HomeMy WebLinkAbout1004-0072 LETTER OF COMPLETIONFEB-4-2011 03:11P FROM: c1:17724621148 P.2 n r 3 BREITENBACH ENGINEERING, INC jbach442@comcast.net 9073 SE Bridge Rd, #A, Hobe Sound, Florida, 33456 Tel/Fax: (772) 546-6809 Cell: (772) 834-4743 February 3, 2011 Building Permit #1004-0072 To: Building Official St. Lucie County -Building Division 2300 Virginia Avenue Fort Pierce, Florida 34982 RE: Building Threshold Inspections and Certification Project: Concrete Repairs and Building Renovations The Miramar 10000 S. Ocean Drive Jensen Beach, FL 34957 Building Offical: As Specialty Inspector, this letter is to certify that Units 401, 501, 601, 701, & 801 have been satisfactorily completed per the plans and specifications prepared by CSM Engineers, LLC, the Engineer of Record. Other units in the building are still in the process of re -construction & repair. Should you BRE17Ej�% Respect���eq� ••. • .'O., •'...ENSF� . ti No 9770 , IS STATE OF .: ,Q John D. Bi'�f�t,�}�Q0�P���\`` please contract me. -•••g111tIN�"' FL PE #59770, FL SI #2072, Firm Reg. #26001 Via Mail: 4-copies, signed and sealed (to Special Forces for'distribution) file= 10033-1 b-Miramar \� GOv ,J 2-2-11 Certification (partial).doc J�5�J-o 1464, FEB-4-2011 03:10P FROM: i _Tn•17724621148 P.1 , [. 1 EA KS 79W CONSINUC770N S7lIllll; 17011CY Restoration & Construction 908 SE Lincoln Avenue, Stuart, FL 34994 Ofc:772-692-0302 Fax:772-692-4112 Lic. #CGC 059083 FACSIMILE COVER SHEET Date: Febru 4, 2011 To: Ilene . Company: PS Building Dept. FAX: 772-462-1148 , Re: Permit 1004-0072 From: # of Pages: 2 Hello Ilene: Please find to follow a letter from the engineer for Miramar — with this in hand does this automatically extend the permit or do we need to submit originals? Thanks so much Anne t j n BREITENBACH ENGINEERING, INC jbach442@comcast.net 9073 SE Bridge Rd, #A, Hobe Sound, Florida - 33455 Tel/Fax: (772) 546-6809 Cell: (772) 834-4743 February 3, 2011 Building Permit #1004-0072 To: Building Official St. Lucie County -Building Division _ 2300 Virginia Avenue Fort Pierce, Florida 34982 RE: Building Threshold Inspections and Certification Project: Concrete Repairs and Building Renovations The Miramar 10000 S. Ocean Drive Jensen Beach, FL 34957 Building Offical: As Specialty Inspector, this letter is to certify that Units 401, 501, 601, 701, &801 have been satisfactorily completed per the plans and specifications prepared by CSM Engineers, LLC, the Engineer of Record. Other units in the building are still in the process of re -construction & repair. Should you havg,gny%Ww pns, please contract me. - W . John D. Breite �f`i;�l�� ®O FL PE #59770, FL SI #2072, Firm Reg. #26001 Via Mail: 4-copies, signed and sealed (to Special Forces for distribution) file= 10033-1 b-Miramar 2-2-11 Certification (partial).doc Lmm WA'I=M= .; BREITENBACH ENGINEERING, INC jbach442@att.net 5334 SE Horseshoe Pt Rd, Stuart, Florida 34997 Cell: (772) 834-4743 April 4, 2012 To: Building Official Building Permit #1004-0072 St. Lucie County -Building Division 2300 Virginia Avenue Fort Pierce, Florida 34982 Re: Miramar letter to Building Department of 4-3-12 Re: Building Threshold Inspections and Certification (clarification) Project: Concrete Repairs and Building Renovations The Miramar 10000 S. Ocean Drive Jensen Beach, FL 34957 Building Official: The purpose of this letter is to address, and correct the units listed in my certification letter of 4-20-11 as follows. Unit 1202" may have been a mis-type. Unit #1106 was not listed for some reason. I have reviewed the inspection drawing sheets this morning. The following units were inspected and satisfactorily completed, units 201 through 801'(stack 01), and units 206 through 11,06.