HomeMy WebLinkAboutGENERATOR16/20/22 kW GENERAC® RECEIVED JUN 0 6 2018 GUARDIAN° SERIES ST, Lpcie County, Permitting Residential Standby Generators Air -Cooled Gas Engine INCLUDES: • True Power'" Electrical Technology • Two Line LCD Multilingual Digital Evolution TM Controller (English/Spanish/ French/Portuguese) • Two Transfer Switch Options Available: 100 Amp, 16 Circuit Switch or 200 Amp Service Rated Smart Switch. See Page 4 for Details. • Electronic Governor • System Status & Maintenance Interval LED Indicators • Sound Attenuated Enclosure • Flexible Fuel Line Connector • Direct -To -Dirt Composite Mounting Pad • Natural Gas or LP Gas Operation • 5 Year Limited Warranty • Capability to be installed within 18" (457 of a building* FEATURES Standby Power Rating Models G007036-0, G007037-0 (Aluminum - Bisque) -16 kW 60 Hz Model G007035-0 (Aluminum - Bisque) - 16 kW 60 Hz Models G007039-0, G007038-0 (Aluminum - Bisque) - 20 kW 60 Hz Models G007043-0, G007042-0 (Aluminum - Bisque) - 22 kW 60 Hz O INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING are at thel heart of Generac's O success in providing the most reliable generators possible. Generac�s G-Force engine lineup offers added peace of mind and reliability for when you need it the most. The G-Force series engines are purpose built and designed to handle the rigors of extended run times in high temperatures and extreme operating conditions. O TRUE POWER'" ELECTRICAL TECHNOLOGY: Superior harmonics and sine wave O form produce less than 5% Total Harmonic Distortion for utility quality, power. This allows confident operation of sensitive electronic equipment and micro -chip based appliances, such as variable speed HVAC systems. GENERAL C@us QUIETTiEff_— LISTED Note: CUL certification only applies to unbundled units and units packaged with pre -wired switches. Units packaged with the Smart Switch are UL certified in the *Only if located away from doors, windows and fresh air intakes, and unless otherwise directed by local codes. SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION: This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque -matching the surge loads to the engine. Digital voltage regulation at ±1 %. SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. O TEST CRITERIA: O GENERAC TRANSFER SWITCHES: Long life and reliability are J PROTOTYPE TESTED V NEMA MG1-221EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this ,/ SYSTEM TORSIONAL TESTED J MOTOR STARTING ABILITY confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility. GENE R AC _ I— PROM ISE OyEPc' h,�A�c` Link TM •9eM In Me USO tWng do el "cendlnre/gnperte. G EN E RAC® 16/20/22 kW features and benefits Engine • Generac G-Force design Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cylinderwalls and plasma molyrings helps the engine run cooler, reducing oil consumption resulting in longer engine life. • "Spiny-lok" cast iron cylinder walls Rigid construction and added durability provide long engine life. • Electronic ignition/spark advance These features combine to assure smooth, quick starting every time. • Full pressure lubrication system Pressurized lubrication to a I vital bearings means better performance, less maintenance and longer engine life. Now featur- ing up to a 2 year/200 hou�I oil change interval. • Low oil pressure shutdown system Shutdown protection prevents catastrophic engine damage due to low oil. • High temperature shutdown Prevents damage due to overheating. Generator • Revolving field Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator. • Skewed stator Produces a smooth output waveform for compatibility with electronic equipment. • Displaced phase excitation Maximizes motor starting capability. • Automatic voltage regulation Regulates the output voltage to ±1 % prevents damaging voltage spikes. • UL 2200 listed For your safety. Transfer Switch (if applicable) • Fully automatic Transfers your vital electrical loads to the energized source of power. for flexibility. • NEMA 313 Can be installed inside or outside maximum • Remote mounting Mounts near your existing distribution panel for simple, low-cost installation. Evolution— Controls • Auto/Manual/Off illuminated buttons Selects the operating mode and provides easy, at -a -glance status indication in any condition. • Two-line LCD multilingual display Provides homeowners easily visible logs of history, maintenance and events up to 50 occurrences. • Sealed, raised buttons Smooth, weather -resistant user interface for programming and operations. • Utility voltage sensing Constantly monitors utility voltage, setpoints 65% dropout, 80% pick-up, of standard voltage. • Generator voltage sensing Constantly monitors genera or voltage to ensure the cleanest power delivered to the home. • Utility interrupt delay Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default setting of 5 seconds by a qualified dealer. • Engine warm-up Ensures engine is ready to assume the load, setpoint approximately 5 seconds. • Engine cool -down Allows engine to cool prior to shutdown, setpoint approximately 1 minute. • Programmable exercise Operates engine to prevent oil seal drying and damage between power outages by running the generator for 5 minutes every other week. Also offers a selectable setting for weekly or monthly operation providing flexibility and potentially lower fuel costs to the owner. • Smart battery charger Delivers charge to the battery!; only when needed at varying rates depending on outdoor air temperature. Compatible with lead acid and AGM -style batteries. • Main line circuit breaker Protects generator from overload. • Electronic governor Maintains constant 60 Hz frequency. Unit • SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding winds up to 150 mph. Hinged key locking roof panel for security. Lift -out front for easy access to all routine maintenance items. Electrostat- ically applied textured epoxy paint for added durability. • Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries. • Small, compact, attractive Makes for an easy, eye appealing installation, as close as 18" away from a building. Installation System • 1 ft (305 mm) flexible fuel line connector Absorbs any generator vibration when connected to rigid pipe. • Direct -to -dirt composite mounting pad Complex lattice design prevents settling or sinking of the generator system. 0 Integral sediment trap Prevents particles and moisture from entering the fuel regulator and engine, prolonging engine life. GENERAC 16/20/22 kW specifications Generator Model G007035-0,G007036-0, G007037-0 (16 kW) G007038-0,G00703M (20 kW) 1% G007042.0,G007043-0 (22 kW) Rated Maximum Continuous Power Capacity (LP) — 16,000 Watts" — 16,000 Watts" _ _ 20,000 Watts' 18,000 Wafts'_ 22,000 19,500 Rated Maximum Continuous Power Capacity (NG) (Rated Voltage _ __--! _ _— — 240 66.6/66.6 Less than 5% — 70 Amp _240 83.3/75 _ Less than 5% 100 Amp _ 240� 91.6/81.3 Less than 5% = 100 Amp Rated Maximum Continuous Load Current —240 Volts (LP/NG) Total Harmonic Harmonic Distortion _— -- Main Line Circuit Breaker ---J Number of Rotor Poles 2 2 2 Rated AC Frequency 60 Hz 60 Hz _ _ — — Power Factor _ — �^ Battery Requirement (not included) _i -- 1.0 1.0 1.0 12 Volts, Group 26R 540 CCA Minimum or Group 35AGM 650 CCA Minimum Unit Weight (IbAg) 406/186 448/203 466/211 — _ Dimensions (L x W x H) irVmm I 48 x 25 x 29/1218 x 638 x 732 —j Sound output in dB(A) at 23 it (7 m) with generator operating at normal load" rCn,,...1 — —4 in .InfA% car 9 PPH P P..rf.ICP. mndp." 66 58 66 58 67 Exercise duration 5 min — 5 min 5 min Engine Type of Engine GENERAC G-Force 1000 Series GENERAC G-Force 1000 Series GENERAC G-Force 1000 Series Number of Cylinders _ _ 2 2 Displacement 999 cc 999 cc 999 cc — Cylinder Block _a �_— Sl Aluminum w/ Cast Iron Sleeve _ _ — — Valve Arrangement —_ Overhead Valve Overhead Valve Overhead Valve Ignitioo SySystem __— _ —_---_ — Solid state w/_Magneto Solid-state w/Magneto Solid-state w/Magneto Electronic Electronic Electronic Governor System '; Compression Ratio _ _ 9.5:1 _ 9.5:1 12 Vdc 12 Vdc Starter — -- _ _ _--- Oil Capacity Including Filter Approx. l.9 gV1.8 L Approx. l.9 gt/1.8 L_—_ Approx. U qV1 8 L —] Operating rpm 3,600 3,600 — 3,600 Fuel Consumption Natural Gas ft3/hr (m3/hr) 1/2 Load 218 (6.17) 204 (5.78) 216 (6.12) i Full Load 309 (8.75) 301 (8.78) 310 (8.78) Liquid Propane ft3/hr (gal/hr) [I/hr] 1/2 Load 91.6 (2.52) [9.53] 86 (2.37) [8.99] 93.2 (2.56) [9.70] Full Load 106.8 (2.94) [11.111 129.6 (3.56) [13_481 140 (3. 