Series TY-FRB, S.i
Upright, Pendent,
Quick Response,
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb -type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
SCA6ED Worldwide www.tyco4ire.com
U Contacts
St Lucia countV
K-factor
and Recessed Pendent Sprinklers
Coverage
o TYCO Series TY-FRB Sprinklers
scribed herein must be installed
:1 maintained in compliance with
s document, as well as with the
glicable standards of the National
s Protection Association, in addition
the standards of any other authori-
s having jurisdiction. Failure to do so
y impair the performance of these
I owner is responsible for main -
ling their fire protection system
I devices in proper operating con-
)n. Contact the installing contrac-
or product manufacturer with any
Sprinkler
Identification
I
Number (SIN)
13.... Upright 5.61K, 1/2 in. NPT
23.... Pendent 5.61K, 1/2 in. NPT
echnical
Refer,
efei to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 plsi (17.2 bar)*
The Limum working pressure of 250 psi (17{1
only apQ lies to the listing by Underwriters Labo aF "fo
ries, Incl (UL).
Discharge Coefficient ,
K=5.6IGPM/psi''/2 (80,6 LPM/bary2)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated I
Physical Characteristics
Frame .1..........................Bronze
Button.)....................Brass/Copper
Sealing issembly ... Stainless Steel w/TEFLON
Bulb...............................Glass
Compres ion Screw.................Bronze
Deflectors..........................Bronze
>:
-�.3
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
Page 1 of 4
AUGUST 2018
TFP172
TFP172
Page 2 of 4
Components:
* Temperature rating is ** Pipe thread. connections per ISO 7-1
1 - Frame
4 - Bulb
indicated on Deflector. can be provided on special request.
2 - Button
5 - Compression
STYLE 15 or 20
3 - Sealing
Screw
ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly
6 - Deflector*
DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE -IN ESCUTCHEON
6* I
5 7/16"
(11,1 mm)
4 NOMINAL 2"
MAKE -IN (50,8 mm)
2 2" �\Q�I/ 1-3/8"
3 (50,8 mm) (34,9 mm)
WRENCH
/ FLATS
1
1/2 NPT** DEFLECTOR * — 2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE i
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT, QUICK RESPONSE
/ WRENCH RECESS
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
t
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb -type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm) for the 135"F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak -tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N •m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over -tightening
the sprinkler. Re -adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe -thread sealant
applied to the pipe threads, hand -
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N•m).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe -thread
sealant applied to the pipe threads,
hand -tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N•m).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
1".
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non -
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP172
Page 3 of 4
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8" (15,9 mm)
FLUSH
3/8±5/16"
(9,5±7,9 mm)
m)
MOUNTING 1/8
SURFACE (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4" DIA.
FITTING (57,2 mm)
5/16±1/4" 1/2" (12,7 mm)
(7,9±6i4 mm)
1 FLUSH
MOUNTING 1/8"
7_mr�_"��___��_
SURFACE (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
imited
/arranty
warranty terms and conditions, visit
w.tyco-fire.com.
Irdering
rocedure
ntact your local distributor for avail-
lity. When placing an order, indicate
full product name and Part Number
Sprinkler Assemblies with NPT
TI)read Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W Type 7 Sprinkler Wrench,
P/N 56-850-4-001
TFP172
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR
TYPE
TEMPERATURE
BULB LIQUID
COLOR
NATURAL
BRASS
CHROME
PLATED
POLYESTER
135°F(57°C)
Orange
UPRIGHT
(TY313)
155°F (68°C)
Red
175°F (79°C)
Yellow
and
1, 2, 3, 4, 5, 6
5.6
1/2 in. NPT
PENDENT
(TY323)
200°F(93°C)
Green
286°F (141°C)
Blue
135°F(57°C)
Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1, 2, 3, 4
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
Notes:
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers.
a. Installed with Style 15 (1/2 in. NPT) 5/81n. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) 1/2 In. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A.
