Loading...
HomeMy WebLinkAbout1902-0589 - BUILDING PLAN PAGE 17-37J MH1.0 HVAC PLAN - 1/4" = 1'-0" 0 ENLARGED PLANS MECHANICAL KEYNOTES a d 1. EXHAUST FAN EF-1 TO BE SUSPENDED FROM STRUCTURE ABOVE. FAN TO RUN Z _ CONTINUOUSLY DURING OCCUPIED HOURS. w 2. WALL MOUNT AHU THERMOSTAT AT 48" AFF ADJACENT TO LIGHT SWITCH. Z N c14 WHERE SHOWN ON PLAN, MOUNT CO2 SENSOR AND HUMIDISTAT (AHU-1 & 3) v E ADJACENT TO THERMOSTAT. 3. NEW DUCTLESS SPLIT SYSTEM AIR CONDITIONING SYSTEM TO BE PROVIDED e� Lu w FOR ELECTRICALIDATA ROOMS. CONDENSING UNIT TO BE LOCATED OUTSIDE ° d WHERE SHOWN. MOUNT ON CONCRETE PAD. ANCHOR UNIT TO THE PAD ^ _ U 'N (HURRICANE HOLD-DOWN). ROUTE LINESETS PER MANUFACTURER'S V w a INSTALLATION INSTRUCTIONS. THE INDOOR UNIT SHALL MOUNT ABOVE THE I_ a 2 o DOOR TO AVOID FUTURE RACKING OR EQUIPMENT. CONDENSATE SHALL ROUTE = a TO FLOOR SINK IN ADJACENT JANITOR CLOSET AND DISCHARGE INDIRECTLY. ` 4. GRADE -MOUNTED AIR HANDLER AHU-1, AHU-2 &AHU-3 TO HAVE SUPPLY AIR AND �"�1 - W z RETURN AIR DUCT -FROM UNIT UP THROUGH SOFFIT INTO CEILING. RETURN AIR v >_ DUCT TO HAVE 1" ACOUSTICAL DUCT LINER FOR FIRST 10'-0" FROM UNIT. O y co COORDINATE WITH THE G.C. FOR NEW 4" HOUSE KEEPING PAD FOR EACH UNIT. Lu g EACH UNIT SHALL MOUNT ON A 14" TALL CURB. THE CURB SHALL BE ANCHORED TO THE PAD, AND THE UNIT TIED TO THE CURB USING HURRICANE HOLD DOWN 0 CLAMPS. CM a cD Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description r m 0 ZLU ® J •') J Q Q LL LU �U W ♦♦/�^ V♦ Oa U~ > o0 O ILL J W 0 If this document is sealed and signed in a digital or electronic format and is received from someonf other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SPB App/d By SDW Sheet Title BILEC()PV ENLARGED HVAC FLOOR PLANS Sheet Number MHU J q. progfPSSIVP Amazon DV61 Ft. Pierce, FL PAE ##83460006 Ventilation CFM/Person Exhaust O.A. CFM with 0.80 Area and ventilation section Square Feet o of Plumbing Fixtures People CFM/SF Required CFM/Plumbing table 403.3AA.1.2 AHU Notes required Fixture Required effectiveness mutiplier 100 VESTIBULE 228.00 0.00 0.00 0.06 0.00 0.00 17.10 1 101 EMPLOYEE STORAGE 450.00 9.00 0.00 0.12 0.00 0.00 67.50 1 102.BREAKROOM 2,882.00 9.00 120.00 0.06 5.00 0.00 966.15 1 103 CONTEMPLATION 52.00 0.00 1.00 0.06 5.00 0.00 10.15 1 104 MOTHERS ROOM 50.00 0.00 1.00 0.06 5.00 0.00 10.00 1 IOS WOMEN'S RESTROOM 615.00 6.00 0.00 0.00 0.00 I 300.00 0.00 3 1 106 MEN'S RESTROOM 615.00 6.00 0.00 0.00 0.00 300.00 0.00 3 1 107 TRAINING 910.00 0.00 21.00 0.06 5.00 0.00 199.50 3 108STORA6E 324.00 0.00 0.00 0.12 0.00 I 0.00 48.60 1 109 JANITOR CLOSET 107.00 0.00 0.00 1.00 0.00 0,00 107.00 N/A 1 110. ELECTRICAL 97.00 0.DO 0.00 0.00 0.00 I 0.00 0.00 N/A 111 CONFERENCE ROOM 296.00 0.00 12.00 0.06 5.00 0.00 97.20 3 112 OPEN OFFICE 537.00 0.00 8.00 0.06 5.00 I 0.00 90.28 3 113 OFFICE 101.00 0.00 1.00 0.06 5.00 0.00 13.83 3 114 STATION MANAGER 149.00 0.00 1,00 0.06 5.00 0.00 17.43 3 115 HR OFFICE 107.00 0.00 1.00 0,06 5.00 0,00 14.28 3 Minimum required OA: AHU-1 O.A.: 1,119.50 AHU-3 O.A.: 199.50 AHU-2 O.A.: 233.00 Notes: 1. Makeup air from warehouse. Ventilation Table - DVB1.xlsx 2/26/2019 AIR HANDLING UNIT SCHEDULE SUPPLY AIR OUTSIDE AIR COOLING COIL MARK BASED ON MODEL CFM BHP ESP TOTAL EDB EWB ELECTRIC HEAT (kW) V PH HZ MCA REMARKS RPM (IN-WG) CFM (TON) LDS LWB E.E.R. AHU-1 TRANE THH180F4RG`**HlB10100BOCO 3880 5 3450 0..5 1150 15 82.5 OF 69.5 OF 54.5 OF 54.4 OF 18.0 460 V 3 60 Hz 38.0 A 12.1 1, 2, 3, 4, 5, 6, 7, 8, 9 AHU-2 TRANE THC048E4EA*"*B6B 1130 0.5 890 0.75 210 4 81.8 OF 68.8 OF 54.5 OF 54.4 OF 5.0 460 V 3 60 Hz 14.0 A 14.2 1, 2, 6, 7, 8, 9 AHU-3 TRANE THC06OE4EA***H6B 1400 0.5 890 0.75 250 5 80.7 OF 67.8 OF 54.5 OF 54.4 °F 5.0 460 V 3 60 Hz 14.0 A 14.2 1, 2, 3, 4, 5, 6, 7, 8, 9 NOTES: 1. BASED ON LISTED MANUFACTURER, NO ALTERNATES. 2. FURNISH WITH CURB TO BE MOUNTED ON CONCRETE PAD ON GRADE. CURB TO BE ANCHORED TO THE PAD. FURNISH CURB WITH HURRICANE HOLD DOWN BRACKETS, 3. SINGLE ZONE VAV FAN CONTROL. 4. 2-STAGE COOLING. 5. FURNISH WITH DEMAND CONTROL VENTILATION, CO2 CONTROL, CO2 SENSOR TO BE WALL MOUNT AT 54"AFF. 6. ECONOMIZER, COMP ENTHALPY 0-100% WITH BAROMETRIC RELIEF, LOW LEAK DAMPERS. 7. 2" PLEATED FILTERS, MERV 8. 8. FURNISH WITH POWERED EXHAUST. 9. PROVIDE ELECTRICAL DISCONNECT SWITCH AT UNIT. DIFFUSER, REGISTER, & GRILLE SCHEDULE MARK MANUFACTURER MODEL CFM RANGE NECK SIZE FACE SIZE MOUNTING PATTERN MATERIAL REMARKS MIN FLOW MAX FLOW H" L" W" 0" L" W. SD-1 PRICE SCD 0 100 6" 24" 24" LAY -IN 4-WAY STEEL SD-2 PRICE SCD 101 200 8" 24" 24" LAY -IN 4-WAY STEEL SD-3 PRICE SCD 201 350 10" 24" 24" LAY -IN 4-WAY STEEL SD-4 PRICE SCD 351 600 12" 24" 24" LAY -IN 4-WAY STEEL SD-5 PRICE ASCD 101 240 8" 24" 24" SURFACE 4-WAY ALUMINUM SD-6 PRICE 22 440 615 8" 18" 10" 20" SIDEWALL STEEL ER-1 PRICE 60 230 400 10" 10" 24" 24" SURFACE 4-WAY ALUMINUM WITH BALANCING DAMPER RG-1 PRICE 60 0 100 6" 12" 12" SURFACE EGGCRATE ALUMINUM RG-2 PRICE 60 101 200 8" 24" 24" SURFACE EGGCRATE ALUMINUM RG-3 PRICE 60 351 600 12" 24" 24" SURFACE EGGCRATE ALUMINUM MINI -SPLIT AIR CONDITIONING UNIT SCHEDULE INDOOR UNIT MARK OUTDOOR UNIT MARK BASED ON MODEL SERVICE NOMINAL COOLNG MSH ELECTRICAL REMARKS V PH MOCP AC-1 CU-1 CARRIER 40MKCB22B-3 / 24AHA244A003 ELECTRICAL ROOM 146 24 208 1 25 1,2 NOTES: 1, FURNISH UNIT WITH DISCONNECT SWITCH. 2. AC-1 HAS DEDICATED POWER SUPPLY, 208.1 PH, MCA =1.0, MOCP = 15 AMPAC-1 HAS DEDICATED POWER SUPPLY, 208.1 PH, MCA =1.0, MOCP =15 AMP EXHAUST FAN SCHEDULE MARK MANUFACTURER MODEL CFM ESP 0,6 RPM SONES 1,725 10.60 ELECTRICAL UNIT WEIGHT NOTES HP(W) VOLTS PHASE EF-1 GREENHECK SO-100-A 1,000 0.25 0.17 120 120 1 1 46 11 1,2 1,2 EF-2 GREENHECK SP-B150 100 0.5 1,050 4.50 NOTE: 1. FURNISH UNITS WITH ELECTRICAL DISCONNECT. 