HomeMy WebLinkAboutGENERATORProtector® QS
Series
INCLUDES:
• Two -Line LCD Multilingual Digital
EvolutionT"' Controller (English/Spanish/
French/Portuguese) with external viewing
window for easy indication of generator
status and breaker position.
• True PowerTM Electrical Technology
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1 % Voltage Regulation
• Natural Gas or LP Operation
• 5 Year Limited Warranty
• UL 2200 Listed
• Capability to be installed within 18"
(457) mm of a building*
*Only if located away from doors, windows, and fresh air
intakes, and unless otherwise directed by local codes.
GENERAL`
PROTECTOR® QS SERIES
Standby Generators
Liquid -Cooled Gaseous Engine
Standby Power Rating
Model RG022 (Aluminum - Bisque) - 22 kW 60 Hz
Model RG027 (Aluminum - Bisque) - 27 kW 60 Hz
Model RG032 (Aluminum - Bisque) - 32 kW 60 Hz
Model RG038 (Aluminum - Bisque) - 38 kW 60 Hz
Model RG048 (Aluminum - Bisque) - 48 kW 60 Hz
E1� QU►�
GORo
'Ru.mM.Eb PekG�¢6q
av-rt'o-aia.�m oem
Meets EPA Emission Regulations
22 & 27 kW are CA/MA emissions compliant
32 & 38 kW not for sale in CA / MA
FEATURES
O INNOVATIVE DESIGN & PROTOTYPE TESTING are key corpponents of O SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
GENERAC'S success in "IMPROVING POWER BY DESIGN." But it This state-of-the-art power maximizing regulation system is standard on
doesn't stop there. Total commitment to component testing, reliability all Generac models. It provides optimized FAST RESPONSE to changing
testing, environmental testing, destruction and life testing, plus testing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
to applicable CSA, NEMA, EGSA, and other standards, allows you to electronically torque -matching the surge loads to the engine. Digital
choose GENERAC POWER SYSTEMS with the confidence) that these voltage regulation at ±1%.
systems will provide superior performance. O SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
i
O TEST CRITERIA: O GENERAC TRANSFER SWITCHES. Long life and reliability are
PROTOTYPE TESTED v NEMA MG1-22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
SYSTEM TORSIONAL TESTED d MOTOR STARTING ABILITY confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
ISO
2001-
2008
22.27.32*38.48kW
GENERATOR SPECIFICATIONS
I )
GENERAC®
application & engineering data
i ENGINE SPECIFICATIONS: 22, 27, 32 & 38 kW
Type
Synchronous
Rotor Insulation Class
H (22 & 27 kW) or
F (32, 38 & 48 kW)
Stator Insulation Class
H
Telephone Interference Factor (TIF)
<50
Alternator Output Leads 1-Phase
4 wire
Alternator Output Leads 3-Phase
6 wire
Bearings
Sealed Ball
Coupling
Flexible
Disc
Excitation System
I pirect
VOLTAGE REGULATION
Type
Electronic
Sensing
Single
Phase
Regulation
I ± 1%
GOVERNOR SPECIFICATIONS
Type
Electronic
Frequency Regulation
Isochronous
Steady State Regulation
± 0.25%
ELECTRICAL SYSTEM
Battery Charge Alternator
12 Volt 30 Amp
Static Battery Charger
2.5 Amp
Recommended Battery (battery not included)
Group 26 (22, 27, 3 & 38 kW)or Group 24F (48 k), 525CCA
System Voltage
12 Volts
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Class H insulation is NEMA rated
Class F insulation is NEMA rated
All models fully prototyped tested
ENCLOSURE FEATURES
Aluminum weather
Ensures protection against mother nature.
protective enclosure
Electrostatically applied textured epoxy paint for added
durability.
Enclosed critical grade
Quiet, critical grade muffler is mounted inside the unit
muffler
to prevent injuries. I
Small, compact, attractive
Makes for an easy, eye appealing installation.
