Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutBUILDING PLAN PAGE 76-90Roll Form Downspout Layout
Gutter i (� rye ^`ry)
dP00001 Downspout Strap Attachment To Wall
'14 01
Rev.
Wall Stitch Screw
(1) per F797
(2) per F81, F903, F1829
"'"'"ON •;i;1
?'`s
Downspout Strap
I L Wall Panel
Field Locate <
„l''!
( F797, F81
(Varies)
Opening In Gutter
:!
"'!;_•::::;;
F1829, F903)
h"
3'•
(4) Fastener #14
Fastener #14
Downspout
Seal Downspout
to
1/8" x 3/16"
x"
Gutter connection
with
(1) each side F797
Wall Panel Attachment
Tube Sealant HW54_
(2) each side F81
F903, F1829
Not provided by Metal
Upper Downspout
Building Manufacturer
F320 (10'-6")�
F313 (14'-6")
°
°
d ,' a . . .
a + •. a
"
N °�
Downspout Strap F797 (TYP)
See DP00011 For Downspout
a
•'
• ° . <' 'A. • e
,... "d
Strap Fasteners
d.<,
.<
Lower Downspout
F320 (10'-6")
°
Downspout Strap
(F797, F81
Masonry
F313 (14'-6")
F1829, F903)
(6) Fastener #14
1/8" x 3/16"
(TYP. At Splice)
Fastener #14
x"
N
°
1 each side F797
()
Masonry Wall Attachment
°
(2) each side 181
F903, F1829
Downspout Kickout —►
F321
Fastener #55
Main
Frame -�
/ 12-24 x 14" DP5
GI
Note:
1. Refer to the building erection drawings for the spacing of the downspouts.
2. Locate all downspouts over a panel major rib if possible.
3. A field splice is required for eave heights greater than 16'-0". Always measure the required
length starting at the swaged end. After cutting to length, insert the swaged end of the cut
downspout into the top of the lower downspout.
4. Downspout straps F797 are Located at the bottom of a downspout, below a splice, and at mid
point of downspout longer than 10'-6". See DP00011 for downspout strap fasteners.
•
RVPBR (RBR) Wall Panel - Three Sided Framed Opening
Field Notch Panel at Head Trim
RR07023
Rev.
ip'141 03
Note: Trim Installation can be done by Field Notch Panel as shown on RR07022 & RRO7023
OR with Field Notch and Bend Tabs at Head Trim as shown on RR07024 & RR07025.
Opening Width + 6" (+2" Lap when req'd)
Head Trim F481
I
I
I
Front View View
2" Lap with (2) Fasteners #14 End
x J" Pop Rivet and HW54_
Caulking
Opening Width 3" Opening Width 3"
r Field notch Panel
1 at Head Trim
o �o
I
Head Trim F481 ° c
°' Caulk with HW54_
See RR07027 III II I I ` at these edges
o after installation
Fastener #14A d" x Pop Field cut Panel
Rivet at 20" O.C. at Cold Form
OR
Fastener #16 12-24 x 14"
Pancake SD DP5 W/O Washer
at 1'-8 O.C. at Hot Rolled
Note: Panel position is shown with Panel Rib
starting 1'-0 from Steel Line and Opening on
Note: All trim is to be 1'-0 module. Location of Panel Rib may vary
installed BEFORE blanket depending on the Opening Width and location.
insulation is applied to walls Field measure before cutting Panel and Trim.
Downspout Strap
(F797, F81
F1829, F903)
Fastener #14
�» x»
(1) each side F797
(2) each side F81
F903, F1829
Column Attachment
RVPBR (RBR) Wall Panel - Three Sided Framed Opening
Trim Installation with Field Notch and Bend Tabs at Head Trim
P00011
'14R°01
Reverse Rolled PBR Wall Panel
Outside Corner Trim
Reverse Rolled
PBR Panel
I�
c
J
le (n
Fastener #17A
iR
12-14 x 1 SD W/Washer
at each girt and
Fastener #4A
Starter Trim
4-14 x J" SD W/Washer
F620
:Steel
at 1'-8 O.C. Max.
each girt
c
Tiween
a
N
v
_ _
Line _ _�.
RR07024
Rev.
'14 03
g Trim Installation can be done by Field Notch Panel as shown on RR07022 & RR070
OR with Field Notch and Bend Tabs at Head Trim as shown on RR07024 & RR07025.
Field Cut
and Remove
Opening Width + 6" (+2" Lap when req'd)
_JJ Opening Width + 3"
ODenina Width
:va 0 0
M
0
Head Trim F481
See
RR07030
Fastener #14A a" x J" Pop Rivet
at 20" O.C. at Cold Form
OR
Fastener #16 12-24 x 1 �"
Pancake SD DP5 W/O Washer
at 1'-8 O.C. at Hot Rolled
o+
RRO3001 RVPBR (RBR) Wall Panel - Three Sided Framed Opening
ir'14[62 Trim Installation with Field Notch Panel at Head Trim
Rib
6"
Reverse Rolled
Corner Trim (Standard) PBR Panel
F830 or F862 Starter Trim
F620
Note:
Standard panel location for Start and End
panels is 6" from steel line to q of panel
rib. Refer to Erection Drawings for panel
location and Corner Trim piece mark.
RVPBR (RBR) Wall Panel - Three Sided Framed Opening
Field Notch and Bend Tabs at Head Trim
RR07
g Trim Installation can be done by Field Notch Panel as shown on RR07022 & RR070
QFf, with Field Notch and Bend Tabs at Head Trim as shown on RR07024 & RR07025.
Opening Width + 6" (+2" Lap when req'd)
3" Opening Width 3"
0 0 0 0
Head Trim F481 I o
See
RR07030
o Fastener #14A x J" Pop Rivet o
at 20" O.C. at Cold Form
OR
Fastener #16
12-24 x 1}"
Pancake SD DP5 W/O Washer
at 1'-8 O.C. at Hot Rolled a
" Bead of HW54_ Tube Caulking
from Header to Floor (see section)
Jamb Trim F482 Jamb Trim F482
or Alternate F484 or Alternate F484
0 0
Seev
RR07029
Finish Floor Line
Width
See RR07023
& RR07027
Note:
For "Optional"
Channel Closure Trim
see RR07028
2" Lap with (2)
Fasteners #14
x J" Pop Rivet
Typ at Head &
Jamb Trim when
required. Field notch
as required.
Note: All trim is to be
Note: Field measure Opening Width
installed BEFORE blanket
and Height before making field cuts
insulation is applied to wal1s.
and adjust cut dimensions accordingly.
RR07025 RVPBR (RBR) Wall Panel - Three Sided Framed Opening
Rev.
�D'14 03 Head Trim Installation
g; Trim Installation can be done by Field Notch Panel as shown on RR07022 & RR07C
QB with Field Notch and Bend Tabs at Head Trim as shown on RR07024 & RR07025.
*Field Cut
See RR07025 Remainder and
& RR07027 Remove
0
Openinq Width + 6" (+2" Lap when req'd)
*Opening Width + 3"
14°
*Opening Width 1°
Head Trim F481
I
I
*Note: Field measure
Opening Width and
cut Head Trim to
required length.
4
Field Notch and Bend
Front View End View
1ri Tab behind Jamb
2" Lap with (2) Fasteners #14
Trim. Attach with
See End Cut Detail x f�"Po Rivet and HW54_
�" P
Fastener #14 il" x { "
Caulking
1»
Pop Rivet. See
Opening Width
RR07025 for details.
Do not cut or Note: All trim is to be
°
remove back leg installed BEFORE blanket
insulation is applied to walls
g
e"
I Bend 1}" Tab
1
I down 90 degrees Note, Panel position is shown with Panel Rib
starting 1'-0 from Steel Line and Opening on
1'-0 module Location of Panel Rib ma var
y Y
" Bead of HW54_ Tube Caulking Field Cut depending on the Opening Width and location.
a from Header to Floor (see section) a. and Remove Field measure before cutting Panel and Trim.
c
a 2' Lap with (2)
o Jamb Trim F482 Jamb Trim F482 Fasteners #14
or Alternate F484 or Alternate F484
x J" Pop Rivet
Typ at Head &
Jamb Trim when
required. Field notch
0 as required.
See
RR07029
Note:
For "Optional"
Channel Closure Trim
see RR07028
Finish Floor Line
0 0
Opening Width
r
Note: All trim is to be
Note: Field measure Opening Width
installed BEFORE blanket
and Height before making field cuts
insu!ation is applied to walls
and adjust cut dimensions accordingly.
End Cut Detail
(Viewed from top of Head Trim)
Opening Width
Field Notch and Bend 1}" Tab
behind Jamb Trim. Attach with
Fastener #14 d" x {j" Pop Rivet
ki
e
Head Trim F481
See RR07027 for Jamb
Trim field cut detail
Jamb Trim F482 or Alternate F484
Fastener #14A A" x i" Pop
Rivet at 20" O.C. at Cold Form
OR
Fastener #16 12-24 x 14"
Pancake SD DP5 W/O Washer
at 1'-8 O.C. at Hot Rolled
Field cut Panel
RVPBR (RBR)
Wall Panel
Fastener #17A—�
12-14 x 1r SD
W/Washer
at 1'-0 O.C. at
Cold Form
OR
Fastener
#67
12-24 x
1 r
SD DP5 W/Washer
at 1'-0 O.C. at
Hot Rolled
-Fastener #14A x Pop -
Civet at 20" O.C. at Cold Form
OR
Fastener #16 12-24 x 1}"
Pancake SD DP5 W/O Washer
at V-8 O.C. at Hot Rolled
ro
U
co
m
0
O
0
ot
4 °
fn r
Lv
)
0
C
0 n
a)
0
0
U...
n p I
z LC
U Q J
N U
c' "a
J a_ O I-�-
rz
a
�—
(3 W
axi
p¢c.)
VJ 6
QU J
tl L2
X
sa
W
O OJz
L-1 Li
o
s
�e oC1�s
n
Z 00
RR07030
Co
�yy
U CS
O ,
U m —
N
ar'14Re01
W N d
L V
u7 0
z
ca °
O r,❑
LJ
0
D z
rr
a
in
V)
v
O0,O
6
wn
Q
Q va-o
OVa
H
•S
3
U Sram^C)
d
Scale: NOT
TO SCALE
_- a
Drawn by.
"Optional" Header Checked by.
Channel Closure Trim (Cold Form shown Project Engineer:
See RR0728 for details Hot Rolled similar)
Job Number: 14-B-83134-1
Sheet Number: R10 of 13
Finish Floor Line
The engineer whose seal
appears hereon is an employee
for the manufacturer for the
materials described herein. Said
seal or certification is limited
to the products designed and
manufactured by manufacturer
only.The undersigned engineer is
not the overall engineer of
record for this project.
DRMEIA ENMEIA
i
Note: All trim is to be N .38305 {e
installed BEFORE blanket ;pc
insulation is applied to walls
TATE OF ;tci
Fri �ZOR.....
THES27 % MS AND ALL PROPOSSD WORK SEP 0 9 2015
ARE SUBJECT TO ANY COFAEC)-lONS
REQUIRED BYFICLD INSFEC?ORS THAT
«JAY HE NEC!'36 tY IN Mi en TO
COw•FLY MTH ALL APPLICABLE CODES.
RVPBR (RBR) Wall Panel - Three Sided Framed Opening
Jamb Trim Field Cut Details
C 1T
Alternate Jamb Trim F484 Jamb Trim F482
Top View Top View
I" 3 J„
Field Cut and Remove
M
:m
Side View at Head Trim
Side View at Sill Trim
Note: Field measure Opening Height
before making field cuts and adjust
cut dimensions accordingly.
c
m
s
RR07027 RVPBR (RBR) Wall Panel - Three Sided Framed Opening
!D'141
Rev. oil Jamb Trim Installation
TT
rer
Cut and remove
remainder of front fold
(2) Fasteners #14
x J" Pop Rivet
at lap
2" Lap when required.
Field cut and notch
as required.
Fastener #14A J" x J" Pop Rivet
at 20" O.C. at Cold Form
OR
Fastener #16 12-24 x 1i"
Pancake SD DP5 W/O Washer
at 1'-8 O.C. at Hot Rolled
Double Sided Tape
(Not by Bldg Mfg)
Blanket Insulation —\
RVPBR (RBR) Wall Panel —/
N—otg:Terminate Blanket Insulation JJ
at capillary lip of Jamb Trim
Field flatten Trim leg when required
Jamb Trim F482 (shown)
or Alternate Jamb Trim F484
RR07029 Parapet Cap Trim Detail
I '14
R°" 02 PBR Back Panel & Rev. PBR Wall w/Collateral
(6) Fastener #4
4-14 x J" LL SO W/W�asherr
(4) Fastener #14 y r
J" x J" Pop Rivet
Jamb
(Cold Form shown
Hot Rolled similar)
"Optional"
Channel Closure Trim
See RR07028 for details.
}" Bead of HW54- Tube Caulking
(Header to Floor)
Field Cut Wall Panel
Opening Width
— Finish Floor Line
Alternate Jamb
Trim F484 Profile
Jamb Trim F482 and
Note: Panel position
is shown with Panel Rib
Alternate Jamb Trim F484
starting 1'-0
from Steel Line and Opening on
Note: All trim is to be
1'-0 module.
Location of Panel Rib may vary
Front View
installed BEFORE blanket
depending on
the Opening Width and location.
Right Jamb Trim as shown
insulation is applied to walls
Field measure
before cutting Panel and Trim.
Left Jamb Trim opposite hand
Attachment
(NOT BY MESCO)
Collateral 1
(NOT BY MESCO)
Page DoubleLok/ UltraDek- Classic Standard and Standard Large Gutter
Date
R°" Fixed High or Hi -Thermal Eave Plate - Sheeted Wall
Mar "14
One bead of Tub01 Fastener #1E
Sealant at lap Gutter Stra 4-14 x 14"IN
Parapet Cap Trim F3530 End Lap-
2" Minimum End Lap,
Field Miter at corners
----
et Cap Trim SP--
Parapet Channel Girt
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Girt
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Hold Trim i"
above Channel
Fastener #17A
12-14 x 14"
SD W/Washer
5"-7 —5" O.C.
Fastener #4A
4-14 x J"
SD W/Washer
1'-0 O.C.
Outside Closure
HW456 at PBR or
HW429 (Metal) at PBR
HW460 at PBU
PBR or PBU Back Panel
Standard F246 (shown)\
Standard Large F289
attached with
(3) Fastener #4
4-14 x J" LL SD W/Washer
(See Erection Drawings for
Spacing)
Screw location used with
notched gutter strap
F246
Eave Gutte
Standard F752 (shown)
Standard Large F4100
Tape Sealant
(HW504) Between
Gutter Strap and
Roof Panel
Do NOT use prey
punched holes
Fastener #4/
4-14xJ"
LL SD W/Washer
V-0 O.C.
Attachment
LL SD W/Washer
(8) Per 24" Panel
(7) Per 18" Panel
(6) Per 12" Panel
See Sheeting
Layout
i
Eave Trim'
2955
M��SC em ral
l F149)
�3
0
O
w
ay
�m
DL02g07x
° R°v.
un'14
Anside Metal Closure (HW426)
Tri-Bead Tape Sealant (HW504)
top and bottom. See GDL02040
/Fastener #1
4-14 x 1"
(2 Per closure)
Fastener #14A
b"o x J,
10'-0" O.C.
Fastener #1
4-14 x I.
12" O.C.
,-Fixed Eave Plate
HW7616 (Purlin > 48")
HW7654 (Purlin < 48") (Shown)
HW7661 Hi -Thermal (DoubleLok
only)
--Fastener #17A
12-14 x 14"
SD W/Washer
Panel
Screw Location used
only with un-notched
Strap F289
DoubleLok 1 UltraDek Roof Panel
Endwall Parapet - Roof Panel Beginning
R06DL23020
DoubleLok 1 UltraDek Roof Panel
Endwall Parapet - Roof Panel Terminating
Ra9GDL23021
oM---ar
R 01
attic 4
R°01
See Parapet Cap Trim Detail
See Parapet Cap Trim Detail
GD15001 for PBR, PBU AVP, RBR
GD15001 for PBR, PBU AVP, RBR
I
& RBU Wall Panel
& RBU Wall Panel
GD15002 for ShadowRib Wall Panel
GD15002 for ShadowRib Wall Panel
T
4�
KU
l-IA
I "Optional" 5'-0" of Tape
"Optional" 5'-0" of Tape I
See FMO1001 for
Expansion Ridge
Saane�nsidela507) at each
2" to 6" 1" p p
Sealant HW507 at each
panel sidelap 1" 2" to 6"
ExeansionORidfer
Flashing End Seal
Flashing End Seal
PBR or PBU Back Panel
PBR or PBU Back Panel I
Inside Closure
Inside Closure
HW455 at PBR
I
et Rake Flash
I
Parapet Rake I
HW455 at PBR
HW459 at PBU
HW459 at PBU
with Tape Sealant
I Para
I
FFlash
324 I
I
with Tape Sealant
H W507 on both sides
I
H W507 on both sides
Tri-Bead Tape Sealant
Tri-Bead Tape Sealant I
HW504
HW504
Fastener #17A
Fastener #17A
W
12-14 x 14" SO W/Washer
12-14 x I' SD W/Washer
Parapet Rake Cleat
Parapet Rake Cleat
5"-7"-5" O.C.
5"-7"-5" O.C.
F292
F292
Rake Angle RA4
Rake Angle
Fastener #1E
Fastener #1E
RA4
4-14 x 14" LL SD W/Washer
4-14 x 14" LL SD W/Washer
2'-0 O.C.
OF
2'-0 O.C.
Rake Support Angle
Rake Support Angle
Low HW7710
Low HW7710
High HW7720
High HW7720
DoubleLok/UltraDek
HTDL HW7664
HTDL HW7664
Panel
Panel
Fastener #12A
Fastener #12A
12 x 1" P.H.
12 x 1" P.H.
(2) required at each Fastener #5
Fastener 5
(2) required at each
Roof Member
1/4'-14 x 1 1/4"
1/4"-14 x 1 114'
Roof Member
24" O.C.
24" O.C.
;
Fastener 14A
Fastener #4
l
1/8" x 3 8"
4-14 x J' LL SD W/Washer
Fastener #4
Dependent on width of Flash use
4-14 x >;" LL SD W/Washer
14A
(1) or (2) screws at lap locating to
Dependent on width of Flash
%8"
clear Panel Rib and Rake Cleat F292
use (1) or (2) screws at lap
i
(2 provided for each lap.)
locating to clear Rake CleatF292
(2 provided for each lap.)
1
Parapet Rake Flash
F324 Parapet Rake Cleat
Rake Cleat
kFt
pa wnh)/j
poW
F292
�29a2pet Parapet Rake Flash
(2) 1/4"
beads
of Tube
Sealant 1/4" bead of
``70 Tube Sealant
1/4" bead of (2) 1/4" beads
Tube Sealant of Tube Sealant
LAP
DETAILS Fastener #1E
Fastener #1E LAP DETAILS
4-14 x 14" LL SD W/Washer
4-14 x 14" LL SD W/Washer
r
t (r;�
�`
-1
^�1
0
S
Cr
y..
E
,�o
�
O
U)
r
N
to
�
co
O �
rn
b
_
}, N
h
U<
J
Z 0_
J
a-Il
y
C
a
y
x
t000
l
a'
,6
O<U
UZ-i
VJ
ru
O
O
•�
tv
O
OJZ
❑
❑
Hwa
o
iD
_ cad
Q=p
bi 0
rn
2
I— .— a-
�o
m )
0
O
a
U m
let
0
U
N
m
�U
O`
u)
p
oa
z
z o
`
t° o
O
❑
O
C)
fr tz
�fr
Qn9
0wo
0
L
U[r0
CO
0
~
0 U
<
3
y
Co
D
U
ZI"r.0
O
Scale:
NOT
TO SCALE
Drawn by.
Checked by. -
Project
Engineer:
Job Number:
14-8-83134-1
Sheet Number:
R11
of 13
The engineer whose seal
appears hereon is an employee
for the manufacturer for the
materials described herein. Said
seal or certification is limited
to the products designed and
manufactured by manufacturer
pnly.The undersigned engineer is
not the overall engineer of
record for this project.
THESE rLMS AND ALL FROPOS5D WORK
ARE SUBJECT TO ANY COr1pECy1r
,jtjS
REOUIR@'D By FIELD lNSPECWjRS THAT
PdAY BE NEC! SSARY IN ORDM TO
CO- +IRLY VITH ALL APPLICABLE CODES,
ENME1A
38305
`•. TATE OF
V,�NAL
0P0
SEP 0 9 2015
CO• •'rIt
STRUCTURAL SCREW
1/4"-14 x 1 1 /4"
SHOULDER DP2, 12" O
FASTENER #5
FLOATING EAVE PLATE:: P
LOW HW7617—
HIGH HW7618—
HIGH THERMAL HW7618—
(ON TOP OF ROOF INSULATION)
NOTE: ROOF RUN TO EAVE
LESS THAN 5'-0
DETAILER NOTE
tzt'�C,
SQ
1%4mw�h'
PURLIN—` \<
TRI—BEAD
TAPE SEALANT
HW504 (CONTINUOUS)
STEP 1
PARAPET RAKE TRIM
F324--
PARAPET RAKE CLEAT-
F292-_
TRI-BEAD TAPE SEALANT
HW504
Fastener #1E
J-14 x 1j" LL
SD W/Washer
3" O.C.
CAP STRIP HW1210
REF. SS15078-00
W/ TRI-BEAD TAPE
SEALANT HW504 \
r
EAVE STRUT —
RAKE ANGLE RA4-_
L8X8X16GA.
Fastener #4
J-14 x J" LL
SD W/Washer
6" O.C.
���
FLOATING -
/ SAVE PLATE
/ �Fastener #1E
J-14 x 1j" LL SD W/Washer
3" O.C.
I � 4"
STRUCTURAL SCREW�40- '
1/4"-14 x 1 1/4 P)
T I SHOULDER DP2, 12" O.C.
t I FASTENER #5
t INSTALL INTERMEDIATE
SUPPORT CHANNELS UNDER
DIVERTER. ATTACH TO
PURLIN/EAVE STRUT WITH
FIELD CUT RA3-- 4 X 8 X
16GA. X 0'-6" ANGLE USING
(12) SCREWS TO ATTACH TO
PURLIN LOCATE AT 1 /3
' POINTS TO SUPPORT DIVERTER J PURLIN
II
PAN PRIOR TO INSULATION
ALTERNATE
SUPPLEMENTARY
SUPPORT MEMBER WHEN
EAVE TRIM INSIDE DIVERTER NOT LOCATED
CLOSURE @ BLDG PURLIN
MINOR RIB TAPE SEALER HW426
HW512 (1) PER MINOR RIB
WALL PANEL (PROFILE VARIES)
PARAPET LINE
� RAKE -PARAPET TRANSITION
DIVERTER SUPPORT -
REFER TO GDL08005-01 OR GDL08006-01.