2. OPERATE VIA TIMECLOCK, 7AM-6PM (ADJ.). LOUVER SCHEDULE PLAN MARK SERVICE SYSTEM AIR FLOW (CFM) SIZE MIN. FREE AREA (SQ FT) PRESSURE DROP (IN. W.G.) BASIS OF DESIGN WIDTH (IN) HEIGHT (IN) LV-1 RESTROOM EXHAUST 1000 36 24 1.94 0.05 RUSKIN EME4625 LV-2 JANITOR EXHAUST 100 18 12 0.2 0.05 RUSKIN EME4625 W a" a z f1 w CLn _ W z L0 t7 v •� z w � V �0 a Y /1 H c. W = � C0 w z w Ow Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02106/201' Revisions No. Date Descdpti r Z U. O P C, a H L c c C C C. c d LU J Uj In BE \CENS". No. 69 1 b ST F If this document is sealed and signed i or electronic format and is received frc other than the sealing professional ide the document, you must contact the sf professional in writing to validate authi the document. The sealing profession the seal and signature and shall not br any liability associated with it where th authenticity of any digital or electronic signature has not been validated in thi I Job Number 834 Drawn By App/d By Sheet Title MECHANICAL SCHEDULES Sheet Number MU J MECHANICAL SPECIFICATIONS m 0 .� 4� H ,n LLI s `5 no 0 w E6:4c z Qi 18 2 U w Q� c"s'. z � � - o f �s o w Iw zy ¢I� ti ¢ Lu a� a 0 I¢ � wR i¢ Z,� 0 � w3 L_g �o ¢I w8 0ZJ ¢ z I �� m �a= ¢ h na w aZ wQ: cow max" w I� U U w Qcc 6 ,ZQ PART1 GENERAL 1.01 SECTION INCLUDES A. Mechanical Systems. PART PRODUCTS 2.01 MECHANICAL IDENTIFICATION A. Nameplates 1. Description: Laminated three -layer plastic with engraved letters. a. Letter Color: White. b. Letter Height: 1/4 inch. c. Background Color: Black. d. Plastic: Conform to ASTM D709. B. Tags 1. Plastic Tags: Laminated three -layer plastic with engraved black letters on light contrasting background color. Tag size minimum 1-1/2 inch diameter. C. Pipe Markers 1. Manufacturers: a. Brady Corporation: www.bradycorp.com. b. Kolb! Pipe Marker Co.: www.kolbipipemarkers.com. c. MIFAB, Inc.: www.mifab.00m. d. Baton Identification Products, a Tricor Company: www.seton.com. e. Substitutions: See Section 01 6000 - Product Requirements. 2. Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic, preformed to fit around pipe or pipe covering; minimum information indicating flow direction arrow and identification of fluid being conveyed. 3. Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure sensitive adhesive backing and printed markings. D. Schedule 1. Air Handling Units: Nameplates. 2. Automatic Controls: Tags. Key to control schematic. 3. Control Panels: Nameplates. 4. Ductwork: Nameplates. 5. Piping: Pipe markers. 6. Relays: Tags. 7. Small -sized Equipment: Tags. 8. Valves: Tags. 2.02 TESTING AND BALANCING A. Perform total system balance in accordance with one of the following: 1. SMACNA (TAB). B. Begin work after completion of systems to be tested, adjusted, or balanced and complete work prior to Substantial Completion of the project. C. TAB Agency Qualifications: 1, Company specializing in the testing, adjusting, and balancing of systems specified in this section. 2. Having minimum of three years documented experience. 3. Certified by one of the following: a. AABC, Associated Air Balance Council: www.aabc.00m/#sle; upon completion submit AABC National Performance Guaranty. b. NEBB, National Environmental Balancing Bureau: www.nebb.org/#sle. c. TABB, The Testing, Adjusting, and Balancing Bureau of National Energy Management Institute: www.tabbceitified.org/#sle. D. TAB Supervisor and Technician Qualifications: Certified by same organization as TAB agency. E. Air System Procedure 1. Adjust air handling and distributions stems to provide required or design supply, 1 9 Y P q 9 PPY, return, and exhaust air quantities at site altitude. 2. Make air quantity measurements in ducts by Pitot tube traverse of entire cross sectional area of duct. 3. Measure air quantities at air inlets and outlets. 4. Adjust distribution system to obtain uniform space temperatures free from objectionable drafts and noise. 5. Use volume control devices to regulate air quantities only to extend that adjustments do not create objectionable air motion or sound levels. Effect volume control by duct internal devices such as dampers and splitters. 6. Vary total system air quantities by adjustment of fan speeds. Provide drive changes required. Vary branch air quantities by damper regulation. 7. Provide system schematic with required and actual air quantities recorded at each outlet or inlet. 8. Measure static air pressure conditions on air supply units, including filter and coil pressure drops, and total pressure across the fan. Make allowances for 50 percent loading of filters. 9. Adjust outside air automatic dampers, outside air, return air, and exhaust dampers for design conditions. 10. Measure temperature conditions across outside air, return air, and exhaust dampers to check leakage. 11, Measure building static pressure and adjust supply, return, and exhaust air systems to provide required relationship between each to maintain approximately 0.05 inches positive static pressure near the building entries. 12. Check multi -zone units for motorized damper leakage. Adjust air quantities with mixing dampers set first for cooling, then heating, then modulating. 2.03 DUCT INSULATION A. Glass Fiber, Flexible 1. Insulation: ASTM C553; flexible, noncombustible blanket. a. 'K' value: 0.36 at 75 degrees F, when tested in accordance with ASTM C518. b. Maximum Service Temperature: 1200 degrees F. c. Maximum Water Vapor Absorption: 5.0 percent by weight. 2. Vapor Barrier Jacket: a. Kraft paper with glass fiber yarn and bonded to aluminized film. b. Moisture Vapor Permeability: 0,02 perm inch, when tested in accordance with ASTM E96/E96M. c. Secure with pressure sensitive tape. 3. Vapor Barrier Tape: a. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film, with pressure sensitive rubber -based adhesive. B. Schedules 1. Interior Supply Air Ductwork, (concealed; units with cooling): a. Flexible Glass Fiber Duct insulation: 1 1/2 inch thick. 2. Interior Return Air Ductwork, (concealed; units with cooling): a. Flexible Glass Fiber Duct insulation: 1 1/2 inch thick. 3. Interior Supply Air Ductwork, (exposed; units with cooling): a. Not Insulated. 4, Interior Return Air Ductwork, (exposed; units with cooling): a. Not insulated. 5. Interior Supply Air Ductwork, (units without cooling): a. Not Insulated. 