SAE
Sound attenuated enclosure ensures quiet operation.
(All ratings in accordance with BS5514, IS03046, ISO8528, SAE J1349 an Id DIN6271)
Make
Generac
Model
In -line
Cylinders
4
Displacement (Liters)
2.4
Bore (in/mm)
3.41/86.5
Stroke (in/mm)
3.94/100
Compression Ratio
9.5:1
Intake Air System
Naturally Aspirated (22 & 27 kW) or
Turbocharged/Aftercooled
(32 & 38 kW)
Lifter Type
Hydraulic
ENGINE SPECIFICATIONS: 48 kW
Make
Generac
Model
VType
Cylinders
8
Displacement (Liters)
5.4
Bore (in/mm)
3.55/90.2
Stroke (in/mm)
4,17/105.9
Compression Ratio
9:1
Intake Air System
Naturally Aspirated
Lifter Type
Hydraulic
ENGINE LUBRICATION SYSTEM
Oil Pump Type
Gear
Oil Filter Type
Full flow spin -on cartridge
Crankcase Capacity (qt/I)
4/3.8 (22, 27, 32 & 38 kW) or
6/5.7 (48 kW)
ENGINE COOLING SYSTEM
Type
Closed
Water Pump
Belt driven
1980-22&27kW
Fan Speed (rpm)
1500 - 32 & 38 kW
1954 - 48 kW
Fan Diameter (in/mm)
18.1/459.7 (22 & 27 kW) or
22/558.8 (32, 38 & 48 kW)
Fan Mode
Pusher (22 & 27 kW) or
Puller (32, 38 & 48 kW)
FUEL SYSTEM
Fuel Type
Natural gas, propane vapor
Carburetor
Down Draft
Secondary Fuel Regulator
Standard
Fuel Shut Off Solenoid
Standard
Operating Fuel Pressure
5-14" water column/9-26 mm HG
LP Fuel Pressure
11 -14" Water Column
NG Fuel Pressure
15 -14" Water Column
22.27.32.38.48kW
GENERAC®
operating data
GENERATOR OUTPUT VOLTAGEAW - 60 Hz
kW LPG Amo LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
120/240 V, 10, 1.0 pf
22
92
22
92
100
RG022
120/208 V, 30, 0.8 pf
22
76
22
76
80
120/240 V, 30, 0.8 pf
22
66
22
66
80
120/240 V, 10, 1.0 pf
27
113
25
104
125
RG027
120/208 V, 30, 0.8 pf
27
94
25
87
100
120/240 V, 30, 0.8 pf
27
81
25
75
90
120/240 V, 10, 1.0 pf
32
133
32
133
150
120/208 V, 30, 0.8 pf
32
111
32
111
125
RG032
120/240 V, 30, 0.8 pf
32
96
32
96
100
277/480 V, 30, 0.8 pf
32
48
32
48
60
120/240 V, 10, 1.0 of
38
158
38
158
175
120/208 V, 30, 0.8 pf
38
132
38
132
150
RG038
120/240 V, 30, 0.8 pf
38
114
38
114
125
277/480 V, 30, 0.8 pf
38
57
38
57
60
120/240 V, 10, 1.0 pf
48 I
200
48
200
200
120/208 V, 30, 0.8 pf
48
167
48
167
175
RG048
120/240 V, 30, 0.8 pf
48
144
48
144
150
277/480 V, 30, 0.8 pf
48
72
48
72
80
SURGE CAPACITY IN AMPS ENGINE FUEL CONSUMPTION
Voltage Dip @ < .4 pf Natural Gas Propane
15% 30%1 (ft3/hr) (m3/hr) (raal/hr) (1/hr) (113/hr)
120/240 V, 10
55
1351
RG022
120/208 V, 30
40
921
120/240 V, 30
35
80
120/240 V, 10
62
170I
RG027
120/208 V, 30
70
120I
120/240 V, 30
61
103
120/240 V, 10
75
1801
RG032
120/208 V, 30
87
210
120/240 V, 30
75
182j
277/480 V, 30
36
871
120/240 V. 10
75
180
RG038
120/208 V, 30
87
21 d
120/240 V, 30
75
182
277/480 V, 30
36
87'
120/240 V, 10
85
195
120/208 V, 30
90
218.