(stack 06). This work was performed, satisfactorily completed, and- inspected from September 2610 through February 2011. My final walk-thru and certification letter were on the same day, 4-20-11 • Units 901, 1001, and 1101 were certified under a previous permit. ok As I am informed by the Miramar letter of yesterday, units may have been mis-numbered on the permit. That, letter and my letter of today should clarify the actual units permitted and completed. Should you have any contract me. ��� Respectfully, ®4F Z� `,6EIVR-QC,�dvN 7� N0. C2, � -o STATE OF �ddpr'•. FCORIO� John D. Breitenbach"6/Df�iA- ' 6�d0008B89900Q u FL PE #59770, FL SI #2072, Firm Reg. #26001. Via e-mail: Miramar (for.. delivery to.bldg dept), Special'forces (signed & sealed), CSM Engineers file= 10033-2-Miramar 4-4-12 Certification (revised).doc BREITENBACH ENGINEERING,, INC jbach442@att.net 5334 SE Horseshoe Pt Rd, Stuart, Florida 34097 Cell: (772) 834-4743 April 4, 2012 To: Building Official St. Lucie County -Building Division 2300 Virginia Avenue Fort Pierce, Florida 34982 Building Permit #1004-0072 Re: Miramar letter to Building Department of 4-3-12 i Re: Building Threshold Inspections and Certification (clarification) Project: Concrete Repairs and Buildinlg Renovations The Miramar 10000 S. Ocean Drive Jensen Beach, FL 34957 Building Official: The purpose of this letter is to address and correct the units listed in my certification letter of 4-20-11 as follows. Unit "202" may have been a mi i -type. Unit #1106 was not listed for some reason. I have reviewed the inspection drawing sheets this morning. The following units were inspected and satisfactorily completed, units 201' through) 801 (stack 01), and units 206 through 1106.(stack 06). This work was performed, satisfactorily, completed, and inspected from September 2010 through ification letter were on the same day, 4-20-11 February 2011. My final walk-thru and cert Units 901, 1001, and 1 101were certified under a previous permit. i As I am informed by the Miramar letter of yesterday, units may have been mis-numbered on the permit. That letter and my letter of today should clarify the actual units permitted and completed. Should you have any c��{ fi�° legpe contract me. Respectfully, o o No. e -o'•/STATE OF nA1 � e John D. Breitenbach,9�o+ssois:aak�ol� FL PE #59770, FL SI #2072, Firm Reg. #26001 Via e-mail: Miramar (for.delivery-to bidg-dept), Special Forces (signed & sealed),.CSM Engineers file= 10033-2-Miramar 4-4-12 Certification (revised).doc i Joe Cicio From: TheMiramar@aol.com Sent: Tuesday, April 03, 201214:37 PM To: Swendy Ariyanayagam; Monica Barrios; Joe Cicio; jbach442@comcast.net; colonel@specialforcesu,s.com; commander@specialforcesus.com; lieutenant@specialforcesus.com; major@specialforcesus.com Cc: hank3243@hotmail.com; Iadyk4101@hotmail.com; deaconed@comcast.net; fischeriii@hotmail.com themiramar@gmail.com; TheMiramar@aol.com; kttlock@aol.com; steelstruk@aol.com; fmwhitel2@yahoo.com Subject: Re: THE MIRAMAR -- CASE #71939 - PERMIT #1004-0072 Attachments: Untitled0l; Building Dept -April 3- 2012.doc Attached is information regarding the above mentioned Case and Permit. Looking forward to your response and clearing ,up this matter. Regards, The Board of Directors, T ie boa rol The Miramar Condominium Association themiramar@aol.com i el&amar 10000 SOUTH OCEAN DRIVE JENSEN BEACH, FLORIDA 34957 PHONE -i 772-229-1330 FAx - 772-229.1305 CERTIFIED MAIL RETURN RECEIPT REQUESTED E-MAIL April 3, 2012 Ms. Monica Vargas Barrios St. Lucie County Board of County Commissioners. Planning & Development Services 2300 Virginia Avenue Ft. Pierce, FL 34982 Dear Ms. Vargas Barrios: Re: Case #71939 — Permit #1004-0072 Pursuant to our telephone call of April 2, 2012 and your letter dated March 7, 2012, 1 contacted Michael Roberts, owner of Special Forces, the GC we contracted to perform the concrete restoration project at The Miramar. He informed me that he would take care of the situation. I have been in contact with Michael Roberts no less than twice a week since mid -March in an attempt to conclude this situation. Over the past weekend (March 31 /April 1) 1 reviewed the paperwork myself. I found that Permit #1004-0072 incorrectly identifies the unit numbers being worked on; in some cases the unit numbers do not exist. It appears that when the original permit was filed the majority of unit