FIELD NOTCH RAKE SUPPORT ANGLE (8 „ ,10,> , OR 12 CEE)
AT DIVERTER.
TRIPLE -BEAD TAPE SEALANT
H W502 - - - -
STEP 3
Page
UD 1 DL Roof - Offset Parapet Diverter GDL28002
Terminating at Eave DMar'14 �e01
VERTER
Fastener #1E __\
—14 x SD W/Wasasher
(6) Per Panel
(1) Per Trapezoid Each Side
TRIPLE —BEAD TAPE SEALANT
HW502 (CONTINUOUS)
DIVERTER SUPPORT
(8",10", OR 12" CEE)
0
0
®
I
URETHANE SEALANT HW54
© PANEL RIB, INLINE
WITH TAPE SEALANT
ROOF PANEL -A
_ (6) FASTENERS REQUIRED AT EACH SUPPORT
FOR PURLINS OR SUPPORTS 14 GA OR LESS USE
FASTENER #113 (J - 14 X 1J DP3)
FOR PURLINS OR SUPPORTS 12 GA OR GREATER USE
FASTENER #55 (12 - 24 X 1J DP5)
L4X8X16GA. XO'-6"
FIELD CUT FROM RA3--
VI E W— A
EAVE STRUT
.11
I
0
I
0
0
(6) FASTENERS REQUIRED AT EACH SUPPORT
FOR PURLINS OR SUPPORTS 14 GA OR LESS USE
FASTENER #113 (J - 14 X 1J DP3)
FOR PURLINS OR SUPPORTS 12 GA OR GREATER USE
FASTENER #55 (12 - 24 X 1J DP5) (6) FASTENER #12A -
12 x 1" PANCAKE HEAD
�GF
�y
q�
c
L4X8X16GA.X0'-6"
FIELD CUT FROM RA3--
VI E W— B
RECOM
DIVERTER INSTAL_....
STEP 2
—MINOR RIB TAPE SEALER
HW512 (1) PER MINOR RIB
PARAPET LINE \
/ I a
/ I
o
II
I II
I I o
o
I
I � o
v w
a 6
O n
'^L 9 cn r,
Z cif
00
O u�i rn 0 Zero o
a,o �o_o' o
• d 00QU U Lu
• • fn x °' Z 1.2 L°
• it O F_ Z H C�
�_ zFw¢
• % t 4 Devi
�—
a • v m 0MC7
• MVia' CtX04.. c c.
• W U h O O
OC) U U
O
w
vn �
cN o
z L° Q L
U
N `W �O
Fastener #1E z a u°Z
J-14 x 1j" LL SD W/Washer
3" O.C. D
V) <
Z}0
Q ���0
/ Z=UJ F
o0 o
o
/ m r(a< o
U SrU �
Scale: NOT TO SCALE
RAPET LINE
Drawn by.
Checked by
Project Engineer:
Job Number: 14—B-83134-1
Sheet Number: R12 of 13
The engineer whose seal
appears hereon is an employee
for the manufacturer for the
materials described herein. Said
seal or certification is limited
to the products designed and
ANS AND ALL RRQFOSuD WORKmanufactured
IBJECT TO ANY COMECTIONS
'_D BY FIELD INSPEC)ORS THAT
by manufacturer
not the overall 'engineer gned glof engineer is
record for this project.
lE NECINA2Y IN ORDLIM TO
WITH ALL APPLICABLE CODES.
FILE COPY
DRMEIA ENMEIA
%� <
2015
F292
Parapet Rake Cleat
l9
O
F320
Downspout
F4101
Cuter End
F321
Downspout Elbow
F4100
Gutter
I I�
C
Note: All Bends 90° Unless Otherwise Noted
C> Denotes Color Side
PART MARK
QUANTITY
STRETCHOUT
GAGE
SP1-1
2
0'-9d'
26
GAL
&M9&T%A
ate
Sheet No.1/15
SP1
SP1-1
i"
Note: AllBends 90" Unless Otherwise Noted
C> Denotes Color Side
PART MARK QUANTITY STRETCHOUT GAGE COLOR LENGTH
SP9-1 14 2'-11" 26 SADDLE TAN 20'-2
SP9
Job Number User Date Sheet No.
i4-8-83134 JPI 05/31/95 SP9-1
d'
7" Max.
F324
Parapet Rake Trim
m'
os Color
m Side
Varies
F3535
Angle Trim
44"
1J�
F326
Parapet High Eave Trim
os Color
N Side
Varies
F3536
Angle Trim
<c
3"
735,
Note, All Bends 90' Unless Otherwise Noted
C> Denotes Color Side
PART MARK QUANTITY STRETCHOUT GAGE COLOR LENGTH
SP6-1 4 1'-1 4 26 SADDLE TAN 20'-2
Job Number User Dote Sheet No.
SP6 14-8-83134 JPI 05/31/15 SP6-1
C
a
M
Note: All Bends 90' Unless Otherwise Noted
C> Denotes Color Side
PART MARK QUANTITY STRETCHOUT GAGE COLOR LENGTH
SP10-1 4 2'-51" 26 SADDLE TAN 20'-2
SP10
Job Number User Date Sheet No.
14—B-83134 JPI 05/31 /15 SP10-1
F481
Framed Opening Head Trim
F22
Optional Jamb Trim
4j"
F482
Framed Opening Jamb Trim
F24
Optional Head Trim
F- c
Note: All Bends 90' Unless Otherwise Noted
C> Denotes Color Side
PART MARK QUANTITY STRETCHOUT GAGE COLOR LENGTH
SP7-1 4 1'-7r 26 SADDLE TAN 20'-2
^I SP7
Job Number User Dote Sheet No.
14-8-83134 I JPI 05/31 /15 Si
F620
Starter Trim
F571
Panel
F797
Downspout Strop
31j"
1
l }
F830
Outside Corner Trim
8i _
C
n
Note: All Bends 90° Unless Otherwise Noted
C> Denotes Color Side
PART MARK QUANTITY STRETCHOUT GAGE COLOR LENGTH
SP8-1 2 1'-4r 26 SADDLE TAN 3'-0
Job Number User Date Sheet No.
SP8 14-8-83134 JPI 05/31/15 SP8-1
THc12 rLk%IS Aj%D ALL FROPOSSD WORK
ARE SUBJECT TO ANY CORREC? 01i
REQUIRED BY FIELD rdSPEC?ORSTHAT
MAY BE WC!5AVIY IN OROM TO
CO i LY WITH ALL APPLICABLE CODES.
DRME1A ENMEIA
w
Y
jNo 38305
/ ac a
ATEOF
!�GORIOP
70IVA1
SEP Q 9 Nib
PORTION OF LOT 2, BLOCK 1 PORTION OF LOT
ST LUCIE GARDENS + ST. LUCIE GAf Landscape Legend .
CITY OF PORT ST. LUCIE + \ CITY OF PORT S
ZONING: ZONINL-
GU/sEU - GENERAL USE/SPECIAL EXCEPTION CG - GENERAL COI
FUTURE LAND USE: + I FUTURE LANE Trees:
UTILITIES ❑ + COMMERCIAL L
7 CURRENT USE: CURRENT L
MYF UTILITY TOWER ❑❑ BST VACANT Qty SYM WU Name
OHE OHE Q-OHE OHE OHE OHE OHE OHE 7 AR O Red Maple (Native)
-- -- -- -- -- - -- -- --- Acer rubrum, FG, 12' ht, 2,5" cal
3
15" OAK 7 24" OAK 20" OAK 32" OAK ,
UH Noo°01'54" 176.67' MYR 3 E, 8 LI1 O White Crape Myrtle (count 2 for 1)
SOD 14.0------ 3 _ _______ _ _ 14.0 SOD VIB i STOP
���--------------------- 1---_____� -__ _ 13_5_ = Lagerstromia indica Natchez , FG, 12 Ht, Multi
2 /,-------------------- i2.5 - f�i�----- 12.5 �I% m 2 LI Red Crape Myrtle (count 2 for 1)
��------------------�11.5-- - - - - -
�PORTIONOFLO O
TD I jl DRY DETENTION AREA / z 11.5 I \ 3 ST. LUCIE 6, Lagerstromia indica 'Red Rocekt', FG, 12' Ht, Multi
/( ST. LUCIE C
I BOT. EL. 11.5 (0.05 AC) / ZONIr
IL - INDUSTR7
TOP EL. 14.0 (0.14 AC) 5 Q V O Live Oak (Native)
/ 11 111.5 11.5 / ® I - FUTURE LAP
to �// 17 IND - INDU Quercus virginiana, FG, 12' Ht, 2.5" cal
10.5 I I CURRENT
1 I Tp - J MUH i FLEX OFFICE
SERVIC 6 SP Cabbage Palm (Native)(Count 3 for 1)
_
-------------------- o \ 3 Sabal palmetto, 18'-24' OA Ht
vIe 3 ---------- 11 TD Bald Cypress (Native)
L J SOD 29 MYR O Taxodium distichum, FG, 12' Ht, 2.5" cal
14 ILE 1� \ 5 I I =
18 23 ® OD I "' ; Shrubs:
--------- ----- MYR MYF
--------- Psv MUH 1 i 4 84 COD O Gold Dust Croton
♦ cr �
i AR 13 Q� FICUS Codiaeum variegatum 'Gold Dust', 3 gal, 24" ht, 24" o.c.
30
LAN 75 ILE 0 Dwarf Youpon Holly (Native)
OD
PSY �
♦ 8
I I o �
• • ::: .. o Dwarf', , 18 h , 24 o.c.
in PROP. ..... vIB
I m Ilex vomit ria 'Shillings rf 3 gal t "
N 1-STORY CBS • •----------------------- -- --------------- 127 MUH 0 Muhly Grass (Native)
N5COUNT STORE 22 Muhlenbergia capillaris, 3 gal, 18" ht, 24" o.c.
GROSS FLOOR AREA = 8,593 S.F. 1< ILE 1
67 w F.F.E. = 15.25 KAM.D.1 o I 24 57 LOR O Chinese Razzleberry
ARA g 21 UH I I = i C(
Loropetalum chinense rubrum 'Plum', 3 gal, 18" ht, 24" o.c.
1 M 10' utility 36 Cot)16 1 i P A 43 MYF Simpson's Stopper (Native)
RHA
QV Offset, typ. AR
I LAN O Myrcianthes fragrans, 15 gal, 4' ht, 48" o.c.
9
"'
45 24 RHA MYF 3 m ;
t N ; 1 20 MYR 0 Wax Myrtle (Native)
Op ARA ®.; QV I; I o ----------
ARA 4.6 m Myrica cerifera, 15 gal, 4' Ht, 48" o.c.
CROS ACCESS 175 I
9 _ _ EA EMENT ®: • w 48 PSY O Wild Coffee (Native)
I w I ®• I ARA I
o 24 EX. Psychotria nervosa, 3 gal, 18" ht, 24" o.c.)
SCH ASPHALT oo
2 ®• . _= I 24 PAVEMENT Z I; I I 238 RHA 0 Indian Hawthorn
AR - I I = - LOR 35 I I o I Rhaphiolepis indica, 3 gal 18" ht, 24" o.c.
28 NGRESS/EGRESS
SCH ® EASEMENT ; 132 SCH O Variegated Dwarf Schefflera
---
28 99 6 IL RHA !---------- Schefflera arboricola 'Trinette', 3 gal, 18" ht, 24" o.c.
SP 1 1
4`A i I 64 i 2LO1s i i i 17 VIB O Walters Viburnum (Native)
ARA I w ! o i EX. Viburnuum obovatum, 15 gal, 4' Ht, 48" o.c.
N V) LLJ `--J ® CONj
4 i 114 i I O Lo Q 20 20 1 i PARKII
LIi CH I v 20 18 AREA Groundcovers:
425 ARA 0 Perennial Peanut
COD 11 I NC
I Arachis glabrata 'Ecoturf', 1 gal, 18" o.c.
•�;+�; - ®_ 60 109 LAN O Purple Lantana
PROP. S D --------- - --- �; -- -- --- --- --- - ---- -- - LAN
Lantana montevidensis, 3 gal, 18"x12", 24" o.c.
20'X20' UTILITY
EASEMENT I - %''` �� �� 69 TRA Dwarf Asian Jasmine
EX.6' S A -�--y- - - -- - -�- --^ -A-
T _____ _. O ticu , gal, 6 x12 , 24 o.c.
N 00°00'00" 177 24' s �f � 11 ll 11
------ ------ --- --------------- ---- ------------- - -- ---
Trachelospermum asia ' m 3 al
----------------------------------------- -------------- ----- -
2 r
5NT U LITY --� E; N
AR 20 EA MEN T 39 69 ?>'
SCH LAN TRA
-----T----T----�---- -.-----,-- ---_-�-_-_ --_-_-C-_--T--_ --_S--.F--4-T4-----7-
T�I -FP-__----_F-_i-_-_ �-_-F4 ----- --- ----
-1 :1 7
,
33 28
35
RHA 95 SCH LOR
5' utility -� Lennard Road
Clear Zone,
Mulch
Landscape Irrigation Notes:
- All areas to receive 100% irrigation coverage
- All zones to be automatically controlled.
- Clocks to have automatic "Rain sensors".
- Water source may be potable or well and shall
be determined at time of building permit application
- The irrigation system will be designed to accept
reclaimed wastewater once it becomes available to the
property
4 MUH
LIl
Sv
{- FM FM FM ---#XeM� FM Water Use (WU) Legend:
High
SCH Q
Medium
OLow
co
e
O
Landscape Data:
Perimeter Landscaping:
Q M �8 a
Southern PL (against other Property)
Q
141 LF - 30' driveway (10' width) = 111 LF
o
1 tree/30 Lf:
4 trees
y
Western PL (against other Property)
c
M
88 LF (10' width) = 88 LF
-'
1 tree/30 Lf:
3 trees
Northern PL (against other Property)
245 LF - 41' driveway (10' width) = 204
LF
1 tree/30 Lf:
7 trees
Eastern PL (against Lennard Road R/W)
177 LF (15' width) = 177 LF
1 tree/30 Lf:
6 trees
Total Exterior Trees required:
20 Trees
Total Exterior Trees provided:
20 Trees
a
Interior Landscaping:
NCDVehicular
Use Area (VUA):
211072 sf
Landscape Area required: 1sf/18sf VUA
= 1,171 sf
a'
Landscape Area provided:
11487
2
Trees required: 1 tree/180 sf =
8 Trees
cn
2
U
additional trees for landscape islands: 2 Trees
Total Interior Trees required:
10 Trees
Total Interior Trees provided:
10 Trees
3
Total Trees Required:
30 Trees
E
Total Trees Provided:
30 Trees
"
m
o
Tree Mitigation:
Inches removed:
48
a
Inches preserved
91
oegEZ
3
Mitigation required:
0
Notes:
1. 7% of the required trees are palm trees.
2. 83 % of the required trees are native
3. 17% of the required trees are flowering trees
4. 100% of the required trees located within landscape
Islands are shade trees.
5. 100% of the required trees are low water use.
6. 100% of the required shrubs are low water use.
7. All proposed trees to have a minimum of 5' Spread.
General Notes:
1. No landscape materials other than sod grasses may be planted within
a 5' radius maintenance area of any PSLUSD facility such as water
meters, backflow devices, fire hydrants, sanitary sewer cleanouts, and
manholes, air release valves, etc.
2. No landscaping shall be planted in such a manner as to adversely
affect utility installation, operation and maintenance.
3. All landscaping within Port St. Lucie Utility Systems Department
(PSLUSD) utility easements shall comply with PSLUSD technical
specifications, policies, and codes. Trees shall not be planted within ten
(10) feet of any PSLUSD underground infrastructure.
3. All landscape material to be Florida No.1
4. All landscaping meets FDOT clearzone and sight distance criteria.
m
Graphic Scale
20 10 0 20
Scale: 1" = 20'
9.18. 1-4
_L.Ll&, 733
LD-n1
Rgwov",u Juk t a 101
PLANTING NOTES:
FERTILIZER
FERTILIZERS SHALL BE SLOW RELEASE, UNIFOOM IN COMPOSITION,
DRY AND FREE FLOWING. THE FERTILIZER SHALL BE DELIVERED
TO THE SITE IN THE ORIGINAL UNOPENED BAGS, EACH BEARING
THE MANUFACTURERS STATEMENT OF ANALY5I5,AND SHALL MEET
THE FOLLOWING REQUIREMENTS: SIX (6) PERCENT
NITROGEN,SIX (6) PERCENT PHOSPHOROUS,ANO SIX (6)
PERCENT POTASSIUM. FERTILIZER SHALL BE APPLIED TO
ALL SHRUBS (113 LB PER 3 GAL POT, 114 LB PER 1 GAL
POT) AND GROUNDCOVER. THE 50D STARTER
FERTILIZER MIXTURE SHALL BE A 5-10-10 ANALYSIS. A
14-14-14 FERTILIZER ANALYSIS IS REQUIRED ON ALL TREES
AND SHRUBS OVER 5' IN HEIGHT (112 LB PER 5' OF
SPREAD). AGRIFORM TABLETS WITH TWENTY (20) PERCENT
NITROGEN, TEN (10) PERCENT PHOSPHOROU5,FIVE (5)
PERCENT POTASSIUM IN 21 GRAM SIZES SHALL BE APPLIED
ALONG WITH THE FERTILIZER PROCESS (1 WITH 1 GAL
PLANTS, 2 WITH 3 GAL PLANTS AND 2 TABLETS PER 1"
OF TREE TRUNK CALIPER). MAGNESIUM SULFATE SHALL BE
APPLIED TO ALL PALMS AT INSTALLATION AT A RATE OF
112 LB PER INCH OF TRUNK CALIPER. MANGANESE SHALL
BE APPLIED AT T74E SAME RATE
MULCH
MULCH MATERIAL SHALL BE COLORED 'A' GRADECERTIFIED RE-
CYCLED MULCH AND MOISTENED AT THE TIME OF APPLICATION TO
PREVENT WIND DISPLACEMENT. MULCH SHALL BE APPLIED TO A
MINIMUM OF 3" DEPTH IN PLANTING BEDS. MULCH SHALL NOT
BE PLACED WITHIN 6" OF TREE OR PALM TRUNKS.
SOD
THE SOD SHALL BE CERTIFIED TO MEET FLORIDA STATE
PLANT BOARD SPECIFICATON5,A95OLUTELY TRUE TO
VARIETAL TYPE,AND FREE FROM WEEDS,FUN6US,INSECT5
AND DISEASE OF ANY KIND.
SUBSTITUTIONS
NO SUBSTITUTION OF PLANT MATERIAL TYPES OR SIZES WILL BE
ALLOWED WITHOUT WRITTEN AUTHORIZATION FROM THE
LANDSCAPE ARCHITECT OF RECORD. CONTAINER GROWN
MATERIAL WILL NOT BE ACCEPTED AS A SUBSTITUTE FOR
8 & 8 MATERIAL UNLESS PREVIOUSLY APPROVED.
INTENDED SUBSTITUTIONS SHALL BE SPELLED OUT IN BID.
MEASUREMENTS
SHADE TREES: HEIGHT SHALL BE MEASURED FROM GROUND
TO THE AVERAGE BRANCH HEIGHT OF CANOPY. SPREAD
SHALL BE MEASURED TO THE END OF BRANCHING EQUALLY
AROUND THE CROWN FROM THE CENTER OF THE TRUNK.
MEASUREMENTS ARE NOT TO INCLUDE ANY TERMINAL
GROWTH. SINGLE TRUNK TREES SHALL BE FREE OF "V"
CROTCHES THAT COULD BE POINTS OF WEAK LIMB
STRUCTURE OR DISEASE INFESTATION.
SHRUBS: HEIGHT SHALL BE MEASURED FROM THE GROUND
TO THE AVERAGE POINT WHERE MATURE PLANT GROWTH
STOPS. SPREAD SHALL BE MEASURED TO THE END OF
BRANCHING EQUALLY AROUND THE SHRUB MASS.
MEASUREMENT AREA Nor TO INCLUDE ANY TERMINAL
GROWTH.
PALMS: CLEAR TRUNK SHALL BE MEASURED FROM THE
GROUND AT THE TIME OF INSTALLATION TO THE POINT
WHERE THE MA TURF AGED TRUNK JOINS THE IMMATURE
OR GREEN PORTION OF THE TRUNK OR HEAD.
GREY WOOD (G. W) - SHALL BE MEASURED FROM THE
GROUND AT THE TIME OF INSTALLATION TO TOP OF THE
HARDENED TRUNK.
OVERALL HEIGHT (O.A.) - SHALL BE MEASURED FROM THE
GROUND AT THE TIME OF INSTALLA TTON TO THE AVERAGE
FROND HEIGHT.
PALMS WITH MARRED OR BURNED TRUNKS WILL NOT BE
ACCEPTED.
PLANTING SOIL AND BACKFILL
PLANTING SOIL SHALL BE RECYCLED TOPSOIL.
RECYCLED TOPSOIL SHALL CONSIST OF A STABILIZED MIXTURE OF
GROUND YARD TRIMMINGS AND POSSIBLY 9105OLIDS PROCESSED
ACCORDING TO STATE OF FLORIDA DEPARTMENT OF ENVIRONMENTAL
PROTECTION GUIDELINES FOR THE PROCESSING AND DISTRIBUTION OF
SEWAGE SLUDGE COMPOST. RECYCLED TOPSOIL SHALL ONLY BE OBTAINED
FROM A STATE PERMITTED RECYCLING FACILITY WHICH 15 ALSO D.O.T.
CERTIFIED AND STORES PRODUCT ON A PAD WITH A CURRENT NEMATODE
CERTIFICATION FROM FLORIDA DEPARTMENT OF AGRICULTURE. RECYCLED
TOPSOIL SHALL HAVE THE FOLLOWING CHARACTERISTICS:
- WEED FREE
- M015TURECONTENT 50% BY WEIGHT MAXIMUM
- WATER HOLDING CAPACITY 200% BY WEIGHT MINIMUM
- CARBON TO NITROGEN RATIO LE55 THAN 25 TO 1
- ORGANIC MA TTER CONTENT 40% BY DRY WEIGHT MINIMUM
- SOLUBLE SALTS LESS THAN 3 MMHOS/CM
-PH RANGE 7.0-7.9
- MINIMUM NUTRIENT LEVELS AS FOLLOWS:
MACRO NUTRIENTS: NITROGEN (N) -1 % MINIMUM, WATER INSOLUBLE
NITROGEN 90% MINIMUM, PHOSPHORUS (P) - 0.5% MINIMUM, POTASSIUM
(K) - 0.2% MINIMUM AND OTHER MACRO AND MICRO NUTRIENTS. THE
RECYCLED TOPSOIL SHALL CONTAIN LEVELS OF THOSE MICRO NUTRIENTS
NECESSARY FOR PLANT GROWTH. THESE INCLUDE CALCIUM, MAGNESIUM,
SULFUR, BORON, COPPER, IRON, MANGANESE AND MOLYBDENUM. RECYCLED
TOPSOIL NOT MEETING THESE REQUIREMENTS WILL NOT BE ACCEPTED.
