Submittal #03 30 00-16.0
1 03 30 00 - Cast -in -Place
Concrete
Ada®yac�� Project: 18-000037 - MRO Hangar - Treasure Coast Int. Airport
3191 Jet Center Terrace
Fort Pierce, Florida 34982
Structural Concrete Mixes
SPEC SECTION: 03 30 00 - Cast -in -Place Concrete SUBMITTAL MANAGER: LaMaya Jennings (AHRENS COMPANIES)
STATUS: Open DATE CREATED: 06/12/2019
ISSUE DATE: // REVISION: 0
RESPONSIBLE RF CONCRETE CONSTRUCT f ION, INC. RECEIVED FROM: JEREMY FOULKS
CONTRACTOR:
RECEIVED DATE: 06/13/2019 SUBMIT BY: 06/13/2019
FINAL DUE DATE: 06/20/2019 LOCATION: Vero Beach
TYPE: Product Information COST CODE:
APPROVERS: Sean Day (Avcon Englneers & Planners), Sue Finney (Avcon Engineers & Planners), Ian Johnson (Avcon Engineers &
Planners), Robert Palm (Avcon Engineers & Planners)
BALL IN COURT:
Sean Day (Avcon Engineers & Planners), Sue Finney (Avcon Engineers & Planners), Ian Johnson (Avcon Engineers & Planners)
, Robert Palm (Avcon Engineers & Planners)
DISTRIBUTION:
JEREMY FOULKS (RF CONCRETE CONSTRUCTION, INC.) , NANCY CORCORAN (RF CONCRETE CONSTRUCTION, INC.)
DESCRIPTION:
This mix needs to go to the structural engineer, not the civil engineer. These are mixes for everything except the hanger slab.
ATTACHMENTS: 1
MRO Hangar Structutal Concrete 201906121215.adf
i
SUBMITTAL WORKFLOW I
#
NAME
SUBMITTER4%
APPROVER
SENT DATE
DUE DATE
RETURNED
DATE
RESPONSE
ATTACHMENTS
COMMENTS
1
Sean Day
Approver I
6/20/2019
Pending
2
Sue Finney
Approver 1
6/20/2019
Pending
3
Ian Johnson
Approver I
6/20/2019
Pending
4
Robert Palm
Approver I
6/20/2019
Pending
Ahrens Companies i Page 1 of 2
FILE COPY
Printed On: 06/13/2019 08 :26 AM
AHERNS COMPANIES
1461 KINETIC ROAD
I
LAKE PARK, FL 33403
Shop Drawing / Product Date Review
REVIED BY LaMaya Jennings DATi 6/13/2019
REVIEWED FOR COMPLIANCE
APPROVED
APPROVED AS NOTED
REJECTED
Review is for conformance with design concept only and intent and
general compliance with contract d ocuments/specip cations. Subcontractor
shall be responsible for all quantities, dimensions, compliance with
documents and related codes, verification of work and trades and
fabrication or techniques of construction. i
BY
DATE
I
Ahrens Companies Page 2 of 2
I
I
Submittal #03 30 00-16.0
03 30 00 - Cast -in -Place
Concrete
COPIES
Printed On: 06/13/2019 08 :26 AM
❑ Tri-County Ready;Mix
2500 S.W. 2nd Ave.
Ft. Lauderdale, FL 33315
Phone: (954) 761-1944
Fax: (954) 760-5925
Date Issued 5/7/2019
Submittal No. 25679
I
I
❑ Eastern Ready Mix I
801 U.S. Higlnvay One
North Palm Beach. FL 33408
Phone: (561) 904.7007
Fax: (561)904-7024
I
I
• Contractor: RF Concrete Construction
I
PO Box 650789 i
• i
Vero Beach I
Florida 32965
❑ North/Central Ready Mix
3928 South Nova Road
Port Orange, FL 32127
Phone: (386) 763-5940
Fax:. (386)763-5969
❑ West Coast Ready Mix
5I'S Gene Green.Rd.
Nokomis, FL 34275
Phone: (941) 412-1260
Fax: (941)412-1609
Project: Treasure Coast International Airport
Dear SidMadam:
We are submitting the following concrete mix design(s) for approval of use for the above referenced project:
Code Number
Intended Use
THE MIX CODE NUMBER MUST BE USED WHEN ORDERING. CONCRETE.
The proposed mixes have been proportioned in accordance with the applicable sections of ACI 211,.and the
concrete section of your specifications and/or your•request.