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX —
SIN
370
5.6K UPRIGHT (1/2 in.NPT)
TY313
371
5.6K PENDENT (1/2 in.NPT)
TY323
Notes:
a. Use suffix "I" for ISO 7-1 connection; for example,
77-370-4-175-1
— XXX
71 SPRINKLER TEMPERATURE
FINISH RATINGS
1
NATURAL BRASS
3
PURE WHITE (RAL9010)a
POLYESTER
4
SIGNAL WHITE (RAL9003)
POLYESTER
5
JET BLACK (RAL9005)
POLYESTER
9
CHROME PLATED
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
135
135°F (57°C)
155
155°F (68°C)
175
175°F (79°C)
200
200°F (93°C)
286
286°F (141°C)
1400 Pennbrook Parkway, Lansdale, PA,194461 Telephone +1-215-362-0700 0201a Johnson Controls. All rights reserved. All specifications and other information shown were.,current as of document revision date and are subject to change without notice. Johnson
IIn
son
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls
TEFLON is a mgiatered trademark of OUPont
tqC00
Series TY-FRB -
Extended Cover
Quick and Stane
General
Description
TYCO Series TY-FRB 5.6 and 8.0
X-factor Extended Coverage Hori-
zontal Sidewall Sprinklers Quick and
Standard Response (Light Hazard) are
decorative 3 mm glass bulb type spray
sprinklers designed for use in hydrau-
lically calculated sprinkler systems in
light hazard, commercial occupancies
such as churches, restaurant seating
areas, hotels, educational facilities,
offices, etc. With their coverage up
to 16 ft (4,9 m) wide by 24 ft (7,3 m)
long, they are designed for installation
along a wall or the side of a beam and
just beneath a smooth ceiling. Hori-
zontal sidewall (HSW) sprinklers are
commonly used instead of pendent or
upright sprinklers due to aesthetics or
building construction considerations,
where piping across the ceiling is not
desirable.
The fast response thermal sensitivity
rating of the Series TY-FRB, 3 mm bulb
type sprinklers provides for a quick
response extended coverage (QREC)
rating for many of the coverage areas
detailed in Tables B and C.
The recessed version of the Series
TY-FR8 Extended Coverage Horizontal
Sidewall Sprinkler utilizes either a two-
piece Style 10 (1/2 in. NPT) or Style
40 (3/4 in. NPT), Recessed Escutch-
eon with 1/2 in, (12,7 mm) of recessed
adjustment or up to 3/4 in. (19,1 mm)
of total adjustment from the flush side -
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING' that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide I www.tyco4ire.com
Contacts
and 8.0 K-factor
Horizontal Sidewall Sprinklers
'Response (Light Hazard)
wall position, or a two-piece Style 20
(1/2 in. NPT) or Style 30 (3/4 in. NPT)
Recessed Escutcheon with 1/4 in. (6,4
mm) of recessed adjustment or up to
1/2 in. (12,7 mm) of total adjustment
from the flush sidewall position. The
adjustment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe lengths to the
sprinklers must be cut.
orrosion resistant coatings, where
pplicable, are utilized to extend the life
f copper alloy sprinklers beyond that
hich would otherwise be obtained
hen exposed to corrosive atmo-
pheres. Although corrosion resistant
oated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
q�ot representative of all possible cor-
rosive atmospheres. Consequently,
i� is recommended that the end user
be consulted with respect to the suit-
apility of these coatings for any given
corrosive environment. The effects of
a bient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
T�e Series TY-FRB Sprinklers
ddIIscribed herein must be installed
an�� maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
an
for
owner is responsible, for main-
7g their fire protection system
levices in proper operating con-
7. Contact the installing contrac-
r product manufacturer with any
Sprinkler
Identification
Numbers (SINs)
TY3332... EC HSW, 5.6K, 1/2 in. NPT
TY4332... EC HSW, 8.OK, 3/4 in. NPT
Page 1 of 8
AUGUST 2018
TFP296
TFP296
Page 2 of 8
Compose is DEFLECTOR 4
2 - Button HAT ` I
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector* 1 \
7 - Ejection Spring
6* 5 2 3 1
* Temperature rating is indicated
on Deflector or adjacent to orifice WRENCH
seat on Frame. 7 FLATS 1/2" **
/ /NPT
'E 7/16" (11,1 mm) 1�II
a_TT1
1-9/16" CENTERLINE
3 mm OF SPRINKLER 7/16"'
( ) WATERWAY (11,1 mm)
NOMINAL
MAKE -IN
** Pipe thread connections per 1-1/2"
ISO 7-1 can be provided on (38,1 mm)
special request.
