZING) MOD MANUALLY OPERATED DAMPER MOCP MAXIMUM OVERCURRENT PROTECTION DEVICE NC NOISE CRITERIA O/A OUTSIDE AIR OBD OPOSITE BLADE DAMPER PD PRESSURE DROP. R EXISTING TO BE RELOCATED R/A RETURN AIR RLA RATED LOAD AMPS. SEER STANDARD ENERGY EFFICIENCY RATIO TSP TOTAL STATIC PRESSURE VD VOLUME CONTROL DAMPER VFD VARIABLE FRECUENCY DRIVE WB WET BULB NOTE: NOT ALL SYMBOLS MAY APPLY TO THESE PLAN. KAMM CONSULTING PROJECT'#: 2015-0250 PROJECT MANAGER: DUANE MILLAR ..u..I;r PROPOSED EXPANSION TO OVA AT THE MAIN STREET VILLAGE OFFICE BUILDING ST. LUCIE COUNTY, FLORIDA Key Plan Issues: No.: Date: Description: _ 05.22.15 PERMIT SET Architect: D O 1V A D 1 & Associates, Architects P.A. 609 17rh St=t Vero Beach, FL 32960 Ta1.772 794.2929 Fax.772.562.8600 ww.donadio-archcom License No. AA0002238 Consultant: THLZ: E' FLANS AND ALL PROPOSE W011K ARE SUBJECT TO ANY CORRECTIMIS REOUIRE'D BY FIELD INSPEC7GRS THAT UAY BE NECINAaY ItI OMDLPA TC COMPLY WITH ALL APPLICABLE CODES. FILE COPY Drawing Title: MECHANICAL NOTES Job North p Z V Drn: Drawing File: JEL Chd: XREF File: HKC Project No.: Plot File: 2013-15.005 Sheet No.: Can. No.: 12,456 Date Signed: M ®e 1 Copyright © 2013, Donedio & Associates, Architects, P.A., All Rights Reserved Project: MECHAMC AL PLAN i ISSUED FOR PERMIT 5/22/15 1 KAMM CONSULTING PROJECT #: 2015-0250 ++t%4 t t r PROJECT MANAGER: DUANE MILLAR ,.+++ , use i PROPOSED EXPANSION TO LANG REALTY AT THE MAIN STREET VILLAGE OFFICE BUILDING ST. LUCIE COUNTY, FLORIDA Key Plan Issues: No.: Date: Description: 05.22.15 PERMIT SET Architect: DONADIO & Associates, Architects P.A. 609 17th Street Vera Bench, FL 32960 Tel.772.794.2929 Fax372.562.8600 www.donadio-arch.c= License No. AA0002238 Consultant: THESE PLANS AND ALL PROPOSM WORK ARE SUBJECT TO ANY CORRECTICNS REQUIRED BY PIELD NSPECXAS THAT 14AY BE NECMASY IN OfiM TO COMPLY INITH ALL APPLICABLE CODES. FILE 00pT Drawing Title: MECHANICAL PLAN Job North w 'n% Drn: Drawing File: JEL Chd: XREF File: HKC Project No.: Plot File: 2013-15.005 Sheet No.: Cart. No.: 12,456 ^/ Date Signed:M2*11 1/4'-1'—U* Copydght C 2013, Conedlo & Associates, ArchRects, PA., All Rights Reserved Project: FAN SCHEDULE DATA FAN DATA MOTOR DATA GENERAL DATA WEIGHT OPENING TAG SERVICE AREA MANUF.(*) MODEL CONFIG. CFM ESP ("WG) SONES HP RPM DRIVE VOLTAGE (LBS) " xW xH" L"xW L"xW" CONTROL ACCESSORIES EF-1 BATHROOMS GREENHECK SP-870 CEILING 50 .2 1.1 45 WATT 563 DIRECT 120/1/60 10 14X12X8 * LIGHT INTERLOCK 1-7 (*) APPROVED EQUAL MANUFACTURER: COOK, TWIN -CITY, ACME, PENN GENERAL FAN NOTES: ACCESSORIES 1. NOTES: PROVIDE GRILLE COLOR PER ARCH. SPECS 0. MOTOR STARTERS, DISCONNECTS (IF NOT FACTORY PROVIDED) AND ALL EQUIPMENT 2. PROVIDE BACK DRAFT DAMPER 3. LOCATE BACK DRAFT DAMPER AT DISCHARGE NORMAL POWER AND EMERGENCY POWER WIRING BY ELEC. CONTRACTOR 4. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND INTEGRAL THERMAL OVERLOAD PROTECTION, b. ALL CONTINUOUS -DUTY MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ANY PURCHASING. ACCORDING TO NATIONAL ELECTRICAL CODE PAR. 430-32. 