BACKFILL:
ALL NEW AND TRANSPLANTED PLANT MATERIAL (INCLUDING NEW SOD)
SHALL BE PLANTED ONLY AFTER PREPARATION OF EXISTING SOIL
AS FOLLOWS:
SPREAD A LAYER OF 3" DEPTH OF RECYCLED TOPSOIL (AS DEFINED ABOVE)
OVER THE ENTIRE PLANTING AREA. THE TOPSOIL SHALL THEN BE
UNIFORMLY DISKED, TILLED OR AERIFIED INTO THE EXISTING SOIL
TO A DEPTH OF 12" UNDERNEATH SHRUBS AND GROUNDCOVERS,
6" UNDERNEATH SOD AND TO A DEPTH OF 36" FOR THE TREE
PITS, WITH THE FOLLOWING EXCEPTION: NO ROTOTILLING OR
DISKING SHALL OCCUR CLOSER TO THE TRUNKS OF ESTABLISHED
PLANTS THAN ONE HALF (112) THE DISTANCE OF THE CANOPY FURTHER
OUT FROM THE DRIP LINE OF THE EXISTING PLANT CANOPY. ALL
PLANTS, INCLUDING HEDGES AND GROUND COVER SHALL BE PLANTED
IN INDIVIDUALLY DUG HOLES AND THE MATERIAL DUG FROM THE HOLES
SHALL THEN BE FURTHER MIXED WITH THE PREPARED SITE SOIL PRIOR
TO BACKFILLING OF THE PLANTING HOLES AROUND THE ROOT BALLS.
NO ADDITIONAL BACKFILL SOIL SHALL BE USED.
AN EXCEPTION ARE PLANTING PITS FOR CABBAGE PALMS, WHICH SHALL BE
BACKFILLED WITH CLEAN NATIVE SAND ONLY.
REMOVE EXCESS MATERIAL TO PROVIDE PROPER FINISHED GRADE.
ALL PLANTING PIT-� AND PLANTING AREAS SHALL BE AMENDED WITH
AGRODIAMONDSB,PER MANUFACTURERS 5PECIFICATTONS.
PLANT MA TERIAL5
TREES, PALMS, 5HRUB5,6ROUND COVERS:
PLANT SPECIES AND SIZES SHALL CONFORM TO TH05E INDICATED IN THE
DRAWINGS. NOMENCLATURE SHALL CONFORM TO STANDARDIZED PLANT
NAMES, 1942 EDITION. ALL NURSERY STOCK SHALL BE IN ACCORDANCE
WITH GRADES AND STANDARDS FOR NURSERY PLANTS, PARTS I & IT,
LATEST EDITION PUBLISHED BY THE FLORIDA DEPARTMENT OF
AGRICULTURE AND CONSUMER SERVICES, UNLESS SPECIFIED OTHERWISE.
ALL PLANTS SHALL BE NORMAL FOR THE VARIETY AND FLORIDA GRADE
NUMBER 1 OR BETTER AS DETERMINED BY THE FLORIDA DIVISION OF
PLANT INDUSTRY.
SPECIMEN MEANS AN EXCEPTIONALLY HEAVY, SYMMETRICAL. TIGHTLY KNIT
PLANT, 50 TRAINED OR FAVORED IN IT5 DEVELOPMENT THAT FIRST
APPEARANCE IS UNQUESTIONABLE AND IT 15 OUTSTANDINGLY SUPERIOR
IN FORM, NUMBER OF BRANCHES, COMPACTNESS AND SYMMETRY.
ALL PLANTS SHALL BE FRESHLY DUG, SOUND, HEALTHY, VIGOROUS, WELL
BRANCHED AND FREE OF D15EASE AND INSECT EGG5 AND LARVAE AND
SHALL HAVE ADEQUATE ROOT SYSTEMS. TREES FOR PLANTING ROWS
SHALL BE UNIFORM IN SIZE AND SHAPE. ALL MATERIALS SHALL BE
SUBJECT TO APPROVAL BY THE LANDSCAPE ARCHITECT, WHERE
REQUIREMENTS ARE OMITTED FROM THE PLANT LIST PLANTS SHALL BE
PRUNED PRIOR TO DELIVERY ONLY UPON THE APPROVAL OF THE LANDSCAPE
ARCHITECT.
ALL CONTAINER GROWN MATERIAL SHALL BE HEALTHY, VIGOROUS, WELL
ROOTED PLANTS AND ESTABLISHED IN THE CONTAINER IN WHICH THEY
ARE SOLD. THE PLANTS SHALL HAVE TOPS OF GOOD QUALITY AND BE IN
HEALTHY GROWING CONDITION. AN ESTABLISHED CONTAINER GROWN
PLANT SHALL BE TRANSPLANTED INTO A CONTAINER AND GROWN IN THAT
CONTAINER SUFFICIENTLY LONG ENOUGH FOR THE NEW FIBROUS ROOTS
To HAVE DEVELOPED 50 T HAT THE ROOT MA55 WILL RETAIN ITS SHAPE
AND HOLD TOGETHER WHEN REMOVED FROM THE CONTAINER.
TreePlanting Detail
Tree Stakes are to be removed between 6-12 months by the NT5
Owner. d
n,J Viv" rin
Palm Plantinq Detail
Tree Stakes are to be removed between 6-12 NT5
Cut fronds and
months by the Owner. bud to increase
survival of e
tree.
Place (3) 2 x 4's,
equally around tree
Remove burlap Secure w/ steel wire
from top of Apply burlap only where strapping
rootball 2 Pieces of rubber hose wood is in contact w/
Construct saucer to 14 gouge galvanized wire tree, to minimize staining
retain trunk.
and twisted 24" Radius.
Construct saucer Mulch 3" thick.
Stake: 2 x Z PT to retain water ` 2 x 4 Stake
24'I Ra
pp r1dius. Backfill mix
Mulch 3" IIII 1=
@fikkter of hole is to be Root Barrier. IIII=_IIII =IIII=IIII
Sidewalk III�011IIII
50%larger than diameter of See plan for location if IIII=IIII =IIII.) _=IIII Diameter of hole is to
IIII=IIII 11=IIII= III=1—iLllFall applicable. IIII=IIII IIII=_IIII =
IIII=II I-IIII= 11=IIII=IIII III= Backfill mix To be installed according - be 50% larger than
IIII_IIII=IIII=_
=IIII=IIII=IIII diameter of root ball
IIII—IIII= =11IIII=IIII to manufacturer's
-IIII=IIII IIII- specification.
GENERAL NOTES:
1. THE CONTRACTOR SHALL PERSONALLY ACQUAINT HIM/HER SELF WITH THE EXISTTN6 SITE CONDITIONS AND THE EXTENT
AND SCOPE OF WORK REQUIRED.
2. THE PLANT LI5T INDICATES THE NAME5, SIZES AND SPACING OF SPECIFIC PLANT MATERIALS. QUANTITIES HAVE BEEN
PROVIDED TO THE CONTRACTOR AS A CONVENIENCE, THE CONTRACTOR 15 RESPONSIBLE FOR HIS/HER OWN QUANTITY
COUNT. IN CASE OF DISCREPANCIES BETWEEN THE DRAWINGS AND PLANT LIST, THE QUANTITIES ON THE DRAWINGS
SHALL PREVAIL.
3. NO SUBSTITUTES ON VARIETIES LISTED WILL BE ALLOWED WITHOUT WRITTEN APPROVAL FROM LANDSCAPE ARCHITECT.
4. PLANTS SHALL BE WATERED AS NECESSARY OR WITHIN 24 HOURS AFTER NOTIFICATION BY THE LANDSCAPE ARCHITECT.
5. THE LOCATION5 OF PLANTS, AS SHOWN IN THESE PLANS, ARE APPROXIMATE. THE FINAL LOCATIONS MAY BE ADJUSTED TO
ACCOMMODATE UNFORESEEN FIELD CONDITIONS. MAJOR ADJUSTMENTS TO THE LAYOUT ARE TO BE APPROVED BY THE
LANDSCAPE ARCHITECT OF RECORD.
6. ALL PLASTIC FABRIC SHALL BE REMOVED FROM PLANT MATERIAL AT TIME OF INSTALLATION.
7. ALL TREES MUST BE STAKED AS SHOWN ON THE LANDSCAPE DETAIL SHEET WITHIN 24 HR5 OF PLANTING. STAKES TO
REMAIN FOR A MINIMUM OF 12 MONTH BUT NO LONGER THAN 18 MONTH. CONTRACTOR RESPONSIBLE FOR MAINTENANCE
AND REMOVAL OF THE STAKES.
8. ALL TREES MUST BE PRUNED AS PER LANDSCAPE ARCHITECT DIRECTION.
9. ALL 50D EDGES SHALL BE TRIMMED AS PER THE LANDSCAPE ARCHITECTS DIRECTION.
10. ALL SHRUBS, TREES, GROUNDCOVER5, SOD AND WILDFLOWER AREAS SHALL HAVE IMPROVED SOIL AS PER PLANTING SOIL
NOTES.
11. DO NOT ALLOW AIR POCKETS TO FROM WHEN BACKFILLING.
12. SOAK PLANTS 17MMEDIAT7=LY WITH WATER FOLLOWING PLANTING.
13. MAINTAIN THE ORIGINAL GRADE OF THE TREE BASE.
14. DO NOT BREAK ROOTBALL.
15. ALL PLANT SHALL BE HARDY UNDER CLIMATIC CONDI7TON5 SIMILAR TO THOSE ON LOCALITY OF THE PROJECT.
16. THE LANDSCAPE CONTRACTOR SHALL WATER, MULCH, WEED, PRUNE„ AND OTHERWISE MAINTAIN ALL PLANTS, INCLUDING
SOD, UNTTL COMPLETION OF THE CONTRACT OR ACCEPTANCE BY THE LANDSCAPE ARCHITECT. SETTLED PLANTS SHALL BE
RESET TO PROPER GRADE, PLANTING SAUCERS RESTORED, AND DEFECTIVE WORK CORRECTED.
17. THE LANDSCAPE CONTRACTOR SHALL AT ALL TIMES KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS
OR DEBRIS CAUSED BY THE CREWS DURING THE PERFORMANCE OF THE WORK. UPON COMPLETION OF THE WORK, THE
CONTRACTOR SHALL PROMPTLY REMOVE ALL WASTE MATERIALS, DEBRIS, UNUSED PLANT MATERIAL, EMPTY PLANT
CONTAINERS AND ALL EQUIPMENT FROM THE PROJECT SITE.
18. UPON COMPLETION OF THE WORK, THE LANDSCAPE CONTRACTOR SHALL NOTIFY THE LANDSCAPE ARCHITECT AND REQUEST
A FINAL INSPECTION. ANY ITEM5 THAT ARE JUDGED INCOMPLETE OR UNACCEPTABLE BY THE LANDSCAPE ARCHITECT OR
REPRESENTATIVE SHALL BE PROMPTLY CORRECTED BY THE LANDSCAPE CONTRACTOR.
19. THE LANDSCAPE CONTRACTOR SHALL GUARANTEE ALL PLANT MATERIAL FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF
FINAL ACCEPTANCE IN WRITING FROM THE LANDSCAPE ARCHITECT. AT THE TIME OF FINAL ACCEPTANCE THE ONE (1) YEAR
PERIOD SHALL COMMENCE. ANY MATERIALS WHICH HAVE DIED DURING THIS PERIOD SHALL SE PROMPTLY REPLACED WITH
SPECIMENS THAT MEET THE MINIMUM REQUIREMENTS CALLED FOR IN THE DRAWINGS. THE LANDSCAPE CONTRACTOR SHALL
NOT BE HELD RESPONSIBLE FOR THE DEATH OR DAMAGE RE5UL LING FROM LIGHTNING, VANDALISM, AUTOMOBILES OR FROM
NEGLIGENCE BY THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR WATERING AND OTHERWISE MAINTAINING PLANTS
DURING THE GUARANTEE PERIOD UNLESS A WRITTEN AGREEMENT WITH THE LANDSCAPE ARCHITECT PROVIDES FOR A
DIFFERENT ARRANGEMENT.
20. ALL LABOR AND MATERIAL FOR SOIL AMENDMENTS AND FERTILIZER THAT I5 REQUIRED TO INSURE THE SUCCESSFUL
ESTABLISHMENT AND SURVIVAL OF THE PROPOSED VEGETATION AS WELL AS ALL C05T FOR THE REMOVAL OF UNSUITABLE
OR EXCESS BACKFILL MATERIAL SHALL BE INCLUDED IN THE CONTRACTORS BID TO PERFORM THE WORK PRESENTED IN
THIS PLAN SET.
21. NO LANDSCAPING ADDED UNDER THIS PROJECT SHALL BE LOCATED SUCH THAT SAID LANDSCAPING OBSCURES MOTORIST'S
VISIBILITY OF ANY EXISTING SIGN(S).
Apply Burlap oAwherPlace
(3) 2 x 4's, equally
wood is in conaround
tree
w/ tree, to miSecure
w/ Steel Wire Strapping
staining trunkof
Rootball
3" Deep Mulch after
in, 24" radius
Construct Saucewatering
to retain wate�
2 x 4 Stake
Backfill
Diamater of Hole is to
be 3x larger than
diamater of root ball
Shrub & Groundcover Planting Detail
Note: All Shrubs And Groundcover Shall Be NT5
Triangular Spaced Along Straight Edges And Will
Be Planted In Parallel Rows Along Curved Edges.
4" Earthen
Edge of Pavement,
Curb or Bedline
Mulch
Planting Soil
Backfill
Scarify Pit Bottom
WA TERINC7
SCHEDULE
APPLICATION SCHEDULE
PALM TREES
20 GAL/APPLICATION/PLANT
LARGE TREES
30 GAL/APPLICATION/PLANT
SMALL TREES
20 GAL/APPLICATION/PLANT
LARGE SHRUBS
10 GAL/APPLICATION/PLANT
SMALL SHRUBS
5 GAL/APPLICATION/PLANT
GROUNDCOVER
5 GAL/APPLICATION/PLANT
APPLICATION AMOUNT
MONTH 1
12 APPLICATIONS
MONTH 2
12 APPLICATIONS
MONTH 3
8 APPLICATIONS
MONTH 4
8 APPLICATIONS
MONTH 5
5 APPLICATIONS
TOTAL:
45 APPLICATIONS
ABBREVIATIONS: C.T.- CLEAR TRUNK
Ht.- HEIGHT
O.C.- ON CENTER
5pr.- SPREAD
NOTE:
,ETAIL TO BE
MPLEMENTED IN
REAS WITH
OOR DRAINAGE AS
PLANTING
UPPLEMENT.
TWO TIMES BALL DIAMETER
TOP OF ROOTBALL TO BE 2"
ABOVE EXISTING GRADE
FILTER CLOTH
SAND - MIN. 12" DEPTH
DRAIN ROCK
PUNCH THROUGH HARD PAN
TREE PITS WITH DRAIN
N.T.S.
Groundcover & Annual Detail
NTS NOTE: Annuals Are To Be Planted As Per
Groundcover Detail Excluding Mulch.
Exist
3" Mulch
""�und all beds for drainage
4" Depth of
Prepared Planting Soil
ai
o
�
a
Ro
Z
3
rn
ti
n
N
Zs
M
J
Z
0
m
E
s
°u
o
(
m
U
°
a<
a
a�
is
m
LD-02
I
PORTION OF LOT 2, BLOCK 1
ST LUCIE GARDENS
CITY OF PORT ST. LUCIE
ZONING:
GU/SEU - GENERAL USE/SPECIAL EXCEPTION
O FUTURE LAND USE:
m i UTILITIES
CURRENT USE:
UTILITY TOWER
1 442.23'
EX. A-11 T T
GRATE EL. 11.89
E INV. EL. 8.94
II
II
II
II
EX. 16" FORCE MAIN
5100, R/W)
----------
EX.A-12
TOP EL. 12.14
N INV. EL. 9.22
5INV. EL. 6.48
E INV. EL. 8.74
W INV. EL. y
-- --- ---- ---- -JI/
----- ---- ---- - - ----
OHE OHE---Q�- OHE OHE OHE OHE OHE Of
❑
15" OAK 24" OAK 20" OAK 320 OAK
� a N 009M'54" W 176.67'
14.0 _ 14.0__
ii----------------------1-------- - - - -
--------------------1---------� �_-- -----� 12.5
I
DRY DETENTION AREA / I
SOT. EL.11.5 (0.05 AC)
TOP EL.14.0 (0.14AC)
I I I I I I
I I
��--L--------------J
F PROP. L
I 1-STORY CBS
DISCOUNT STORE
F GROSS FLOOR AREA = 8,593 S.F. 6 I
W F.F.E. =15.25 N.A.V.D.1988
$ I I
F
I
I I
F I
Lt
---
IL
EX. 6' COW. SIDEWALK
-- --------------- ---------
- ----- ------ -----
-- --------
PROP.
5'x5' UTILITY
EASEMENT
ZONE 1
- 39
Irrigation Specifications
Well
4" Well with submersible pump, as shown located on this sheet
Main Line Qty
Sprays
1,331
Qty
21/2"
GPM
PVC Class 200 Irrigation Main Line
T Flow (GPM) Run Time Gallons
Manufacturer
Type
Pattern
Bubbler
39
1.00
39.00
0:20
780
HunterO or RalnBlyd®
6"
Pop -Up
V Bubbler
8HC
15
0.58
8.70
0:20
174
Hunter® or RainBirdg1
6"
Pop -Up
7' Radius Half Circle (180) Spray Head
8QC
7
0.29
2.03
0:20
41
Hunter® or RainBlyd®
6"
Pop -Up
7' Radius Part Circle (90) Spray Head
8TC
2
0.87
1.74
0:20
35
Hunter® or RainBird®
6"
Pop -Up
7' Radius Part Circle (90) Spray Head
10HC
35
0.98
34.30
0:20
686
Hunter► or RalnBlyd®
6"
Pop -Up
10' Radius Half Circle (180) Spray Head
100C
9
0.49
4.41
0:20
88
Hunter® or RainBird®
6"
Pop -Up
1 V Radius Part Circle (90) Spray Head
10TC
3
1.47
4.41
0:20
88
Hunter® or RainBird®
6"
Pop -Up
IV Radius Part Circle (270) Spray Head
12HC
34
1.26
42.84
0:20
857
Hunter® or RalnBirdO
6"
Pop -Up
12' Radius Half Circle (180) Spray Head
120C
3
0.63
1.89
0:20
38
Hunter® or RainBb%M
6"
Pop -Up
1T Radius Part Circle (90) Spray Head
15HC
28
1.86
52.08
0:20
1042
Hunter® or RainBk%W
6"
Pop -Up
1 V Radius Half Circle (180) Spray Head
15QC
14
0.93
13.09
0:20
260
Hunter® or RainBkft
6"
Pop -Up
16 Radius Part Circle (90) Spray Head
15TC
1
2.79
2.79
0:20
56
Hunter® or RalnBird®
6"
Pop -Up
15' Radius 314 Circle (270) Spray Head
170C
3
1.20
3.60
0:20
72
Hunter® or RainBkW
6"
Pop -Up
17' Radius Part Circle (90) Spray Head
CST
8
1.21
9.68
0:20
194
Hunter® or RainBtrd®
6"
Pop -Up
IV Center Rectangular Spray Head
EST
9
0.61
5.49
0:20
110
Hunter® or RalnBk0
6"
Pop -Up
IV Rectangular Spray Head End Spray
Total
210
225.98
4,520
b4 �
I Average Water Output:
I Run time Method:
F3 Irrigation Main Line:
I
Zone Type and Count
Bubbler.
----------------- Spray (Sod):
Spray (Shrub):
TOTAL
I
II
to
A
i�
❑ N 00'00'00" E 177.24'
_ ____
_ ______ _____________-_____--_____________-_
.Y
I'
v>
F�
I
_
<
----------------------------- --------------------------
A
EX 2" POLY
WATER SERVICE
6
i<
N
-----
r--- --
---- --- ----
-------
--- ---
--- ---
--- --- ---
------------
---
---
- EX 6" WATER MAIN
II
- ,I
- 1 II
1
_
X .V., 'A'..'A'..ulw, II
w
,u„ rw•
I
, n.ww
.u,w
r
I
I
I
I
I
f FM
FM
EX
ASPHALT
PAVEMENT
ri
FI
38 gpm
Full Site In 8h Window
1 1/2" PVC Gass 200
Qty Run Time
1 0:40
2 0:40
3 1:00
6 3:20
Irrigation Zone List
Zone #
GPM
Valve
Type
1
39
2"
Bubbler
2
39
2"
Spray (Sod)
3
38
2"
Spray (Sod)
4
38
2"
Spray (Shrub)
5
36
2"
Spray (Shrub)
6
36
2"
Spray (shrub)
Symbol Denotes 12" Pop -Up
R Symbol Denotes use of a riser
© Pump Station Hoover Pump Prefabricated, Fiberglass enclosed, submersible,
Clock Start Pump Station, MODEL #HSF-5PDV-230/3-M,W,Z.
Power is 230/3 Phase. the water supply is a new 4" Well.
© Controller Controller Is a Rain Bird ESP Modular 6 Station Controller
with a pole mounted MINI CLIK Rain Sensor #502.
1 112" Valve IRRITROL Century 100P Series RCV(Sized per
Plan) In a Canton Jumbo valve box
\I � VaW NIBCO T-113 Brass Gate Valve (Line Size) In a
I\ Canton 1419 Valve Box.
MIL MIL 1 1/2" Main line PVC Class 160
Sub -main PVC Class 160
Schedule 40 Sleeve
2 Spare Wires are to be Installed.
All Wire shall be 18 gauge.
MAINLINE LOCATION, WHEN SHOWN, IS FOR GRAPHIC CLARITY PURPOSES ONLY. ALWAYS INSTALL
INSIDEPROPERTYLINES. LOCATEAT THE BACK OFCURB, FRONTOF WALK BACKOF WALK, OR
ADJACENT 710 OTHER HAR05CAPES TO FACILITATE FUTURE LOCATION AND TO PROTECTFROM
EX. A-9 DAMAGE ENSURE MADE IS INSTALLED ACC7R1%IN6 TO THE IRRIGATION SPECIFICATIONS AN) TOP EL. 12.73 DETAILS'
N rNV. EL. 9.44
5 INV. EL. 9.44
E I.NV_ EL. 8_92 -------- QUANTITIES GIVEN ARE FOR CONTRACTOR CONVENIENCE ONLY. THE ACCURACY 10 NOT GUARANTEED- ALL QUANTITIES
------------------ SHALL BE VERIFIED.