7/16" 2-3/16"
(11,1 mm) (55,6 mm)
FIGURE 1
SERIES TY-FRB (TY3332)
EXTENDED COVERAGE
HORIZONTAL SIDEWALL SPRINKLER
5.6 K-FACTOR, 1/2 INCH NPT
Components DEFLECTOR
1 - Frame HAT ` 4
2 - Button I '
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector* /
7 - Ejection Spring
6* 5 2 3 1
* Temperature rating is indicated
on Deflector or adjacent to orifice
WRENCH
seat on Frame. 7 FLATS 3/4" **
(� NPT
7/16° 11,1 mm)
1-1/2° CENTERLINE
OF SPRINKLER 1/2"
(38,1 mm) WATERWAY (12,7 mm)
NOMINAL
MAKE -IN
** Pipe thread connections per 1-1/2"
ISO 7-1 can be provided on (38,1 mm)
special request.
9/16" 2-1/4"
(14,3 mm) (57,2 mm)
FIGURE 2
SERIES TY-FRB (TY4332)
EXTENDED COVERAGE
HORIZONTAL SIDEWALL SPRINKLER
8.0 K-FACTOR, 314 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table Afor complete approval infor-
mation including corrosion resistant status,
as well as the Design Criteria section per-
taining to special design considerations.)
Maximum Working Pressure
Refer to Table B.
Discharge Coefficient
K=5.6 gpm/psis/2 (80,6 Ipm/bars/2)
K=8.0 gpm/psis/2 (115,2 Ipm/bars/2)
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table E.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ............................Bronze
Button......................Brass/Copper
Button......................Brass/Copper
Sealing Assembly.. Beryllium Nickel w/TEFLON
Bulb...............................Glass
Compression Screw.................Bronze
Deflector ......................... Copper
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must be
installed and utilized in- Light Hazard
Occupancies, under smooth ceilings
as outlined in the appliable installation
standard recognized by the Approval
Agency (e.g., UL recognizes NFPA 13,
and FM recognize the FM Loss Preven-
tion Data Sheets). Only the Style 10,
20, 30, or 40 Recessed Escutcheon, as
applicable, is to be used for recessed
installations.
TFP296
Page 3 of 8
BULB
SPRINKLER FINISHM
K-FACTOR
SPRINKLER
TEMPERATURE
LIQUID
TYPE
RATING
COLOR
NATURAL
CHROME
POLYESTER-
BRASS
PLATED
I 135°F (57°C)
Orange
5.6
1/2 in.
HSW
(TT Y3332)
1, 2, 3, 4
I 155°F (68°C)
Red
175°F (79°C)
Yellow
NPT
135°F (57°C)
Orange
1%2 n
RECESSED EC HSWa
1, 2,4
155°F (68°C)
Red
NPT
(TY3332)
175°F (79°C)
Yellow
135°F (57°C)
Orange
5.6
1/2 In.
RECESSED EC HSWb
1, 2, 3, 4
1155°F (68°C)
Red
NPT
(TY3332)
175°F (79°C)
Yellow
1135°F (57°C)
Orange
8.0
3/4 in.
EC HSW
TY4332)
(T
1, 2, 3, 4
155°F (68°C)
Red
175°F (79°C)
Yellow
NPT
1135°F(57°C)
Orange
8.0
3/4 in.
RECESSED EC HSWa
1, 2, 4
I155°F (68°C)
Red
NPT
TY4332)
I175°F (79°C)
Yellow
1, 2, 3, 4
I135°F (57°C)
Orange
8.0
3/4 in.
RECESSED EC HSWb
1, 2, 3, 4
55°F (68°C)
Red
NPT
(TY4332)
75°F (79°C)
Yellow
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL) per Table C
2. Listed by Underwriters Laboratories, Inc. for use in Canada perTable C
3. Approved by Factory Mutual Research Corporation (FM) perTable D
4. Approved by the City of New York under MEA 354-01-E
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed corrosion -resistant sprinklers.
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3A in. Total Adjustment Recessed Escutcheon, as applicable
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable
c. Frame and deflector only
I TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
SPRINKLER FINISH
K-FACTOR
SPRINKLER
NATURAL
CHROME
POLYESTER
TYPE
BRASS
PLATED
EC HSW
5.6
(TY3332)
1/2 in.
NPT
250 PSI (17,2 BAR)
RECESSED EC HSW
(TY3332) I
OR
175 PSI (12,1 BAR)
EC HSW
8.0
3/4 in.