5. PROVIDE BIRD SCREEN C. FIELD ADJUST OPENINGS WITH STRUCTURE. 6. SUPPORT FROM STRUCTURE COMPLETE WITH VIBRATION ISOLATORS 7. PROVIDE WEATHERHOOD DRAIN AND CORROSION COATING. d. ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE ORDINANCE OR NOT EXCEED A NOISE LEVEL OF 65dB AS MEASURED RADIALLY 30 FT. FROM THE EQUIPMENT IN ALL DIRECTIONS. e. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR ORDERING ANY EQUIPMENT. f. SEE PROJECT PLANS AND SPECIFICATIONS FOR OTHER FIELD SUPPLIED ITEMS AND ADDITIONAL INFORMATION. g. ALL FANS ON ROOF SHALL BE PAINTED AS PER ARCHITECTURAL SPECS. AIR CONDITIONING SPLIT SYSTEM EQUIPMENT SCHEDULE CONDENSING UNIT CU TAG MANUFACTURER & MODEL NOMINAL TONNAGE CAP. STAGES (S)EERAPLV I REFRIG-/LBS LIQ./SUCT. LINES I NO. FANS I FAN FLA(EA) NO. COMP. OMP.RLA(EA) VOLTAGE/PH I MCA/MOCP I WEIGHT (LBS) L x W x H (IN) NOTES CU-1 CARRIER/24ABC63OA003 2.5 1 1 16.0 R41OA/- 3/8-3/4 1 1 1 0.75 1 1 12.8 1 208/1/60 16.8/25 1 153 32X32X33 1-8 AIR HANDLING UNIT AHU TAG MANUFACTURER & MODEL I TOTAL MBH SENSIBLE MBd TOTAL CFM I O/A CFM E.S.P.("W.G.) ENT. DB/WB LEAV. DB/WB ROWS/FPI FAN HP/FLA HEATER KW I VOLTAGE/PH MCA/MOCP WEIGHT (LBS) L x W x li (IN) NOTES AHU-1 CARRIEER/FV4CNF003T00 1 28.3 1 20.8 1 1000 1 100 0.4 80/67 - - 4.3 3.8 208/1 31.2/35 150 22X23X54 1-8 NOTES: 1. UNITS RATED PER ARI 210, 240 AND 270, APPROVED EQUAL: TRANE, YORK, LENOX, ETC. 2. PROVIDE WITH ELECTRIC EXPANSION VALVES, LIQUID LINE FILTER DRYER AND MULTI -USE SERVICE VALVES 3. PROVIDE COMPRESSOR WITH CRANKCASE HEATER AND MIN. 5-YEAR WARRANTY 4. PROVIDE HIGH AND LOW PRESSURE CONTROL AND OVER TEMPERATURE PROTECTION. 5. PROVIDE WEATHERPROOF ELECTRIC CONTROLS AND SINGLE SIDE SERVICE ACCESS 6. PROVIDE DISCONNECT BY ELECTRICAL CONTRACTOR FOR C.U., COORDINATE PRIOR TO PURCHASING COORDINATION NOTE: 7. PROVIDE REFRIGERANT LINES SIZE AS RECOMMENDED BY MANUFACTURER, NOT TO EXCEED 50 FT. EQUIV. LENGTH MECHANICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL REQUIREMENTS FOR LONGER RUNS COORDINATE WITH MANUFACTURER PRIOR TO PURCHASE OR ANY WORK. AND ACCESSORIES WITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASING AND 8. CONTRACTOR TO COORDINATE WITH ELECTRICAL TO INSURE THAT THE CONDENSING UNIT AND RACK ARE TIED TO THE INSTALLA11ON AND SHALL BRING ANY DISCREPANCIES TO THE ATTENTION OF ENGINEER EXISTING LIGHTNING PROTECTION SYSTEM ON THE ROOF. T� SUPPLY AIR GRILLE SCHEDULE TAG MANUF. & MODEL FACE SIZE NECK SIZE MATERIAL FRAME FINISH DAMPER THROW NC CFM RANGE NOTES A TITUS/ TDCA-AA 24X24 SEE SCH. ALUM. NOTE #3 WHITE OBD 4-WAY MAX. 30 SEE SCH. 1-6 B TITUS/ TDCA-AA 12X12 SEE SCH. ALUM. NOTE #3 WHITE OBD 4-WAY MAX. 30 SEE SCH. 1-6 (*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B, NAILOR OIB43ML 1. NOTES PROVIDE SPIN -IN COLLAR AT TRUNK TO FLEX DUCT CONNECTION. FLEX SCHEDULE 2. PROVIDE TYPICAL 4-WAY DIFFUSION, 2-WAY OR 3-WAY ONLY WHERE INDICATED ON PLAN 6N" 50-125 CFM 3. REFER TO ARCHITECT PLANS FOR CEILING TYPE. 80" 130-200 CFM 4. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL. 5. FLEX DUCT SIZE TO BE SAME AS DIFFUSER NECK SIZE. I 205-330 CFM 6. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE. CONTRACTOR SHALL VERIFY NTH ARCHITECT AND TENANT/OWNER, 120" 335-450 CFM PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BULDING 140" 455-600 CFM STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO 160" 605-700 CFM THE ATTENTION OF ENGINEER. C RETURN AIR GRILLE SCHEDULE TAG MANUF. & MODEL FACE SIZE NECK SIZE MATERIAL FRAME FINISH DAMPER THROW NC CFM RANGE NOTES AA TITUS/ PAR -AA 24X24 SEE SCH. ALUM. NOTE #1 WHITE OBD - MAX. 30 SEE SCH. 2-3 BB TITUS/ PAR -AA 12X12 SEE SCH. ALUM. NOTE #1 WHITE OBD - MAX. 30 SEE SCH. 2-3 (*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B, NAILOR GENERAL 1. REFER TO ARCHITECT PLANS FOR CEILING TYPE. 2. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL. 3. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT OR OWNER, PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BUILDING STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO THE ATTEN11ON OF ENGINEER. NECK 89E CFM RANG NECK WE CFM RANG 6X6 0-150 CFM 15X15 0-900 CFM 8X8 0-250 CFM 18X18 0-1350 CFM 10X10 0-400 CFM 22x22 0-2000 CFM 12X12 0-600 CFM EF-1 ST WEB 1/4" ALL - THREAD ROD "C" TOP CHORD SHEET METAL EXHAUST DUCT TYP. VIBRATION ISOLATOR (RUBBER GROMMET) \\ �-TYPICAL CEILING CABINET ;ft�EXHAUST FAN WITH BACK DRAFTDAMPER, LOW NOISE AND NO VIBRATION. FRONT FACE GRILLE WITH FASTENING SCREWS EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CABINET FAN DETAIL NOT TO SCALE OUTSIDE AIR CALCULATIONS (PER TABLE 6-1, ASHRAE 62.1-2010) DEFAULT VALUES COMBINED OUTDOOR VED ST T NET OCCUPIABLE AREA OUTDOOR AIR RATE (RA) AL NO. PEOPLE OUTDOOR AIR RATE (RP) TOTAL NO. OF PEOPLE FROM AIR RATE TOTAL CFM TOTAL CFM NOTES OCC. DENS. P/ CFM/PERSON OREUNTAG AREA SQU CFM/FT^2 OFTPEOPLE CFM/PERSON 1000FT"2 FL. AR. DEFAULT VALUES 0/A REQUIRED 0/A PROVIDED AHU-1 OFFICES 885 0.06 13 5 - - 53+62 118 120 SEE NOTES TOTAL 885 - - - - - - 118 120 NOTES: 1. CALCULATIONS ARE BASED ON ESTIMATED MAX. OCUPPANCY RATES PER ARCHITI CTURAL PLANS AND ASHRAE 62.1-2010. VENTILATION RATES PER ASHRAE 62.1-2010. 2. FOR OFFICE AND OTHER SIMILAR AREAS CALCULATIONS ARE BASED ON CONTINUOUS OCCUPANCY LOCKING QUADRANT GALV. STEEL ROD OR TO BE EXPOSED STRAP SUPPORTS PER SMACNA STANDARDS FLEXIBLE DUCT WITH SIDE TAKE -OFF FITTING INSULATION & WITH DAMPER, BELL MOUTH VAPOR BARRIER OR SHOETAP TYPE (SEE NO MAIN SUPPLY AIR TIE TO DUCT, SEE PLANS FOR STRUCTURAL TYPE AND INSULATION SUPPORTS _ _= 7 2" WIDE METAL BAND SUPPORT - II ` 1-1/2" X 1-1/2" X 1/8" GALV. SQUARE TO ANGLE OR STRAP PER SMACNA ROUND CONNECT INNER DUCT WITH DRAWBAND ADAPTER AND SEAL WITH TAPE/MASTIC OUTERDUCT AT NECK CONNECTION PROVIDE THERMAL INSULATION BLANKET IF INSTALLED IN UNCONDITIONED SPACE SUSPENDED TYPE LOUVERED FACE CEILING DIFFUSER CEILING SYSTEM WITH 2' X 2' LAY -IN ALUM. PANEL NOTE: PROVIDE CABLE CONTROL DAMPER FOR HARD CEILING AREAS. TYPICAL DUCT TAP -OFF MAIN RETURN OR