6. Interior Return Air Ductwork, (units without cooling): a. Not insulated. 7. Exterior Supply and Return Air Ductwork: a. Double wall ductwork with 2-inch-thick flexible Glass Fiber Duct insulation. 8. Exhaust Ductwork: a. Not Insulated. 9. All Transfer Air Ductwork; a. Duct Liner: 1 inch thick 2.04 PIPING INSULATION A. Regulatory Requirements 1. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723. B. Flexible Elastomeric Cellular Insulation 1. Manufacturer: a. Armacell LLC; AP Artnaflex: www.armacell.us/#sle. 2. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM C534IC534M Grade 1; use molded tubular material wherever possible. a. k value of 0.28 at 75 degrees F. b. Minimum Service Temperature: Minus 40 degrees F. c. Maximum Service Temperature: 180 degrees F. d. Connection: Waterproof vapor barrier adhesive. e. Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation. C. Schedule 1. Cooling Systems: a. Refrigerant Suction: Flexible Elastomeric Cellular Insulation: Thickness: 1 inch. a. Refrigerant Hot Gas: Not insulated. 2.05 REFRIGERANT SYSTEMS A. Copper Tube: ASTM B280, H58 hard drawn or 060 soft annealed. 1. Fittings: ASME B16.22 wrought copper. 2. Joints: Braze, AWS A5.8M/A5.8 BCuP silver/phosphorus/copper alloy. B. Copper Tube to 7/8 inch OD: ASTM B88 (ASTM B88M), Type K (A), annealed. 1. Fittings: ASME B16.26 cast copper. 2. Joints: Flared. C. Pipe Supports and Anchors: 1. Provide hangers and supports that comply with MSS SP-58. a. If type of hanger or support for a particular situation is not indicated, select appropriate type using MSS SP-58 recommendations. 2. Hangers for Pipe Sizes 1/2 to 1-1/2 Inch: Malleable iron adjustable swivel, split ring. 3. Copper Pipe Support: Carbon steel ring, adjustable, copper plated. 4. Hanger Rods: Mild steel threaded both ends, threaded one end, or continuous threaded. 5. Inserts: Malleable iron case of galvanized steel shell and expander plug for threaded connection with lateral adjustment, top slot for reinforcing rods, lugs for attaching to forms; size inserts to suit threaded hanger rods. D. Refrigerant: R-134a, tetrafluoroethane as defined in ASHRAE Std 34. E. Moisture and Liquid Indicators: Indicators: Single port type, UL listed, with copper or brass body, flared or solder ends, sight glass, color coded paper moisture indicator with removable element cartridge and plastic cap; for maximum temperature of 200 degrees F and maximum working pressure of 500 psi. F. Valves 1. Ball Valves: a. Two piece bolted forged brass body with teflon ball seals and copper tube extensions, brass bonnet and seal cap, chrome plated ball, stem with neoprene ring stem seals; for maximum working pressure of 500 psi and maximum temperature of 300 degrees F. 2. Service Valves: a. Forged brass body with copper stubs, brass caps, removable valve core, integral ball check valve, flared or solder ends, for maximum pressure of 500 psi. G. Strainers 1. Straight Line or Angle Line Type: a. Brass or steel shell, steel cap and flange, and replaceable cartridge, with screen of stainless steel wire or monel reinforced with brass; for maximum working pressure of 430 psi. H. Check Valves 1. Globe Type: a. Cast bronze or forged brass body, forged brass cap with neoprene seal, brass guide and disc holder, phosphor -bronze or stainless steel spring, teflon seat disc; for maximum temperature of 300 degrees F and maximum working pressure of 425 psi. 2. Straight Through Type: a. Brass body and disc, phosphor -bronze or stainless steel spring, neoprene seat; for maximum working pressure of 500 psi and maximum temperature of 200 degrees F. I. Solenoid Valves 1. Valve: AHRI 760 I-P, pilot operated, copper, brass or steel body and internal parts, synthetic seat, stainless steel stem and plunger assembly (permitting manual operation in case of coil failure), integral strainer, with flared, solder, or threaded ends; for maximum working pressure of 500 psi. 2. Coil Assembly: UL 429, UL listed, replaceable with molded electromagnetic coil, moisture and fungus proof, with surge protector and color coded lead wires, integral junction box with pilot light; J. Expansion Valves 1. Angle or Straight Through Type: AHRI 750 design suitable for refirgerant, bra ss body, internal or external equalizer, bleed hole, adjustable superheat setting, replaceableinle t strainer, with non -replaceable capillary tube and remote sensing bulb and remote bulb well. 2. Selection: Evaluate refrigerant pressure drop through system to determine available pressure drop across valve. Select valve for maximum load at design operating pressure and minimum 10 degrees F superheat. Select to avoid being undersized at full load and excessively oversized at part load. K. Flexible Connectors 1. Corrugated stainless steel hose with single layer of stainless steel exterior braiding, minimum 9 inches long with copper tube ends; for maximum working pressure of 500 psi. 2,06 DUCTWORK A. Galvanized Steel for Ducts: Hot -dipped galvanized steel sheet, ASTM A6531A653M FS Type B, with G601180 coating. B. Joint Sealers and Sealants: Non -hardening, water resistant, mildew and mold resistant. 1. Type: Heavy mastic or liquid used alone or with tape, suitable for joint configuration and compatible with substrates, and recommended by manufacturer for pressure class of ducts. 2. Surface Burning Characteristics: Flame spread index of zero and smoke developed index of zero, when tested in accordance with ASTM E84. C. Hanger Rod: ASTM A361A36M; steel, galvanized; threaded both ends, threaded one end, or continuously threaded. D. Hanger Fasteners: Attach hangers to structure using appropriate fasteners, as follows: 1. Concrete Wedge Expansion Anchors: Complying with ICC-ES AC193. 2. Masonry Wedge Expansion Anchors: Complying with ]CC -ES AC01. 3. Concrete Screw Type Anchors: Complying with ICC-ES AC193. 4. Masonry Screw Type Anchors: Complying with ICC-ES AC106. 