(TY4332)
SEE NOTE 1
RECESSED EC HSW
NPT
(TY4332)
Notes:
1. The maximum working pressure of 250 psi (17,2 bar) only appliel to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in
Canada (C-UL); and, the Approval by the City of New York.
TABLE B
MAXIMUM WORKING PRESSURE
TFP296
Page 4 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)
Response
Coveragge
Minimum
Minimum
Deflector -to -Ceiling
Sprinkler
Minimum
Rating
Area( ),
Flow(2),
Pressure(2),
Distance(3),
Temperature
Spacing(4),
ft x ft (m x m)
gpm (Ipm)
psi (bar)
Inches (mm)
Rating, °F
ft (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
21.6 (1,48)
4 to 12 (100 to 300)
135, 155, 175
10(3,1)
Quick
16 x 18 (4,9 x 5,5)
29 (110)
26.8 (1,85)
4 to 12 (100 to 300)
135, 155, 175
10(3,1)
Quick
16 x 20 (4.9 x 6,1)
32 (121)
32.7 (2,25)
4 to 6 (100 to 150)
135
10(3,1)
Quick
16 x 22 (4,9 x 6,7)
35 (133)
39.1 (2,70)
4 to 6 (100 to 150)
135
10(3,1)
Standard
16 x 20 (4,9 x 6,1)
32 (121)
32.7 (2,25)
4 to 6 (100 to 150)
155
10(3,1)
Standard
16 x 22 (4,9 x 6,7)
35 (133)
39.1 (2,70)
4 to 6 (100 to 150)
155,175
10 (3,1)
8.OK EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Response
Coveragge
Minimum
Minimum
Deflector -to -Ceiling
Sprinkler
Minimum
Rating
Areal ),
Flow( ),
Pressure(2),
Distance(3),
Temperature
°F
Spacing(4),
ft x ft (m x m)
gpm (Ipm)
psi (bar)
Inches (mm)
Rating,
ft (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
10.6 (0,73)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)/13 (4,0)(5)
Quick
16 x 18 (4,9 x 5,5)
29 (110)
13.1 (0,90)
4 to 12 (100 to 300)
135, 155, 175
10 (3,1)/13 (4,0)(5)
Quick
16 x 20 (4.9 x 6,1)
32 (121)
16.0 (1,10)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)(5)
Quick
16 x 20 (4.9 x 6,1)
33 (125)
17.0 (1,17)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)(5)
Quick
16 x 22 (4,9 x 6,7)
35 (133)
19.1 (1,32)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)(5)
Quick
16 x 22 (4,9 x 6,7)
36 (136)
20.3 (1,59)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)(5)
Quick
16 x 24 (4,9 x 7,3)
39 (148)
23.8 (1,64)
4 to 6 (100 to 150)
135
10 (3,1)/13 (4,0)(5)
Quick
16 x 24 (4,9 x 7,3)
40 (151)
25.0 (1,72)
4 to 12 (100 to 300)
135
10 (3,1)/13 (4,0)(5)
Standard
16 x 20 (4.9 x 6,1)
32 (121)
16.0 (1,10)
4 to 6 (100 to 150)
155
10 (3,1)/13 (4,0)(5)
Standard
16 x 20 (4.9 x 6,1)
33 (125)
17.0 (1,17)
4 to 12 (100 to 300)
155
10 (3,1)/13 (4,0)(5)
Standard
16 x 22 (4,9 x 6,7)
35 (133)
19.1 (1,32)
4 to 6 (100 to 150)
155,175
10 (3,1)/13 (4,0)(5)
Standard
16 x 22 (4,9 x 6,7)
36 (136)
20.3 (1,59)
4 to 12 (100 to 300)
155,175
10 (3,1)/13 (4,0)(5)
Standard
16 x 24 (4,9 x 7,3)
39 (148)
23.8 (1,64)
4 to 6 (100 to 150)
155,175
10 (3,1)/13 (4,0)(5)
Standard
16 x 24 (4,9 x 7,3)
40 (151)
25.0 (1,72)
4 to 12 (100 to 300)
155,175
10 (3,1)/13 (4,0)(5)
Notes:
1. Backwall (where
sprinkler is located) by sidewall (length of throw)
2. Requirement is based on minimum flow in gpm from each sprinkler.
The Indicted residual
pressures are based on the nominal
K-factor.