EXHAUST DUCT MANUAL VOLUME DAMPER T RETURN OR EXHAUST GRILLE W/ OBD SEE M6.1 FOR TYPE RETURN AND EXHAUST DUCT MOUNTED GRILLE DETAIL SELF FLASHING BASE ATTACH DUCTWORK TO CAP & SEAL - INSECT SCREEN z 7 V.D. `cat V.D. V.D. V.D. BRANCH 1/4 W BRANCH DUCT (4" MIN,) DUCT I t DIVIDED BRANCHES FLOW DIVIDED FLOW BRANCHES V.D. �= AIR FLOW 1/4 W (4" MIN.) W 3 V.D. (W=4" MIN.) •� BRANCH V.D. DUCT 1 � THROAT -]SQUARE THROAT STANDARD 45' RADIUS _ _ ELBOW OPTIONAL RECTANGULAR BOOT CONNECTION (Z 25% FLOW IN BRANCH) (5 25% FLOW IN BRANCH) BRANCH TAKE -OFF AND DIVIDED FLOW NOT TO SCALE E L : OO �l►i CC TURNING HANWNG I HANG ALL DUCT PER SMACNA STANDARDS * D STRAP & SADDLE HVAC DUCT TEE TURNING V CHANNEL 5/22/I5 KAMM CONSULTING PROJI;(A It 2015-0250 ....I sf I(/II PROJECT MANAGER: WANE MILLAR V 1 Ake - PRINCIPAL Bradly L Brown Florida I icense 85S232 1 SA PROPOSED EXPANSION TO LANG REALTY AT THE MAIN STREET VILLAGE OFFICE BUILDING ST. LUCIE COUNTY, FLORIDA Key Plan Issues: No.: Date: Description: 05.22.15 PERMIT SET Architect: D O A D l® & Associates, Architects P.A. 609 17th St.& Vero Beech, FL 32960 Te1.772.794.2929 Fsx.772.562.8600 www.donadio-arcecom License No. AA0002238 Consultant: iPLANS AND ALL PROPOSSO Wol tt ARE SUBJECT TO ANY CORRECTICHoc REQUIRED BY PIELD INSPECXF.%THAT' MAY BE NECENA%Y IN ORMA Tit COMPLY WITH ALL APPLICABLE CG;PE& Drawing Title: MECHANICAL SCHEDULES Job North VV Drn: Drawing File: JEL Chd: XREF File: HKC Project No.: Plot File: 2013-15.005 Sheet No.: Cert. No.: 12,456 Ml6 Date Signed: • l Copyright ©2013, Donadio &Associates, Architects, PA., All Rights Reserved Project: INLINE FLOW CONTROL MOUNTING FLANGES (4] INSTANT -FLOW HEATER JUNCTION BOX O HOT OUTI COLD INLET MAIN 3/8" COPPER TUBING 1/2" ANGLE STOP VALVE COMPRESSION FITTINGS (2) ATER � _ i TIE NEW SANITARY LINE TO STUB OUT IN THIS AREA. CONTRACTOR TO FIELD VERIFY LOCATION PRIOR TO CONSTRUCTION. SANITARY ISOMETRIC N. T. S. 10, I__5 TIE NEW DOMESTIC LINE TO EXISTING STUB OUT IN THIS AREA. CONTRACTOR TO FIELD VERIFY LOCATION PRIOR TO CONSTRUCTION. DOM. WATER ISOMETRIC N.T.S. PLUMBING FIXTURE SCHEDULE HANDICAP LAVATORY, AMERICAN STANDARD, DECLYN WALL HUNG LAVATORY MODEL #0321.075. HLAV WHITE, WITH SLOAN POLARIS FAUCET #SL-2711. CONTRACTOR TO SUPPLY CONCEALED ARM SUPPORT CARRIER FOR MOUNTING OF LAV. WADE MODEL # 520-M36. SUPPLY PLUMBEREX MODEL # 4333 INSULATION KIT. MUST MEET A.D.A. CODE. HANDICAP WATER CLOSET, AMERICAN STANDARD #2377.100 FLOOR MOUNTED, WHITE, CENTOCO SEAT HWC #50OCC, OPEN FRONT WITH COVER. A.D.A EL 1.6 ELONGATED 18" HIGH OR EQUAL. SINGLE STAINLESS STEEL SINK, 25 X 22 DAYTON MODEL #K-12522 WITH A SK SLOAN POLARIS FAUCET # SL-2865 KITCHEN 5-9/16" SPREAD GOOSENECK WITH 4" WRIST BLADE FAUCET HANDLES. TANKLESS WATER HEATER SHALL BE BOSCH POWERSTAR MODEL # AE9.5, 208V, 1 IWH PHASE, 3.5 KW. HANDICAP/DRINKING FOUNTAIN, SUNROC BI-LEVEL WALL MOUNTED HDF/DF BARRIER FREE MODEL ADA-8-BL-SG-WF1. 7.8 GPH, WADE 440-AM11-M36 CARRIER AS REQUIRED. 115V, 4.5 A, MUST MEET A.D.A. CODE. GENERAL NOTES: 1) - FIXTURES SHALL BE AS SHOWN OR EQUAL. 