72 HOURS
BEFORE YOU DIG
CALL SUNSHINE
1-800-432-4770
FOR EMERGENCY CONTACT OF
i
m
6FgP, a Scn/s
20 !p 0 m
Surds: i' = 20'
o
ao
d
r
g�
(5
Cn
9
r
RECEI�' D 1UL 16 2015
1E
15' OAK
ZONE 2
1 1/2'1 39
PORTION OF LOT 2, BLOCK 1
BT LUCIE GARDENS
CITY OF PORT ST. LUCIE
ZONING:
GU/SEU - GENERAL USE/SPECIAL EXCEPTION
FUTURE LAND USE:
UTILITIES
CURRENT USE:
UTILITY TOWER
—OHE
Q—OHE
OHE OHE
OHE
--
OHEZ
-- ❑
— — —
— — 24"
OAK 2W OAK
tt
N W001'5V W 176.67'
14.0—_—_—_—_—_—_—_—_—_---
14=0_—_
13.5
���---------------------
---------------------
_------------------------
i2
125—�\\\ 1
--------------------
(�
DRY DETENTION AREA
BOT. EL.11.5 (0.05 AC)
�_—==J l
f
TOP EL. 14.0 (0.14 AC
L 115
10.511
r10.5� 1
I I I I
C III
I I I I
\
��
I
-�----------------
I
' ,
�---i
�' i
i
PROP.
1-STORY CBS
DISCOUNT STORE
GROSS FLOOR AREA = 8,593 S.F. 6
F.F.E. =15.25 N.A.V.D.1988
ell,
I
E
d
I II
I
I I
I I i I IQ
I I
y I I
y I I
I
EX. 6' CONC. SIDEWALK ❑ N 00900100• E 177.24'
------------------------------------ ------
-------------------------
PROP. ------ ------ L I>'' y'> I
5'x5' UTILITY
F
EASEMENT (I
zvlve J o
■» wm = FLE
MINI 38
I
o
Im
rn
,
c
o h----
I
I
m
W
I
�
�
co
i
EX
ASPHALT m
PAVEMENT Z 11 I
0
,y> >� I sFj�v
-=Fi4=-------------------F�4------- E4------ GPM--------'~----_--�4--=� t� FM FM FM M yI
c_T_� __ __ _ =n rrt—�c—rc-r�— T� _7__s_T_�__r_T �\ 1 \> >1 > \I/
yy'y,'yyyyyyyy> yyyyyyyyyyy, c`< < < c <� �� c c c < c c �� ;>y>y>I
< < c t c < c t < x `c `c < `< `< < < c < < < < c c <
>T,,> > > y> y> y,�,,�, >, ; , ; , >, y y y y y y y y y
t� ^�_ . as= t-------- >`��`<� — — — -
-- --- ---- ------ ---
------ -- ---- ---- -- _ _
--- --fir-- -_ -- -zl C -- -- I--
ZSi> 'yp(2 POLY WATER SERVICE ' �> 4 EX. A-9C1> > > TOP EL. 12.73IN INV. EL. 9.44
">Xy) >11 5INV. EL. 9.44<E INV. EL. 8.921r*,+-----------------19`--------------------------- ---- -A------------------ 3'
�Y n,.. EX 6" WATER MAIN 11 .. t .>, d..�
n.. n
'OAK
* Symbol Denotes 12" Pop -Up
R Symbol Denotes use of a riser
© Pump Station Hoover Pump Prefabricated, Fiberglass enclosed, submersible,
Clock Start Pump Station, MODEL #HSF-5PDV-230/3-M,W,Z.
Power is 230/3 Phase. the water supply is a new 4" Well.
© Controller Controller Is a Rain Bird ESP Modular 6 Station Controller
with a pole mounted MINI CLIK Rain Sensor #502.
1 112" Valve IRRITROL Century 100P Series RCV(Sized per
Plan) In a Carson jumbo valve box
Gob Valm NIBCO T-113 Brass Gate Valve (Line Size) in a
Carson 1419 Valve Box.
MIL MIL 1 1/2" Main line PVC Class 160
Sub -main PVC Class 160
Schedule 40 Sleeve
2 Spare wires are to be Installed.
All Wire shall be 18 gauge.
72 HOURS
BEFORE YOU DIG
CALL SUNSHINE
1-800-432-4770
FOR EMERGENCY CONTACT OF
AT&T CALL 1-800-252-1133
MAINLINE LOCATION, WHERE SHOWN, IS FOR GRAPHICCLARITY PURPOSES ONLY. ALWAYS INSTALL
INSIDE PROPERTY LINES. LOCATE AT THE BACK OFCUR9, FRONT OF WALK BACK OF WALK; OR
ADJACENT TO OTHER HARDSCAPES TO FACILITATE FUTURE LOCATION AND TO PROTECT FROM
DAMAGE. ENSUREMAXN INE IS INSTALLED ACCORDING TO THEIRRIGATION SPECIFICATIONS AND
DETAILS.
auANTm E8 GIVEN ARE FOR CONTRACTOR CONVENIENCE ONLY. THE ACCURACY IS NOT GUARANTEED. ALL CiWMES
SHALL BE VERIFIED.
E4
PORTION OF LOT 2, BLOCK 1
ST LUCIE GARDENS \
CITY OF PORT ST. LUCIE S
2:
GU/SEU - GENERAL USE/SPECIAL EXCEPTION
FUTURE LAND USE:
UTIIST❑ *�
CURRENTUSE:
E:
UTILITY TOWER ❑❑
—OHEQOHE OHE OHE OHE OHE 0
24" OAK 205 OAK ❑ ❑ 320 OAK {
a N 00°01'54 W 176.67
14.0 _" ____ 14.0
--------------------- —-------------------------13.5
13.5
— — — — — — — — — — — — — — — — --
12512.5
DRY DETENTION AREA • I I I I BOT. EL.11.5 (0.05 AC)
TOP EL. 14.0 (0.14 AC)
----�--_ I I I L 11.5
I I I 10.5� r 10.5
II I I C II
a
\ —
\� —L------------- C4
• �`���'----------------------' ��' ; ZONE 16 II � � � �
0
JI
jj
F
F
,I
PROP.
1-STORY CBS
DISCOUNT STORE
GROSS FLOOR AREA = 8,593 S.F. S
F.F.E. =15.25 N.A.V.D.1988
I
'I
I
I
Iw �1
r ,I
.II���� ��► !n ull _NONE
------------------------
EASEMENT—
i 4
ZONE 5
11/21 36
N 00'00'00• E177.24_ - ---
{— FM
W
E` N
ASPHALT
PAVE
tt�
�J
_M —v
Q i
INC
U r� r'I
z
<' 11 I'IJ�> �� J �r2 1]
C/)
L VIA
xxy_x> Y > x �i.
.O
FM F
m
w -- -------------------------------------
-------------------------------------------- ------------------------------------------------------
' <{
1 1 1 1
I I
I' '(\ 1
> '
'1<
Sostk: i" = ZO'
EX 20 POLY
WATER SERVICE
n� \<;
I,
�� > y>\>� EX. AA
TOP EL.12.73
t
`<I
N INV. EL. 9.44
D' > >1 5INV. EL. 9.44
_
--- -
___
E INV. EL. 8.92
------------------------ V------------------------ ---------
-----
---j1
IRRIGATION NOTES & SPECIFICATIONS
r
WIRING
BACK FILL
Irrigation design based on the Landscape Design Associates Landscape Plan
dated 12/18/2013. Contractor shall refer to these plans to coordinate sprinkler
and pipe locations.
The system has been designed to conform with the requirements of all
applicable codes. Should any conflict exist, the requirements of the codes shall
prevail. It is the responsibility of the owner/installation contractor to insure the
entire system is installed according to all applicable laws, rules, regulations and
conventions. Irrigation contractor responsible for obtaining all required permits
according to federal, state and local laws.
The scope of work is shown on the plans, notes and details. The Irrigation
Contractor shall be certified as a CERTIFIED IRRIGATION CONTRACTOR by the
Irrigation Association. The certification shall be current and in good standing.
The work specified in this section consists of furnishing all components
necessary for the installation, testing, and delivery of a complete, fully
functional automatic landscape irrigation system that completely complies with
the irrigation plans, specifications, notes, details and all applicable laws,
regulations, codes and ordinances. This work shall include, but not be limited
to, the providing of all required material (pipe, valves, fittings, controllers, wire,
primer, glue, etc.), layout, protection to the public, excavation, assembly,
installation, back filling, compacting, repair of road surfaces, controller and low
voltage feeds to valves, cleanup, maintenance, guarantee and as —built plans.
All irrigated areas shall provide 100% head —to —head coverage from a fully
automatic irrigation system with a rain sensor. The rain sensor shall be
installed to prevent activation of rain sensor by adjacent heads. All watering
procedures shall conform to local codes, as well as this project's regional
Water Management District restrictions and regulations. Zones are prioritized
first by public safety and then by hydraulic concerns. This sequencing will be a
mandatory punch list item. These plans have been designed to satisfy/exceed
the Florida Building Code (FBC) Appendix F and the Florida Irrigation Society
Standards and Specifications for Turf and Landscape Irrigation Systems, fourth
edition.
Contractor shall verify all underground utilities 72 hours prior to commencement
of work.
It is the responsibility of the irrigation contractor to
familiarize themselves with
all grade differences, location of walls, retaining walls, structures and utilities.
Do not willfully install the sprinkler system as shown
on the drawings when it is
obvious in the field that unknown obstruction, grade
differences or differences
in the area dimensions exist that might not have been
considered in the
engineering. Such obstructions, or differences, should
be brought to the
attention of the owner' authorized representative. In
the event this notification
is not performed, the irrigation contractor shall assume
full responsibility for
any revisions necessary.
Irrigation contractor shall repair or replace all items
damaged by their work.
Irrigation contractor shall coordinate their work with
other contractors for the
location and installation of pipe sleeves and laterals
through walls, under
roadways and paving, etc.
The contractor shall take immediate steps to repair,
replace, or restore all
services to any utilities which are disrupted due to their
operations. All costs
involved in disruption of service and repairs due to negligence on the part of
the contractor shall be their responsibility.
POINT OF CONNECTION (P.O.C.)
The P.O.C. is a new Hoover Pumping Systems submersible pump station model
#HSF-7.5CS-230/3—A,E-20,M,W and a new 6" well. The P.O.C. must be
capable of delivering a minimum of 65 GPM at 180 TDH.
Contractor to verify these minimum conditions can be met prior to the
beginning of installation. If the conditions can not be met, the contractor must
notify the designer prior to proceeding with the work. If the contractor does
not do so, the contractor proceeds at their own risk and becomes responsible
for any future work required to make the system perform as required.
1r.1091»
Pipe locations shown on the plan are schematic and shall be adjusted in the
field. When laying out mainlines place a maximum of 18" away from either the
back of curb, front of walk, back of walk, or other hardscape to allow for ease
in locating and protection from physical damage. Install all lateral pipe near
edges of pavement or against buildings whenever possible to allow space for
plant root balls. Always install piping inside project properties boundary.
All pipes are to always be placed in planting beds. If it is necessary to have
piping under hardscapes, such as roads, walks, and patios, the pipes must be
sleeved using Class 200 PVC with the sleeve diameter being twice the size of
the pipe it is carrying with a minimum sleeve size of 2".
Pipe sizes shall conform to those shown on the drawings. No substitutions of
smaller pipe sizes shall be permitted, but substitutions of larger sizes may be
approved. All damaged and rejected pipe shall be removed from the site at the
time of said rejection.
Mainline shall be 2-1/2" Class 200 gasketed '0' ring PVC with Sch 40 gasketed
PVC fittings.
Contractor to ensure all mainline piping is properly restrained using mechanical
joint fittings, restraining collars, threaded rods, thrust blocks, etc., as and
where required. Contractor shall refer to pipe manufacturers recommended
installation practices for further direction.
PVC pipe joint compound and primer: slow —drying, heavy duty cement and
tinted (purple) primer that is compatible with the cement. The PVC cement
shall be Weld —On 2711 grey and the primer shall be Weld —On P70 purple
primer, or approved equals.
ELECTRICAL POWER SUPPLY
Electrical supply for pumps and controllers to be provided by irrigation
contractor. Contractor to coordinate with local utilities for the installation of,
and connection to, site available power supply's for required electrical
components as set forth in the irrigation plans.
All electrical to comply with the National Electrical Code and any, and all, other
applicable electrical codes, laws and regulations. A licensed electrician shall
perform all electrical hook—ups. Power for the controller shall be 120 volt, 20
amp.
Irrigation control wire shall be thermoplastic solid copper, single conductor, low
voltage irrigation controller wire; suitable for direct burial and continuous
operation at rated voltages.
Tape and bundle control wires every 10' and run alongside the mainline. At all
turns in direction make a 2' coil of wire. At all valve boxes coil wire around a
3/4" piece of PVC pipe to make a coil using 30 linear inches of wire. Make
electrical connections with 3M—DBY,DBR connectors.
Number all wires, using an electrical book of numbers, according to the plans.
Number wires in all valve boxes, junction boxes and at the controller.
Wire sized, numbered and colored as follows:
#14 white for common
#14 spare black common
#14 red for hot wires
#14 spare yellow hot wire
Spare wires
— Run spare wires into every RCV valve box. Install a minimum of 2
common and 4 hot wires, in all directions, to every RCV connected to its
respective controller.
Controller grounding — Contractor to utilize 4"X8'X5/8" copper grounding plates,
5/8"X10' copper clad grounding rods, 'One Strike' CAD wells at all connection
points, #6 bare copper wire, and earth contact material. Install these and other
required components as outlined in the detail. Contractor to verify that the
earth to ground resistance does not exceed 10 ohms. Contractor shall provide
a written certification, on a licensed electrical contractors letter head, showing
the date of the test, controller location, and test results. Each controller shall
be so grounded and tested.
AI Tilsjl
Lay out irrigation system mainlines and lateral lines. Make the necessary
adjustments as required to take into account all site obstructions and
limitations prior to excavating trenches.
Stake all sprinkler head locations. Adjust location and make the necessary
modifications to nozzle types, etc. required to insure 100% head to head
coverage. Refer to the Edge of Pavement Detail on the Irrigation Detail Sheet.
Spray heads shall be installed 4" from sidewalks or curbed roadways and 12"
from uncurbed roadways and building foundations. Rotors shall be installed 4"
from sidewalks or curbed roadways, 12" from building foundations, and 36" from
uncurbed roadways.
Shrub heads shall be installed on 3/4" Sch 40 PVC risers. The risers shall be
set at a minimum of 18" off sidewalks, roadway curbing, building foundations,
and/or any other hardscaped areas. Shrub heads shall be installed to a
standard height of 4" below maintained height of plants and shall be installed
within planted masses to be less visible and offer protection. Paint all shrub
risers with flat black or forest green paint, unless irrigation system will be
installed from a reuse water system with purple PVC risers.
Locate valves prior to excavation. Insure that their location provides for easy
access and that there is no interference with physical structures, plants, trees,
poles, etc. Valve boxes must be placed a minimum of 12" and a maximum of
15" from the edge of pavement, curbs, etc. and the top of the box must be
2" above finish grade. No valve boxes shall be installed in turf areas without
approval by the irrigation designer — only in shrub beds. Never install in sport
field areas.
VALVES
Sequence all valves so that the farthest valve from the P.O.C. operates first
and the closest to the P.O.C. operates last. The closest valve to the P.O.C.
should be the last valve in the programmed sequence.
Adjust the flow control on each RCV to ensure shut off in 10 seconds after
deactivation by the irrigation controller.
Using 3" high number stencils paint the valve number in white on the lid of
each valve box.
EQUIPMENT
Bubblers shall be installed using Sch 80 nipples and shall be placed at the
base of trees for low level watering.
All pop—up heads and shrub risers shall be pressure compensating. All pop—up
heads shall be mounted on flex —type swing joints.
All sprinkler equipment not otherwise detailed or specified shall be installed as
per manufacturers recommendations and specifications, and according to local
and state laws.
TRENCHING
Excavate straight and vertical trenches with smooth, flat or sloping bottoms.
Trench width and depth should be sufficient to allow for the proper vertical and
horizontal separation between piping as shown in the pipe installation detail on
the detail sheet.
Protect existing landscaped areas. Remove and replant any damaged plant
material upon job completion. The replacement material shall be of the same
genus and species, and of the size of the material it is replacing. The final
determination as to what needs to be replaced and the acceptability of the
I replacement material shall be solely up to the owner or owner's representative.
INSTALLATION
Cut all pipe square and deburr. Clean pipe and fittings of foreign material; then
apply a small amount of primer while ensuring that any excess is wiped off
immediately. Primer should not puddle or drip from pipe or fittings. Next apply
a thin coat of PVC cement; first apply a thin layer to the pipe, next a thin
layer inside the fitting, and finally another very thin layer on the pipe. Insert
the pipe into the fitting. Insure that the pipe is inserted to the bottom of the
fitting, then turn the pipe a 1/4 turn and hold for 10 seconds. Make sure that
the pipe doesn't recede from the fitting. If the pipe isn't at the bottom of the
fitting upon completion, the glue joint is unacceptable and must be discarded.
Pipes must cure a minimum of 30 minutes prior to handling and placing into
trenches. A longer curing time may be required; refer to the manufacturer's
specifications. The pipe must cure a minimum of 24 hours prior to filling with
water.
The back fill 6" below and 5" above all piping shall be of clean sand and
anything beyond that in the trench can be of native material but nothing larger
than 2" in diameter.
Main Fine pipe depth measured to the top of pipe shall be 36" minimum,
including at vehicular crossings.
Lateral line depths measured to top of pipe shall be:
18" minimum for 3/4"-3" PVC with a 30" minimum at vehicular
crossings;
24" minimum for 4" PVC and above with a 30" minimum at vehicular
crossings.
Contractor shall backfill all piping, both mainline and laterals, prior to
performaning any pressure tests. The pipe shall be backfilled with the exception
of 2' on each side of every joint (bell fittings, 90's, tees, 45's, etc.). These
joints shall not be backfilled until all piping has satisfactorily passed its
appropriate pressure test as outlined below.
yllIJIlwam[f
Prior to the placement of heads, flush all lines for a minimum of 10 minutes
or until lines are completely clean of debris, whichever is longer.
Use screens in heads and adjust heads for proper COVERage avoiding excess
water on walls, walks and paving
TESTING
Remove all remote control valves and cap using a threaded cap. Fill mainline
with water and pressurize the system to 125 PSI.. Monitor the system pressure
at two gauge locations; the gauge locations must be at opposite ends of the
mainline. With the some respective pressures, monitor the gauges for two
hours. There can be no loss in pressure at either gauge for solvent —welded
pipe. Gasketed piping shall lose no more water than allowed per the Florida
State Building Code, Volume II Plumbing, Part VI, Appendix 'F'. Refer to this
section for the formula to be used to calculate the maximum allowable water
loss during the testing time. If these parameters are exceeded, locate the
problem; repair it; wait 24 hours and retry the test. This procedure must be
followed until the mainline passes the test.
The lateral lines must be filled and visually checked for leaks. Any leaks
detected must be repaired. No pressure test of the lateral lines is required.
Once the mainline and lateral lines have passed their respective tests, and the
system is completely operational, a coverage test and demonstration of the
system is required. The irrigation contractor must demonstrate to the owner, or
his/her representative that proper coverage is obtained and that the system
works automatically from the controller. This demonstration requires that each
zone is turned on, in the proper sequence as shown on the plans, from the
controller. Each zone will be inspected for proper coverage and function. The
determination of proper coverage and function is at the sole discretion of the
owner or owner's representative.
Operational Testing — Upon completion of back filling, finish grading and
contouring, test the entire system for proper operation; including electrically
actuating the remote control valves. Run each zone until water begins to
puddle or run off. This will allow you to determine the number of irrigation
start times necessary to meet the weekly evapotranspiration requirements of
the planting material in each zone. In sandy soils no puddling will occur,
instead; calculate the required run times.
SUBMITTALS
The contractor must submit for approval, prior to installation, copies of the
manufacturer's cut sheets/specifications for all components to be used in the
irrigation system.
After project completion, and as a condition of final acceptance, the irrigation
contractor shall provide the owner with a high quality, accurate, and legible set
of as —built drawings. The as—builts must identify all remote control valves,
gate valves, ball valves, splice boxes, controllers, mainline, sleeving, and low
voltage wiring. Each of these items is to be located using a submeter GPS
system. The irrigation contractor must also provide accurate, informative, and
easy to follow and understand operation and maintenance manuals for all
components of the irrigation system.
Controller charts — Upon completion of "as —built" prepare controller charts;
one per controller. Indicate on each chart the area controlled by a remote
control valve (using a different color for each zone). This chart shall be
reduced to a size that will fit inside of the controller door. The reduction shall
be hermetically sealed inside two 2ml pieces of clear plastic.
Furnish extra materials described below that match prod
ucts ucts installed and that
are packaged with protective COVERing for storage and identified with labels
describing contents. Include tools to service these products.
1. Sprinkler Units: Five of each unit for each type and size installed, but
no fewer than two units.
2. Emitter Units: Five of each unit for each type and size installed, but no
fewer than two units.
3. Drip Tube Units: Five of each unit for each type and size installed, but
no fewer than two units.
FINAL ACCEPTANCE
Final acceptance of the irrigation system will be given after the following
documents and conditions have been completed and approved. Final payment
will not be released until these conditions are satisfied.
1. Final walk—thru and correction of all punch list items.
2. Completion and acceptance of 'as —built' drawings.
3. Acceptance of required controller charts and placement inside of
controllers.
4. Turn over of all required parts and tools as outlined in the project
specifications.
GUARANTEE: The irrigation systems shall be guaranteed for a minimum of one
calendar year from the time of final acceptance.
MINIMUM RECOMMENDED
IRRIGATION MAINTENANCE PROCEDURES
1. Every irrigation zone should be checked monthly and written reports
generated describing the date(s) each zone was inspected, problems identified,
date problems repaired, and a list of materials used in the repair. At minimum,
these inspections should include the following tasks:
A. Turn on each zone from the controller to verify automatic operation.
B. Check schedules to ensure they are appropriate for the season, plant
and soil type, and irrigation method. Consult an I.A. certified auditor for
methods used in determining proper irrigation scheduling requirements.
C. Check remote control valve to ensure proper operation.
D. Check setting on pressure regulator to verify proper setting, if present.
E. Check flow control and adjust as needed; ensure valve closure within
10-15 seconds after deactivation by controller.
F. Check for leaks — mainline, lateral lines, valves, heads, etc.
G. Check all heads as follows:
1. Proper set height (top of sprinkler is 1" below mow height)
2. Verify head pop—up height — 6" in turf, 12" in ground cover, and
pop—up on riser in shrub beds.
3. Check wiper seal for leaks — if leaking, clean head and re —inspect.
If still leaking, replace head with the appropriate head with
pressure regulator and built—in check valve.
4. All nozzles checked for proper pattern, clogging, leaks, correct make
& model, etc. — replace as needed
5. Check for proper alignment — perfectly vertical; coverage area is
correct; minimize overspray onto hardscapes.
6. Riser height raised/lowered to accommodate plant growth patterns
and ensure proper coverage.
7. Verify the pop—up riser retracts after operation. If not, repair/replace
as needed.