3. The centerline of
the sprinkler waterway is located 7116 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4. Minimum spacing Is for lateral distance between sprinklers located
along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum
listed protection area of the extended coverage sidewall sprinkler being utilized.
5. Minimum spacing is 13 ft (4,0 m) when design pressure exceeds 175 psi (12,1 bar), otherwise the minimum spacing is 10 ft (3
m).
TABLE C
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
I TFP296
Page 5 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)
Response
Coverage
Area(II),
Minimum
Flow( ),
Minimum
Pressure(2),
Deflector -to -Ceiling
Distance( ),
Sprinkler
Temperature
Minimum
Spacing(4),
Rating
ft x ft (m x m)
gpm (Ipm)
psi (bar)
Inches (mm)
Rating, °F
ft (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
22 (1,51)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 18 (4,9 x 5,5)
30 (1II14)
29 (2,00)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 20 (4.9 x 6,1)
33 (1I25)
35 (2,41)
4 to 12 (100 to 300)
135,155
10(3,1)
Standard
16 x 16 (4,9 x 4,9)
26 (9I8)
22 (1,51)
4 to 12 (100 to 300)
175
10(3,1)
Standard
16 x 20 (4,9 x 6,1)
30 (1 j4)
29 (2,00)
4 to 12 (100 to 300)
175
10(3,1)
Standard
16 x 22 (4,9 x 6,7)
33 (1?I5)
35 (2,41)
4 to 12 (100 to 300))
175
10(3,1)
8.OK EXTENDED ((COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Response
Coverage
Minimum
Minimum
Deflector -to -Ceiling
Sprinkler
Minimum
Rating
Area(1),
FIoW(2),
Pressure(2),
Distance(3),
Temperature
°F
Spacing(4),
ft x ft (m x m)
gpm (lam)
psi (bar)
Inches (mm)
Rating,
ft (m)
Quick
16 x 16 (4,9 x 4,9)
32 (12)
16 (1,10)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 18 (4,9 x 5,5)
36 (136I)
20 (1,38)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 20 (4.9 x 6,1)
40 (151)
25 (1,72)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 22 (4,9 x 6,7)
44 (167
30 (2,06)
4 to 12 (100 to 300)
135,155
10(3,1)
Quick
16 x 24 (4,9 x 6,7)
48 (182
36 (2,48)
4 to 12 (100 to 300)
135,155
10(3,1)
Standard
16 x 16 (4,9 x 4,9)
32 (121)
16 (1,10)
4 to 12 (100 to 300))
175
10(3,1)
Standard
16 x 18 (4,9 x 5,5)
36 (136)I
20 (1,38)
4 to 12 (100 to 300)
175
10(3,1)
Standard
16 x 20 (4.9 x 6,1)
40 (151)
25 (1,72)
4 to 12 (100 to 300))
175
10(3,1)
Standard
16 x 22 (4,9 x 6,7)
44 (167)
30 (2,06)
4 to 12 (100 to 300)
175
10(3,1)
Standard
16 x 24 (4,9 x 6,7)
48 (182)
36 (2,48)
4 to 12 (100 to 300)
175
10(3,1)
Notes:
1. Backwall (where
sprinkler is located) by sidewall (length of th ow)
2. Requirement is based on maintaining both minimum flow and minimum residual pressure.
3. The centerline of the sprinkler waterway is located 7/16 In. (1j11 mm) below the deflector (Ref. Figures 1 and 2).
4. Minimum spacing is for lateral distance between sprinklers located
along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
TABLE D
FM COVERAGE AND FLOW RATE CRITERIA
TFP296
Page 6 of 8
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must
be installed in accordance with this
section.
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak tight 112 inch NPT sprinkler joint
should be obtained with a torque of
7 to 14 lb-ft (9,5 to 19,0 N•m). A leak
tight 3/4 in. NPT sprinkler joint should
be obtained with a torque of 10 to
20 lb-ft (13,4 to 26,8 N•m). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under- or over -tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Series TY FRB EC
Sidewall Sprinkler
The Series TY-FRB EC Sidewall Sprin-
klers must be installed in accordance
with the following instructions:
Step 1. Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the deflector is to face towards the
ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figures 1 and 2, the
W-Type 6 Sprinkler Wrench is to be
applied to the sprinkler wrench flats.