RG048
120/240 V, 30
78
189
277/480 V, 30
36
87,
Nate: Fuel pipe must be sized for full load.
For Btu content, multiply ft3/hr x 2520 (LP) or 113/hr x 1000 (NG)
For megajoule content, multiply m3/hr x 93.15 (LP) or m3/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and
SCAQMD permitting purposes. I
Exercise cycle
42
1.2
0.44
1.7
16
25% of rated load
100
2.8
1.1
4.2
40
RG022
50% of rated load
190
5.4
2.1
7.8
75
75% of rated load
255
7.2
2.8
10.5
101
100% of rated load
316
9
3.4
13
125
Exercise cycle
42
1.2
1 0.44
1.7
1 16
25% of rated load
108
3.1
1.2
4.5
43
RG027
50% of rated load
197
5.6
2.1
8.1
78
75% of rated load
287
8.2
3.1
11.8
114
100% of rated load
359
10.2
3.9
14.8
143
Exercise cycle
79
2.2
1 0.8
3.2
30
25% of rated load
144
4.1
1.7
6.3
60
RG032
50% of rated load
226
6.4
2.7
10.3
97
75% of rated load
298
6.4
3.7
13.9
132
100% of rated load
375
10.6
4.6
17.5
166
Exercise cycle
83
2.3
0.9
3.2
31
25% of rated load
1 162
4.6
1.7
6.6
62
RG038
50% of rated load
255
7.2
2.9
10.8
103
75% of rated load
345
9.8
4
15
142
100% of rated load
437
12.4
5.2
19
185
Exercise cycle
95
2.7
1
3.9
38
25% of rated load
204
5.8
2.16
8.5
82
RG048
50% of rated load
392
11.1
4.14
15.7
151
75% of rated load
547
15.5
5.8
22.8
220
100% of rated load
756
1 21.5
1 7.96
31.3
302
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
I
GENERAC®
22.27.32.38.48kW
ENGINE COOLING
operating data
22 kW 27 kW 32 & 38 kW 48 kW
Air flow (inlet air including alternator and combustion air in cfm/cmm)
I
2400/68
2400/68
2200/62.3
4350/123.2
System coolant capacity (gal/liters)
2.5/9.5
2.5/9.5
2.5/9.5
3/11.4
Heat rejection to coolant (BTU per hr/MJ per hr)
99,000/104.5
105,000/110.8
145,000/153
186,000/196.2
Maximum operation air temperature on radiator (°C/°F)
60/150
Maximum ambient temperature (°C/°F)
50/140
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm) 1 68/1.9 1 68/1.9 1 106/3 1 163/4.6 1
SOUND EMISSIONS
Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode` i
1 61
1 61
58
1 63
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load'
1 70
1 70
64
1 68
"Sound levels are taken from the front of the generator. Sound levels taken from othej sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm)
1
1 165/4.7
1 180/5.1
1 300/8.5
1 414/11.7
Exhaust temperature at muffler outlet (°C/°F)
j
1 482/900
1 538/1000
1 579/1075
1 552/1025
ENGINE PARAMETERS
Rated Synchronous rpm 1 1 1800 1
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration....................................................................!.......,.............................3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F
Altitude Deration (22, 27 & 48 kW)...................................................................................1 % for every 100 m above 183 m or 3% for every 1000 ft above 600 ft
Altitude Deration (32 & 38 kW)....................................................!......................I........... 1 % for every 100 m above 915 m or 3% for every 1000 It above 3000 ft
CONTROLLER FEATURES
Two -Line Plain Text LCD Display....................................................................................................................................Simple
user interface for ease of operation.