5. Concrete Adhesive Type Anchors: Complying with ICC-ES AC308. E. Low Pressure Supply (Heating Systems): 1/2 inch w.g. pressure class, galvanized steel. F. Low Pressure Supply (System with Cooling Coils): 1/2 inch w.g. pressure class, galvanized steel. G. Return and Relief: 1/2 inch w.g. pressure class, galvanized steel. H. General Exhaust: 1/2 inch w.g. pressure class, galvanized steel, 1. Joint Sealers and Sealants: Non -hardening, water resistant, mildew and mold resistant. 1. Type: Heavy mastic or liquid used alone or with tape, suitable for joint configuration and compatible with substrates, and recommended by manufacturer for pressure class of ducts. 2. Construct of 16 gage, 0.0598 inch sheet steel using continuous external welded joints in rectangular sections. 3. VOC Content: Not more than 250 g/L, excluding water. J. Outside Air Intake: 1/2 inch w.g, pressure class, galvanized steel. K. Hanger Rod: ASTM A 36/A 36M; steel, galvanized; threaded both ends, threaded one end, or continuously threaded. L. Ductwork Fabrication 1. Fabricate and support in accordance with SMACNA (DCS) and as indicated. 2. Provide duct material, gages, reinforcing, and sealing for operating pressures indicated. 3. Increase duct sizes gradually, not exceeding 15 degrees divergence wherever possible; maximum 30 degrees divergence upstream of equipment and 45 degrees convergence downstream. 4. Fabricate con tinuously welded round and oval duct fittings in accordance with SMACNA (DCS). 5. Where ducts are connected to exterior wall louvers and duct outlet is smaller than louver frame, provide blank -out panels sealing louver area around duct. Use same material as duct, painted black on exterior side; seal to louver frame and duct. 2.07 DUCT ACCESSORIES A. Volume Control Dampers 1. Single Blade Dampers: 1) Fabricate for duct sizes up to 6 by 30 inch. 2) Blade: 24 gage, 0.0239 inch, minimum. 2. Multi -Blade Damper: Fabricate of opposed blade pattern with maximum blade sizes 8 by 72 inch. Assemble center and edge crimped blades in prime coated or galvanized channel frame with suitable hardware. 1) Blade: 18 gage, 0.0478 inch, minimum. 3. End Bearings; Except in round ducts 12 inches and smaller, provide end bearings. On multiple blade dampers, provide oil -impregnated nylon, thermoplastic elastomer, or sintered bronze bearings. a. Manufacturers: 1) Carlisle HVAC Products; Dynair End Bearing Leak Resistant Sets: www.cadlslehvac.com/#sle. 1) Elgen Manufacturing Company, Inc; Snap -in Bushing: www.elgenmfg.com/ #sle. 4. Quadrants: a. Provide locking, indicating quadrant regulators on single and multi -blade dampers. b. On insulated ducts mount quadrant regulators on stand-off mounting brackets, bases, or adapters. c. Where rod lengths exceed 30 inches provide regulator at both ends. d. Manufacturers: 1) Carlisle HVAC Products; Dynair Double Shear Rattle Free Quadrants 112 inch: di m vow ca s ehvac co /#sle. 2.08 VENTILATORS A. Manufacturers 1. Greenheck: www.greenheck.00m. B. Power ventilators - general 1. Static and Dynamically Balanced: AMCA 204 - Balance Quality and Vibration Levels for Fans. 2. Performance Ratings: Determined in accordance with AMCA 210 and beading the AMCA Certified Rating Seal. 3. Sound Ratings: AMCA 301, tested to AMCA 300 and bearing AMCA Certified Sound Rating Seal. 4. Fabrication: Conform to AMCA 99. 5. Electrical Components: Listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated. C. Roof Exhausters 1. Fan Unit: V-belt or direct driven as indicated, with galvanized steel with baked -on enamel housing; resilient mounted motor; 112 inch mesh, 0.62 Inch thick aluminum wire birdscreen; square base to suit roof curb with continuous curb gaskets. 2. Roof Curb: 24 inch high self -flashing of galvanized steel with continuously welded seams, built-in cant strips. 3. Disconnect Switch: Factory wired, non -fusible, in housing for thermal overload protected motor and wall mounted multiple speed switch, 4. Backdraft Damper: Gravity actuated, aluminum multiple blade construction, felt edged with offset hinge pin, nylon bearings, blades linked, and line voltage motor drive, power open, spring return. 5. Sheaves: Cast iron or steel, dynamically balanced, bored to fit shafts and keyed; variable and adjustable pitch motor sheave selected so required rpm is obtained with sheaves set at mid -position; fan shaft with self -aligning pre -lubricated ball bearings. D. Cabinet exhaust fans 1. Centrifugal Fan Unit: V-belt or direct driven with galvanized steel housing lined with acoustic insulation, resilient mounted motor, gravity backdraft damper in discharge. 2. Grille: Molded white plastic. 3. Sheaves: Cast iron or steel, dynamically balanced, bored to fit shafts and keyed; variable and adjustable pitch motor sheaves selected so required rpm is obtained with sheaves set at mid -position; fan shaft with self -aligning pre -lubricated ball bearings. E. Low velocity, high volume (Ivhv) fans 1. Manufacturers: a. Big Ass Fans - Basic Six: www.bigasssolution9,com. 2. Features: a. Airfoils - Six patented aluminum airfoils (mill finlsh). b. Winglets - Powerfoil winglets eliminate wind noise (safety yellow). c. Motor and Gearbox - Industrial -grade motor and gearbox feature inline helical -cut gears for efficient, durable, and reliable operation; lubricated for life with synthetic oil. d. Hub System - Machine -cut precision components for uniform load distribution. e. Controller - Onboard NEMA 4X VFD eliminates RFI and EMI noise; wall -mounted keypad allows floor level control of all fan functions. f. Mounting Options - Standard upper mount installs to 1-beams and angle iron; optional kits allow for mounting to large ]-beams, solid beams, Z-purlins, and pitched roofs. g. Safety Features - Airfoil retainers, hub retainer clips, safety cables, Grade 8 bolts, fire relay, h. Size: 1) 24 ft diameter. 2 231 lb weight. 