77)_[14^651—� Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet _ at all load ranges - 3.5-7" water column (7-13 mm mercury) for natural gas,10-12" water column (19-22 mm mercury) for LP gas. For Btu content multiply fts/hr x 2500 (LP) or ft3/hr x 1000 (NG). For Megajoule content, multiply m3/hr x 93.15 (LP) or ms/hr x 37.26 (NG) Controls 2-Line Plain Text Multilingual LCD Display I Simple user interface for ease of operation. — �— ons:Auto LMade Butt _— _ � to _ _ Aumatic Start on Utility failure. 7 day exerciser. _] _ — Manual j� Start with starter control, unit stays on. If utility fails, transfer to load takes place. rnvi — --- Steps unit. Power is removed. Control and charger still operate. Ready to Run/Maintenance Messages —�— _ Standard — Engine Run Hours indication ____ Standard —T _J Programmable start delay between 2-1500 sveconds Standard (programmable by dealer only) Future Set Capable Exerciser/Exercise Set Error Warning __— Standard ^— RurVAlarm/Maintenance Logs 50 Events Each Engine Staff Sequence _ — _ Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration). Loc Starter k-out_ __ _ _— — — — ! _— Staffer cannot re-engage until 5 sec after engine ppe has stod_— Smart Battery Charger — Standard — `--^--_� Charger Fault/Missing AC Warning Low Battery/Battery Problem Protection and Battery Condition Indication _Standard Under-Frequency/Overload/Stepper Overcurrent Protection stanaaro— Sag Fused/Fuse Problem Protection _— _^ _Standard_— Automatic_ Low Oil Pressure/High Oil Temperature Shutdown Standard OvercranWOverspeed (Q 72 Hz)%rpm Sense Loss Shutdown ' -^ — - _Standard High Engine Temperature Shutdown Standard Internal Fauloncorrect Wiring Protection — Standard — — _ Common External Fault Capability Standard -J — Field Upgradable Firmware _— — Standard "Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator maybe higher depending on installation parameters. Rating definitions- Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, IS03046 and DIN6271). • Maximum kilovoltamps and currentare subject to and limited by such factors as fuel Btu/megalcule content, ambient temperature, allitude, engine powerand condition, etc. Ma>amum power decreasesabout3.5 percentforeach 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percentfor each 6 °C (10 °D above 16 oC (60 `F). 16/20/22 kW Limited Circuits Switch Features • 16 circuits. • Electrically operated, mechanically -held contacts for fast, positive connections • Rated for all classes of load,100% equipment rated, both inductil a and resistive. • 2 pole, 250 VAC contactors. • 30 millisecond transfer time. • Dual coil design. • Rated for both copper and aluminum conductors. • Main contacts are silver plated or silver alloy to resist welding and sticking. • NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility. • Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers from Siemens, Murray, Eaton and Square D for the most flexible and cost effec- tive install. Dimensions 200 Amps 120/240,1 e Open Transition Service Rated Height Width H1 I H2 W1 W2 Depth in 27.24 30.0 11.4 13.5 7.09 mm 692.0 1 762.4 289.0 343.0 180.0 Note: The 50 amp switch is flush mountable. H1 and W1 refer to mounting hole spacing. H2 and W2 are cover dimensions. H3 and W3 are the enclosure dimensions without cover. Wire Ranges Conductor Lug Neutral Lug Ground Lug 1/0-#14 2/0-#14 2/0-#14I Service Rated Smart Switch Features • Includes Digital Power Management Technology standard (DPM). • Intelligently manages up to four air conditioner loads with no additional hardware. • Up to four more large (240 VAC) loads can be managed when used in conjunction