Series TY FRB Recessed EC
Sidewall Sprinkler
The Series TY-FRB Recessed EC
Sidewall Sprinklers must be installed
in accordance with the following
instructions:
Step 1. Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the deflector is to face towards the
ceiling.
Step 2. After installing the Style 10, 20,
30, or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and with
pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1
or 2, the W Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step 4. After the wall has been installed
or the finish coat has been applied,
slide on the Style 10, 20, 30, or 40.
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes
in contact with the wall.
Care and
Maintenance
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must be
maintained and serviced in accordance
with this section. Before closing a fire
protection system main control valve
for maintenance work on the fire pro-
tection system that it controls, per-
mission to shut down the affected fire
protection system must be obtained
from the proper authorities and all per-
sonnel who may be affected by this
action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non -operation in
the event of a fire or inadvertent oper-
ation may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Refer to Installa-
tion Section.)
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions. It is recommended
that automatic sprinkler systems be
inspected, tested, and maintained by
a qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
J
MOUNTING
SURFACE
CLOSURE
SERIES
TY FRB EC
5/8±1/4"
15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE I/ 1/8"
(3,2 }nm)
1-1/4" (31,8 mm) 3/4" (1g1,1 mm)
3/4" (19,1 mm) 1/4" (6, mm)
FIGURE 5
SERIES TY-FRB RECESSED EC
SPRINKLER ASSEMBLY WITH 7
314 INCH TOTAL ADJUSTI
STYLE 10 RECESSED ESCUi
5.6 K-FACOTR, 112 INCH
5/8±1/4"
(1 ,9±6,4 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
CLOSURE
2-7/8" DIA.
SERIES (73,0 mm)
TY-FRB EC 2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE rmm
1/8"
(3,2 m�)
1-1/4" (31,8 mm) 3/4" (19,1 mm)
3/4" (19,1 mm) 1/4" (6,41mm)
FIGURE 7
SERIES TY-FRB RECESSED EC S
SPRINKLER ASSEMBLY WITH TVI
314 INCH TOTAL ADJUSTMI
STYLE 40 RECESSED ESCUTC
8.0 K-FACTOR, 314 INCH N
TFP296
Page 7 of 8
1/2±1/8"
(12,7±3,2 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
C*OSURE
2-7/8" DIA.
(73,0 mm)
SERIES
TY-FRB EC1/4" DIA.
7,2 mm)
MOUNTINGPLATE
(3,2 mm)
1-1/4" (31,8 mm) 1/2" (12,7 mm)
1" (25,4 mm) 1/4" (6,4 mm)
FIGURE 6
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 112 INCH NPT
1/2±1/8"
(12,7±3,2 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
1(1111V
CLOSURET7
2-7/8" DIA.
SERIES (73,0 mm)
TY-FRB EC 2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE 11 II)I/,II
I I 1/8"
(3,2 mm)
1-1/4" (31,8 mm) 1/2" (12,7 mm)
1" (25,4 mm) 1/4" (6,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
112 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K FACTOR, 314 INCH NPT
TFP296
Page 8 of 8
57 - XXX - X - XXX
SPRINKLER FINISH
1
NATURAL BRASS
TEMPERATURE
SIN
3
PURE WHITE (RAL9010)
RATING
POLYESTER
135
135oF (57°C)
376
5.6K EC HSW
TY3332
4
SIGNAL WHITE (RAL9003)
155
155°F (68°C)
396
8.OK EC HSW
TY4332
POLYESTER
175
175°F(79°C)
5
JET BLACK (RAL9005)
POLYESTER
9
1 CHROME PLATED
TABLE E
SERIES TY—FRB EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION
Limited
Warranty
For warrany terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly with
NPT Thread Connections
Specify: Series TY-FRB, (specify SIN),
Extended Coverage Horizontal Side -
wall Sprinkler, K=(specify), (specify)
temperature rating, (specify) finish, P/N
(specify from Table E)
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify`)
finish, P/N (specify')
Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 r� �J 1
0201SJohnson Controls. All rights reserved.All specifications and otherinformation shownwere current as of document revision date and are subjectto change without notice. Johnson - V0
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA we registered trademarks of National Fire Protection Association; Controls
TEFLON Isa registered trademark of DuPont 1