2 61 RPM maximu,sP eed. 1. SmartSense Wall Control 1) SmarfSense is an automated system with three user modes: Winter, Summer and Manual. a) Winter Mode: Automatically adjusts speed to minimize temperature differential between the floor and ceiling b) Summer Mode: Increases fan speed as the floor -level temperature rises c) Manual Mode: Takes the system off autopilot and gives the user full control of fan operation 2.09 AIR OUTLETS . A. Rectangular ceiling diffusers 1. Type: Provide plaque diffuser to discharge air in four way pattern with sectorizing baffles where indicated. 2. Connections: Round. 3. Frame: Provide inverted T-bar type. 4. Fabrication: Steel with baked enamel finish. 5. Color: As selected by Architect from manufacturer's standard range. B. Ceiling exhaust and return registers/grilles 1. Type: Streamlined blades, 3/4 inch minimum depth, 3/4 inch maximum spacing, with blades set at 45 degrees, vertical face. 2. Frame: 1.1/4 inch margin with concealed or panelized lay -in ceiling mounting. 3. Fabrication: Steel with 20 gage, 0.0359 inch minimum frames and 22 gage, 0.0299 inch minimum blades, steel and aluminum with 20 gage, 0,0359 inch minimum frame, or aluminum extrusions, with factory baked enamel finish. 4. Color: To be selected by Architect from manufacturer's standard range. 5. Damper: Integral, gang -operated; opposed blade type with removable key operator, operable from face where not individually connected to exhaust fans. C. Louvers 1. Acceptable Manufacturers a. Ruskin b. Greenheck c. Louvers and Dampers d. Type: 4 inch deep with blades on 45 degree slope with center baffle and return bend, heavy channel frame, 1/2 inch square mesh screen over exhaust and 1/2 inch square mesh screen over intake. e. Fabrication: 12 gage, 0.1046 inch thick extruded aluminum, welded assembly, With factory prime coat finish. f. Color: To be selected by Architect from manufacturer's standard range. g. Mounting: Furnish with exterior angle flange for installation. 2.10 AIR HANDLING UNITS A. Manufacturers 1. Trans, a brand of Ingersoll Rand: www.trane.00m. B. Manufactured units 1. General a. The units shall be dedicated vertical airflow. The operating range shall be between 115OF and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition. b. Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340/360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces (gas heating units). 2. Casing a. Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch, 1- pound density foil -faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2-Inch, 1-pound density foil -faced, closed -cell material. The downflow unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8-inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. 3. Compressors a. All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus b. 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Dual compressors are available on all standard efficiency models and 12.5 to 20 tons high efficiency models and allow for efficient cooling utilizing 3 stages of compressor operation (high efficiency models only). 25 tons high efficiency units have 3 compressors for up to 4 stages of compressor operation. 4. Controls a. Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24- volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, sOd provides better building comfort. A centralized control shall provide anti -short cycle timing and time delay between compressors to provide a higher level of machine protection. Crankcase Heaters a. These band heaters provide improved compressor reliability by warming the oil to prevent migration during off -cycles or low ambient conditions. These are standard on all Voyager models. Defrost Controls a. Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin to significantly reduce unit capacity. 1) Discharge Line Thermostat a) A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in rase of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage. Evaporator and Condenser Coils a. Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard on high efficiency models and microchannel shall be standard on standard efficiency for evaporator coils. b. Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 prig and pressure tested to 450 psig. Sloped condensate drain pans are standard. Filters a. Two inch standard filters shall be factory supplied on all units. Optional MERV 8 or MERV 13 filters with filter removal tool shall be available. 1. Gas Heating Section a) The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. b) In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition. c) After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions. The 12Yr 25 tons shall have two stage heating (Gas/Electric only). 2. Indoor Fan a) Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler -arm assembly for quick -adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 3. Outdoor Fans a) The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built- in thermal overload protection. 4. Phase Monitor a) The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition. 5. Refrigerant Circuits a) Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Thermal Expansion Valves (TXVs) shall be standard on all high efficiency units. 6. Unit Top a) The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. 7. Variable Frequency Drive a) Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation, as well as modulating gas heat. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. b) Bypass control will simply provide full nominal airflow in the event of drive failure. c) Modulating gas heat models with VFDs allow tighter space temperature control with less temperature swing. 