Please see below for response to the above listed project.
4CANNLU
BY
Sta/
Luciemuff,
Comment 1: PLEASE ADD THE LI`1E LOAD FOR THE FLOOR AND THE LIVE
LOAD FOR THE ROOF IN ACCORDANCE WITH TABLE 301.5 AND TABLE 301.6
OF THE 2017 FLORIDA RESIDENTIAL CODE-SIXTH'EDITION.
Response 1: Please see Section 2 under GENERAL NOTES on sheet GN for .
information on minimum superimposed floor and roof live loads.
Comment 2: PLEASE ADD THE LIVE LOAD FOR THE ROOF IN ACCORDANCE:
WITH TABLE 301.5 AND TABLE 361.6 OF THE 2017 FLORIDA RESIDENTIAL
CODE SIXTH EDITION.
Response 2: Please see Section 2 under GENERAL NOTES on sheet GN for
information on minimum superimposed roof live loads.
Comment 3: PLEASE PROVIDE A, DETAIL FOR THE VEHICLE BARRIER FOR
APPLIANCE IMPACT PROTECTION IN ACCORDANCE WITH 1607.8.3 OF THE
2017 FLORIDA BUILDING CODE SIXTH EDITION.
Response 3: Please refer to detail 17/17A on revised sheet D4-provided with this
response package.
Comment 4: PLEASE SHOW AUTOMATIC GARAGE DOOR OPENER BEING. IN
ACCORDANCE WITH 309.4 OF THE 2017 FLORIDA RESIDENTIAL CODE SIXTH
EDITION IF APPLICABLE.
Response 4: Please refer to the revised sheet' 5.1, electrical notes provided with this
response package.
i
FILE COPY
1441 N. Ronald Reagan Blvd. • Longwood; FL 32750 • Phone: (407) 77476078 • Fax: (407) 774-4078
AA0003325
www:abdesigngroup.coin
ARCHITECTS
roue
Comment 5: PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC
DESIGN CRITERIA WEATHERING AND TERMITE AREA IN ACCORDANCE
WITH TABLE 301.2(1).
Response 5: Please see revised sheet,2 for the climatic and geographic design criteria
weathering and termite area table.
Comment 6: PLEASE SHOW CERAMIC TILE IS IN ACCORDANCE WITH 702.4
OF THE 2017 FLORIDA RESIDENTIAL. CODE SIXTH EDITION.
Response 6: The is no Ceramic tile used on this house.
Comment 7: PLEASE SUBMIT DETAIL FOR SOFFIT INSTALLATION AS PER
CHAPTER I SECTION 107 SUBSECTION 107.1 OF THE 2017 FLORIDA
BUILDING CODE SIXTH EDITION.
Response 7: Soffit installation is per the Manuf Spec. We are including the Product
Approval installation with .this revision package.
I
Comment 8: PLEASE SHOW. ON PLANS DETAIL FOR THE POST
ATTACHMENT ON THE PORCH. -SEE CHAPTER.1 SECTION 107 OF THE 2017
FLORIDA BUILDING CODE SIXTH EDITION.
Response 8: Installation of the post its listed on the Framing Plan. Please refer to sheet
4D. (2) 2x12 BM. TO 6X6 POST (2) MSTA-24 & (1) HTS716. POST TO SLAB.
ABU66. (TYP 2) 1
Comment 9: PLEASE REVIEW AND CORRECT ACCORDINGLY. THE ENERGY
CALCULATIONS CUBIC VOI UMFJ IS DIFFERENT THEN WHAT THE PLANS
INDICATE.
Response 9: Please see the revised Cover Sheet and. Floor Plan sheet 2 provided with
this response package for changes.
Should you have any questions, please feel free to contact me.