numbers were inverted, 602 vs. 206, 603 vs. 306, 609 vs. 906, 610 vs. 1006, etc. Briefly, in the order as they appear on the Permit, units #602, 603, 604, and 605 are inside units and not part of the restoration project. One unit, #606, is in the south end stack and has been restored and final inspected. (Units #607, 608, 609, 610, and 611 do not exist.) The unit numbers for the south end stack, #206, 306, 406, 506, 606, 706, 806, 906, 1006, and 1106, were restored and final inspected. The inspection reports submitted to your office may seem a bit ambiguous due to the aforementioned numbering conflict. I spoke with John 'D. Breitenbach, P.E., the Threshold Engineer (Inspector) on this project. Mr. Breitenbach will produce an additional report indicating all units in the south end stack have been restored and inspected and deemed satisfactory to the specifications prepared by CMS Engineers, LLC, the Engineer of Record. I believe this is The Miramar's only open building permit. If there are any other open permits in the north end stack or any other place, please let me know as soon as possible. I request this, as Mr. Breitenbach was the Threshold Engineer for both the north as well as the south end stacks. If additional documentation is required from Mr. Breitenbach, I would like to do this all at once. Insofar as the deadline of April 9t I is. concerned, again I am working with Special Forces who is working with your Permitting Dept. to remedy this. I am not as yet sure how- long this will take to conclude. I would appreciate a 60-day extension on this matter. To make this request more reasonable, Mr. Breitenbach would issue a letter stating that both end stacks have been inspected to conform to all specifications. I feel confident that I could get this letter from Mr. Breitenbach; this week. Please confirm receipt of this letter, either by e-mail (KTTLocka-aol.com) or telephone, (772.229.2429 or 772.631.2343) and to whether the letter re- confirming that the #6 stack was completed is all that is required from Mr. Breitenbach. I will be working closely with Michael Roberts 'to assure that the permitting requirements are met as soon as ,possible. Thank you for your cooperation. Very truly yours, Kenneth T. Theriault Vice President Board of Directors cc: Planning Department Permit Department John D. Breitenbach, PE Special Forces BREITEN BACH ENGINEERING,, INC jbach442@comcast.net 9073 SE Bridge Rd, #A, Hobe Sound, Florida 33455 Tel/Fax: (772) 546-6809 Cell: (772) 834-4743 breitenbachengineering. com April 1, 2010 I (May 11, 2010, Note #3 corrected to read 17 units) TO: Building Official St. Lucie County Building Division 2300 Virginia Avenue Fort Pierce, Florida 34982 RE: Building Inspections Project: Concrete Repairs and Building Renovations The Miramar 10000 S. Ocean Drive Jensen Beach, FL 34957 This letter is to inform you that threshold building special inspector, John Breitenbach PE 59770. will be performing building Threshold Inspection services for the upcoming structural restoration project at the above referenced location. You should have received project specifications from the general contractor, Special Forces, which were prepared by CSM Engineers, LLC, the Engineer of Record. My threshold building special inspector number is 2072: firm registration #26001. Additionally, the following will be authorized by me to perform inspections: Judy Perkins, PE 62332 and Charles Darden, BSCE. I will be sending you copies of inspection reports and a final inspection report when the project is completed. The following is the inspection plan: 1. Concrete repair of balcony slabs. 2. Door buck attachment per specifications. 3. Door attachment per product approval submittals (17-units). Should you have any questions, please contract me. Respectfully, John D. Breitenbach, PE FL PE #59770, FL SI #2072, Firm Reg. #26001 Via Mail: 3-copies, signed and sealed e-mail: St Lucie Co Bldg Dept- cicioj@stlucieco.org file= 10033-1 b-Miramar Miramar Letter of Intent (Summary).doc APR-22-2010 11:15A FROM: APR-16-2010 03:05P FROM:CSM ENG `RING, LLC 7722204603 TO:17724622522 P.1 __`924112 P.1 CIVIL • 13TRUCTLIQAL• MARINI£ :I EN INEERS, LLC Date: .