2. Check controller/C.C.U. grounds for resistance (10 ohms or less) once per
year. Submit written reports.
3. Check rain shut—off device monthly to ensure it functions properly.
4. Inspect all filters monthly and clean/repair/replace as needed.
5. Inspect backflow devices by utilizing a properly licensed backflow inspector.
This should be done annually, at minimum.
6. Inspect all valve boxes to ensure they are in good condition, lids are in
place and locked.
7. Check pump stations for proper operation, pressures, filtration, settings, etc.
— refer to pump station operations manual.
8. Check and clean intake screens on all suction lines quarterly, at minimum.
Clean and/or repair, as needed.
9. Winterize, if applicable, as weather in your area dictates. Follow manufacturer
recommendations and blow out all lines and equipment using compressed air.
Perform seasonal startup of system as per manufacturer recommendations.
10. Conduct additional inspections, maintenance tasks, etc. that are particular
for your site.
Few F COPY
:iNO a
�
CID
o
IR-03
PUBLIX VERANO
SPECIFICATIONS
SINGLE SUBMERSIBLE PUMP SYSTEM
FIBERGLASS ENCLOSED CLOCK START
PURPOSE:
To provide a complete prefabricated skid mounted fiberglass enclosed
submersible clock start pump system from a sole source company, herein after
referred to as the 'manufacturer', whose primary business is the manufacture
of prefabricated pump systems. The manufacturer will manufacture, install and
warrant the system to meet all specified operating requirements described
below and in the system detail. The system shall be a Model
HSF-5PDV-230/3—M,W,Z as manufactured by Hoover Pumping Systems of
Pompano Beach, Florida USA 954-971-7350 specified below and shown on the
plan details. This specification describes the general components and minimal
operating requirements and shall not be construed as a manufacturing guide or
complete list of required system components and appurtenances.
The contractor shall submit seven (7) complete copies of the shop drawings to
the designer for approval, prior to system order placement. The submittal shall
contain cut sheets for all system components. To be considered an equal, 12
days prior to bid opening the contractor must submit the following:
manufacturer brochure showing prefabricated pump systems manufacturing is
the primary business of the manufacturer or division proposed to manufacture
the system, written specifications, dimensioned layout detail, electrical
schematic, product sheets for all main components, Underwriters Laboratories,
Inc. 508A Industrial Control Panels' and QCZJ 'Packaged Pumping Systems'
manufacturer's certification numbers, list of 6 projects with similar operating
systems with current name and phone number of person responsible for system
operation, manufacturer's insurance certificate for general Liability showing
minimum COVERage of $1 million, and written certification from the
manufacturer stating the proposed system meets all requirements described in
this specification, the detail and the bid documents.
If the data submitted is determined to be an equal by the designer the bidder
will be notified prior to the bid date.
FIBERGLASS ENCLOSURE:
The pump station shall be protected by a fiberglass enclosure, 3'-6' x 14'
through 25 Hp and 4' x 8' for 30 Hp and larger with chemical grade ultraviolet
resistant open mold resin with exterior finish that is uniform in color and
texture, reinforced with fiberglass and stiffeners for rigidity. The enclosure shall
open clear of the station for ease of service and have a stainless steel hinge
and self —latching lockable handle. The enclosure shall be of dimensions
adequate to contain the entire pump station including the discharge header and
controls.
MOUNTING ASSEMBLY:
The pump station
shall
be mounted on a prefabricated aluminum
skid 3'-6' x
4' through 25 Hp
and
galvanized steel structural skid 4' x 8' for
30 hp and
larger. Aluminum
pedestals shall be provided to mount the control panel
assemblies. The entire
station shall be installed on a reinforced
concrete slab
sized as noted on
the
system detail.
PUMP AND MOTOR:
The pump shall be a submersible type coupled to a submersible motor rated at
5 HP, 230 volts, 3 phase, 60 Hz. The pump system shall be designed for
operation at 3450 RPM.
Submersible Pump 4': The pump will have acetal impellers with polycarbonate
diffusers, stainless steel pump shell, shaft, and coupling, with polypropylene
intake screen.
The motor shall be a submersible type designed for continuous underwater
operation and with a combination of a maximum water temperature and
minimum velocity past the motor, such that the service factor shall be 1.15
minimum. The motor shall be of the water —filled type and fitted with a
segmented plate type thrust bearing. A stainless steel cable guard for the
entire bowl length shall protect the motor leads. The motor rating shall be
selected so that the load at design is not greater than the name plate rating
at 1.0 service factor and at no point on the curve shall the load exceed the
name plate rating plus 10 percent.
The power cable shall be sized such that the voltage drop will not exceed three
percent at the motor rated full load current and voltage. Cables shall be
designed specifically for submersible pump service and shall consist of either
individually insulated conductors or individual conductors insulated and the whole
COVERed with an outer jacket.
PUMP STATION PERFORMANCE:
The required pump performance with a maximum of 30 ft. of suction lift is as
follows:
a) discharge pressure of 60 psi, b) maximum required flow of 50 GPM at 195
TDH, and c) minimum required flow of 25 GPM.
IRRIGATION PUMP CONTROL PANEL:
The control panel assembly shall be Underwriters Laboratories listed in
accordance with section 508A for 'enclosed industrial control panels.' All control
devices and electronic auto —sensory circuitry shall be housed in a
self—contained weather —resistant NEMA 4 or 4X control cabinet. An electrical
schematic shall be permanently mounted inside the cabinet. The control
cabinet shall contain the following protection and control equipment:
Operation
The station operates as a clock start, clock retirement system. System
features include Low Pressure and No Flow protection. The system is equipped
with tow Pressure" and 'No Flow" indicator lights, and a 'Hand—Off/Reset—Auto'
(H—O—A) selector switch. The self —diagnostic control panel assembly includes
LED status indicator lights for power failure, no flow, low pressure, and pump
run. Pump clock start relay and auxiliary contacts are also provided.
Clock Start
The pump starts when the irrigation controller (clock) begins a watering
sequence.
Clock Retirement
The pump shuts off when the clock completes a watering sequence.
Low Pressure Protection
If the pressure at the pump discharge falls below 20 PSI for 45 seconds during
pump operation, the pump will shut off and the tow Pressure" light will turn
on. The system will remain off until manually reset with the H—O—A selector
switch.
No Flow Protection
If no flow is
detected
for 60 seconds during pump
operation,
the pump will
shut off and
the 'No
Flow' light will turn on. The
pump will
remain off for 12
minutes and
then will
restart. The 'No Flow' light
will remain
on until manually
reset with the
H—O—A selector switch to notify the irrigation
maintenance
personnel of
potential
field valve failure.
Hand — Off / Reset — Auto Switch
The station is equipped with an H—O—A selector switch, which operates as
follows:
Position Function
---------- --- ------------------------- -----
Hand — Manual pump start. This position overrides all protective features
and start controls.
Off / Reset— Pump will not run. This position resets all alarms.
Auto — Pump will start automatically. In this position, all start controls
and protective features are active.
Protection Equipment
— Front operated main power disconnect
— Time delayed motor starter fuses for motor short circuit protection
— Full voltage class 10 IEC motor starter
— Metal oxide varistors (MOV) for transient voltage suppression per phase
— Fused control circuitry with blown fuse lighted indicator for each circuit
DISCHARGE PIPE MANIFOLD:
The pipe discharge manifold shall be constructed of galvanized steel pipe with
galvanized roll groove fittings. A flow —switch, pressure gauge and hosebib will
be provided on the station discharge. A wafer type butterfly valve or bronze
ballvalve will be provided at pump station discharge.
AUTOMATIC CONTROL VALVE:
The automatic control valve shall be 230 psi working pressure, single —seated,
hydraulically operated, diaphragm —actuated, pilot —controlled globe or angle
pattern drip tight valve incorporating the following features:
— Pressure reducing pilot
— Glycerin filled pressure gauges up and downstream of the valve
— Large capacity disk filter on pilot control tubing
— 220 psi polyethylene control tubing with prest—o—lock fittings
— Ductile iron body and bonnet with polymer coating
— 316 Stainless steel nuts, bolts, washers, shaft and spring
— Rubber diaphragm
— Stainless steel seat
— Grooved or flanged ends
FLOWMETER:
The flowmeter shall provide total and rate display with plus or minus 2%
accuracy within its rated flow range at 14 to 228 psi. Reed switch provides
pulse output. Body is constructed of cast iron with baked powder coating.
A normally open continuous duty solenoid shall be mounted on the meter and
wired to the Hoover Flowguard controls.
PUMP DISCHARGE:
The minimum pump discharge size shall be 2' diameter or larger as required
for a maximum of 15 feet per second velocity flow. The pipe shall be schedule
40 galvanized steel with galvanized roll groove or threaded fittings. Each
discharge shall have a bronze poppet check valve for lines smaller than 3' and
cast iron roll groove swing check valve for larger sizes located as shown on
the system detail.
Well Source: Each pump will be placed in a separate well.. The pump/motor
assembly shall be placed directly in the well unless a flow inducer is required
for adequate water velocity across the motor. The discharge pipe and
submersible cable shall exit the well head through a well seal with a junction
box as shown in the system detail.
IRRIGATION CONTROLLER:
A Rain Bird model ESP —Modular 20 station irrigation controller and rain sensor
shall be mounted on the pump system. The controller shall be powered from a
fuse block in the pump system control panel. The controller shall activate the
pump via a relay in the control panel.
WARRANTIES:
The manufacturer of the pumping station shall warrant all components for a
period of one (1) year from date of manufacture.
PN #9338
NOTE: DISCHARGE PIPES & HEADER TO IRRIGATION MAIN SHALL BE SCHED
40 GALVANIZED STEEL PIPE WITH GALV. ROLL GROOVE FITTINGS. PUMP DROP
PIPE SHALL BE HDPE HEAT FUSED. SET PUMP 60' ON 2" PIPE.
INSTALL MOTOR CABLE SPLICE BETWEEN MOTOR AND CONTROL PANEL IN NEMA
4X JUNCTION BOX ADJACENT TO WELL IN ACCORDANCE WITH ELECTRICAL CODES.
WELL DRILLER SHALL NOTIFY THE PUMP SYSTEM MANUFACTURER IN WRITING WITHIN
24 HOURS OF DEVELOPING THE WELL IF THE WELL PUMPING LEVEL IS GREATER
THAN 45' BELOW FINISHED GRADE AFTER 8 HOURS OF CONTINUOUS PUMPING AT
150% OF THE DESIGN FLOW BELOW.
PROVIDE MINIMUM OF 4' CLEARANCE ON ALL SIDES OF PUMP SYSTEM
* OPTIONAL FEATURES ARE INCLUDED IF MARKED WITH AN "X"
__PRESSURE CONTROL VALVE
X IRRIGATION CONTROLLER RAIN BIRD ESPLXME 20 STATIONS, WITH RAIN SENSOR ON 8' POLE
_-PRESSURE TANKS FOR PRESSURE DEMAND SYSTEM
NOTE: DISCHARGE PIPES & HEADER TO IRRIGATION MAIN SHALL BE SCHED
40 GALVANIZED STEEL PIPE WITH GALV. ROLL GROOVE FITTINGS, PUMP DROP
PIPE SHALL BE HDPE HEAT FUSED. SET PUMP 60' ON 2" PIPE.
INSTALL MOTOR CABLE SPLICE BETWEEN MOTOR AND CONTROL PANEL IN NEMA
4X JUNCTION BOX ADJACENT TO WELL IN ACCORDANCE WITH ELECTRICAL CODES.
WELL DRILLER SHALL NOTIFY THE PUMP SYSTEM MANUFACTURER IN WRITING WITHIN
24 HOURS OF DEVELOPING THE WELL IF THE WELL PUMPING LEVEL IS GREATER
THAN 40' BELOW FINISHED GRADE AFTER 8 HOURS OF CONTINUOUS PUMPING AT
125% OF THE DESIGN FLOW BELOW.
PROVIDE MINIMUM OF 4' CLEARANCE ON ALL SIDES OF PUMP SYSTEM
17
11
10
15
16
Me
me
PLAN VIEW NTS
PUMP PERFORMANCE
50 GPM © 195 TDH
SAFETY FEATURES:
PRESSURE DEMAND:
-TRANSIENT SURGE
-NO FLOW
MAINTAIN 3.5' CLEARANCE IN FRONT OF CONTROL
PANEL AND 4' ALL SIDES OF PUMP SYSTEM.
3' X 3' FIBERGLASS REINFORCED ENCLOSURE
FOREST GREEN GELCOAT FINISH
2
REINFORCED CONCRETE PAD (4" THICK)
3
N/A
I 4
WELL SEAL
5
D 6
WELL, JUNCTION BOX & DISCHARGE PIPE
SUBMERSIBLE PUMP MOTOR ASSEMBLY 5 HP
(NOT SHOWN)
7
CHECK VALVE
8
GALV. STEEL DISCHARGE
9
VARIABLE FREQUENCY DRIVE
10
N/A
11
PRESSURE TRANSDUCER
12
ISOLATION VALVE
13
DISCHARGE ISOLATION VALVE
14
IRRIGATION MAIN
15
IRRIGATION CONTROLLER POWER SUPPLY
AND PUMP START CIRCUIT
16
RAIN SENSOR
17
CONTROL PANEL ASSEMBLY UL LISTED
MAINTAIN 42" CLEARANCE
18
N/A
19
LOCKABLE HASP
IVI 1114 1 IVI V IVI 1)V IP11V1 L I L.ID
WELL CASING REQUIRED
HOOVER PUMPING MODEL: HSF-5PDV-230/3-M,W,Z
Pompano Beach, Florida, Tel: 954-971-7350
I � "W" ."." 1 01 a'1
FILE PN13113.DWG 07/14
co
�
�
o
Sri
z
co
tco
al�l��ls
■
NOTE:
REFER TO PRODUCT LITERATURE FOR
ADDITIONAL INSTALLATION AND ADJUSTMENT
INFORMATION.
O IRRITROL CENTURY 100P
SERIES ELECTRIC RCV
(SIZE PER PLANS)
© FINISH GRADE
O CARSON JUMBO VALVE
BOX W/ BOLT DOWN LID
® 6" PVC SCH 80 NIPPLE
O 3M WATERPROOF WIRE
CONNECTORS
© PVC LATERAL LINE (SIZE
AND TYPE AS PER
LEGEND)
Q7 COMMON RED BRICK (4
REQUIRED)
Q PEA GRAVEL — 12" DEEP
Q PVC SCH 80 NIPPLE
(SIZE AS REQUIRED)
® COMMON AND CONTROL
WIRES TO CONTROLLER
LOCATION.
© PRESSURE MAIN LINE
PIPING WITH MAIN LINE
FITTING (DEPTH, SIZE
AND TYPE AS REQUIRED)
B) IRRITROL RCV
Oj
LATERAL PIPE
O
MAIN LINE
O
CONTROLLER WIRE
®
MULCH OR TURF
O
CURB
©
STREET
NOTES:
BACKFILL MINIMUM DEPTHS:
1. MAIN LINE — 36"
2. LATERAL PIPE — 18"
L MAINLINE AND LATERAL PIPING
(D
POP—UP SPRAY SPRINKLER:
RAIN BIRD 1804—SAM W/PA-80
ADAPTER W/1404 BUBBLER
Q
1/2—INCH MALE NPT X .490 INCH
BARB ELBOW: RAIN BIRD MODEL
SBE-050
O
PVC LATERAL PIPE
®
SWING PIPE, 12—INCH LENGTH:
RAIN BIRD MODEL SP-100
O
PVC SCH 40 TEE OR ELL
©
FINISH GRADE/TOP OF MULCH
O
PLANT MATERIAL
UO RAIN BIRD 1804-SAM POP-UP WITH
1404 BUBBLER
1
t t
36" TYP.
ROADWAY EDGE WITHOUT CURBING
O O
4" TIP.
ROADWAY EDGE WITH CURBING OR SIDEWALK EDGE
3
O O 12" TYP.
ROADWAY EDGE WITHOUT CURBING
4
O O 12" TYP.
BUILDING FOUNDATION
T
LOCATION
O ROTOR HEAD TYPICAL
O SPRAY OR ROTOR
HEAD TYPICAL
O SPRAY HEAD TYPICAL
® SPRAY OR ROTOR
HEAD TYPICAL
TOP VEW
5 8
all
a 7— 3' MIN 8
I--12' 10' — �� i-
8 DO NOT INSTALL ANY OTHER WIRES OR CABLE
WITHIN THE SPHERE OF INFLUENCE
SIDE VIEW
UK CGWW VKUblUNG, WH[UHEVEK IS DEEPER
(D
CONTROLLER
O
GROUND PLATE (4" X 96" X .0625")
O
CONCRETE PAD
©
EARTH CONTACT MATERIAL
Q
PVC SWEEP ELL (1 1/2" OR LARGER)
O
GROUND ROD (5/8" X 10')
®
#6 AWG SOLID BARE COPPER WIRES.
O
ELECTRODE SPHERE OF INFLUENCE
BOUNDARIES
C) GROUNDING DETAIL
SECTION VIEW
MAINLINE, LATERAL, MAINLINE LATERAL WIRING IN
AND WIRING IN PIPE PIPE CONDUIT
THE SAME TRENCH
PLAN V1EW
WIRE W/O CONDUIT
RUN WIRING BENEATH ALL TIE A 24—INCH LOOP IN
AND BESIDE MAINLINE. PVC PIPING ALL WIRING AT CHANGES
TAPE AND BUNDLE AT TO BE SNAKED IN OF DIRECTION OF 30'
10—FOOT INTERVALS. TRENCH AS SHOWN. OR GREATER. UNTIE
AFTER ALL CONNECTIONS
HAVE BEEN MADE.
1. SLEEVE BELOW ALL HRDSCAPE ELEMENTS WITH CL 200 PVC TWICE THE
DIAMETER OF THE PIPE OR WIRE BUNDLE WITHIN — MINIMUM OF 2"
2. FOR PIPE AND WIRE BURIAL DEPTHS SEE SPECIFICATIONS.
L) PIPE AND WIRE TRENCHING
(D
POP—UP SPRAY SPRINKLER:
RAIN BIRD 1806 SAM—PRS
POP—UP WITH RAIN BIRD MPR
NOZZLE
O
1/2—INCH MALE NPT X .490 INCH
BARB ELBOW: RAIN BIRD MODEL
SBE-050
O
PVC LATERAL PIPE
®
SWING PIPE, 12—INCH LENGTH:
RAIN BIRD MODEL SP-100
O
PVC SCH 40 TEE OR ELL
©
FINISH GRADE/TOP OF MULCH
Oj
PLANT MATERIAL
R) RAIN BIRD 1806 SAM-PRS SPRAY
BUILDING WALL OR
POP—UP ON RISER TYP.
I I
>>>> b>>>>>—i
IRRIGATION LATERAL LINE
SIDEWALK OR PAVEMENT EDGE—TYP.
POP—UP ON RISER TYP. POP—UP ON RISER TYP.
NOTE: THE DESIGN INTENT IS FOR THE RISERS TO BE INSIDE OF THE PLANT MASS TO OBSCURE IT FROM MEW
AND OFFER PROTECTION. THE TOP OF THE SPRAY HEAD SHOULD BE 4" BELOW THE MAINTAINED HEIGHT OF THE
SHRUBBERY. THE SPRAY HEAD ON RISER SHOULD BE 'INSET' INTO THE SHRUBS 6". THIS 'INSET' DISTANCE IS THE
CONTROLLING FACTOR. THEREFORE THE 18" MINIMUM DISTANCE FROM SIDEWALK/PAVEMENT IS APPROXIMATE ONLY.
T POP-UP HEAD ON RISER
LOCATION DETAIL-B
C
45' ELL
WYE
L
( SPLICE BOX WITH COVER: 12—INCH
SIZE
O FINISH GRADE/TOP OF MULCH
Q3 BRICK (1 OF 4)
® 3.0—INCH MINIMUM DEPTH OF
3/4—INCH WASHED GRAVEL
O DIRECT BURIAL LOW VOLTAGE CONTROL
WIRE (TYP.)
© 3M—DBY WATER PROOF CONNECTOR
(TYP.)
WIRE SPLICE
/
_e
45' ELL
O UNDISTURBED SOIL
(TYPICAL)
O CONCRETE THRUST BLOCK
(TYPICAL)
Q3 PIPE (TYPICAL)
® REBAR BENT AROUND
FTFTING (TYPICAL
O FITTING (TYICAL)
1. ALL PVC MAINLINE PIPING
SHALL RECEIVE CONCRETE THRUST
BLOCKS.
2. REFER TO PIPE MANUFACTURER'S SPECIFICATIONS.
FOR AMOUNT OF CONCRETE TO BE USED FOR
THRUST BLOCK
THRUST BLOCK
POP—UP SPRAY SPRINKLER:
RAIN BIRD 1812—SAM—PRS W/
PLASTIC MPR NOZZLE
1/2—INCH MALE NPT X .490 INCH
BARB ELBOW: RAIN BIRD MODEL
SSE-050
PVC LATERAL PIPE
SWING PIPE, 12—INCH LENGTH:
RAIN BIRD MODEL SP-100
PVC SCH 40 TEE OR ELL
FINISH GRADE/TOP OF MULCH
PLANT MATERIAL
S > RAIN BIRD 1812 SAM-PRS SPRAY
O FINISH GRADE
O
HUNTER MODEL 1-20-6P ROTOR
HEAD WITH CHECK VALVE
Q
3/4" PVC STREET ELLS (3)
®
SCH 80 NIPPLE
O
LATERAL TEE OR ELL
©
LATERAL PIPE
T07�.
L�
V) HUNTER 1-20-6P GEARED ROTOR
O7 CARSON 1419
VALVE BOX
W/BOLT—DOWN
COVER MARKED
GATE VALVE.
GATE VALVE, SIZE
AS NOTED ON
PLANS.
VALVE BOX
EXTENSION, LENGTH
AS REQUIRED
4D SCH 80 PVC
THREADED NIPPLE
TYPICAL SIZE AS
REQUIRED
SCH 80 PVC SXT
ADAPTOR, SIZE AS
REQUIRED.
5) PVC MAINLINE,
TYPE & SIZE AS
NOTED ON PLANS,
7) BRICK
D) T-113 GATE VALVE
U1 PAVING
Q DITCH
4" Min. Clearance O SLEEVES
.2 . 1
3 18" MIN. I--
F24 . TO
IRISM GRADE
1
1 �%\�/`\/\\\ 36" MIN.
48" MAX.
NOTES,
1. ALL PVC IRRIGATION SLEEVES TO BE CL 200 PVC PIPE.
2. ALL JOINTS TO BE SOLVENT WELDED AND WATERTIGHT.
3. MECHANICALLY TAMP TO 95X PROCTOR.
O SLEEVING
O
WALL OR STRUCTURE
O
POP-UP SPRAY HEAD
/ v
O
NOTE: INSTALL TOP OF HEAD (THIS IS
NOT TO INCLUDE POP-UP PORTION) 4"
BELOW SURROUNDING PLANT MATERIAL,
SEE LANDSCAPE PLANS & PLANT LIST.