2 - ALL FIXTURES SHALL COMPLY WITH TABLE 604.4 OF FBC 2010 3 - ALL FIXTURE TRIM PACKAGES INCLUDING BUT NOT LIMITED TO TRAP, ANGLE STOP, FLUSH VALVE, SUPPLY TUBES, AND CLEANOUT COVER PLATES SHALL BE OF THE SAME FINISH AS THE ABOVE SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE. (4) - ALL FIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY. PLUMBING NOTES 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH FBC 2010, APPLICABLE LOCAL CODES, RULES AND ORDINANCES. 2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS. 3. ALL MATERIALS SHALL BE NEW. 4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE A PART OF THIS CONTRACT. 5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES. 7. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES, PIPING, EQUIPMENT, ETC. B. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER/ARCHITECT PRIOR TO BEGINNING CONSTRUCTION. 9. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES. 10. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE "L" COPPER. COORDINATE WITH LOCAL JURISDICTION FOR ADDITIONAL REQUIREMENTS. PROVIDE ALTERNATE FOR CPVC PIPING EQUAL TO BFGOODRICH "FLOWGUARD GOLD" FOR WATER KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS. CONTRACTOR SHALL PERFORM A WATER TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLATION AND SHALL SUBMIT TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL. 11. SOIL, WASTE, VENT AND RAINWATER PIPING SHALL BE CAST IRON OR PVC, WHERE CODE ALLOWS. PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS. 12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION. 13. FURNISH AND INSTALL APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING FIXTURES, SIZED AND LOCATED PER MANUF.'S INSTALLATION INSTRUCTIONS AND WH-PDI 201. 14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND EQUIPMENT CONNECTIONS. 15.ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL. 16.ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS AS PART OF THE PLUMBER'S WORK. 17. PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE BY OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASF OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED. 18. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED. 19. PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS PANEL FOR ALL WALL CLEANOUTS FINISH TO MATCH FIXTURE TRIM. 20. NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES WHERE USED AS RETURN AIR PLENUMS. 21. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR EQUIPMENT ROOMS. 22.ALL CONTROL VALVES SHAL_ BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER/OPERATOR. 23. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH ARMAFLEX INSULATION PER TABLE 4-11 F.B.C. 2010 WHERE USED IN A RETURN AIR PLENUM. PVC PIPING WITH ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES. SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING. 24. CONDENSATE LINES SHALL NOT DRAIN ON THE ROOFING SYSTEM OR ANY OF ITS COMPONENTS AND CONDENSATE LINES NEED NOT COMPLY WITH MIN. CLEARANCE REQUIREMENTS PER FBC 2010, PAR. 1522.3.5 25.PROVDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL SHUT-OFF. 26.PROVIDE TRAP PRIMER FCR ALL FLOOR DRAINS, FLOOR SINKS, AND HUB DRAINS SHOWN ON PLANS. IF SPECIFICATION IS NOT PROVIDED, SUPPLY PRECISION PLUMBING PRODUCTS MODEL #PR-500. INSTALL PER MANUFACTURES RECOMMENDATIONS. 