�= I To: Phone: Fax: From: Pages: t� Including Subject: U '�U CSM Engineers, LLC • 183 SW Monterey Road, Stuart, Florida 34 94 Phone (772) 2204601 • Fax (772) 2204603 • VOW-CSMENGINEERS.COMV11) APR-22-2010 11:16A FROM: TO:17724622522 P.2 APR-16-2010 03:06P FROM:CSM ENG:;�-RING LLC 7722204623 77— 924112 N•e- CIVIL • ®TRUCTURAL• MARINE ENGINEERS, LLC SCOPE OF WORK. 1, Protection of Existing Conditions: a) Provide protection systems for existing exterior and interior building component and site work to remain, which may be damaged or altered as a result of the Contractor's performance of the work. Existing conditions of all building components that are in proximity of the Work shall be surveyed and documented by the Contractor prior to commencement of work. 2. Removal of Existing Accordion Shutters as Required: a) Shutters shall be removed from the balconies, stored, and then replaced per original construction. 3. Balcony Surface Preparations: a) Remove and dispose existing; tile and other floor finishes, including adhesives that may exist beneath floor coverings. b) Prepare concrete surface to achieve proper adhesion of a waterproof traffic coating. 4. Concrete Repairs at Balconies and Walkways a) Demolition, surface preparation and installation of repair materials of the deteriorated concrete and reinforcing steel as authorized by the Engineer. b) At balcony edge repairs, excavated areas will be repoured to match adjoining surfaces. c) Provide Sika Galvasshield XP+ galvanic anodes at perimeter of repaired area as directed by the Engineer. 5. Replacement of the Balcony Sliding Glass Doors a) Remove, dispose, and replace all of the existing sliding glass doors of units 101, 201, 301, 401, 501, 601, 701, 801, 602, 603, 604, 605, 606, 607, 608, 6010, & 6011. See door manufacturer's specifications/NOA's attached.. All other units shall have the doors removed and reinstalled per original door manufacturer's specifications. b) Contractor shall provide design shop drawings, product approvals and engineering calculations in accordance with Miami -Dade County Notice of Acceptance (NOA) criteria, signed and sealed by a:Professional Engineer licensed in the State of Florida if sliding glass doors are to be replaced. Follow the manufacturer's specifications/NOA for installation instructions. 6. Installation of Balcony Waterproofing System: a) Apply Sika Ferrogard or Deggusa Protectosil over repaired concrete deck. b) Prepare balcony surface so that it has a positive slope. Provide repair mortar of approximately'/4" depth under new sliding glass doors and slope to balcony edge using Sikaquick 1000 or equal. c) Provide Sika Sikalastic, STO Decocoat, or BASF Sonoshield waterproofing system in accordance with manufacturer's specifications. 1) Primer PAme 3 CSM ENGINSERG, LLC 182 6W ,MONTeREY ROAD, STUART, FI.OWoA 34994 PMome (7721 230.4601 FAx 17721 230-4603 • WWW.C9MENGI14EER9.00M CIVIL- STRUCTURAL- MARINE (a L-' L_7j ENGINEERS, LLC SCOPE OF WORK 1. Protection of Existing Conditions: a) Provide protection systems for existing exterior and interior building component and site work to remain, which may be damaged or altered as a result of the Contractor's performance of the work. Existing conditions of all building components that are in proximity of the Work shall be surveyed and documented by the Contractor prior to commencement of work. 2. Removal of Existing Accordion Shutters as Required: a) Shutters shall be removed from the balconies, stored, and then replaced per original construction. 3. Balcony Surface Preparations: a) Remove and dispose existing tile and,other floor finishes.,- ---ling adhesives that may exist beneath floor coverings. 1� b) Prepare concrete surface to achieve pros `of traffic coating.