Re: Special Inspections
Building Structural Repairs and
Location: Atlantic View Condominium
5047 North AIA
Fort Pierce, Florida 34949
Mr. Cicio:
Civil & Structural Engineering Consultants
33408 Phone (561) 844-4060 Fax (561)844-1001
,,R OF INTENT
This letter is to inform you we will be prc
structural restoration project at the above
project specifications from the'contractor
during the project, including shoring, con
placements. The inspection plan is as fol
May 19, 2003
Project
fo. One Association, Inc.
iding Special Inspections for the upcoming
.ferenced location. You should have received
We will be inspecting all the structural work
•ete steel reinforcement, forms, and concrete
Inspection Plan:
• WORK LOCATIONS & DIRECTION: The engineer shall inspect repair areas and
direct work, as required, regarding thel location and estimated extent of all repairs.
• EXCAVTION LIMITS: The engineer shall inspect and approve, as required, all
limits of concrete removal and all steel reinforcement repairs.
• APPROVAL TO PLACE CONCRETE: The engineer shall inspect all areas prior to
concrete placement and give approval,1 for all concrete placements. The engineer
shall inspect all prep work, including forms, shoring, safety, steel bar repairs, and any
adjustments to excavation limits.
PLACEMENT OF CONCRETE: All
engineering and shall be inspected du
FINAL: The engineer shall inspect at
repairs for each phase of work.
of concrete require on -site
the placements.
approve, as required, the completion of all
If there are any forms to complete, please let me know. We will be sending you copies of
inspection reports and a final inspection report when the project is completed. If you
have any questions or require additional information, please let me know.
F
OP
ILE
i5 � h
Pavid • •
FL • Eng. #555014
Structural Engineering Associates,
Civil & Structural Engineering Consultants
751 Northlake Blvd., Suite 2C, North Palm Beach,
33408 Phone (561) 844-4060 Fax (561)844-1001
May 19, 2003
To: Mr. Joe Cicio I
St. Lucie County Public Works
Building and Zone Department
2300 Virginia Ave
Fort Pierce, Florida 34982-5652Building Official
� f
Re: Correction to Specifications
For: Atlantic View Condominium No. One Association, Inc.
5047 North A I A
Fort Pierce, Florida 34949
-1W .
Mr. Cicio:
This letter is to clear up the question on w ich waterproofing membrane is to be used at
the above referenced concrete restoration project. The specifications state CRW, when in
fact, the waterproofing membrane in which should have been specified is Sonneborne
Flextight. We do apologize for any inconvenience his may have caused you or your
Department. Please let us know if there is anything else we may be able to do to help.]
Sincerely,
i . Cols , P.E.
FL Reg. Eng. #55501
Cc: Ray Weber, Chase and Weber, Inc.
Structural Engineering Associates,
Civil & Structural Engineering Consultants
751 Northlake Blvd., Suite 2C, North Palm Beach,
To: Building Official
City of Fort Pierce
Re: Certification and Inspection of Bi
Atlantic View Condominium No,
5047 North AlA
Fort Pierce, Florida 34949
Dear Sir:
33408 Phone (561) 844-4060 Fax (561)844-1001
ilding Repairs
One Association, Inc.
May 13, 2003
This letter is to inform you of the upcoming repair project at the above referenced
address. The project consists of repairing spalled concrete on balconies around the
building, along with waterproofing the e�isting and repaired concrete.
We have surveyed the needed repairs and discussed demolition and repair options with
the contractor (Chase & Weber, Inc.). This letter is inform you that we would like to
proceed with repairs and have presented your office with project specifications prepared
for this effort.
In addition, I will be inspecting all work during the project, including demolition, limits
of excavation, repair procedures in accordance with ACI 318, ICRI guidelines, and FBC
code requirements. We will provide your office with copies of inspection reports as they
occur and a final inspection report upon completion of the project.
Should you have any questions or
please contact me.
Respectfully,
t
David Colston
FL Reg. Eng. #55501
any additional forms need to be completed,