The proposed mix design(s) will meet Iihe stated strengths, when test specimens are made, cured and tested in
accordance with current ASTM standards, and evaluated per ACI recommended standards and practices.
It is TITAN Concrete's policy to statistically analyze strength tests as a measure of Quality Assurance. As
required per ASTM C 94-00, Sec. 4.p please instruct the testing laboratory for this project to include TITAN
• Concrete on their distribution list at testreports(@titanamerica.com.for.all strength test reports for'this project.
X NO EXCEPTION TAKEN I _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
_REJECTED _UNREVIEWED. FOR RECORD PURPOSES ONLY
Checking is only for general
project and general complial
documents. Any action shoe
and specifications. Contract
be confirmed and correlated
techniques of construction; (
trades and the satisfactory p
AVCON, INC.
By: LDV
Danielle Rexroad
Concrete Quality Technical Su,
1991- M19 Quadrei, Inc.
nformance with the design concept of the
with the information given in the contract
is subject to the requirements of the plans
is responsible for dimensions which shall
the job site; fabrication processes and
rdination of his work and that of all other
ormance of his work.
Date: 6-13-19
Representative
Pagel
' 'TAN
15.aterhi5 for Life'
Quadrel:iService SM
OTri-County Ready Mix
13EastentReady Mix
TITAN Ft. L S. V. 2ndale Ave.
Ft. Lauderdale, FL 33315
Bol U,S.IliHeicyOne
North Palm Beach, FL 33408
CON4CRETIE Phone: (954) 761-1944
Phone: (561) 904-7007
Materials for Life' Fax: (954)760-5925
Fax: (561)904-7024
Submittal No. 25679
I
j
.Date Issued: 5/7/2019
I
Customer: RF Concrete Construction
Project: Treasure Coast International Airport Usage
I
Q Iorth/Central Ready Mix
OWeit Coast Ready Mix
3928 South Nova Road
425 Commercial Ct., Suite ➢3
Port Orange, FL 32127
Venice, FL 34292
Phone: (386) 763-5940
Phone: (941) 486.2220
Fax: (386)763-5969
Fax: (941)486.2222
Mix Code: SW695R30 Mix Code must be used when ordering concrete.
SPEC W/C:0.50 #57
Material ASTM Spec. Gravity Volume (oz/cy)
Welght flb/cy)
Cement Type IL
C-595 3.15
600
#-57
C-33 2:38
1,600
Manufactured Sand
C-33 2.55
1,246
Water
C-94 1.00 36.0 gal/cy
300
Type A & D Water Reducer I
C-494 1.00 30
Air Entrainer I
C-260 1.00 2
.Specified F'c : 4000 psi @ 28 days
Specified Slump: 4.00 to 6.00 " I
Specified Air: 1.50 To 4,50 %
Designed WIC + P Ratio: 0.50 TOTAL
'Designed Volume: 27.00 cu.ft.
Designed Unit Weight: 138.7 lbs./cu.ft.
3.;746
NOTES:
TITAN Concrete has no knowledge or
project architect, engineer, and/or cont
water -to -cement ratio, cement content,
ACI-31.8, and local Building Codes); ar
procedures by a facility evaluated by a
evaluated by ACI standards.
Chemical admixtures are added in e
to adjust these dosages to meet the
TITAN Concrete also reserves the
The minimum requirements for
Ready Mixed Concrete Testing
field -measured properties and I
thority regarding where this mix is to be placed; therefore, it is the responsibility of the
ctor to ensure that the above designed mix parameters of compressive strength,
nd air content are appropriate for the anticipated environmental conditions (i.e.
that acceptance testing is conducted in accordance to all applicable ASTM test
accredited by industry agencies for proper lab protocol and that test results are
with the manufacturer's recommendations. TITAN Concrete reserves the right
in jobsite demands.
to adjust cementitious contents in accordance to ACI 318.
of ready mixed concrete at the project site are. established in ACI 311.6 Specification for
as when acceptance of concrete as delivered to. the site is based on specific
ry=measured compressive strength.
TITAN Concrete requests to be included on the distribution list for test data.
TITAN Concrete reserves the right to substitute material sources that meet the same specification requirements and exhibit.
substantially equivalent performance.
Unless indicated otherwise,
COMMENTS:
may use either Type 1/II or Type IL cement in this mix.