with Smart Management Modules (SMMs). • Electrically operated, mechanically -held contacts for fast, clean connections. • Rated for all classes of load,100% equipment rated, both inductive and resis- tive. ! • Up to four more large (120/240 VAC) loads can be managed when used in con- junction with 50 amp Power Management Modules (PMM**). • 2 pole, 250 VAC contactors. • Service equipment rated, dual coil design. • Rated for both aluminum and copper conductors. • Main contacts are silver plated or silver alloy to resist welding and sticking. • NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor mount- ing flexibility. Dimensions 200 Amps 120/240,1 a Open Transition Service Rated Height Width H1 H2 Wt W2 Depth in 27.24 30.0 11.4 13.5 7.09 mm 692.0 762.4 289.0 343.0 180.0 GENE RAC® switch options Model G007036-0 (16kW) No. of Poles 2 Current Rating (Amps) too Voltage Rating (VAC) 120/240,10 Utility Voltage Monitor (Fixed)* -Pick-up 60% -Dropout 65% Return to Utility* approx.15 sec Exerciser bi-weekly for 12 minutes*t Standard UL Listed Standard Total of Pre -wired Circuits 16 No. 15A120V 5 No. 20 A 120 V 5 No. 20 A 240 V 1 No. 30 A 240 V - No. 40 A 240 V 1 1 No. 50 A 240 V Tandem Breaker Capabilities 8 spaces Circuit Breaker Protected Available RMS Symmetrical 10,000 Fault Current @ 250 Volts *Function of Evolution Controller Exercise can be set to weekly or monthly DEPTH Model 6007037-0 (16 kW)/G007039-0 (20 kW)/ G007043-0 (22 kW) --� No. of Poles 2 Current Rating (Amps) 200 Voltage Rating (VAC) 120/240,10 Utility Voltage Monitor (Fixed)* -Pick-up -Dropout 80% 65% Return to Utility* approx.13 sec Exerciser weekly for 12 minutes* Standard UL Listed Standard Enclosure Type NEMA/UL 3R --� Circuit Breaker Protected 22,000 Lug Range 250 MCM - #6 *Function of Evolution Controller DEPTH GENERAC 16/20/22 kW available accessories Model # Product Description Generac's Mobile Link allows you to check the status of your generator from anywhere that you have ac- G006463-4 Mobile Link- cess to an Intemet connection from a PC or with any smart device. You will even be notified via e-mail or text message when a change in the generator's status occurs. Available in the U.S. only. G005819-0 26R Wet Cell Battery Everystandby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery for use with all air-cooled standby product (excluding PowerPact®). The pad wanner rests underthe battery. Recommended for use if the temperature regularly falls below 0°F. G007101-0 Battery Pad Wanner (Not necessary for use with AGM -style batteries). Oil warmer slips directly over the oil filter. Recommended for use if the temperature regularly falls below G007102-0 Oil Warmer 0°F. The breather warmer is for use in extreme cold weather applications. For use with Evolution controllers G007103-0 Breather Warmer only in climates where heavy icing occurs. Auxiliary Transfer Switch The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load G005621-0 Contact Kit you may not need. Not compatible with 50 amp pre -wired switches. The fascia base wrap snaps together around the bottom of the new air cooled generators. This offers a G007027-0 - Bisque Fascia Base Wrap Kit sleek, contoured appearance as well as offering protection from rodents and insects by covering the lifting (Standard on 22 kW) holes located in the base. If the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from G005703-0 - Bisque Paint Kit future corrosion. The paint kit includes the necessary paint to property maintain or touch-up a generator enclosure. G006485-0 Scheduled Maintenance Kit Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine maintenance) on a Generac automatic standby generator. G006873-0 Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its Smart Management Module power management capabilities. It provides additional power management flexibility notfound in any other (50 Amps) power management system. dimensions & UPCs Dimensions shown are approArnate. Refer to installation manual for erdct dimensions. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES. LEFr snDE VIEW r"A n FRCW%AM Model UPC G007035-0 696471070354 G007036-0 696471070361 G007037-0 696471070378 G007038-0 696471070385 G007039-0 696471070392 G007042-0 696471070422 G007043-0 696471070439 GENE RAC® Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com ©2016 Generac Power Systems, Inc. All rights reserved. Ali specifications are subject to change without notice. Part No.10000000194-C 08/18/16 Automatic Transfer Switches Description GENERAL" Service and non -Service rated Automatic Smart Transfer Switches 100 - 400 Amps, Single Phase Generac Automati G. Transfer Switches are designed for use with single phase generators that utilize an Evolution TM or Nexus TM Controller. The 100, 200, and 400 amp open transition switches are available in single phase in both service equipment rated and non -service equipment rated configurations. The 1 0 and 300 amp open transition switches are only available in a service rated equipment configuration. Standard Features Service rated (RTSW) Generac Automatic Transfer Switches are housed in an aluminum NEMA/UL Type 3R enclosure*, with electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for years of service. The controller at the generator handles ,all the timing, sensing, exercising functions, and transfer commands. All switches are covered by a 5 year limited warranty. * Non -service rated (RTSC) switches are housed in a steel enclosure. DPM Technology Through the use of digital power technology (DPM), these switches have the capability to manage up to 4 individual HVAC (24 VAC controlled) loads with no additional hardware. When used in tandem with Smart Management Modules, up to 8 more loads can be managed as well, providing the most installation efficient power management options available. 99!M, ISO Zoos 9__ GENERAC® 100-400 Amps, Single Phase Automatic Smart Transfer Switches Functions All timing and sensing functions originate in the generator controller Utilityvoltage drop-out......................................................................................................................................................................................................................<60% Timer to generator start ..................................................................................................10 second factory set, adjustable between 2-1500 seconds by a qualified dealer' Enginewarm up delay........................................................................ .......................................................................................................................................5 seconds Standbyvoltage sensor......................................................................i...........................................................................................................................60% for 5 seconds >80% Utilityvoltage pickup............................................................. ............................................................................................................................................................ Re -transfer time delay........................................................................I......................................................................................................................................15 seconds Enginecool -down timer...........................................................................................................................................................................................................60 Exerciser........................................................................................... I..................................................................................................................12 seconds minutes every 7 days The transfer switch can be operated manually without power applied. `When used in conjunction with units utilizing Evolution- controls Specifications Model RTSC100A3 RTSW100A3 RTSW150A3 RTSC200A3 RTSW2C0A3 RTSW300A3 RTSC400A3 RTSW400A3 