27. WATER PIPING INSULATION SHALL BE ARMAFLEX OR EQUAL INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS FOR ALL HOT WATER PIPING. WHERE DOMESTIC WATER TEMPERATURES CAN CAUSE SWEATING ALL COLD WATER PIPING SHALL BE INSULATED WITH ARMAFLEX INSULATION, THICKNESS AS PER TABLE 4-11 OF FLORIDA ENERGY CODE. 28• STUDOR MINI/MAXI AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO VENT PIPING THRU ROOF WHERE ACCEPTABLE BY THE PLUMBING OFFICIAL AND LOCAL CODES. INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS. 29. ALL HORIZONTAL RAINWATER PIPING THE RECEIVES CONDENSATE DISCHARGE FROM AIR CONDITIONING EQUIPMENT SHALL BE INSULATED WITH 1" THK. ARMAFLEX. 30. PLUMBING PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ IN CONJUNCTION WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, FIRE SPRINKLER, STRUCTURAL AND CIVIL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. PIPING MODIFICATIONS SUCH AS OFFSETS, BENDS, TRANSITIONS, AND SIZES SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN PIPE SIZES AND ROUTING SHALL BE REQUIRED BY THE CONTRACTOR TO AVOID CONFLICTS AND TO ADAPT TO EXISTING FIELD CONDITIONS PROVIDED THAT INSTALLATION MEETS ALL APPLICABLE CODES. 31. SUPPLY TRAP PRIMER FOR ALL FLOOR DRAINS, FLOOR SINKS, HUB DRAINS, ETC. SHOWN ON PLANS. PLUMBING SHEET INDEX SHEET# DESCRIPTION PO.1 PLUMBING NOTES, LEGENDS, AND DETAILS P2.1 PLUMBING PLAN PLUMBING LEGEND CO CLEAN OUT S --i SANITARY SEWER PIPING S.O.V. SHUT-OFF VALVE rr - - - 5 VENT PIPING COTC CLEAN OUT TO GRADE S---S DOMESTIC COLD WATER PIPING FS FLOOR SINK---5 HOT WATER PIPING (110') CW DOMESTIC COLD WATER S- - - - - S HOT WATER PIPING (140') HW DOMESTIC HOT WATER ----5 HOT WATER RECIRCULATING PIPING HWR DOMESTIC HOT WATER RECIRCULATING S- CD - $ CONDENSATE PIPING HB HOSE BIBB MCA-j COMPRESSED AIR PIPING VTR VENT THRU ROOF �-T&P --- j TEMPERATURE AND PRESSURE RELIEF pQ GATE VALVE S-SD-s STORM DRAIN PIPING �oQ GLOBE VALVE S- G - 5 GAS PIPING CHECK VALVE 5 o-S PIPE RISE UP QN pQ GAS SOLENOID VALVE PIPE DOWN OR DROP i GAS COCK E CAPPED END OF PIPE WATER HAMMER ARRESTER (PDI No.) POINT OF CONNECTION 0 FD FLOOR DRAIN -LJ P-TRAP PROVIDE TEST TEE 7 WITH SCREWED COUNTER- i COLUMN OR PARTITION SUNK ABS PLASTIC PLUG: I I AS SHOWN ON FLOOR PLAN TAPERED -THREAD WITH i CLEANOUT FACE SHALL TFE JOINT COMPOUND. I BE WITHIN 4" OF WALL J SURFACE. PROVIDE WHERE CLEANOUT TEE PIPE EXTENSION IF REQUIRED. IS CONCEALED IN A CHASE OR PARTITION, - PROVIDE A ROUND 18 GAUGE STAINLESS STEEL COVER WITH BEVELED EDGES AND FLATHEAD �) y MACHINE SCREW. I I d CONCRETE FLOOR SLAB NOTE: PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES NOT SERVED WITH A