X NO EXCEPTION TAKEN _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
_REJECTED _UNREVIEWED. FOR RECORD PURPOSES ONLY
Checking is only for general conformance with the design concept of the
project and general compliance with the information given in the contract
documents. Any action shown is subject to the requirements of the plans
and specifications. Contractor is responsible for dimensions which shall
be confirmed and correlated at the job site; fabrication processes and
techniques of construction; coordination of his work and that of all other
trades and the satisfactory performance of his work.
AVCON, INC.
By: LDV
Date: 6-13-19
1992 - 2619 Quadrel, Inc. ) Page2 Quadrel iService sM
Date: 5=019
. Mix Name: SW695R30
8000
6000
7000
6000,
5000
4000
3000
s
2000
100 200 300 400
Maturity
Strengths
,No. Of Avg 28 Std
Tests bay, Dev
---------------------------
30 6520 560
DETAILED STRENGTH; Compresl
Batch Test
'Number Number
I'60663380
'1642115
I60663.415
1649115
I
I606634.15
164'9215
160663416
1649315
I60663416
16494.15
I`60663417
1649515
I60663417
164.9615
16G663418
1649715
I60663419
1649815
I606,63420
16,49915
160663439
16.54715
I-60663440
1654815
I60663440
PN21015
1606,63440
1654915
I60663441
PN21115
I60663.442
1655115
I60663441
1655015 J01
I62�103998
D01016
162103998
D00816 !
I60116094
P0004161
I60116094
P000316
600
TITAN
CONCRETE
�i%lialerials fox Life-
Units: US
.I
3I
9000
9.00
.0,07
8000
8.00
0.06
7.00
0.05
7000
6.00
0.04
6000
5.00
0.04
5000
4.00
0.03
3.00
0,02
4000
2.00
0,01
3000
1.00
0.01
2000
0.00
0.00
700
4500
5000 5500 6000 6500 7000 7500 8000 8500
PSI
95% of tests lie above cross=h"atched area
RENGTH SUMMARY, Compression Either 4" x 8" Or $" x 12"
ion Either 4" x 8" Or 6" x 12"
Strengths
28 Day
5920
6000
6180
6370
6750
'6700
6510
7400
7.030
6760
7620
7930
6380
7030
6860
6380
6650
5750
5750
7110
712.0
1992-2019Quadcel,Inc. I Page3 QuadreliService SM
i
DETAILED STRENGTH, Compression Either 4" x 8" Or 6" x 12"
Batch
Test
Strengthsr
Number
-----------------------------------
Number
r
28 Day
162104148
D03716
5590
I62104147
D03616
5970
I60116355
P001516
6630
�160116356
P001616
6900
I
162106304
D09017
6000
I60118437
P0065
5830
�160227974
FL10218
5990
I60227971
FL10118
5850
160228370
FL17218
6670
1992 - 2019 Quadrel, Inc, II Page4 Quadrel iService SM
1
I
117rd-County Ready Mix DEaslemReady Mix
25011 S.W. 2nd'FL. No U.S. Highway One
■ ITAN Ft. Lauderdale, FL, 33.315 North Palm Beach, FL 33408
.✓'� CONCRETE Phone: (954) 76.1.1944 Phone: (561) 904-7007
Materials for Llfe' Fax: (954)760-5925 Fax: (561)904-7024
I
I
Submittal No. 25679
. Date Issued: 5/7/2019
Customer: RF Concrete Construction
Project: Treasure Coast International Airport Usage
1
I
North/Central Ready Mix
3928 SouthfNova Road
Port Orange, FL 32127
Phone: (386)763.55A0
Fax: (386) 763.5969
West Coast Ready Mix
425 Commercial CC, Suite B3
Venice, FL 34292
Phone: (941) 486-2220
Fax: (941)48.6-2222
Mix Code: SW695R32
SPEC W/C 0:50 #57 HRWR
Material
M& Code must be used when ordering concrete.
i
( ASTM Spec. Gravity Volume (oz/cy)
Weight (Iblcy)
Cement Type 1L
C-595 115
530
# 57
C-33 2.38
1,630
Manufactured Sand
I 0-33 2.55
1,291
Water
C-94 1.00 32.0 gal/cy
267
Type B Retarder
C=494 1.00 19
Type F High Range Water Reducer j
0-494 1,:00 20
Air Ei-trainer
C-260 1 00 1
Specified F'c : 4000 psi @ 28 days Designed W/C + P Ratio: 0.50 TOTAL
Specified. Slump: 6.50 to 0.50 " Designed Volume: 27.00 cu.ft.
Specified Air: 1.50 To, 4.50I%a Designed Unit Weight: 137.7 lbs./cu.ft.
