LOAD CALCULATIONS
Taddei Residence
2178 sq/ft X 3VA
6534 VA
Dishwasher
1500 VA
Disposal
600 VA
Microwave
j
800 VA
Refrigerator
j
1000 VA
Appliance X 2
3000 VA
Washer
1500 VA
Range
9000 VA
Garage Door Opener
600 VA
Dryer
4500 VA
Water Heater
i
4500 VA
TOTAL
i
33534 VA
15Y 10 KVA + 40% of 23534 KVA
19414 VA
1- 10 KW AHU @ 65% 6500 VA Use Load Shed Module
0000 VA
TOTAL LOAD: 19414 VA
USE 22 KW GENERATOR