8. Factory Installed Options a) CO2 Sensor Wiring 1) The unit wiring for field installed CO2 sensors. Factory -installed CO2 sensor wiring saves time and ensures proper unit connections for the field installed CO2 sensor kits. b) Complete CoatTM' Microchannel Condenser Coil 1) The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air, and other corrosive environments. This coating shall be available on microchannel condenser coils. c) Condensate Overflow Switch 1) This option shall shut the unit down in the event that a clogged condensate drain line prevents proper condensate removal from the unit. d). High Efficiency Motors 1) This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models. a) Hinged Access Doors 1) Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all downflow, models. f) Stainless Steel Drain Pan 1) This option provides excellent corrosion and oxidation resistance. Drain pan shall be constructed of 304 stainless steel. g) Stainless Steel Heat Exchanger 1) Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/ Electric only). h) Supply, Return and Plenum Air Smoke Detector 1) With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all downflow, models. Supply and/or Return Detectors may not be used with the Plenum Smoke Detector. i) Two -Inch Pleated Filters 1) Two-inch MERV 8 and MERV 13 media filters with filter removal tool shall be available on all models. j) Electric Heaters 1) Electric heat modules shall be available for installation within the basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide single point connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory installed. 9. Factory or Field Installed Options a) Indoor Fan Motor Shaft Grounding Ring 1) Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Ring shall be maintenance free circumferential ring of conductive micro fibers that discharges voltages to ground. b) Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered. This option is available on all downflow models. 10. Field Installed Options a) Economizer - Low Leak 1) This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ftA2@1" wg exterior air, 4 cfm/ftA2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. b) Powered Exhaust 1) The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization. c) Roof Curb 1) The roof curb shall be designed to mate with the unit and provide support and a water tight installation when installed property. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. d) Zone Sensors 1) This option shall be provided to interface with ReliaTel and shall be available in either manual, automatic, programmable with night setback, with system malfunction lights or remote sensor options. 2.11 SPLIT SYSTEM AIR CONDITIONERS A. Manufacturers 1. Carrier Corporation: www.carrier.com. 2. Trans Inc: www.trane.com. 3. York International Corporation / Johnson Controls: www.york.com. B. System Design 1. Split -System Cooling Unit: Self-contained, packaged, matched factory -engineered and assembled, pre -wired indoor and outdoor units; UL listed. a. Cooling: Air -source electric unit located in outdoor unit with evaporator. b. Provide refrigerant lines internal to units and between indoor and outdoor units, factory cleaned, dried, pressurized and sealed, with insulated suction line. 2. Performance Requirements: See Drawings for additional requirements. C. Indoor Units for Ductless Systems 1. Indoor Units: Self-contained, packaged, factory assembled, pre -wired unit consisting of cabinet, supply fan, evaporator coil, and controls; wired for single power connection with control transformer, a. Location: High -wall. b. Cabinet: Galvanized steel. a. Finish: White. c. Fan: Line -flow fan direct driven by a single motor. d. Filter return air with washable antioxidant pre -filter and a pleated anti -allergy enzyme filter. e. Evaporator Coils: Copper tube aluminum fin assembly, galvanized or polymer drain pan sloped in all directions to drain, drain connection, refrigerant piping connections, restricted distributor or thermostatic expansion valve. 1) Construction and Ratings: In accordance with AHRI 210/240 and UL 207. 2) Manufacturer: System manufacturer. f. Furnish unit with integral cooling coil condensate pump. D. Condensing Unit 1. Condensing Unit: Self-contained, packaged, pre -wired unit consisting of cabinet, with compressor and condenser. a. Comply with AHRI 210/240. b. Refrigerant: Use only refrigerants that have ozone depletion potential ODP of 9 Y 9 P P a( ) zero and global warming potential (GWP) of less than 50, c. Refrigerant: R-410A. d. Cabinet: Galvanized steel with baked enamel finish, easily removed and secured access doors with safety interlock switches, glass fiber insulation with reflective liner. e. Construction and Ratings: In accordance with AHRI 210/240 with testing in accordance with ASHRAE Std 23.1 and UL 207. 2. Air Cooled Condenser: Aluminum fin and copper tube coil, AHRI 520 with direct drive axial propeller fan resiliently mounted, galvanized fan guard. a. Condenser Fans: Direct -drive propeller type. b. Condenser Fan Motor: Enclosed, 1-phase type, permanently lubricated. 3. Coil: Air-cooled, aluminum fins bonded to copper tubes. 4. Accessories: Filter drier, high pressure switch (manual reset), low pressure switch (automatic reset), service valves and gage ports; thermometer well (in liquid line). a. Provide thermostatic expansion valves. 5. Operating Controls: a. Control by room thermostat to maintain room temperature setting. E. Accessory Equipment 1. Room Thermostat: Wall -mounted, electric solid state microcomputer based room thermostat with remote sensor to maintain temperature setting; low -voltage; with following features: Preferential rate control to minimize overshoot and deviation from setpoint. Thermostat Display: 1) Actual room temperature. 