-i��1p\\ 4. Concrete Repairs at Balconies and Walkwa}, , a) Demolition, surface preparation and iy f the deteriorated concrete and reinforcing s� CO eer. b) At balcony edge repairs, excavated areajoining surfaces. �� c) Provide Sika; Galvashield XP+ galvanic _,r1Meter of repaired area as directed by the Engineer. hf 1 5. Replacement of the Balcony Sliding Glass Doors a) Remove, dispose, and replace all of the existing sliding glass doors of units 101, 303, 501, 505, 1102, 1103, & 1104. See door manufacturer's specifications/NOA's attached. All other units shall have the doors removed and reinstalled per original door manufacturer's specifications. b) Contractor shall provide design shop drawings, product approvals and engineering calculations in accordance with Miami -Dade County Notice of Acceptance (NOA) criteria, signed and sealed by a Professional Engineer licensed in the State of Florida if sliding glass doors are to be replaced. Follow the manufacturer's specifications/NOA for installation instructions. 6. Installation of Balcony Waterproofing System: a) Apply Sika Ferrogard or Deggusa Protectosil over repaired concrete deck.. b) Prepare balcony surface so that it has a positive slope. Provide repair mortar of approximately V depth under new sliding glass doors and slope to balcony edge using Sikaquick 1000 or equal. c) Provide Sika Sikalastic, STO Decocoat, or BASF Sonoshield waterproofing . system in accordance with manufacturer's specifications. 1) Primer PAGE 3 CSM ENGINEERS, LLC 1 83 SW MONTEREY ROAD,STUART, FLORIDA 34994 PHONE (772) 220-4601 FAX (772) 220-4603 • WWW.CSMENGINEEP-S•C❑M CIVIL- STRUCTURAL -MARINE u. ky: ENGINEERS, LLC SCOPE OF WORK 1. Protection of Existing Conditions: a) Provide protection systems for existing exterior and interior building component and site work to remain, which may be damaged or altered as a result of the Contractor's performance of the work. Existing conditions of all building components that are in proximity of the Work shall be surveyed and documented by the Contractor prior to commencement of work. 2. Removal of Existing Accordion Shutters as Required: a) Shutters shall be removed from the balconies, stored, and then replaced per original construction. 3. Balcony Surface Preparations: a) Remove and dispose existing tile and,other floor finishes, including adhesives that may exist beneath floor coverings. b) Prepare concrete surface to achieve proper adhesion of a waterproof traffic coating. 4. Concrete Repairs at Balconies and Walkways a) Demolition, surface preparation and installation of repair materials of the deteriorated concrete and reinforcing steel as authorized by the Engineer. b) At balcony edge repairs, excavated areas will be repoured to match adjoining surfaces. c) Provide Sika Galvashield XP+ galvanic anodes at perimeter of repaired area as directed by the Engineer. 5. Replacement of the Balcony Sliding Glass Doors a) Remove, dispose, and replace all of the existing sliding glass doors of units 101, 303, 501, 505, 1102, 1103, & 1104. See door manufacturer's specifications/NOA's attached. All other units shall have the doors removed and reinstalled per original door manufacturer's specifications. b) Contractor shall provide design shop drawings, product approvals and engineering calculations in accordance with Miami -Dade County Notice of Acceptance (NOA) criteria, signed and sealed by a Professional Engineer licensed in the State of Florida if sliding glass doors are to be replaced. Follow the manufacturer's specifications/NOA for installation instructions. 6. Installation of Balcony Waterproofing System: a) Apply Sika Ferrogard or Deggusa Protectosil over repaired concrete deck.. b) Prepare balcony surface so that it has a positive slope. Provide repair mortar of approximately 3/a" depth under new sliding glass doors and slope to balcony edge using Sikaquick 1.000 or equal. c) Provide Sika Sikalastic, STO Decocoat, or BASF Sonoshield waterproofing . system in accordance with manufacturer's specifications. 1) Primer PAGE 3 CSM ENGINEERS, LLC 1 83 SW MONTEREY ROAD, STUART, FLORIDA 34994 PHONE (772) 220-4601 FAX (772) 220-4603 • WWW.CSMENSINEERS.COM