3,718
NOTES:
TITAN Concrete has no knowledge or authority regarding where this mix is to be placed; therefore, it is the responsibility of the
project architect, engine eri and/or contractor to ensure that the above designed mix parameters of compressive strength,.
water -to -cement ratio, cement contenI!, and air content are appropriate for the anticipated environmental conditions (i.e.
ACI-318, and local Building Codes); and that acceptance testing is conducted, in accordance, to all applicable ASTM test
procedures by a facility evaluated byand, accredited by industry agencies for proper lab protocol and that test results are
,evaluated by'ACI standards.
Chemical admixtures are added in accordance with the manufacturer's recommendations. TITAN Concrete reserves the right
to adjust: these dosages to meet the changes in jobsite demands.
TITAN Concrete -also reserves theiright to adjust cementitious contents in accordance to ACI 318.
The minimum requirements for testing of ready mixed concrete. at the project site are established in ACI 311.6 Specification for
Ready Mixed Concrete Testing Services when acceptance of concrete as delivered to the site is based on specific
field -measured properties and Ial oratory -measured compressive strength.
TITAN Concrete requests to be included on the distribution list for test data.
TITAN Concrete reserves the right to substitute material sources that meet the same specification requirements and exhibit
substantially equivalent performance.
Unless indicated otherwise, Titan may use either Type 1/11 or Type IL cement O EXCEPTION TAKEN _MAKE CORRECTIONS NOTED
_SUBMIT SPECIFIED ITEMS _REVISE & RESUBMIT
_REJECTED _UNREVIEWED. FOR RECORD PURPOSES ONLY
i
COMMENTS: Checking is only for general conformance with the design concept of the
project and general compliance with the information given in the contract
Idocuments. Any action shown is subject to the requirements of the plans
and specifications. Contractor is responsible for dimensions which shall
be confirmed and correlated at the job site; fabrication processes and
techniques of construction; coordination of his work and that of all other
trades and the satisfactory performance of his work.
AVCON, INC.
1992 - 2019 Quadrel, Inc. Pages By: LDV Date: 6-13-19 sm
l�
Date: 5/7/2019
TITAN
CONCRETIE
• 1 Materials for Life'
Mix Name: SW69SR32 Units: US
:I iI
7000 7000 6.00 1 7r 1 10.05
6500
6000
5500
5000
4500
4000
3500
1
Maturity,
Strength's
No. Of Avg 28 Std
Tests Day Dev
------------------------
19 5590 650
6500 5.00
6000 4.00
5500
3.00
5000
4500 2.00,
4000 1.00
0.04
0.03
0.03
0.02
0.01
3500 0.00 L .«tsilllU111PIlIl�IIL- `�.' 0.00
3. 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000
TRENGTH SUMMARY, Compression
,DETAILED STRENGTH, Compression
Either 4" x 8" Or 6" x 12"
Batch
Test
Strengths
'Number
Number
28 Day
786527
EL-234
6510
786533
EL-235
6580
786538
EL-236
6620
786546
EL-237
65180
786550
EL-238
6590
786554
EL-239
6560
523397
E523397
4890
510093
E510093 J
5470
595713
E595713
5540
511055
E510055j
5680
538803
E538803i
5120
5733.08
E5.73308I
5130
511883
E511883
5720
560082
E560082
5540
590673
E590673.
4620
590883
E590883
5460
I69090943
M811#2A
i
4590
I69090543
M811#3
4550
I69090942
M811#1
4560
1992 - 2019. Quadrel, Inc.
i
Page6
PSI
'95% of tests lie above cross -hatched area
Either 4" x 8" Or 6" x 12"
Quadrel iService SM
r
7nF Ti tN j
i
Titan FloridaAggregates
Quality Control Department �
11000 NW 121st Way
t Medley, FL 33178 (1
+1(305) 364-2200'
YmAv.Utanamedca.com
PRODUCT: .............................I........................... PORTLAND-LIMESTONE CEMENT Type..........................iL(14)
STANDARD(S):....._.............. ....._. ASTM C595 / C595M -18 Date...,..... I................... March 11, 2019
...................
NOW MEDLEY FL - USA) Production Date........... 2/01119 to 2128/19
MANUFACTURING FACILITY :......................._.. PEN
SILO(S):.....:.,.... ......... _._., ................................
18,10
I
I
STANDARD' REQUIREMENTS
Results for
Item I
ASTM
Units
Limit
Specification
period
Magnesium Oxide (MgO) !