2) System Mode Indication: Heating, Cooling, Fan Auto, Off, and On, Auto or On, Off. W �� VA_ W 01 0 ^� C1 Issuances PERMITS: 02127/2019 SITE PLAN REVIEW: 02/06/20 Revisions No. Date Descrip r Im 0 P ISt A IT now J UJ 0 ee^• g ­..',0 Ny�\Nark, �Q :N`' 1` rr`,`C. E NS ,,Q, 9Q , Nfo. 69 1 * j A If this document is sealed and signed or electronic format and is received fr other than the sealing professional id the document, you must contact the: professional in writing to validate autt the document. The sealing professor the seal and signature and shall not t any liability associated with it where tl authenticity of any digital or electronic signature has not been validated in tf Job Number 83, Drawn By Appld By Sheet Title am- RL J C 0 f, I MECHANICAL SPECIFICATIOI' Sheet Number MTO ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS A AMPERES KV KILOVOLT AAC ABOVE ACCESSIBLE CEILING KVA KILOVOLT -AMPERES AC AIR COMPRESSER KVAR KILOVOLT -AMPERES REACTIVE ACU AIR CONDITIONING UNIT KW KILOWATTS AD ACCESS DOOR KWH KILOWATT-HOURS ADO AUTOMATIC DOOR OPENER LEED LEADERSHIP IN ENERGY AND ENVIRONMENTAL AFG ABOVE FINISH GRADE DESIGN AR ARC FAULT CIRCUIT INTERRUPTER LP LIGHT POLE AHJ AUTHORITY HAVING JURISDICTION LT LITE LIGHT AHU AIR HANDLING UNIT LTG LIGHTING AL ALUMINUM LV LOW VOLTAGE AMPL AMPLIFIER M/C MOMENTARY CONTACT ANNUN ANNUNCIATOR MAX MAXIMUM AP ACCESS PANEL MC MECHANICAL CONTRACTOR APPROX APPROXIMATE MCA MINIMUM CIRCUIT AMPS AS AMP SWITCH MCB MAIN CIRCUIT BREAKER AT AMP TRIP MCC MOTOR CONTROL CENTER ATS AUTOMATIC TRANSFER SWITCH MD MOTORIZED DAMPER AUX AUXILARY MD MOTION DETECTOR AWG AMERICAN WIRE GAUGE MDC MAIN DISTRIBUTION CENTER B BOILER MOP MAIN DISTRIBUTION PANEL BAS BUILDING AUTOMATION SYSTEM MECH MECHANICAL BATT BATTERY MFDS MAIN FUSED DISCONNECT SWITCH BF BARRIER FREE MH MANHOLE BFG BELOW FINISHED GRADE MIC MICROPHONE BMS BUILDING MANAGEMENT SYSTEM ML MAGNETIC DOOR LOCK BOD BOTTOM OF DEVICE MLO MAIN LUGS ONLY BSMT BASEMENT MMS MANUAL MOTOR STARTER C CONDUIT MOA MULTIOUTLET ASSEMBLY CAB CABINET MOP MAXIMUM OVERCURRENTPROTECTION CAP CAPACITY MS MAGNETIC STARTER CATV COMMUNITY ANTENNA TELEVISION MSBD MAIN SWITCH BOARD CB CIRCUIT BREAKER MT MOUNT CCTV CLOSED-CIRCUIT TELEVISION MTR MOTOR, MOTORIZED CIF CEILING FAN MTS MANUAL TRANSFER SWITCH CFL COMPACT FLUORESCENT NO NORMALLY CLOSED CH CABINET HEATER NEMA NATIONAL ELECTRICAL MANUFACTURER'S CKT CIRCUIT ASSOCIATION CL CENTERLINE NF NONFUSED CLR CLEAR, CLEARANCE NFDS NONFUSED DISCONNECT SWITCH CMPR COMPRESSOR NIL NIGHT -LIGHT COL COLUMN NO NORMALLY OPEN COMB COMBINATION NPF NORMAL POWER FACTOR CONC CONCRETE OH OVERHEAD CONN CONNECT, CONNECTED, CONNECTION OHD OVERHEAD DOOR CONV CONVECTOR OIL OVERLOAD CID CIRCULATING PUMP P PUMP CR CARD READER PA PUBLICADDRESS CT COOLING TOWER PB PULL BOX CT CURRENT TRANSFORMER PE PNEUMATIC ELECTRIC CU COPPER PED PEDESTAL DEPT DEPARTMENT PERF PERFORATE,PERFORATED DIET DETAIL PF PUMP - FIRE PROTECTION DISC DISCONNECT PH PHASE DIST DISTRIBUTION PIV POST INDICATING VALVE DL DEAD LOAD PNL PANEL DPR DAMPER PP POWER POLE DS DOOR SWITCH PRI PRIMARY DT DOUBLE THROW PROJ PROJECTOR DW DISHWASHER PRV POWER ROOF VENTILATOR DWH DOMESTIC WATER HEATER PTZ PAN TILT ZOOM EF EXHAUST FAN PVC POLYVINYL CHLORIDE EHC ELECTRIC HEATING COIL PAR POWER EIH ELECTRIC INFARED HEATER RA RETURN AIR ELEC ELECTRIC, ELECTRICAL RAF RETURN AIR FAN ELEV ELEVATOR RECEPT RECEPTACLE EM EMERGENCY RIO ROUGH -IN ONLY EMS ENERGY MANAGEMENT SYSTEM RMC RIGID METAL CONDUIT EMT ELECTRICAL METALLIC TUBING RNMC RIGID NONMETALLIC CONDUIT ES ELECTRICAL STRIKE RT RAINTIGHT EWC ELECTRIC WATER COOLER RTU ROOFTOP UNIT EWH ELECTRIC WATER HEATER S/S START/STOP PUSHBUTTONS EXP EXPLOSION PROOF SA SUPPLY AIR F FAHRENHEIT SAF SUPPLY AIR FAN FA FIRE ALARM SEC SECONDARY FACP FIRE ALARM CONTROL PANEL SECT SECTION FBO FURNISHED BY OTHERS BHT SHEET FC FLEXIBLE CONNECTION SM SURFACE MOUNTED FCU FAN COIL UNIT SIN SOLID NEUTRAL FOR FEEDER SP SPARE FDS FUSED DISCONNECT SWITCH SPD SURGE PROTECTIVE DEVICE FIXT FIXTURE SPKR SPEAKER FL FLUORESCENT SS STAINLESS STEEL FLA FULL LOAD AMPS SSW SELECTOR SWITCH FLEX FLEXIBLE STA STATION FLR FLOOR, FLOORING STOR STORAGE FMC FLEXIBLE METAL CONDUIT SW SWITCH FSB FLAT SCREEN BOX SWBD SWITCHBOARD FU FUSE SWGR SWITCHGEAR FURN FURNISH, FURNISHED SYM SYMMETRY, SYMMETRICAL GALV GALVANIZED SYS SYSTEM GEN GENERATOR TEL TELEPHONE GFI GROUND FAULT CIRCUIT INTERRUPTOR TERM TERMINAL GFP GROUND FAULT CIRCUIT PROTECTOR TL TWIST LOCK GND GROUND TOD TOP OF DEVICE GRMC GALVANIZED RIGID METAL CONDUIT TR TAMPER RESISTANT HG HOSPITAL GRADE TTC TELEPHONE TERMINAL CABINET HOA HAND-OFF AUTOMATIC TU TERMINAL UNIT HP HORSEPOWER TV TELEVISION HPF HIGH POWER FACTOR TVTC TELEVISION TERMINAL CABINET HSKP HOUSEKEEPING PAD UN UNIT VENTILATOR HTG HEATING UC UNDER CABINET HTP HEAT PUMP UE UNDERGROUND ELECTRICAL HTR HEATER UG UNDERGROUND HTR HEATER UH UNIT HEATER HUM HUMIDIFIER UT UNDERGROUND TELEPHONE HV HIGH VOLTAGE UV ULTRAVIOLET HWP HYDRONIC WATER PUMP V VOLTS IBC INTERNATIONAL BUILDING CODE VA VOLT-AMPERES IC INTERRUPTING CAPACITY VDT VIDEO DISPLAY TERMINAL IG ISOLATED GROUND VFD VARIABLE FREQUENCY DRIVE IMC INTERMEDIATE METAL CONDUIT W WATTS IR INFRARED WG WIRE GUARD JBOX JUNCTION BOX WH WATER HEATER KO KNOCKOUT WP WEATHERPROOF KS KEY SWITCH XFER TRANSFER XFMR TRANSFORMER 0 PHASE DATA SYMBOL LEGEND E - ELECTRICAL CONTRACTOR 06 m m X- OTHERS xo ¢ m w m HEIGHT TO m 0 LU ¢ o MIDDLE OF U U m > o N ? SYMI',OL DEVICE DESCRIPTION U.N.O. E E E E DATAIPHONE OUTLET, 3/4" TO ACCESSIBLE CEILING OR CABLETRAY 18" ----------- E E E E ABOVE COUNTERTOP DATA/PHONE OUTLET, MOUNT 4" ABOVE BACKSPLASH OR 44" MULTIOUTLET WIREMOLD ASSEMBLY, MOUNT 4" ABOVE BACKSPLASH OR 44" E E E E J PROVIDE DATA OUTLETS AS SHOWN ON DRAWING E E E E L WA 'J FLOOR DATAIPHONE OUTLET CEILING DATAIPHONE OUTLET CEILING WIRELESS ACCESS POINT E E E E E X X E CL 1 X X E X T� 11c, TELEVISION OUTLET 18" CLOCK 84" INTERCOM OUTLET LOCATION 48" E E X E X E X E AV ........... --- - - E X X X INTERCOM - AUDIONISUAL 48" E X X E S E Y' SPEAKER (WALL OR CEILING MT.) 84" SOUND MASKING EMITTER ALL OR CEILING MT.) 84" VOLUME CONTROL 48" MICROPHONE OUTLET 18" PROJECTOR CONTROL OUTLET 18" HUMIDISTAT 48" E E E E E X X X E X X X E X X X E M M E E M M E EM) THERMOSTAT 48" OUTLET IN FLOOR (MICROPHONE SHOWN) E X X X FIRE ALARM SYMBOL LEGEND E- ELECTRICAL CONTRACT( R m m M - MECHANICAL CONTRACT OR x a m Lu m X- OTHERS HEIGHT TO m w a o MIDDLE OF DEVICE m o ? SYMBOL DESCRIPTION U.N.O. WALL PULLSTATION DEVICE 44" WALL AUDIONISUAL DEVICE (CANDELAS NOTED) 90" WALL VISUAL DEVICE (CANDELAS NOTED) 90" WALL AUDIO STATION 90" CEILING