FLOOR CLEANOUT: LOCATE ABOVE FIXTURE FLOOD RIM WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR OTHER WCO REQUIREMENTS. WALL CLEANOUT DETAIL NOT TO SCALE SHOCK ARRESTOR SCHEDULE P.D.I. DESIGNATION MANUF, & MODEL FIXTURE UNITS CONNECTION A SIOUX CHIEF 652-A 1-11 1/2" B SIOUX CHIEF 653-B 12-32 3/4" C SIOUX CHIEF 654-C 33-60 1" SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO ACCESS DOOR REQUIRED. CONFORMS TO ANSI/ASSE 1010 STANDARDS. SLOPE OF HORIZ. DRAINAGE PIPE SIZE (inches) MINIMUM SLOPE (inch per foot) 2-1/2 or less 1/4 3 to 6 1/8 8 or larger 1/16 TABLE 704.1 OF THE FLORIDA PLUMBING CODE 2010 ISSUED I'OR PERMI F KAMM CONSULTING PROJECT B: 2015-0250 loll PROJECT PROJECT MANAGER: DU.ANE MILLAR 1408 Orategggg�� Gnuo••.,, A R A R A Port Pidtc6i FloiJi PRINCIPAL Bradly L Brawn Iloi da License;458232- 0 PROPOSED EXPANSION TO LAN G REALTY AT THE MAIN STREET VILLAGE OFFICE BUILDING ST. LUCIE COUNTY, FLORIDA Key Plan Issues: No.: Date: Description: 05.22.15 PERMIT SET Architect: DONADIO & Associates, Architects P.A. 609 17th Street Vero Bench, FL 32960 TO 772.794.2929 Fax.772.562.8600 www.donadio�arch.com License No. AA0002238 Consultant: i SE PLANS AiND ALL PROPOi livo lC ARE SUBJECT TO ANY COPAECTICNS REQUIRED BY PIELD'NSPEC70RS THAT MAY BE NECP%A%Y IN Ogg" TG COMPLY WITH ALL APPLICABLE CODES, Drawing Title: PLUMBING NOTES Job North ^ "V Drn: Drawing File: JEL Cho: XREF File: HKC Project No.: Plot File: 2013-15.005 Sheet No.: Cart. No.: 12,456 1 Date Signed: Pool 'If Al .11"`�V� Copyright © 2013, 0onadio 8 Associates, Architects. P.A, Al Rights Reserved Project: KEY NOTES Oj TIE NEW SANITARY LINE TO EXISTING IN AREA. CONTRACTOR TO FIELD VERIFY LOCATION AND SIZE PRIOR TO CONSTRUCTION. OTIE NEW DOMESTIC LINE TO EXISTING IN AREA. CONTRACTOR TO FIELD VERIFY LOCATION AND SIZE PRIOR TO CONSTRUCTION. PROPOSED EXPANSION TO LANG REALTY AT THE MAIN STREET VILLAGE OFFICE BUILDING ST. LUCIE COUNTY, FLORIDA Key Plan Issues: No.: Date: Description: 05.22.15 PERMIT SET Architect: DONADIO & Associates, Architects P.A. 609 17th Street Vero Bench, FL 32960 Tel 772.794.2929 Fa 772.562.8600 www.doncdio-arch.wm License No. AA0002238 Consultant: THESE PLANS AND ALL PROPOSSID WORK ARE SUBJECT TO ANY COPMSCTICNS RE©UIReD BY PIELD INSPECXMS THAT 14AY BE NECESBANY IN ORDN TO COMPLY WITH ALL APPLICABLE CODES, Drawin Title: PLUIIDING PLAN Job North ww vV ISSUED FOR PERMIT 5/22/15 Drn: Drawing File: - JEL Chd: XREF File: KAMM CONSULTING PROJECT'#: 2015-0250 .••�01 11Ulrr/J// HKC PROJECT MANAGER: DUANE MILLAR •••e E({NE J0i11 Project No.: Plot File: Fort iir I F n n n n^ n n n n Fort c: e77 F.fi' ' Fax 772'• �1 Sheet N 5.005 � U Ilin\`///Jul lU� IIjjQ\IJI PLAN Ilij�\\IJI m Phon�i7 j95. 744 Faz 772.555.174'S Sheet No.: comet bbroTn@kgmm�pys$ ' 2om Certt icatlon of QuYIt ization #8189 Cart. No.: 12,456 1�4'�1•-0' PRINCIPAL 7 �SI�Yl1p5 ^// 11 Bradly L Brown Florida License:• D le'r • •- d!ry Q Date Signed: P e JL Copyright © 2013, Donadlo & Associates, Architects, P.A., All Rights Reserved