Mode Switch: Auto..............................................................................................................................................Automatic
Start on Utilityfailure. 7 day exerciser
Off.........................................................................1.........................................,.......Stops
unit. Power is removed. Control and charger still operate.
Manual..................................................................I...........,......,...
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds..............................................................................................................................................10
sec standard
i
Engine Start Sequence..................................................................:..................................................
Cyclic cranking:16 sec on, 7 rest (90 sec maximum duration)
EngineWarm-up....................................................................................................................................................................................................................5
sec
EngineCool-Down........................................................................t................,......,...................,.............................................................................................1
min
Starter Lock-out............................................................................!....................................................Starter
cannot re-engage until 5 sec after engine has stopped.
SmartBattery Charger........................................................................................................................................................................................................
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection................................................................................................................................
Standard
AutomaticLow Oil Pressure Shutdown...............................................................................................................................................................................
Standard
OverspeedShutdown..............................................................................................................................................................................................
Standard, 72 Hz
HighTemperature Shutdown...............................................................................................................................................................................................Standard
OvercrankProtection..........................................................................................................................................................................................................
Standard
SafetyFused......................................................................................................................................................................................................................Standard
Failureto Transfer Protection..............................................................................................................................................................................................Standard
Low Battery Protection......................................................................................................................................................................................................
ry
.. Standard
50 Event Run Log.........................................................................!...................,.......................................................,.........................................................Standard
FutureSet Capable Exerciser........................................................l..,..,...........,..............................,..........,,,,......................................................................Standard
IncorrectWiring Protection................................................................................................................................................................................................
Standard
InternalFault Protection.....................................................................................................................................................................................................
Standard
CommonExternal Fault Capability.....................................................................................................................................................................................Standard
GovernorFailure Protection..............................................................................................................................................................................................Standard
22.27.32.38.48kW
GENERAC®
available accessories
Model # Product-
rDescription
Generac's Mobile Link allows you to check the status of your generator from
anywhere that you have access to an Internet connection from a PC or with
G006463-4
Mobile Link TM
any smart device. You will even be notified when a change in the generator's
status occurs via e-mail or text message. Note: Harness Adapter Kit required.
Available in the U.S. only.
The Harness Adapter Kit is required to make liquid -cooled units compatible
G006478-0
Harness Adapter Kit
with Mobile LinkTM
G005630-1 - 22, 27, 32 & 38 kW
If the temperature regularly falls below 32 OF (0 °C), install a cold weather kit
Cold Weather Kit
to maintain optimal battery temperature. Kit consists of battery warmer with
G005632-1- 48 kW
thermostat built into the wrap.
G005616-0 - 22, 27, 32 & 38 kW
Extreme Cold
Recommended where the temperature regularly falls below 32 OF (0 °C) for
G007088-0 - 48 kW
Weather Kit
extended periods of time. For liquid cooled units only.
G005651-0
Base Plug Kit I
Add base plugs to the base of the generator to keep out debris.
If the generator enclosure is scratched or damaged, it is important to
G005703-0 - Bisque
Paint Kit
touch-up the paint to protect from future corrosion. The paint kit includes the
necessary paint to properly maintain or touch-up a generator enclosure.
G005656-0 - 22 & 27 kW
Scheduled
The Liquid -Cooled Scheduled Maintenance Kits offer all the hardware
G005984-0 - 32 & 38 kW
Maintenance Kit
necessary to perform complete maintenance on Generac liquid -cooled
G006205-0 - 48 kW
generators.
G006664-0
Local Wireless
Completely wireless and battery powered, Generac's wireless remote monitor
Monitor
provides you with instant status information without ever leaving the house.