C114
%
--
—
1.1
2.5
Sulfate reported isS08 i
C114
%
max
3.0
Fineness (specific surface)
C204
m Ikg
—
--
509
Fineness-resldueon45-Nm1No.121sieve
0430
%
—
1.3
Loss on Ignition I
C114
%
max
10.0
5.5
%
min
5
12
Umeslone (%) il
%
max
15
CaCO3 in limestone (°k)
C114
%
min
70
84
% Autoclave expansion f
C151
%
max
0.90
%Autoclavecontraction
C151
%
max
0.20
0.02
.Air content of mortar, volume
C185
%
max
12
8
Compressive strength
—
2356
1 day
C1091C109M
psi
3 days
C1091C109M
psi
min
1890
4142
7 days
C1091C109M
psi
min
2900
5282
Heat or Hydrogen (3 day
Time of setting (minutes)
Initial
Vcat
lfical.
C188
gloms —
C1702
cellg —
C191
minutes min
C191
hours max
_ 3.17
— 63
45 108
7
NOTES:
This product and the clinker used In its production were manufactured in the United Slates of America;
The amount of limestone in the finish cement�dll not vary by more than +1-2.5 mass %of the finished cement.
C1702 testing was performed fly CTL Group,'quallified vendor to perform [his lesUng:(AASHTO R18 accredited and IAS•17025 aeoredited).
This product also meets the. requirements of ASTM C1W Type GU and Type MS.
'Value reported for Compressive Strength for 28 days corresponds to the previous monthly period.
"Test result represents the average of the previous 12 months. �—
Cynthia Jimenez
QC Manager
Form Rev.11 May 2018
f
We create chemistry
Certificate of Conform,
MasterAir®, AE'.90 Adr
BASF Corporation Air
I, Richard Hubbard,. Sr
certify:
That MasterAir AE 90
and I
re (formerly MB-AE 90).
-aining Admixture for Concrete
cal Marketing Specialist for BASF Corporation, Cleveland, Ohio,
mixture is a BASF Corporation Air -Entraining Admixture for concrete;
That MasterAir AE 91? and MB AE 90 admixture are the same product having identical.
q composition, diffeein only in designation; and
That no. calcium.ch[Sride or chloride based ingredient is used in the manufacture of MasterAir AE
90 admixture; and
That MasterAir AE 90 admixture, based.on the chlorides originating from all the ingredients used
in its manufacture contributes less than 0.000068 percent (0.68 ppm) chloride ions by weight of
the cement when used at the rate of 65 mL per 100 kg (I fluid ounce per 100 pounds) of cement,
and
That MasterAit AE 90 admixture meets- the requirements of ASTM C260, the Standard
Specification fo Air -Entraining Admixtures for Concrete,.as well:as the requirements for air -
entraining adm; tures as specified in Corps of Engineers' CRD-C 13 and AASHTO M154.
Richard ubbard
Sr. Technical Marketing Specialist
Ohio 44122
(216)839-7500
MASTER°
»BUILDERS
SOLUTIONS
We create chemistry
Certificate of Conformance
MasterGlenium® 7920 BASF Corporation AdmixtI
ure for Concrete
'To Whom It May Concern:
I, Richard Hubbard, S - Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterGlenium /7920 admixture is a high -range water. -reducing admixture manufactured by
BASF Corporation; a'nd
That no calcium chl��ride or chloride based ingredient is used in the manufacture of
MasterGlenium 7920 admixture; and
That MasterGlenium 7920, admixture, based on the chlorides originating from all the, ingredients
used in its manufrture, contributesless than 0.00021 percent (2.1 ppm) .chloride ions by weight
of the, cement when used at the rate of 65. mL per 100 kg (1 fluid' ounce per 100 pounds) of
cement; and
That MasterGle ium 7920 admixture meets the requirements for a Type A, Water -Reducing and
Type F, Water -Reducing, High Range Admixture specified in ASTM C494IC494M and AASHTO
M194, the Standard Specification for Chemical Admixtures for Concrete, as well as the,
requirements for Type A and Type F admixtures as specified in Corps of Engineers' CRD-C 87.