®
TWO (2) STAINLESS STEEL HOSE
CLAMPS
3/4" PVC SCH. 40 RISER, PAINTED
FLAT BLACK.
4
©
MULCH
5
O7
1" X 1" STEEL ANGLE. 24" DEPTH
O
PVC SCH. 80 ELBOW
6
Og
LATERAL LINE
®
PVC SCH. 80 NIPPLE, POSITION RISER
SEE ENLARGEMENT BELOW
Z
O
(1)
AT 45' ANGLE 3/4" DIA., MAX 18"
LENGTH.
PVC TEE W/ THREADED REDUCER
r
! SEE DETAIL ABOVE
®
CONNECTION.
TWO (2) STREET ELLS.
T� POP-UP HEAD ON RISER
CID
Z
co
�
O
r
Lo
n
4"13.15
lR_,05
CM n T aAi AM I ewww•.
CIVIL CONSTRUCTION PLANS & SPECIFICATIONS
SECTION 12, TOWNSHIP 37 S, RANGE 40 E
ST. LUCIE COUNTY, FLORIDA
t.
_ Sero yxne
j
LOCATION MAP
N.T.5.
LEGAL DESCRIPTION:
A PARCEL OF LAND LYING IN A PORTION OF SECTION 12, TOWNSHIP 37 SOUTH,
RANGE 40 EAST, ST, LUCIE COUNTY, FLORIDA. AL50 LYING IN A PORTION OF
THE EAST HALF OF LOT 2, BLOCK 1, ST. LUCIE GARDENS ACCORDING TO THE
PLAT THEREOF, AS RECORDED IN PLAT BOOK 1, PAGE 35, PUBLIC RECORDS OF ST,
LUCIE COUNTY, FLORIDA. SAID PARCEL OF LAND BEING MORE PARTICULARLY
DESCRIBED AS FOLLOWS:
COMMENCING AT THE NORTHEAST CORNER OF LOT 1, LENNARD ROAD
SQUARE, AS RECORDED IN PLAT BOOK 34, PAGE 7, PUBLIC RECORDS OF ST,
LUCIE COUNTY, FLORIDA, SAID NORTHEAST CORNER ALSO BEING ON THE
WESTERLY RIGHT-OF-WAY OF LENNARD ROAD; THENCE NORTH ALONG
SAID WESTERLY RIGHT-OF-WAY OF LENNARD ROAD, A DISTANCE OF 446.23
FEET TO THE POINT OF BEGINNING; THENCE N 90000'00" W DEPARTING
SAID WESTERLY RIGHT-OF-WAY, A DISTANCE OF 270.85 FEET, THENCE
NORTH 00001'54" WEST, A DISTANCE OF 176.67 FEET; THENCE NORTH
89052'49" EAST, A DISTANCE OF 270.94 FEET TO A POINT ON THE
WESTERLY RIGHT OF WAY LINE OF LENNARD ROAD; THENCE 5 00°00'00" W
ALONG SAID WESTERLY RIGHT OF WAY LINE, A DISTANCE OF 177.24 FEET
TO THE POINT OF BEGINNING.
SAID PARCEL OF LAND CONTAINING WITHIN SAID BOUNDS 47,937
SQUARE FEET (1.10 ACRES)m MORE OR LESS.
VAZ, INC.
7102 SW PORT ST, LUCK BOULEVARD
PORT ST. LUCIE, FL 34953
PHONE: 772-879-0477
mug w
mom
•
N
V.ELCON GROUP., INC.
ENGINEERS & SURVEYORS
702 SW PORT ST. LUCIE BOULEVARD
PORT ST. LUCIE, FL 34953
PHONE: 772-879-0477
EMAIL: info@velcongroup.com
ARCHITECT
LARRY L. CHRISTIAN A.I.A.
3801 KIRBY DRIVE
SUITE 600
HOUSTON, TX 77096
PHONE: 713-664-7974
11 1 1 illmll�
LANDSCAPE DESIGN ASSOCIATES
10194 NE HIGHWAY 351
OLD TOWN, FL 32680
PHONE: 352-542-4996
INDEX OF DRAWINGS
COVER SHEET
1. MINOR SITE PLAN
2. PAVING, GRADING, & DRAINAGE PLAN AND SPECIFICATIONS
3. PAVING, GRADING, & DRAINAGE DETAILS
4. WATER & WASTE WATER PLAN
5. WATER & WASTEWATER DETAILS AND SPECIFICATIONS
6. GRINDER STATION DETAILS & SPECIFICATIONS
7. DEMOLITION AND SEDIMENT & EROSION CONTROL PLAN
8. STORMWATER POLLUTION PREVENTION PLAN
cD
z
W
co
co
O
N
r
O
z
co
O
an
BEFORE YOU 016
ENGINEER'S PROJECT NO. 12-066 ENG
30 0 15 30 60
( IN FEET )
1 inch = 30 ft.
LEGEND
HANDICAP STALL
TRAFFIC FLOW DIRECTION
O
NUMBER OF PARKING
SPACES
---- vvm -
EXISTING WATER MAIN
EXISTING FORCE MAIN
FM
----
EXISTING EDGE OF
PAVEMENT
u0u
PROPOSED CATCH BASIN
(8
PROPOSED CLEAN OUT
-
Q
PROPOSED ASPHALT
PAVEMENT
PROPOSED SITE LIGHTING
W/ 25' MOUNTING HEIGHT
2.375" DIAM.
GALVANIZED
STEEL TUBE
PAINT TO MATCH
BUILDING COLOR
SURFACE FLANGE
MOUNT WITH
STAINLESS STEEL
ANCHOR BOLTS
(TYPj•
TALL PER
SIDEWALK MANUFACTURER'S
RECOMMENDATIONS
BIKE RACK DETAIL
�
` 0%) ReMA, P
EX.
EX.
PORTION OF LOT 2, BLOCK 1 ST LUCIE GARDENS PORTION OF LOT 2, BLOCK 1 CITY OF PORT ST. LUCIE ST LUCIE GARDENS
ZONING: CITY Of PORT ST. ZONING:
FUTURELUCIE
GU/SEU - GENERAL LAND USE EXCEPTION GU/SEU - GENERAL USE/SPECIAL EXCEPTION
IES '. p
UTILITIES m I FUTURE LAND USE
CURRENT USE: O I
UTILITIES
RADIO STATIONd TOWER O'le UTILITY TOWER
OHE OHE OHE OHE OHE -OP
15" OAK e -O 24" OAK 20" OAK --
"'lll��� m Q NOO°OI'WW 176.67' I I a
_ - - 1 DRY DETENTION AREA o O� N
I
j to PROP. lm-:
I j 12'x12' CONC. DUMPSTER PAD _ • l
W/ 5' HIGH MASONRY WALLS
t -- I I h OPAQUE GATES r ,:d
I (SEE DETAIL) „
------ - `WALL PACK LOADING
--- MOUNTED AT ZONE
11.5' ABOVE FFE
(TYPJ
PROP. CONC.
PAVEMENT
(,rvP.1
EX. SHELLROCK a PROP' o
PARKING AREA 1-STORY CBS
(TO REMAIN) DISCOUNT STORE
W GROSS FLOOR AREA = 8,593 S.F,
F.F.E. = 15.25 N.A.V.D.1988
EX. ASPHALT -------------------------------
PAVEMENT (TO REMAIN) m
-----------------------------,6--
6' --------------------------�
32J
EXISTING PROP.
ALUMINUM 6 STEEL
POLE BARN WATER
0.00' SERVICE
1F"nn ,lld
\ \ PORTION OF LOT 1, BLOCK 1 �^ "1 F Q .�..Uj
\ ST. LUCIE GARDENS w' O Q
.� CITY OF PORT ST. LUCIE
ZONING: ?'
u CG - GENERAL COMMERCIAL y M
m I FUTURE LAND USE•. N
COMMERCIAL LIMITED F'° K
,
VAJ CURRENT USE: W
`� R5T VACANT _ .., .. C9 N
HE m OHE r.. p
cc
m m ] u
_- -- a SITE-� J J
32" OAK Of Q Q O
� sr , , W �i O Z
EX. ,o. a+= LLI o Z Lj
STORAGE f `"y a <
YARD _ z
w
PORTION OF LOT 1, BLOCK 1-
ST. LUCIE GARDENS ee. X
ST. LUCIE COUNTY m . Q
ZONING: - , ` LL
/ IL- INDUSTRIALLI6HT 1 1 N
j FUTURE LAND USE: " • ' - VVV a) 'It
IND- INDUSTRIAL '�01
16.34' p CURRENT USE;
e . , s z d-
FLEX OFFICE/SHOPS/
SERVICES i,e _y
VI O -z
"ar � -J O
` m C0 -
ti ij
0 ------------------
O _WLLn ^Q
�.,.:,�.. N N_
I I g iyr j U
I I" O
,p LL _j
fn 2
LOCATION MAP 0 I- W It o
16,47' I I ® U 0 O
I l m N.T.S. j W U
LEGAL DESCRIPTION: W
IN
A PARCEL OF LAND LYING IN A PORTION OF SECTION 12, TOWNSHIP 37 SOUTH, > Z p Of
O W
I I EX RANGE 40 EAST, ST. LUCIE COUNTY, FLORIDA, ALSO LYING IN A PORTION OF W h 0_ .r..0
CONC. THE EAST HALF OF LOT 2, BLOCK 1, ST. LUCIE GARDENS ACCORDING TO THE
PARKING PLAT THEREOF, AS RECORDED IN PLAT BOOK 1, PAGE 35, PUBLIC RECORDS OF ST. t Y�
AREA LUCIE COUNTY, FLORIDA. SAID PARCEL OF LAND BEING MORE PARTICULARLY
R20' DESCRIBED AS FOLLOWS: `rL
COMMENCING AT THE NORTHEAST CORNER OF LOT 1, LENNARD ROAD
III
'!I9-E2IT-T4I11F tr,ya '' ems, PROP. B 16' 8 cD 10'L
PROP.
GRINDER : ., N.T.S. Anw TYPSIGN
P ❑ ®®8� , ^,y m STATION - •� ®LLS
EX. FIRE ,, wr �_ Q. PROP. PROP. PROP.
EX. R-O-W
HYDRANT
¢NVVI
EX. ASPHALT FORCE MAIN OUTFACE 20'x2O' UTILITY
i in
r� EASEMENT
r -I EA EMEN
.+..w+.........w...� ...,.......•..�.�........�... ��........+...................+........w.........�......e......... :' DRIVEWAY CATION E58 Y"a...-Y"j-';"ry
ESB EX. W CONC. SIDEWALK E58 -- COCA E
O __ ° %.',' APRON \`. "•""'•""'•••"' ^�•�-�..........• � � � •C�,
AL
EASEMENT ..
_________________________________________________________________________-______________-__________________=c=.- W K SB
N00"0O'00"E 177.2' F _-__ -___L_____-__- ______ _________ ____________-___
______-____-___ -_--_ _ ____________---- r - -
-------------------
`�-� o < Ex. A-u : I PROP. - -------------------------
i a v GRATE EL. 11,89
ww '- --•- ------ ----_ s'� E INV. EL 8,94 1 10' UTILITY ' `," t y - , '
F --- -- - EASEMENT`
- FM - FM - F - FM - FM - FM - F - - hM -- FM FM __- FM �____.F.ye _-_-___ =x IF r=norE Y� i
____-__--_____•--________-_______________---_ "Ffh_--___y-�+_--_--_�"y,-_-_--T-pq,-___._-_---__-E .__ _ _ _ _ _.-
3 - - -- -- - -- - - _:�: - - - - - -
___ ______ _ _ _ _ __ _ --_ -_ __ _ _ -_ _ r M FM r M r M, -
J _-_---:--__-___ e:_- ____-___ _ _ -
__�-._-- LENNAR ROAD ---#.----��_______�_�____�� F,4__�.�,�-���.____..��N _ � ; cm,µ .
TI ,. :�> )', i. >,>, >' - 'z: -s,'X �, -i: i,-i^-+r-n-:�:+ :> y_9 `C ✓`V I'',�,,
---------- _------ - ----- - ------- - ------- -- x '4M < ,< ,< ,< ,<' ,<,i < ,: ,c ,., , >,%'> �. ) ,:�,' <
CITY OF PORT ST. LUCIE OWNED MAINTAINED `` `� C �) ;, ). `, a >. >, ), Y >. ). ). ), ;, ?. >. ), ), ), ), a ,. a ;, >, ), ; : ), ), �, r ), >e,,>, �. ), ), I M �,C.C',< m O >.
-------------------------°------- -------------- ----------- ---------------- ------- ( N $ M N INED PAVED f00 R/W) �. �,. P� ?�.,_`„ „ ; ,, ,, ,, ,, ,, ,, ), ., > > > v)..._Z�.i), > j, Y,I,
`✓ 3 - - --_--_ - ___ _ - -
Y
act "..i�+ i
),
g
Y!r
________________-____-___ - - - -- -- - - --------- -- - - - - _ _ ___:_ - - - - - -----------------•_-_
EX. A-13-_-_ ____-_________-- -' N INV. EX. A-12EL 9.22 ! Im WAT �� ) V'� � H ,: •Y),V
3
--' --✓ --- GRATE EL 12.89 - --. ,-- ®� x ER SERVICE `--. >' ,')) EX. EL. 1273 'CL )`
TOP EL 12.14 _X. 2" POLY
N INV. EL 6.49- E INV. ELL 8.74 j j �'< '` N INV. EL. 9.44 +'
_ �'_ S INV. EL 6.65 W INV. EL. 8.49 '----------------------- -----------=�= i
x
_______________________________________________________________________________________________________________________________________________________
_ S INV. EL. 9.44
EX. 36"RCP I.__________________________________ n _______________________________________'-______ _ _ _
"-.-•--_..-..-_--...--._...-.....,.._..........--..,-....,.....-............_.-......._.........-.........�...........,....._.........m...�.............�,..�.e.....,....,..�,.....,........�,..... ` _ ____
- -- - = - �_------ �_ _:_ _.:_-_ __ ------------------ - -------------------- -
g EX.6" WATERMATN f--> --_---_� --a°" -_ -_ a::== - _ 'K D;''------------------------ -------------_--------------------------------------'D ''r_�E _____ ;_ W �,
s
EX. WM WM - ______ -- __ -_ „-, - 'WM __________SCi�'_________ __
_--•_"=�v� -__� ilk_
YW17_-a---tMNt--- -l7JMl W� - WM V-1V v7 i�9nn--- VJM__- '- a5 _
✓UM -- wN1"---'-^•_ - x: -1 M - WM WM - RA WM WM,-�.'-I:, WM - T'\,t� WM - WM _-- WM WM 1r�AhZy?V
__- -_ EX. 8' CONC. SIDEWALK -__-__ -'•`Cq _ ,(,
_-_---.-_-- ----- X. 6" WATER MAIN
-�-- `- -------------------- __,,.F=e:=e:_::r -----OFF--�-=::= :::::__:<__ -�= -- -- - --- - _ _�•`,� �... �'y:S
___-_-_____-______________ _ - - �y�D4 •`�____-EX___ EX. 6' CONC. SIDEWALK _ _ _ _ _ __Y
_____--___-_--,_________________-__-____-_____ _____-__-___ ___-_-__ DRIVEWAY _--- -_______-__----__---_-___-__-___-- ---- - ------- _----- ___---_-_ ` ��� `. PAVED 80' R/W '' SIGN NO. FTP-2t-O6 ` ' 8" I+ 7" PORT. CEMENT CONCRETE PAVEMENT 4,000 PSI ' " PRIMECOAT SEALANT TO BE APPLIED
AND FTP-22-06 2" 2 16 f ( ) 1.25 TYPE SP 9.5 PROJECT STATEMENT:
TYP.)
E EXISTING OFFICE BUILDING AND
FINE ASPHALTIC ON TOP OF BASE COURSE THE PROJECT CONSISTS OF THE S"WHITE F A •� A .,'A ';• '° ~ CONCRETE EXISTING PAVED PARKING AREA AND OTHE CONSLITION OTRUCTION F A NEW 8,593 SQ, FT. DISCOUNT
w ° • < ' • ' TRAFFIC LEVEL B CONSTRUCT 6" LIMEROCK OR STORE AND ASSOCIATED PAVED PARKING AREA. ACCESS TO THE PROJECT WILL BE AT THE
® < COQUINA BASE COMPACTED TO CURRENT DRIVEWAYS ON LENNARD ROAD. THERE ARE NO WETLANDS ON OR IMMEDIATELY
� y WHITE RETROAEFLECTP/E _ - 8 6
F1P-21d8 TOP TRAFFIC PAIM(TY•P.) ,N, a �� 98% MAX. DRY DENSITY PER AASHTO SURROUNDING THE PROJECT SITE. THE PROJECT LIES WITHIN FLOOD ZONE 'X' AS
m �
3 ; y T 180 METHOD, LBR 100 INDICATED ON THE SURVEY. THE PROPOSED IMPROVEMENTS ASSOCIATED WITH THIS
7 7 ,7 PROJECT WILL NOT INTERFERE WITH THE DEVELOPMENT AND USE OF THE NEIGHBORING
CAR STOP
$0• w (TMP) STABILIZED SUBGRADE MIN. DEPTH �o PROPERTIES AS ALL REQUIRED BUFFERING AND SETBACKS HAVE BEEN MET IN THE PROJECT
° a" wHITE 3 PARKING BY
OF 12", COMPACTED TO 98 % MAX. DRY DENSITY MOD. DESIGN.
DISABLED PROCTOR PER AASHTO T-180 METHOD, MIN, LBR40. iv THE PROJECT IS ZONED CG - COMMERCIAL, GENERAL WITH A FUTURE LAND USE OF IND -
PONLYO `O INDUSTRIAL. THE SITE TO THE NORTH LIES WITHIN ST. LUCIE COUNTY AND IS CURRENTLY A
(3) 6" NOTE:
WHITE
CHEV EVENLY
$250 FINE COMMERCIAL/INDUTRIAL STRIP PLAZA COMPRISED OF VARIOUS BUSINESS TYPES AND I5
EVENLY F.S 318.1E 1. CONCRETE PAVEMENT, AT A MINIMUM, MUST BE
STABILIZED SUBGRADE MIN. DEPTH OF ZONED IL -LIGHT INDUSTRIAL WITH A FUTURE LAND USE OF IND. THE SITE TO THE NW LIES
SPACED Fm-2zoBSOT CONSTRUCTED OF FDOT APPROVED CLASS M CONCRETE, AX. DRY WITHIN THE CITY OF PORT ST. LUCIE AND IS VACANT WITH A ZONING OF CG - COMMERCIAL
OF TWELV6RADEE
MATERIAL SHALL BE A MINIMUM THICKNESS PAVEMENT SHALL HAVE MARSHALL DENSITY PER AASHTO T/MPACTED TO 98% 180 METHOD, GENERAL AND A FUTURE LAND USE OF COMMERCIAL LIMITED. THE SITE TO THE WEST LIES
18' OF TWELVE INCHES WITH A MINIMUM LIMEROCK BEARING STABILITY OF 1,000 LBS. MIN. LBR40, MIXED AND HOMOGENEOUS WITHIN THE CITY OF PORT ST. LUCIE AND I5 A UTILITY TOWER SITE WITH A ZONING OF GU -
6" WHITE I RATIO OF 40. MATERIAL GENERAL USE AND A FUTURE LAND USE OF UTILITIES, THE SITE I5 BORDERED ON THE EAST
12'
BY LENNARD ROAD, WHICH IS A CITY OF PORT ST. LUCIE OWNED AND MAINTAINED 100, PUBLIC
5' 2. CONCRETE SHALL BE REINFORCED WITH FIBER MESH R-O-W, AND LAND THAT THAT LIES WITHIN THE CITY OF PORT ST. LUCIE AND IS ZONED RM-11
TYPICAL PARKING STALL ADDITIVE OR WITH 6x6 #io/#10 W.W.M. TYPICAL ONSITE ASPHALT PAVEMENT DETAILS WITH A FUTURE LAND USE OF ROI - RESIDENTIAL/OFFICE/INSTITUTIONAL.
NOTES:
i. HANDICAP STALL IS BASED FROM FDOT STANDARD INDEX 11 ` 5 3. SAW -CUT JOINTS @ 15' O.C. N.T.S.EXPANSION JOINTS @ 40' O.C. FILL MAY BE REQUIRED IN LIMITED QUANTITIES IN ORDER TO ACHIEVE THE REQUIRED
#17346, SHEET 12 OF 14. DESIGN ELEVATIONS ANY REQUIRED FILL WILL BE OF A GRAN
2. DIMENSIONS ARE TO THE CENTERLINE OF MARKINGS.
3. BLUE PAVEMENT MARKINGS SHALL BE TINTED TO MATCH
SHADE 15180 OF FEDERAL STANDARDS 595a.
4. FTP-22-06 PANEL SHALL BE MOUNTED BELOW THE FTP-21-06
SIGN.
5. FOR DESIGN OF THE UNIVERSAL SYMBOL OF ACCESSIBILITY,
REFERENCE FDOT STANDARD INDEX #17346, SHEET 12 OF 14.
6. FOR DESIGN OF THE ASSOCIATED SIGNS, REFERENCE FDOT
STANDARD INDEX #17355, SHEET 4 OF 11.
HANDICAP SPACE DETAIL
N.T.S.
I
A{,yaye a3n 8.a v.f. m yu✓ J.y
BEFORE YOU ING
Gvt Mtl(U Bug/NF8e MY9
wurraan.arBroBEo
AEA44'l MEANPo(8
RroeaF¢r
LIGHTING FIXTURE POLE
MANUFACTURER SHALL SUBMIT
SIGNED AND SEALED DRAWINGS
VERIFYING THAT WIND LOADING
AND OVERTURNMOMENTFOR
THE LIGHT FIXTURE AND POLE
INSTALLATION MEETS THE
REQUIREMENTS OF THE FLORIDA
BUILDING CODE. in
N
NOTE:
LIGHTS LOCATED ALONSPERIMETER
OF THE PROPERTY SHALL BE SUPPLIED
WITH "HOUSE -SIDE" SHIELD TO
ELIMINATE LIGHTING SPILLOVER ONTO
ADJACENT PROPERTIES.
FINISHED
GRADE
PARKING AREA LIGHTING FIXTURE
TUTS
ULAR MATERIAL SUITABLE FOR
TYPICAL ONSITE CONCRETE PAVEMENT DETAILS COMMERCIAL SITE DEVELOPMENT AND WILL BE OBTAINED FROM AN APPROVED BORROW PIT.