G006665-0
Wireless Remote
Recommended for use with the Wireless Remote on units up to 60 kW,
Extension Harness
required for use on units 70 kW or greater.
Smart Management Modules are used in conjunction with the Automatic
G006873-0
Smart Management
Transfer Switch to increase its power management capabilities. It provides
Module (50 Amps),
additional power management flexibility not found in any other power
management system.
G006510-0
E-Stop
E-stop allows for immediate fuel shutoff and generator shutdown in the event
of an emergency.
The Wi-Fi enabled LP fuel level monitor provides constant monitoring of the
Wi-Fi LP Fuel Level
connected LP fuel tank. Monitoring the LP tank's fuel level is an important
G007005-0
Monitor
step in making sure your generator is ready to run during an unexpected
i
power failure. Status alerts are available through a free application to notify
when your LP tank is in need of a refill.
RADIATOR(EXHAUST
DISCHARGE AIR
(BOTH SIDES)
BATTERYI2V-
GRP 26
NEGATIVE GROUND
PIN:077483
REMOVE COVER --
FOR ACCESS TO
RADIATOR FILL CAP
427
----- [16.8]- --
EXHAUST MUFFLER -
ENCLOSED WITHIN
GENERATOR ENCLOSURE
RADIATOR/EXHAUST
DISCHARGE AIR
AIR INTAKE
(BOTHSIDES)RADIATOR
' 1
aL DRaN xosE
DRaA
cooLANTREcovERve
RADIATORFlLLC/+
�[\/[j
aR CLEANER ELEMI
SPARK PLUGS
141
15.61 629.9 [24.8] -�
CENTER OF GRAVITY
(SEE NOTE 5)
TOP VIEW
48
11.91
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PART LISTINGS.
CIRCUIT BREAKE
SEE NOTE 3
1040
(40.91
UEL LINE CONNECTION
3/4' NPT FEMALE COUPLING
LEFT SIDE VIEW
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 1885 (74.2°) LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL I CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB -UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE SM-11 GRADE 5
(USE STANDARD SAE TORQUESPECS) -
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
-REAR ENCLOSURE
980
COVER PANEL
[38.61
SEE NOTE 4
OVERALL
HEIGHT
[
USTOMER ACCESS
48
ASSEMBLY, CONTROL
11.9]
PANEL ACCESS,
TYP
BATTERY CHARGER
j
LOCATED WITHIN
SEE NOTE 4
45
OVERALL WIDTH
11 8]
REARVIEW
TYP
WEIGHT DATA
ENGINE/KW
ENCLOSURE
WEIGHT
O LY
GEKG
WEIGHT
SI(ID
SHIKG
SHIPPING WEIGHT
KVA
MATERIAL
KG [LBSf
[L
ILB
KG p.BS]
KG [LBSI
2AL 22KW (60HZ)
SINGLE PHASE 17.4KVA (50HZ)
AL
410.519051
30 [661
440 (9711
THREE PHASE 22KVA (50HZ)
2AL 27KW (60HZ)
SINGLE PHASE 21.6KVA (50HZ)
AL
426 [940]
30 [661
456 [I006)
THREE PHASE 27KVA (50HZ)
631
- 1490 [58.7] TYP -
- 1580 [62.2]—
OVERALL LENGTH
RIGHT SIDE VIEW
DIMENSIONS: MM [INCH]
VICE ACTION LATCH,
ONE PER DOOR,
ONE LIFT OFF
DOOR PER SIDE
OF GENERATOR
0
45 [1.8]
TOP VIEW
LEFT SIDE VIEW
TE - STUB -UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS.
CUIT BREAKER, NEUTRAL AND CUSTOMER CONNECTION OPENING.
STUB -UP COVER
735
1 1
27 [1.01 723 [28.5I TYP --'i
TYP MOUNTING SLOT CENTERS
776 [30.6I
DIMENSIONS: MM [INCHI
REAR VIEW
96 [3.8I
CD