Amps 100 100 150 200 200 300 400 400 Voltage 120/240,1e 120/240,1e 120%240, to 120/240, 1e 120/240,1e 120/240, 16 120/240, 19 120/240, to Load Transition Type (Automatic) Open Transition Open Transition Service Rated Open Transition Service Rated Open Transition Open Transition Service Rated Open Transition Service Rated Open Transition Open Transition Service Rated Enclosure Type NEMA/UL 3R NEMA/UL 3R NEMA/UL 3R NEMA/UL 3R NEMAtUL 3R NEMA/UL 3R NEMA/UL 3R NEMA/UL 3R UL Rating UUCUL UL UL UUCUL UL UL UUCUL UL Withstand Rating (Amps) 1 10,000 10,000 22,000 10,000 22,000 22,000 22,000 22,000 Lug Range 1/0 - #14 250 MCM - #6 600 MCM - #4 or 1/0 - 250 MCM I Dimensions w1 Model RTSC100A3 RTSW100A3 RTSW150A3 RTSC200A3- 11SW200A3 RTSW30OA3 RT9C400A3 RTSW400A3 Height H1 17.24/437.9 17.24/437.9 26.75/679.4 17.24/437.9 26.75/679A 42.91/1089.9 31.25/793.8 42.91/1089.9 (inJmm) H2 20/508 20/508 30/762 20/508 30/762 48/1219.2 36/914.4 48/1219.2 Width W1 12.5/317.5 125/317.5 10.5/266.7 12.5/317.5 10.5/266.7 16.69/423.9 19.18/487.2 16.69/423.9 (inJmm) W2 14.6/370.8 14.6/370.8 13.5/342.9 14.6/370.8 13.5/342.9 21.82/554.2 24/609.6 21.82/554.2 Depth (inJmm) 7.09/180.1 7.09/180.1 6.3/160.1 7.09/180.1 6.3/160.1 10.06/255.5 10.06/255.5 10.06/255.5 Weight (Ibs./Idlos) 20/9.07 22.5/10.21 39/17.69 20/9.07 39/17.69 r140/63.5 133/60.33 140/63.5 DePrH DEPTH r 1 GENE RAC® Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com ©2015 Generac Power Systems, Inc. AR rights reserved. All specifications are subject to change without notice. Bulletin OL3205-B Printed in U.S.A. 0728/15 1 1 1GENERATQR U_�'IT BY-7 SEPARATE SUBMITTAL (SEE CONCRETE PAD SCHEDULE FOR MINIMUM 1NEIGHT-R QQIREQ:)�> Ea� LEDIN EERil�� G 1 FRONT VIEW r PAD LENGTH — HURRICANE CONC (GENERAC A (ON -GRAD W x Z J PAD THi('KNESS E;iNJIG], NJ EEERING TYPICAL ANCHORAGE: (4) 3/8" DIA. AMIFAST CONCRETE INSERTS (PART# 165003 & TEST REPORT 95329 BY ELEMENT MATERIALS TECHNOLOGY) W/ 3/8" DIA. BOLT ASTM A307, 3" MIN. EDGE DISTANCE, 1-3/8" EMBED. INTO CONCRETE (BASE PAN MIN. THICKNESS = 0.69" AND MIN. BEARING STRENGTH = 6 KSI) � I w WIND LOAD F- ° RESULTANT _ \I w_ N Z 2 C7 W I i S Z 950 SIDE VIEW PAD PAD WIDTH THICKNESS of s ANCHOR LOCATION FG3154-4G 1 ' _-- �---17 f ------ r 9.859" L V I ❑ —_--_- - I I I - 1 t 17.625" —� o ITEM I GENERATOR I 1 18KW 2 1OKW 3 14KW 4 - 16KW ! 5 16KW 6 17KW 7 17KW 8 2OKW 9 20KW 10 22KW tE.T\4GI i\1 EE Rl1 NO•TES'7 1- CONCRETE PADS WE] FULL THICKNESS OF 3- ALL OTHER UNITS NC 4- CONTRACTOR SHALL EMBED. AS PER CURRED FROM ANY CONCRETE F, :ETE PAD FOR GENERATORS D HONEYWELL UNITS) APPLICATIONS ONLY) ALLOWABLE DESIGN PRESSURE: SEE TABLE REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A JOB -SPECIFIC BASIS IN - ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE POSITIVE OR NEGATIVE DESIGN �� �� PRESSURE'ASD" CAPACITY VALUES LISTED HEREIN FOR liGZEN,ERAL NOTES ANY ASSEMBLY AS SHOWN. 114* THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE SIXTH EDITION (2017). 2. POSITIVE'AND NEGATIVE DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL BE \ -�' iDETERMINED BY OTHERS ON A JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE. MAXIMUM DIMENSIONS AND WEIGHT OF GENERATORS UNIT SHALL CONFORM TO SPECIFICATIONS STATED HEREIN. 4. THE AREA UNDER CONCRETE SLAB ON GROUND SHALL HAVE ALL VEGETATION, STUMPS, ROOTS, �hI �., ;` SAND FOREIGN (MATERIALS REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY l I� d ' �'I t� j_C_0''[HERS.'i-rf ESE.EONCRETE PADS HAVE BEEN DESIGNED FOR A MINIMUM SOIL COEFFICIENT OF FCTIONi=,0.25 AND MINIMUM BEARING CAPACITY OF 2,000 PSF AND MINIMUM SUBGRADE Glfad'� ,� 1r�M0pU_LUS = 100 PCI. SHOULD OTHER CONDITIONS OR MATERIALS BE ENCOUNTERED, THE ENGINEER OF RECORD SHALL BE NOTIFIED PRIOR TO PROCEEDING WITH THE WORK. 5. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY OTHERS. ALL \ \ MECHANICAL SPECIFICATIONS (CLEARSPACE, TONNAGE, ETC.) SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS RESPONSIBILITY OF THE CONTRACTOR. 6. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY, USE OF THIS SPECIFICATION BY CONTRACTOR, et al. INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM -MATERIAL O L�NGCH FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICESBEYOND`THAZWHICH IS%CALLED FOR ?P BY LOCAL, STATE, & FEDERAL CODES & FROM DEVIATIONS OFTMIS PLAN.45.-" �� ISOMETRIC VIEW 7. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BEITHE FULL`ORSPONSISiLrrf ,OF�THEINSTALLING CONTRACTOR. CONTRACTOR SHALL ENSURE THAT ANY REMOVED_OR-ALTERED�WATERPROOFING MEMBRANE IS RESTORED AFTER FABRICATION AND INSTALLATION,OFSTRUCTURE'PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE.FQR ANY VUATERFRQOFIfVG OR.LEAKAGE ISSUES WHICH MAY OCCUR AS WATER -TIGHTNESS SHALL BE THE�FULL.RESPONISI6ILITY` jTHE INSTALLING CONTRACTOR. �'� ��� _ �/^� 8. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIAL7Yj ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING. SURFACES TO HIIS�DESIGWWHICH SHALL BE COORDINATED BY THE PERMITTING CO...... Ofi.:l '\� �`i �� � � s j 9. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO.ANY SPECIFhC RROJECLSITE:, •„ INFORMATION CONTAINED HEREIN IS BASED ON CONTRACTOR -'SUPPLIED DATA"AND�7 ' MEASUREMENTS. ENGINEERING EXPRESS SHALL NOT BE HELD 9SPON'SIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN. WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION. ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE INFORMATION `-PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS AND FABRICATION AND INSTALLATION -----,'OF MATERIAES. ALTERATIONS OR ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND IPIVALIDATE OUR CERTIFICATION. I �10.•�'EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE ENC!ED. CQICJ E[E PAD SCHEDULE UNIT DIMENSIQNS(IN)` PAD DIMENSIONS (IN) WIND LOADS � MINIMUM � WEIGHT CONCRETE COCR PAD1 MODEL # PAD WEIGHT T -- ALLOWABLE ALLOWABLE WIDTH LENGTH 'HEIGHT ' WIDTH LENGTH THICKNESS (LBS) PRESSURE RESULTANT ice.' (PSF) (LBS) 2-5.00 48:00's J 29 j00'y -�i36:0; r FG3154 4G 30.56 53.56 4.00 240 30.72 296.93 25.00 48.00 29.00 407 FG3154-4G 30.56 53.56 4.00 240 33.13 320.25 25.00 48.00 29.00 435 FG3154-4G 30.56 53.56 4.00 240 34.57 334.21 25.00 48.00 29.00 448 FG3154-4G 30.56 53.56 4.00 240- 35.26 340.85 25.00 48.00 29.00 513 FG3154-4G 30.56 53.56 4.60-, 38:53 ?1372.44 -240-- ` 25.00 48.00 29.00 471 FG3154-4G 30.56 53.56 4.00 240z 1 \� /� 351.88 --.. it , 25.00 48.00 29.00 431 FG3154-4G 30.56 53.56 4.00 �_. -2407 3l37'v % 332.20 25.00 48.00 29.00 451 FG3154-4G 30.56 53.56 4.00 �240 �\342.12 25.00 48.00 29.00 516 FG3154-4G 30.56 53.56 4.00 -' -240-- i r-3SO 25.00 48.00 29.00 526 FG3154-4G 30.56 53.56 4.00 240 39.20 378.93 T PROVIDED BY MANUFACTURER, VERIFIED BY OTHERS. .� `a r� �� :• IS SHALL BE CONSTRUCTED WITH SOLID PRECAST CONCRETE, MINIMUM COMPRESSIVE STRENGTH�Ptr4;000•PSI=AT 2&-DAASjT� HOWN SHALL BE DESIGNED ON A CASE BY CASE BASIS. LARGER CONCRETE PADS MAY BE DESIGNED PER DIFFEREN-f�LOAD COMBINATIONS. )VIDE 5/8" DIA. (0.675" O.D.) GALV. TUBE ASTM A53B SCH 40 MIN. OR 1/2" DIA. SOLID COPPER BAR SPIKE, 4' MIN. EMBED. (ALSO SEE MIN. LECTRICAL CODE, BY OTHERS) INTO GROUND THROUGH CONCRETE PAD FOR SLIDING RESISTANCE PURPOSE, 12 DIAMETERS EDGE DISTANCE (NOT SHOWN) . W L-. BEN O, P.E,.. 00465d,9 _ :Z018 J rcaaD, P.LmEus NLyn IF_ BDN [ T15f0, P.E - - 82 8 D t-PERMIT ONLYN. ICE: IFTHIS SHEET DOES< - .CONTAIN AN ORIGINAL NATURE & ENGINEERS .i SIGNATURE ON SHEET 1,1HIS SHEET IS PART OF A DIGITALLY SIGNED FILE, SHALL REMAIN IN DIGITAL FORMAT, & PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED. IF THERE IS NO DIGITAL SIGNATURE ON SHEET 1 OR THIS SHEET DOES NOT CONTAIN AN ENGINEER'S ORIGINAL SIGNATURE & SEAL, THIS SHEET IS A COPY/DRAFT. to N Z o d' 'i d o O ILI m Y U i W� N� LL Xw ZWal O aL90� ><-0 Wtu wuiKN p-1 -1 wWu LuuI O LU mO,Z. 7 II., `. J l7 N a=w W p W ui tD p O oCD ., F__4 r' d v w O 1F- Q o N W z rn Q o I _ O�¢� Zov"i C9 g L wo U a m =U, U9OJo �al� Lu oD Lu z i-Q� �W Cn 5 u m p[ N Z O In t u �--I W o US F- a ao0 0 0 0 0o III ai III co SIR 7. O �w o S� Z 3 caa¢5 J J J W L" �>j W ~• K N N F<�6� COPYRIGHT ENGINEERING EXPRESS- 14-1669A SCALE: NTS UNLESS NOTED