N.T.S. THE CONTRACTOR WILL BE RESPONSIBLE FOR PROVIDING EROSION AND SEDIMENT CONTROLS
USING THE LATEST FDOT STANDARDS. BALED HAY, STRAW, AND SILTATION BARRIERS WILL
HINGES SHALL BE OUTSIDE OF BE INSTALLED WHERE NEEDED TO PREVENT SILTATION OF ADJACENT PROPERTY, PUBLIC
10'-8" CLEAR AREA R-O-W, WETLANDS, AND WATERWAYS. THESE WILL REMAIN IN PLACE UNTIL GRASSING OR
SODDING HAS BEEN COMPLETED OR UNTIL SILTATION AND EROSION ARE NO LONGER A
10'-8" CLEAR THREAT TO THE ADJACENT PROPERTIES OR WATERWAYS.
100%OPAQUE 12" x 16" CONCRETE
BATES FOOTING W/ 3 #5
BARS CONT I OC
<
I
I
j
8" CONCRETE BLOCK WALL W/
I
q
STUCCO (BOTH SIDES) W/
I Q
FILLED CELLS 611 #5 BAR AT
NOTE:
LOCATIONS SHOWN
I O
OPENING MUST BE
PERPENDICULAR TO
LINE OF FLIGHT OF
8" AND I 4" DIA, x 42" SERVICE VEHICLE.
M6H
STEEL BOLLARD W/ IS" L_ _ - _ J
'/'7- EMBEDDED INTO
8" x V. BOND BEAM -�- CONCRETE
W/ 2 #5 BARS CONT C? 12' ••....
"woo
.....
........•
STUCCO STEEL I
BOLLARD 8"CONCRETE BLOCK •••••••••••••Agxag
WALLS W/ STUCCO .............• -
-------------- 12' x 12' DUMPSTER DETAIL .............................
12'-0' __________________________--
,
660'
... Acp......,
.........................................
EX
DRIVEWAY"Z ........v
. LENNARD RD....
DRIVEWAY LOCATION MAP
SCALE: V =100'
PROJECT SITE
EX.
SQUARE, AS RECORDED IN PLAT BOOK 34, PAGE 7, PUBLIC RECORDS OF ST.
LUCIE COUNTY, FLORIDA, SAID NORTHEAST CORNER ALSO BEING ON THE
WESTERLY RIGHT-OF-WAY OF LENNARD ROAD; THENCE NORTH ALONG
SAID WESTERLY RIGHT-OF-WAY OF LENNARD ROAD, A DISTANCE OF 446.23
FEET TO THE POINT OF BEGINNING; THENCE N 90*00'00" W DEPARTING
SAID WESTERLY RIGHT-OF-WAY, A DISTANCE OF 270.85 FEET, THENCE
NORTH 00001'54" WEST, A DISTANCE OF 176.67 FEET; THENCE NORTH
89°52'49" EAST, A DISTANCE OF 270.94 FEET TO A POINT ON THE
WESTERLY RIGHT OF WAY LINE OF LENNARD ROAD; THENCE S 00000'00" W
ALONG SAID WESTERLY RIGHT OF WAY LINE, A DISTANCE OF 177.24 FEET
TO THE POINT OF BEGINNING.
SAID PARCEL OF LAND CONTAINING WITHIN SAID BOUNDS 47,937
SQUARE FEET (1.10 ACRES)i MORE OR LESS.
OWNER:
VAZ, INC.
702 SW PORT ST. LUCIE BOULEVARD
PORT ST. LUCIE, FL 34953
PH:772/879-0477
PARCEL IDENTIFICATION NUMBER:
3414-501-4702-000-7
PRO
PERTY CLASSIFICATIONS:
ZONING: CG - COMMERCIAL, GENERAL
FUTURE LAND USE: IND - INDUSTRIAL
MINIMUM BUILDING SETBACKS:
FRONT: 25 FEET
REAR: _ 20 FEET
SIDE: 10FEET
PROP. BUILDING DATA:
DISCOUNT RETAIL = 8,593 S.F.
BUILDING HEIGHT - ONE STORY = 25 FEET
PARKING CALCULATIONS:
4.49 SPACES PER 1,000 S.F. GROSS FLOOR AREA
8,593 S.F. 4.49 - . 9 SPACES / 1,000 S.F. - 39 SPACES
SPACES REQUIRED = 39 SPACES (2 HANDICAP, 37 REGULAR)
SPACED PROVIDED = 42 SPACES (2 HANDICAP, 40 REGULAR)
LOADING ZONE REQUIRED = 1(12'x3O')
LOADING ZONE PROVIDED = 1(24'x3O')
DRAINAGE STATEMENT:
THE PROJECT I5 SERVED BY SITE GRADING, INLETS, AND CULVERTS THAT
DIRECT STORMWATER TO THE DRY DETENTION AREA. DISCHARGE WILL BE TO
THE LENNARD ROAD DRAINAGE SYSTEM. SFWMD CRITERIA FOR WATER QUALITY
AND QUANTITY TREATMENT WILL BE PROVIDED.
UTILITY PROVIDERS:
POTABLE WATER = CITY OF PORT ST. LUCIE UTILITY SYSTEMS DEPARTMENT
WASTEWATER = CITY OF PORT ST, LUCIE UTILITY SYSTEMS DEPARTMENT
IRRIGATION =EXISTING WELL
PERMITS REQUIRED:
SLC STORMWATER PERMIT
CITY OF PORT ST. LUCIE RIGHT-OF-WAY PERMIT
FDEP NOI
CONSTRUCTION SCHEDULE:
CONSTRUCTION START: NOVEMBER2014
CONSTRUCTION COMPLETION: 180 DAYS
SITE DATA:
TOTAL PROJECT AREA 47,937 S.F. 1.100 AC 100.00 %
IMPERVIOUS AREA
PROP. BUILDING 8,593 S.F. 0.197 AC 17.93%
PROP. PAVEMENT /WALKS 21926 S.F. 0.503 AC 45 74%
TOTAL IMPERVIOUS 30,519 S.F. 0.701 AC 63.66%
TOTAL PERVIOUS (OPEN) 17,418 S.F. 0.400 AC 36.34%
..r....................
660'
MASTER
AVE. ,
r
Z
J
I�
LLw
/r
VJ
0
_Z
2
..0 I
O
¢ Y
J 4 N
O
Z
3 U d
U
O U U
SHEET
NO.:
OF
JOB No.
12-066 ENG
30 0 15 30 60 +,?�
( IN FEET }
1 inch = 30 ft. m
�HEF I + +�
�j +��°
OHE OHE�-OHE OHE OHE OHE-
15- OAK 24" OAK 20" OAK
I �y1 5 yy ii4%%%
+
' I
I I I
I +�3.
I ;
'I
I I
O 6w
�o� I
Caw
zF
I 1 I
I
0+
ti. i3O
I I'
'I I
I I
I
I ,
I '
I '
I
II +b°
E_ orwr_wv - I
LE6EN6
+ 0
EXISTING GRADE
ELEVATION
T/CURB
2150
21.00
B/CURB
PROPOSED ELEVATION
(H.P. = HIGH POINT)
RUNOFF FLOW DIRECTION
O
PIPE INTERFERENCE
POINTS
- - m ---
EXISTING WATER MAIN
EX157ING FORCE MAIN
EXISTING EDGE OF
PAVEMENT
EXISTING LIGHT POLE
i0l
PROPOSED CATCH BASIN
0
PROPOSED CLEAN OUT
m
a
Q N00`0154"W 176.67
-�+
i
______________+�0________________ _
k
_____
_.........."
_ __+_--"---' I
13.8
ii i -- --- -- -12-g _------------_
i-- --- --- --- ------
11.5
14.00
Ip
_
1 I 1 ( DRY DETENTION AREA
---
+y'
��
o
I I I I DOT. EL. 11.5 (0.05 AC) ,�---J /T-
E-
I I
+
I I I I TOP EL. 14.0 (0.14 AC) j i --'�,�A
A
,6V cola[.; �y
{
22 L.F.15"'
11 I L.1.5 11.5J -���
11 1 1
<''.
-
--------
RCP @ 0.0%
t .0,
I I MES IN�. MES INV.'
�14.40
-13.80
qol----_ 'I
\ EL. 30.5C L. 10.50 , /
F`'---J---
v�
__+
C.S. #1
(CONTROL STRUCTURE)
\ \ -�--------- A 1
`��----------------------� iA
0
RGP F 15"
@
5
32" OAK
+Yy° j TOP EL. 14.85 �'------------------ ---"• 09Y,
NW INV. EL, 10.50 Vb� 15.15 TOP N 13.50.I
I E INV. EL. 10.00 5 E+iNV. EL 10.95
BENCHMARK#2 J BLEEDER EL. 10.50 8192 - 14.5 •1yfh
5/0-IRON ROD I 0*'� +
+y _______ OVERFLOW EL, 13.85 #y. .
EL 15.31 G _ C
NA V.D. 1988, ___- ______ ____}______-
1y1 T BENCHMARK## 3 PROP. 15.0 • o
5/8" IRON ROD 1-STORY
EL. 16.17 31
N A.V D. 1988 16 " ' 1ys/1' FICUS
�y t�10 y DISCOUNT STORE 14.95 > +
+ ,y G.F.A. = 8,593 S.F. 1 .35' ,z, 14.35
+ I FFF:15PFiMAV1)
i EX. SHELLROCK +' CO
PARKING AREA "
I ob 14.00 14.85 0 ""
B + +0
es SAWCUT EX.
14.35 p0 PAVT. AND
ny
0 ,y
1 1+ + +�b• Ql MATCH EL. 1 I
ti fib. o- y9 ^ � �
bb �' EX. ASPHALT +t_______-
Ky� bf __--__ PAVEMENT of
>`' + t �y. -----+----------'------------- H.P. „�
+
Sr 126.6' 1b!A
lyy
+
n
EX
a
J
.
�CONC.-
.�,
EXISTING
50#7
N
I
E_�e;__==a__._r3•
ALUMINUM 6 STEEL
TOP EL. 16.00
50 #6
I
POLE BARN
N,E INV. EL. 9,35
TOP EL. 15.00
EX
S,W INV. EL. 9.40
/
I
,
/
R.
�q
I �I ♦spy
,I
! I
�A
0
3:1
I
1.,5�
+
;
RCP @ %
15.15
R:, rc
b+
I
I
b
N
�
+y'
PROP.
14.65
8
♦�a1
I
'',
�-
�
��e
DRAI
DRAINAGE
14.20 ;,
126.6' 14.60
------- ------------
10
EASEMENT.
ga
�
I
TOP
o o O
Ra o
I
EL,13.95
,'.
"o,5y"
?� 34 L.F. INV.
14.40
e
U !
74 L.F; INV; CR.
14,20
H P:
TOPfL.13;�9y5
(,
4'
H.P,
'KL''S.-I
.:V
',7,,.,1
r 14.1: i . m'w
,.. n,�
1t • _SaJ
�!` /h; 1 v'r
i
+°gSAWCUT EX.
+
14.20
14.60 95 L.F. 15" I
I 14.40
I
PAVT. AND
RCP @ 0.1%
°
MATCH EL.
15.25
EX. FIRE
♦1
n,
EX. ASPHALT
HYDRANT 0
d
/' 6y 1r2s3
1 IV
1
m
�
DRIVEWAY
I
? �
3
..................�
ESB 12. 6
-,+�.6 ...ww..e.......e...... -___
E%. 6' CONC. SIDEWALK ESB
�", D
APRON Y.
b r
A
1 . 6' CONC. SIDEW l
P'.+
2S
.^
EX A-11 j py
ti4
,�,
< _ ��
,,;
GRATE EL It89 � SAWCUT, REMOVE, ♦ti SEE SIDEWALK
E INV. EL 8,94 I & REPLACE CONC. CONNECTION
-
- -�
w o
VV-TW�-
E � R 5;; SIDEWALK AT EX. DETAIL
A 3 <_.=__°
f..M
FM FM - F
.,, .d1
'o� '4A VT-_
gy > V 1°
y
1:� O JOINTS AS RE D. ,y>,
F.,'.�..' ._^.^. t2. 11 Q �r 1
- FM FM F M _ F -- F _-_. M .-__._._ FM -'
-_- FM __ FM .'"-09-------- 4------ice'-'r-H^-i 4-
-F-FL_...�,,...._F-00.-_''- --- H_
_�T-
-Fr':__---44- i-P4- -Fl+ x i F#--^--i-H- FdF---^M---F#-
'
I C � 1
NAR
ll > >
R
z y L
a+ 1ti V V -U-------'✓-
--------------- v
m
<
< `<
- --- ---
_:---c.-ccc.-c_-.._c_ cc------ -----�=c= �-�..:� _-__rc_ :--_� -
-��"_:,--
(CITY OF PORT ST. LUCIE OWNED & MAINTIANED
PAVED 100' R/W)
----------- --
-
:---..
- 11
w W 2" POLY E%.A-13 NINV. EL19.22 ilm WATER SERVICE
x
S INV. EL 6.48 n,
GRATE EL l2.89 -u�
-
E INV. EL 6.74
n^
N INV. EL 6.49
II
_______________-INV. EL_BA9
_ y
-- S INV. EL. 6.65 r �
_ __ _ _ _1__E%. 36"RCP _____ ___�_ ....... _ yl Ir __ ____________________ EX. 36 RCP 1(,r_______________________________ 77777777777
_- _ EX. b" WATER MAIN i- -- , - - r .. VVM WM WM WM6" WATER MAIN -. .-_• •,
a EX _____ _�__ ,, „6
__---_ , n _ -- _ -- '^. - - i+'A, EFi WM --__ WM M -_.- VVM __ WM
WM `-WM---„"_V�(yL.-_-_ WM VJM NM -_- WM WM RIVEWA 61' WM WM--_'-- ^_\ MrtVI---_--- -VJIA WM-TNIu_-__--_PJNF_-_-WN-_ Y+IM'__'_-'__-_•__'---_ �¢eeee_�,_ 11 .. �;�
-__ '-'--- _' - EX. 8' CONC. SIDEWALK �: " '
EX.
- - EX. 6' CONC. SIDEWALK
------- --_-- ----- - ------ __-_-- ---- _----- - 1----______
CATCH BASIN SCHEDULE
SPACING OR REQUIRED ROADWAY /PARKING AREA TESTS
NOTE:
ALL ELEVATIONS SHOWN OR REFERENCED WITHIN THESE PLANS ARE BASED
UPON NORTH AMERICAN VERTICAL DATUM OF 1988 (N.A.V.D.). TO CONVERT
FROM N.A.V.D. '88 TO N.G.V.D. '29, ADD 1.48' TO THE N.A.V.D. ELEVATIONS TO
GET N.G.V.D. ELEVATIONS.
NOTE:
DRAINAGE PIPE JOINTS, INCLUDING ROUND CONCRETE PIPES, SHALL HAVE
A FILTER FABRIC JACKET IN ACCORDANCE WITH FOOT ROADWAY AND TRAFFIC
DRAINAGE STANDARDS. ALL RCP PIPE USED FOR EXFILTRATION SHALL HAVE 8D
SLOTS, IN ACCORDANCE TO FOOT INDEX #285.2 OPTIONS'.
-
SIDEWALK SLOPES PER ADA
LENGTH MAX. SLOPE LONGITUDINAL
L<6' 1:12 NO HANDRAILS
6'< L < 30' 1:12 HANDRAILS BOTH SIDES
STRUCTURE
NO.
ELEVATION - FT. N.A.V.D.
BOX TYPE
PER F,D.O.T.
INDEX #232
COVER
ITEMS TO BE TESTED
F.B.V.
DENSITY
L.B.R.
THICKNESS
TOP
NORTH
EAST
SOUTH
WEST
WEIR
BLEEDER
C.S.
CONTROLSTRUCTURE
1485
NW 10.50
10.00
-
-
-
-
TYPE'E
USE 83M
sD#z
13.50
10.95
10.95LL
TYPE'C'
USE
COMPACTED OR
STABILIZED SUBGRADE
MAX, SPACING
MAX. SPACING
MAX.MaXSPACING
MAX. SPACING
SD#3
13.50
-
-
11.15
11.15
-
-
TYPE'C'
USE 6212
LIN.FT. SO.FT.
LIN.FT. 50.FT.
LIN.FT. SQ.FT.
LIN.FT. SQ.FT.
SD
13G5
11.35
-
11.35
-
-
-
TYPE'C'
USE 8212
300
10,000
300
10,000
_
_
300
10,000
SD#5
13.95
11.36
-
-
-
-
-
TYPE'C!
USE6212
SD#8
15.00
-
-
9.40
9,40
-
-
4' 0 M.H.
USE 170-E
LIMEROCK BASE
_
300
10,000
_
300
10,000
SO #7
16.00
9.3s
9.35
-
-
-
-
4' 0 M.H.
USE 170-E
SHELLROCK BASE
300
10,000
300
10,000
ASPHALT
_
_
_
-
-
_
PERINSP,
PER INSP.
u II
tea.
13.00 13.40 13.50
I-190
�y0
in
11n
v'
in
LAND.
SLOPE
AND.
5>iE
LAND.
6
5' 5'
5'
5'
N
��
�+
p
�
12,90
13.30 13.40 13.80
LMATCH
-
EX.
EX 6'CONC.
SIDEWALK EL. 12.5±
SIDEWALK
SIDEWALK CONNECTION DETAIL
SCALE: V = 10'
Al..ay. u118v Lc L,c vo. Jig:
BEFOREY DIG
o'" rxoWmsu�Bars
xxnroA»EsrteroeErrxEn
AExcrnr.wlw
maw¢r
NOTE: ALL TESTING SHALL BE TAKEN IN A STAGGERED SAMPLING PATTERN FROM A POINT 12" 6'< L < 50' 1:20 NO HANDRAILS
INSIDE THE LEFT EDGE OF THE ITEM TESTED, TO THE CENTER, TO A POINT 12" INSIDE
OF THE RIGHT EDGE.
TOP EL 14.85
13.00
Z
GROUT 8'
E'-
(TYP.1
12.00
m
I 225'
GROUT
LL
Illm
mPa
0.50
0
W
11.00 INV EL
m f~-
J
.Z�
w
BLEEDER
15, RCP
LU
�.
EL 10.50
INV. EL. IDOD
10,00
EL. 10,00
2.25,
BOTTOM
SCALE` ri = V H
C.S. #1 V C.S. #1
CONTROL STRUCTURE WEIR PLATE
TYPE IF BOX
CROSS SECTION LOOKING NORTH
14.00 PROP. PAVT. EL. 14.0--
p
12,00
PROP. 151, RCP
Q
INV. EL.11.3±
Z
11.00
ILL
6" MIN.
W
10.00
PROP.151,
W
RCP
INV. EL. 9.3±
9.00
8.00
INTERFERENCE POINT #4
SCALE: k" = 3' H
V=3'V
14
�
Y5,15
• �
^I
LO
A
+
EX.
ASPHALT
PAVEMENT
�
•
I15.00
14.50
rvyZ���
♦
N
SO #9
TQP EL. k3.5p
�
1a.
CR, ^
1 5,W INV EI 1115
\yb�+
�+
A-.7-- 1
z
N 0WOO'WE 177.24'
FM FM FM --�mM FM
1117
}
2
i>
>' >' TOP EL 12.73 p
Z
N INV. EL 9.44
>' Y ) SINV. EL. 9.44
/ X
EIN --- --
It'>.T.92
41 1
WMWM WM WM --1 WM --
ME�IIALEUCA BLVfD�
(PAVED 80' R/W) 3
EX.
STORAGE
YARD
EX.
BUD&
EX
CONC.
PARKING
AREA
EX.
BLDG.
EX
cow.
PARKING
AREA
1/2" CHAMFER SEE SITE PLAN
3,OW PSI CONCRETE -
PAVEMENT a
BASE
COMPACTED SUBGRADE
SIDEWALK/PAVEMENT DETAIL
N.T.S.
WARN l INNGG \ 1 \
WN\\VIA
HANDICAP RAMP DETAIL
N.T.S.
GENERAL CONSTRUCTION NOTES:
te
1.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING THE SITE PRIOR TO
o
N
w
BIDDING WORK AND SHALL TAKE INTO CONSIDERATION ANY OMISSIONS,
M
UNDERGROUND UTILITIES, OR OTHER ITEMS AFFECTING THE INSTALLATION OF
�
PAVING, DRAINAGE, AND UTILITIES, SHOULD UNCHARTED OR INCORRECTLY CHARTED
UTILITIES OR OTHER ITEMS BE ENCOUNTERED DURING CONSTRUCTION, CONSULT
w N
ENGINEER OF RECORD IMMEDIATELY FOR DIRECTIONS. REPAIR DAMAGED UTILITIES
0
OR OTHER ITEMS TO SATISFACTION OF UTILITY OWNER AND ENGINEER OF
O 00
RECORD.
0_'D
2.
ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH ALL APPLICABLE
sn ¢
-) Z
CITY, COUNTY, STATE, AND FEDERAL REGULATIONS, CODES, AND ORDINANCES,
INCLUDING OSHA AND FOOT SPECIFICAIONS, LASTE5T EDITION UNLESS OTHERWISE
Li
z �
1 w
AUTHORIZED BY THE ENGINEER IN WRITING.
(Do-
Z
a
3.
LOCATION AND SIZES OF ALL EX. UTILITIES ARE APPROXIMATE ONLY. CONTRACTOR IS
w Q
m
RESPONSIBLE FOR EXACT FIELD LOCATION AND SIZES PRIOR TO COMMENCEMENT OF
ANY CONSTRUCTION TO ALLOW FOR PIPE RECONFIGURATION IF NEEDED. THE
CONTRACTOR SHALL CONTACT ALL AFFECTED UTILITIES AT LEAST 48 HOURS IN
(Q
N
ADVANCE OF CONSTRUCTION OPERATIONS.
0) d.
4.
ANY DISCREPANCIES ON THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF
(0 �
THE ENGINEER PRIOR TO COMMENCING WORK.
c0
5.
NO FIELD CHANGES OR DEVIATIONS FROM DESIGN SHALL BE MADE WITHOUT PRIOR
o I
J
WRITTEN APPROVAL OF THE ENGINEER OF RECORD.
00 p
D
6.
CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS / LICENSES PRIOR TO
J 0]
O Or w Ln (N N
COMMENCING WORK.
/ W U 0)
�L
L> >� �O
7.
THE CONTRACTOR SHALL KEEP COPIES OF ALL PERMITS, PLANS, AND SPECIFICATIONS
J tr
w l `-'_
ON SITE DURING CONSTRUCTION.
11
• k
8.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REQUIRED TESTING TO BE
(\ Q
PERFORMED BY AN INDEPENDENT TESTING LABORATORY APPROVED BY THE ENGINEER
Z W LL
OF RECORD. THE CONTRACTOR SHALL SUPPLY DENSITY TESTS TO ENGINEER OF
0' U `t O
O �,
RECORD ON ALL SUB GRADE AND BASE. TESTS SHALL BE PREPARED IN ACCORDANCE
W O
WITH AASHTO T-180 METHOD AT ALL AREAS OF DISTURBED ASPHALT & PIPE
r , a
TRENCHING.
V W
J W 00U
9.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING ANY DAMAGE RESULTING
Z N w
FROM HIS OPERATIONS, TO EXISTING PAVEMENT, SWALES, ETC.
