SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
}` Port Saint Lucie, FL 34983
eigANNED Telephone: 772-621-3322
�FDIS my iFax: 772-621-3604
Lugo Address: www.slcfd.com
Building Dept. SLC FMO Permit #
Project Name 15eacoast Curb Adaptors & Curbs
Address I Industrial Avenue 3
Contractor IRK Davis Construction
Address IP.O. Box 186
City Ft Pierce
BLDG Permit #
City Ft Pierce
B-17-303
1709-0183 7771
State FL Zip 34954 Telephone (772)
Architect/Engineer Brasseur & Drobot Telephone (561) 820-8088
OccupancyTyIndustrial Construction Type 11113 Square Feet 30,295
- I
Occupant Load �"Lperp43ns Number ofStories Access Box Required Access KeySwitch
� I
AFS Permit Required FA Permit �tequired77:1 FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, Including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air�conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
r A CERTIFICATE OF OCCUPANCY.
W
See General Notes Aoove and Kedulred Kevisions Below.
1. The lnstallation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit.
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct detector shall be tied
into the fire alarm system.
3. A minimum 1 hour separation from the Business Occupancy to Industrial Occupancy is required.
Page 1❑ of 1F Reviewed by Tony Jerger Date 12-21-17