6
Sr. Technical Marketing Specialist
Systems
in Boulevard
mo 44122
>.16)839-7500
MASTER°
»BUILDERS
SOLUTIONS
We create chemistry
Certificate of Conform,
Master Pozzolith® 700
BASF Corporation Wa
re (formerly Pozzolith 700N)
cing Admixture for Concrete
1, Richard Hubbard, Si. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify,
That MasterPozzolit 700 admNture. is a BASF Corporation Water -Reducing Admixture for
concrete; and
That MasterPozzolith '700 admixture and Pozzolith 700N admixture are the same product having
identical composit)'on, differing only in, designation; and
That no calcium ;,100
hloride or chloride based ingredient is used in the manufacture of
MasterPozzolith admixture; and
That MasterPozzolith 700 admixture, based. on the chlorides Originating from all the ingredients
used in its manufacture, contributes less than 0.00060 percent (6.0, ppm) chloride ions_ by weight
of the cement' hen used at the rate. of 65 mL per 100 kg (1 fluid ounce per 100 pounds) of
cement; and
That MasterP/ozzolith `700 admixture meets the requirements for a Type A, Water -Reducing,
Type B, Retarding,. and Type D, Water -Reducing and Retarding Admixture specified in ASTM
C494/C494 , and AASHTO M1,94, the Standard Specifications for Chemical Admixtures for
Concrete, s well as the requirements for Type A, Type B and Type D admixtures as specified in
Corps of E gineers' CRD-C 87.
hard Hubbard
Technical Marketing Specialist
Corporation.
Telephone (2;16) 839-7500
MASTER°
BUILDERS
SOLUTIONS
a a BASF
We create chemistry
Certificate of Conformance
MasterSet® R 961 Admi�ture (formerly Pozzolith 961 R)
BASF Corporation Admixture for Concrete
I, Richard Hubbard, - r. Technical Marketing Specialist for BASF Corporation, Cleveland, Ohio,
certify:
That MasterSet R 9;61 admixture. Is a BASF Corporation S.et Retarding Admixture for concrete;
and 7
That MasterSet R�61 and Pozzolith 961 R admixture are the same product having identical
composition, diffe ing only in designation; and
That no calcium hloride or chloride based ingredient. is used in the manufacture of MasterSet R
961 admixture; nd
That MasterSo R 961 admixture, based on the -chlorides originating from all the ingredients
used in its ma// ufacture, contributes less than 0.00013 percent (1,.3 ppm) chloride ions by weight.
wh
of the cement en used at the rate of 65 mL per 100 kg (1. fluid ounce per, 100 pounds) of
.cement; and
That Master,* et R 961 admixture meets the :requirements for a Type B, Retarding and Type D,
Water -Reducing and Retarding -Admixture specified in ASTM C4941C494M.and AASHTO M194,
the Standard Specification for Chemical Admixtures for Concrete, as well as the requirements
for Type 'and Type D admixtures as specified in Corps of. Engineers' CRD-C 87.
�CV-J A6W4
-M�
chard Hubbard
Technical Marketing Specialist
BASF Corporation RA
Admixtures Systems ASTER
237,00 Chagrin. Boulevard
Cleveland, Ohio M» BUILDERS
Telephone. (216)'8394 M9-7500
SOLUTIONS
0 ®BASF
We, create chemistry
February 16, 2016
Project: .
Project location: .
Certificate of Conformance
MasterSure® Z 60 Admixture (formerly RheoTEC Z-60)
BASF Corporation Admixture for Concrete
I, Richard Hubbard, Sri Technical Marketing Specialist for BASF'Corporation, Cleveland, Ohio,
certify: '
That MasterSure Z 60 admixture is a Workability -Retaining Admixture manufactured by BASF
Corporation; and
That MasterSure Z 60 admixture and RheoTEC Z-60 •admixture are the same product having
identical composition, differing only in designation, and
That, no calcium chloride or chloride based ingredient is used in the manufacture of MasterSure
Z 60 admixture; and
That MasterSure Z 60 admixture, based on the chlorides originating from all the ingredients used
in its manufacture,/ contributes- less than 0.00007 percent (0.7 ppm) chloride ions by weight of
the cement whenf used at the rate of 65 mL per 100kg (1 fluid ounce per 100 pounds) of cement;
and
That MasterSure Z 60 admixture meets the requirements for a Type S, Specific Performance,
Admixture as specified 'in Table 1 of ASTM C494/C494M and AASHTO M194, the Standard
Specifications for Chemical Admixtures for Concrete.
Richard Hubbard
Sr. Technical ,Marketing Specialist
1
f
BASF Corporation
Admixtures systems
23700 ChagrinfBoulevard
Cleveland, Ohio 44122
Telephone (216) 839-7500
MASTER°
»BUILDERS
SOLUTIONS