W 3
IKN
10.
THE CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF
N
ZLLJ
W r 11 .�-.0
ONE YEAR FROM THE DATE THAT PROJECT HAS BEEN ACCEPTED. ALL FAULTY
' t'
CONSTRUCTION AND/OR MATERIALS THAT OCCUR DURING AFORESAID PERIOD SHALL
LLI
BE CORRECTED AT THE CONTRACTORS'S EXPENSE AND IN A TIMELY MANNER.
11.
THE CONTRACTOR SHALL COMPLY WITH ALL RULES AND REGULATIONS OF THE STATE,
r�
COUNTY AND CITY AUTHORITIES REGARDING CLOSING OR RESTRICTING THE USE OF
F�
PUBLIC STREETS OR HIGHWAYS.
12.
THE CONTRACTOR SHALL GIVE ADEQUATE NOTIFICATION TO ALL AFFECTED UTILITY
OWNERS
FOR REMOVAL, RELOCATION AND ALTERATION OF THEIR EXISTING FACILITIES.
13.
THE CONTRACTOR SHALL NOTIFY THE ENGINEER AT LEAST 48 HOURS PRIOR TO ANY
REQUIRED INSPECTIONS AND SHALL SUPPLY ALL EQUIPMENT NECESSARY FOR
W
INSPECTIONS AND/OR TESTING.
Z
G
14.
THE CONTRACTOR SHALL PROVIDE THE ENGINEER A5-BUILT SURVEYS CERTIFIED BY A
LICENSED SURVEYOR UPON COMPLETION OF CONSTRUCTION AND SCHEDULE A FINAL
N
INSPECTION WITH THE ENGINEER OF RECORD.
w
�0
1
15.
ANY PUBLIC LAND CORNER WITHIN THE LIMITS OF CONSTRUCTION SHALL BE
W
�
PROTECTED. IF A CORNER MONUMENT IS IN DANGER OF BEING DESTROYED AND HAS
,
NOT BEEN PROPERLY REFERENCED, THE CONTRACTOR SHOULD NOTIFY THE COUNTY
w
SURVEYOR WITHOUT DELAY BY TELEPHONE.
0
16.
IF HARDPAN I5 ENCOUNTERED WITHIN RETENTION AREA OR SWALES, IT SHALL BE
REMOVED AND REPLACED WITH A GRANULAR MATERIAL.
,
m
17.
IF MUCK OR ANY OTHER UNSUITABLE MATERIAL I5 ENCOUNTERED, THE MATERIAL
SHALL BE COMPLETELY REMOVED AND BACK FILLED WITH A GRANULAR MATERIAL AND
COMPACTED TO DENSITIES SUFFICIENT TO ACCOMMODATE THE INTENDED USE.
06
18.
LOCATION OF
STRUCTURES SHALL GOVERN AND PIPE LENGTHS MAY HAVE TO BE
ADJUSTED TO ACCOMPLISHCONSTRUCTION A 5 SHOWN ON THESE PLANS.
19,
RCP INDICATES REINFORCED CONCRETE PIPE. P NFOR ED CONC E E P E. CM INDICATES GALVANIZED
CORRUGATED METAL
V
n
7 V
Z
PIPE. BCCMP INDICATES BITUMINOUS COATED CORRUGATED
J
A METAL PIPE. CAP INDICATES CORRUGATED ALUMINUM PIPE. CPP INDICATES
CORRUGATED POLYETHYLENE PIPE (N12) MANUFACTURED BY ADVANCED DRAINAGE
� ^ L
SYSTEMS, INC. (ADS).
20.
MITERED END SECTIONS SPECIFIED ON THE PLANS SHALL BE IN ACCORDANCE WITH
W U
FOOT STANDARD D INDEX
N N0.272.
21.
COMPACTION REQUIREMENTS FOR PIPE BEDS SHALL BE 90% OF MAXIMUM DRY
Ij V
V a ILL
DENSITY.
Z
22.
TEMPORARY DRAINAGE SHALL BE PROVIDED DURING CONSTRUCTION TO ELIMINATE
W
ANY FLOODING OF PRIVATE PROPERTY.
23.
ALL STORM SEWER LINES AND DRAINAGE STRUCTURES SHALL BE CLEANED OF DEBRIS
AND ERODED MATERIALS TH
\
DURING E FINAL STAGES OF CONSTRUCTION.
O
24.
ANY DRAINAGE PROBLEMS CREATED BY CONSTRUCTION,OR EXISTING BEFORE
wx
CONSTRUCTION AND NOT ALLEVIATED AS PART OF THE PROPOSED IMPROVEMENTS,
/� W
SHOULD BE BROUGHT TO THE ATTENTION OF THE GOVERNING AUTHORITY AND THE
L.L
ENGINEER OF RECORD.
25.
THE CONTRACTOR SHALL TAKE PRECAUTIONS TO PROTECT EXISTING TREES SHOWN
TO REMAIN. IF ANY TREES MARKED TO BE REMOVED CAN BE SAVED, THE CONTRACTOR
SHALL SAVE SAID TREES. SHOULD ADDITIONAL TREES NEED TO BE REMOVED, THE
CONTRACTOR SHALL NOTIFY THE OWNER AND THE ENGINEER OF RECORD FOR
APPROVAL PRIOR TO REMOVING SAID TREES.
26.
IF EXCAVATED FILL MATERIAL IS REUSABLE, STOCKPILE EXCESS FOR USE IN
LANDSCAPED AREAS.
27.
UNUSABLE CLEARED MATERIAL SHALL BE REMOVED FROM SITE AND HAULED TO AN
APPROVED DISPOSAL SITE. AS AN ALTERNATIVE, BURNING ON SITE WILL BE ALLOWED
WITH PROPER PERMITS. LOCATION OF BURN SITE SHALL BE APPROVED BY OWNER.
28.
ALL AREAS DISTURBED BY CONSTRUCTION SHALL BE RESTORED TO
WA
Q _�
PRE -CONSTRUCTION CONDITIONS OR BETTER. ALL EXISTING SIGNAGE, PAVEMENT
MARKINGS, ABOVE GROUND APPURTENANCES, ETC. SHALL BE RESTORED IN KIND.
0/ O
29.
WHEN PAVEMENT IS SHOWN NEXT TO A CURB OR SIDEWALK, THE ELEVATION OF THE
LL LL
TOP OF CURB OR SIDEWALK IS 6" ABOVE THE PAVEMENT, UNLE55INDICATED AS
r
FLUSH. IN SOME CASES, BOTH ELEVATIONS ARE SHOWN FOR ADDITIONAL CLARITY.
Q Z
30.
ALL CONCRETE SHALL DEVELOP A 28-DAY COMPRESSIVE STRENGTH OF 3,000 PSI
UNLESS
OTHERWISE NOTED.
0
ul
31.
ALL REINFORCING STEEL SHALL CONFORM TO ASTM A-615 AND HAVE A TENSILE
Z U
STRENGTH
J
OF 60,000 PSI UNLESS OTHERWISE NOTED.
_
Z
32.
ALL WATER FLUSHED FROM MAINS SHALL BE DIRECTED AS APPROVED BY THE ENGINEER
( )
J
OF RECORD.
33,
NO WATER OR SEWER SERVICE IS TO BE SUPPLIED, UNTIL A LETTER OF CLEARANCE IS
RECEIVED FROM FDEP,IF APPLICABLE.
34.
MAINTENANCE OF TRAFFIC SHALL BE IN ACCORDANCE WITH THE "MANUAL ON
UNIFORM TRAFFIC CONTROL DEVICES FOR STREETS AND HIGHWAYS", AND THE FOOT
"ROADWAY AND TRAFFIC DESIGN STANDARDS INDEX #600", LATEST EDITIONS.
35.
EROSION AND SEDIMENT CONTROL - CONTRACTOR IS RESPONSIBLE FOR PROVIDING
EROSION AND SEDIMENT CONTROL USING THE LATEST F.D.O.T. STANDARDS. BALED
HAY, STRAW, AND SILTATION BARRIERS WILL BE INSTALLED WHERE NEEDED TO
PREVENT SILTATION OF ADJACENT PROPERTY, PUBLIC RIGHT-OF-WAY, WETLANDS AND
}
WATERWAYS. THESE WILL REMAIN IN PLACE UNTIL GRASSING OR SODDING HAS BEEN
COMPLETED OR UNTIL SILTATION AND EROSION ARE NO LONGER A THREAT TO
.. °n I
ADJACENT PROPERTY AND WATERWAYS.
w n
3 u o 0
36.
ALL BERMS AND GRASSED AREAS SHALL BE SEEDED AND MULCHED IN ACCORDANCE
w°
a
S o p o c= a =
WITH THE APPROPRIATE SECTIONS OF THE ABOVE REFERENCED SPECIFICATIONS
UNLESS OTHERWISE AUTHORIZED BY THE ENGINEER OF RECORD.
SHEET NO.:
37.
BOUNDARY AND TOPOGRAPHIC INFORMATION PREPARED BY VELCON GROUP, INC.
DRAWING NO. 12-066, ALL ELEVATIONS PER BENCHMARKS REFERENCED ON SURVEY.
OF
JOB No.
12-066 ENG
17_00
16.00
Fy[rIw
Q 14.00
Z
H 13.00 EX. CONC.
L SIDEWALK
LU
LU 12.00
17.00
16.00
15,00
14.00
>
Z
F- 13,00
tL
LU
W 12.00
11.00
10.00
9.00
SOD / LANDSCAPE
`- MATCH EX.
( GRADE EL.12.7t
5' 3 0
SOD SOD 50
31'
PROP. PAVT.
EL. 14.30 INVERTED CROWN EL.
VARIES 13.50 -14.15
PROP. FIFE =15.25 1 1 1
CROSS SECTION
CROSS SECTION
3 0 10'
530 SOD
1,25" TYPE SP 9.5 PRIMECOAT SEALANT TO BE APPLIED
FINE ASPHALTIC ON TOP OF BASE COURSE
CONCRETE
TRAFFIC LFVFI B CONSTRUCT1 PACT( ,C
8„ COQUINA BBASS COMPACTED COMPACTEDD
� „11 98%MAX. DRY DENSITY PER AAA
SHTO
T-180 METHOD, LBR 100
b
�J5TABILIZEO SUBGRADE MIN. DEPTH
NOTE: OF 8", COMPACTED TO 98% MAX. DRY
PAVEMENT SHALL HAVE MARSHALL DENSITY PER AASHTO T-180 METHOD,
STABILITY OF 1,000 LES. MIN. FBV 75 PSI OR LBR40, MIXED
AND HOMOGENEOUS MATERIAL
TYPICAL ONSITE ASPHALT PAVEMENT DETAILS
Or
N.T.5
PROP.15" RCP
INV. EL.11.2t
7'
50D/
LANDSCAPE
42'
PROP. PAVT.
SCALE: V = It,' H
P= 2'V
6' 6'
CONC. LANDSC
SIDEWALK
EL
EL. EL.
15.000 15.10 15,15
EL. ,
14.50 1 ..
17.00
16,00
15.00
-----�
p
14,UU
>
MATCH EX,
e
Z
GRADE 14.0±
1-
13.00
LU
W
12.00
11.00
10.00
9,00
CROSS SECTION
SCALE: 1" = f0' H
V = 2' V �../
8"
6" PORT, CEMENT CONCRETE PAVEMENT (3,000 PSI)
R. ,a • .y . ,d a
.o ., . • • . d y .• �.
I .4
STABILIZED 5USGRADE MIN. DEPTH
OF 6", COMPACTED TO 96 { MAX. DRY DENSITY
MOD. PROCTOR PER AASHTO T-180 METHOD, MIN.
NOTE: FBV 75 PSI OR LBR40.
1. CONCRETE PAVEMENT, AT A MINIMUM, MUST BE
CONSTRUCTED OF FDOT APPROVED CLA55 II CONCRETE.
SUBGRADE MATERIAL SHALL BE A MINIMUM THICKNESS
OF SIX INCHES WITH A MINIMUM LIMEROCK BEARING
RATIO OF 40 OR 75 P5I FBV,
2. CONCRETE SHALL BE REINFORCED WITH FIBER MESH
ADDITIVE OR WITH 6x6 #10/#10 W.W.M.
3. 5AW-CUTJOINT5 @ 15' O.C.
EXPANSION JOINTS @ 40' O.C.
TYPICAL ONSITE CONCRETE PAVEMENT DETAIL5
N.T.5
PROP. PAVT, I 10'
-SOD / LANDSCAPE
EL. VARIES
14.10 -14.50
17.00
6'
4'
50D / LAI,
DSCA
16.00
MATCH EX.
I
EL-
15.00
GRADE 16.0±
15.0
I
a
4
14.00
>
er
I
Z
13.00
3'
LL
W
W
1200
I
11.00
10.00 PRO0P. 15" RCP
INV. EL. 9.7+
9,00
EL.14.5
CROSS SECTION
EX, PAVT_
I
MATCH EX. I
GRADE 14.5t
1"=10'H
I" = 2' V
SAW -CUT AND TACK COAT g'_plt
EXISTING-\
EXISTING ASPHALT \
f L tl
pPQPQSEE) A5PHAI TPAVEMENT
EXISTING BASE / � � � PROPOSED BASE
EXISTING SU8-GRADE PROPOSED SUB -GRADE
ASPHALT PAVEMENT SAWCUTA BUTTJOINT DETAIL
N.T.S.
7" Std.
7% 6" Min!
8"
When
2'-0" • Mte used on high side re roadways, the cross slope of the
gu ttar shall match the cross slope of }he ad Jacent pavergppl•.ce On Low Side Of Pavement
TYPE F The thickness of the lip shell be 6-,1 unless othsrwlse she
on plans, a Be } Above Lip Of Gutter, Surface
Note: For use adjacent to concrete or flexible pavement, concrete shown. On High Side To Be Flush With Lip Of
For details depicting usage adjacent to flexible pavement, see diagram right. Curb Or Curb & Gutter.
Exponsion joint, preformed joint filler and joint seal are required between curb & gutter
and concrete pavement only, see diagram right. Slope Varies
CONCRIEA CURB AND GUTTER
L.� Flexible Pavt.
_I /Joint Seal
m 0 Applies to both hlgh and low aides of pavement, tow side shown.
cane. Pav't. ADJACENT TO GUTTER
PAVEMEN CURB
} Exp. t And
Pro formedJoinJoint Flller
TYPE D Joint Seolo
TI --_ -� Nuts: For we adjacent p to concrete or flexible an pavement, concrete shown. ;J.
Sad I' Bevaletl Ce Round Comers '" Ead I' -Beveled Cr Round Camera „ J Expansion Joint, preform etl Joint filler and joint seal are required between cur eQ, ?
and concrete pavement only, see diagram right E Cwaate Con cret
CONCRETE CURB Gutter Pavement
°M'x. Depth 0/ Snwcut 4"�Prefor Joint And
/ -L Preformed Joint Fillelo
0" Min. 5' Max, Preformed
to both high and low sides of pavement, low side shown.
W F_ o° Max. EXPANSION JOINT BETWEEN GUTTER
s S TYPE F AND CONCRETE PAVEMENT
\ Sawcuts should be avoided within valley gutter and within curb and gutter endings.
X CONTRACTION JOINT IN CURB AND GUTTER GENERAL NOTES
^ 1. For eurb,gutter,and curb and gutter prot}tla }" contraction
joints at 10• centers (max.). Contraction joints adjacent to eoncn
pavement on tangents and Cot curves are to match the pavement
Conrnte Sae, J" 0dA' Thli joints, with intermediate joints not to exceed 70' centers.
Relnfamed sun wvn' 66x8-Ix.", � Sad , ° --- -- m Curb,gutter and curb & gutter expansion joints shall be located In
accordance with Section 520 of the standard specifications.
2. Ends of Curbs Types 8 and D shall transition from full to zero
/-�-�s TOP VIEW -SINGLE PIPE
5' Min.heights in 3 feet.
own
5} �o'o'pNo n 5.� Max.\ ior}°Holes
=Yal Around oat.
Edge Of Flpe Por6 91 "- Concrete Slat, 3" 06�I'
RelnWin
Thli, b
D
Z'r Porced WinroseBxa-1V1.4x1M.4 Soe
° Concrete
PIP® connect TOP NEW -MULTIPLE PIPE
es
• m Blde OilcM1 Grad _ ,dRo
���
i t ale I n I' a NOTE: See sheet 8 far details and notes. CROSSUnleNeeo PiperaJvdednt B aThrmeNlEend Neer S0 > Sod DRAIN
E •Slope: 4:1 Miter. To
Pa P'Ppea 24'PIAnE arga ° s^°"°` MITERED END SECTION
Paid Farb Pipe Cal t F (Pipe io Be Include Untler Unit Pnce For N'tered Entl Section
21 MRen To I Pipe Far Plans 16" And Smallc. SINGLE AND MULTIPLE ROUND CONCRETE PIPE
SECTION I:I Far Pipes 24" And Larger. F.D.O.T. INDEX NUMBER 272
2" Min.
3" Max.
th DepOf Sawcu4
3y th
1
TYPE D
CONTRACTION JOINT IN CURB
R
CONCRETE BUMPER GUARD
CURB & GUTTER DETAIL
F.D.O.T. INDEX NUMBER 300 1 of
1" is JU H
V= 2'V
PRIME COAT 1' TYPE 'FC'
SEALANT 3' TYPE 'SP' ASPHALT OR MATCH
ASPHALT EXISTING
EXISTING STABILIZED SAW CUT EX,
SURFACE ASPHALT (TYP,)
MATERIAL
NEW INSTALLATION
(PIPE) r >
r
USE EX, MATERIAL
TO BACKFILL DITCH I
12' I.. 12'
VARIES
GENERAL NOTES
1, REPLACED BASE MATERIAL OVER DITCH SHALL BE TWICE
THE THICKNESS OF THE ORGINAL BASE,
2, BASE MATERIAL SHALL BE PLACED IN TWO OR THREE
LAYERS AND EACH LAYER THOROUGHLY ROLLED OR TAMPED TO
MAXIMUM DENSITY,
3, ASPHALT CONCRETE PAVEMENT JOINTS SHALL BE MECHANICALLY
SAWED.
4, SURFACED TREATED PAVEMVNT JOINTS SHALL BE LAPPED AND
FEATHERED,
5, SURFACE MATERIAL WILL HE CONSISTENT WITH THE EXISTING
SURFACE,
REPLACEMENT OF FLEXIBLE PAVEMENT
CONSTRUCTION FIELD OBSERVATIONS
I. DRAINAGE
A. LAYING OF PIPE (BEFORE BACKFILL)
B. ALL DRAINAGE STRUCTURES AND PIPE LAYING COMPLETE.
C. CONSTRUCTION AND STABILIZATION OF RETENTION AREAS AND
SWALES.
D. SEEDING, MULCH AND SODDING IN AREAS WHERE EROSION 15
EVIDENT.
II. UTILITIES (PERMITS)
A. PIPE LAYING IN RIGHTS -OF -WAYS.
B. JACK AND BORING / DIRECTIONAL BORING.
C. WET TAPS.
D. ABOVE GROUND MANHOLE INSPECTIONS AND INSTALLATIONS,
III. CONCRETE
A. CONSTRUCTION OF CURBING, SIDEWALK, NON -BUILDING SLABS,
Q
w
� j
w O
Z Six
Z ¢
w
cat
Ic
sylD
�,
w
p
N
LLJ N
N
GO
w
o z°
Q w
Lt
X
AND RETAINING WALLS BEFORE PLACEMENT OF CONCRETE,Ll
r 1
IV.
PAVEMENT
V
6)
A. LINE AND GRADE (CERTIFICATION).
Z
0)
B, SUBBASE (PRIOR TO ADDING BASE MATERIAL)
Ln
C. BASE (PRIOR TO PRIMING AND SAND SEAL)
D. BASE(AFTER PRIMING, SAND SEAL AND BEFORE PLACING OF
p
ASPHALT)
z
E. ASPHALT OR CONCRETE (WHILE PAVING I5 IN PROCESS).
X m
00 O
F, TURN OUT CONSTRUCTION ONTO CITY, COUNTY, OR STATE ROAD
O
.-.Q
(ABOVE INSPECTIONS APPLY).
®
>__LI
W
N N
G. TEST RESULTS ON SUBBASE, BASE AND ASPHALT.
ry
U 0) r -
H.FINAL PROJECT OBSERVATION.
J �O
PROJECT CERTIFICATION REQUIREMENTS
\,/
N L
:D
L.
PAVEMENT TESTING
Z
LJJ
r
N
A. FLORIDA BEARING VALUE (FBV) OR LIMEROCK BEARING RATIO
w`�
� �-
(LBR) TEST RESULTS.
0
U O
O
(1) Q ?
P. CC"'PACTrCN xcr 511 Tc
i
LL y
C. BASE MATERIAL TEST RESULTS.
U
0) F
0, ASPHALT TEST RESULTS.
W �� CO U
II.
WATER AND SEWER
W
Z F- �E
("� N
A. DEPARTMENT OF ENVIRONMENTAL PROTECTION CERTIFICATION
N 0'
FOR BOTH WATER AND SEWER (OPERATION AND MAINTENANCE),
ZOO LU
0
IF APPLICABLE.
I'+•I R �U
B. HEALTH DEPARTMENT CERTIFICATION, IF APPLICABLE.
'Y'
r L,
C. BACTERIOLOGICAL AND PRESSURE TESTING FOR WATER MAINS,
W
0. VIDEO AND EXFILTRATION TESTING FOR GRAVITY SEWER MAINS,
IF APPLICABLE.
L
E. PRESSURE TESTING FOR FORCE MAINS, IF APPLICABLE.
eew
f
F. UTILITY ACCEPTANCE FOR OPERATION AND MAINTENANCE, IF
APPLICABLE,
III.
CERTIFICATION AND RECORD DRAWINGS
A. SEALED CERTIFICATION BY THE ENGINEER OF RECORD FOR
7
COMPLIANCE WITH APPROVED PLANS AND SPECIFICATIONS
ALONG WITH RECORD DRAWINGS FOR THE PROJECT,
NOTE:
ALL ELEVATIONS SHOWN OR REFEREN(AED WITHIN THESE PLANS ARE BASED
UPON NORTH AMERICAN VERTICAL DATUM OF 1988 (N.AN.D.). TO CONVERT
FROM N.A.V.D. ' 88 TO N.G.V.D. ' 29, ADD 1.48' TO THE N.A,V.D. ELEVATIONS TO
GET N.G. V.D. ELEVATIONS.
AL.r.tGus.u.r ya"dsyi )
86PORE YOU DIG
cue Tw0cphuwNEssa M
"AITFaRTHEsne re ar.rikED
assGECTfNE MgRN$
a G6g E Y
•♦
r
(W v
V W
V
Z
its
W
3 U
°
4 a h
0
p o
V) o
U
U '-
SHEET NO.:
3
OF
JOB No.
ex
2-066
ENG
ex