AUDIONISUAL DEVICE (CANDELAS NOTED) E E E E E © E E E E E E E E E E E E E E E E E E E OV Fp CEILING VISUAL DEVICE (CANDELAS NOTED) CEILING AUDIO STATION E E E E E E WALL SMOKE DETECTOR WITHIN 12" OF CEILING E E SD E E E E SD WALL AUDIO/VISUAL SMOKE DETECTOR WITHIN 12" OF CEILING E E E E CD WALL COMBO SMOKE/CO DETECTOR WITHIN 12" OF CEILING WALL HEAT DETECTOR 90" E E E E HD E E E CEILING SMOKE DETECTOR E E E E E SD CEILING AUDIONISUAL SMOKE DETECTOR E E E CEILING COMBO SMOKE/CO DETECTOR E C� E E E E ® CEILING HEAT DETECTOR DUCT SMOKE DETECTOR (RETURN SIDE) E E E E E E E DUCT SMOKE DETECTOR (SUPPLY SIDE) SPRINKLER FLOW SWITCH SPRINKLER VALVE TAMPER SWITCH WALL MAGNETIC HOLD OPEN 80" REMOTE TEST SWITCH 44" E DS E X X E FS E X X E TS E E E E E E M� RT E E E E E E FIRE FIGHTER TELEPHONE 44" FIRE ALARM CONTROL PANEL 80" FIRE ALARM ANNUNCIATOR PANEL 44" FIRE ALARM NAC PANEL 44" E E E FAACCP E LE E E E F� E E E E �NAC POWER SYMBOL LEGEND E - ELECTRICAL CONTRACTOR > m M - MECHANICAL CONTRACTOR « on xa m w X- OTHERS HEIGHT TO Q LU m MIDDLE OF Y w 2 w DEVICE m 4n o ? 3: SYMBO I DESCRIPTION U.N.O. E E E E SINGLE RECEPT ("EM" = EMERGENCY, "HG" = HOSPITAL GRADE, "TR" = TAMPER RESISTANT) 18" E E E E GFCI RATED SINGLE RECEPT 18" E E E E ISOLATED GROUND SINGLE RECEPT 18" E E E E SWITCHED SINGLE RECEPT 18" E E E E DUPLEX RECEPT ("C" = PLUG LOAD CONTROL ,CONTROLLED BY LOCAL 18" OCCUPANCY CONTROL) E GFCI RATED DUPLEX RECEPT 18" E E E E ISOLATED GROUND DUPLEX RECEPT 18" E E E E E E E SWITCHED DUPLEX RECEPT (SPLIT -WIRE) 18" E E E E USB/DUPLEX RECEPT 18" ABOVE COUNTERTOP DUPLEX RECEPT, MOUNT 4" ABOVE BACKSPLASH OR 44" FOURPLEX RECEPT ('C" = PLUG LOAD CONTROL,CONTROLLED BY LOCAL 18" E E E E E E E E OCCUPANCY CONTROL) E E E E GFCI RATED FOURPLEX RECEPT 18" E E E E 1qr ISOLATED GROUND FOURPLEX RECEPT 18" E E E E SWITCHED FOURPLEX RECEPT (SPLIT -WIRE) 18" E E E E ABOVE COUNTERTOP FOURPLEX RECEPT, MOUNT 4" ABOVE BACKSPLASH OR 44" E E SPECIAL RECEPT OR CONNECTION, PROVIDE DIRECT POWER CONNECTION 18" E E ® OR MATCHING RECEPTACLE AS REQUIRED, COORDINATE W/ EQUIPMENT MANUFACTURER E E E E MULTIOUTLET WIREMOLD ASSEMBLY, MOUNT 4" ABOVE BACKSPLASH OR 44" PROVIDE POWER RECEIPTS AS SHOWN ON DRAWING E E E E FLOOR RECEIPT (DUPLEX SHOWN) E E E E O CEILING RECEPT (DUPLEX SHOWN) E X X X [Q)] (j) O JUNCTION BOX (FLOOR, WALL, CEILING SHOWN) AS NOTED E E E E z PUSH BUTTON STATION 44" E M MOTOR HORSEPOWER RATED SWITCH 44" E E E E E E E $ FUSED SWITCH 44" E E E E Lia SAFETY DISCONNECT SWITCH (FUSED) 72" E E E E LH COMBO MOTOR STARTER/DISCONNECT SWITCH (FUSED) 72" E E/M E/M E VFD VARIABLE FREQUENCY DRIVE E E/M E/M E SINGLE PHASE MOTOR (SEE SCHEDULE) E E/M E/M E THREE PHASE MOTOR (SEE SCHEDULE) E E E E CIRCUIT BREAKER PANEL 72" E E ® POWER OR DISTRIBUTION PANEL 72" E E E E ---- E SPECIAL CABINET (TYPE DENOTED) 72" - E ---------- o E TRANSFORMER (TYPE DENOTED) E E E ❑T E E E E �25 KVA GENERATOR (KVA DENOTED) WIRING SYMBOL LEGEND E - ELECTRICAL CONTRACTOR m m M- MECHANICALCONTRACTOR HEIGHT o¢ m o m X- OTHERS TO mY w a w MIDDLE U U > OF DEVICE m o ? 3 SYMBOL DESCRIPTION U.N.O. E E E E CONDUIT CONCEALED IN WALL OR OVERHEAD E E E E CONDUIT CONCEALED BELOW FLOOR E CONDUIT EXPOSED E E E E E E E CONDUIT TRANSITION UP E E E E - CONDUIT TRANSITION DOWN E E E E CONDUIT STUBBED OUT UNDERFLOOR RACEWAY SYSTEM E E E E M=-- E E E E CABLE TRAY (TYPE DENOTED) E E E E E CONDUIT SLEEVE (SIZE DENOTED) E E BRANCH CIRCUIT HOME RUN E E E E E E -_ LOW VOLTAGE POWER WIRING E E E E __-_ UNDERGROUND ELECTRICAL E E E E SHE— OVERHEAD ELECTRIC E X X E Apr UTILITY SERVICE POWER POLE (SITE) E E E E —G— GROUND CONDUCTOR E E E E LIGHTNING PROTECTION AIR TERMINAL E E E ❑ E LIGHTNING PROTECTION CONDUCTOR SPLICE E E E ® E GROUND ROD (PLAN VIEW) E E E E GROUND CONNECTION TO STEEL OR STRUCTURE E E E E • GROUND CONNECTION - EXOTHERMIC WELD GENERAL ELECTRICAL NOTES 1. UNDERGROUND RACEWAY OUTSIDE THE STRUCTURE SHALL BE PVC. 2. ALL LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS SHALL BE IN METAL RACEWAY WHERE INSTALLED WITHIN WALLS OR INACCESSIBLE SPACES, LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS ABOVE ACCESSIBLE CEILINGS WHERE NOTED. 3. WHERE POSSIBLE, ALL CONDUIT AND CABLE SHALL BE RUN UNDER THE TOP CHORD OF THE JOISTS. UNDER NO CIRCUMSTANCE SHALL CONDUIT BE RUN WITHIN 1-1/2" OF THE ROOF DECK. 4. COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND DETAILS. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON ELECTRICAL DRAWINGS. 5. ALL ELEVATION HEIGHTS SHOWN ARE MEASURED TO THE MIDDLE OF THE DEVICE UNLESS NOTED OTHERWISE. 6. ALL RECESSED LIGHTING FIXTURES IN LAY -IN CEILINGS SHALL BE INSTALLLED WITH 6' LONG FLEXIBLE METAL CONDUIT. 7. WHERE CONNECTED TO A 20A BRANCH CIRCUIT SUPPLYING AN INDIVIDUAL RECEPTACLE (SIMPLEX OR DUPLEX), THE RECEPTACLE SHALL BE RATED AT 20A. 8. CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS. 9. TV OUTLETS, VOLUME CONTROLS, TELEPHONE OUTLETS, DATA OUTLETS, AND FIRE ALARM DEVICES SHALL CONSIST OF A BACK BOX WITH CONDUIT STUBBED ABOVE THE ACCESSIBLE CEILING, VERIFY SIZE OF BACK BOX REQUIRED WITH DEVICE TO BE INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT POWER RECEPTACLE INTENDED FOR COMPUTER USE. 10. FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE FOLLOWING DEVICES INTO THE ACCESSIBLE CEILING SPACE IN THE CORRIDOR, UNLESS NOTED OTHERWISE: 314"C TV OUTLETS 314"C VOLUME CONTROLS 3/4"C TELEPHONE OUTLETS 314"C INFORMATION OUTLETS 3/4"C FIRE ALARM DEVICES LIGHTING SYMBOL LEGEND E - ELECTRICAL CONTRACTOR m M - MECHANICAL CONTRACTOR m xo a m w m X- OTHERS HEIGHT TO m 3 cw i o MIDDLE OF 0 0 m 9 > o Cl) z 3: SYMBOL DEVICE DESCRIPTION UA-0- E E E E $ SINGLE POLE SWITCH 44" E E E E $ $ 3-WAY SWITCH 44" E E E E 4-WAY SWITCH 44" DIMMERSWITCH 44" OCCUPANCY SENSOR SWITCH 44" E E E E E E $ E E $ s E E E E $ c MOMENTARY CONTACT SWITCH 44" E E E E E E $ TIMER SWITCH 44" GENERATOR TRANSFER DEVICE E E GTD E E E E OS CEILING OCCUPANCY SENSOR- DUAL TECHNOLOGY TYPE E E E E LS PC CEILING LIGHT LEVEL SENSOR PHOTOCELL E E E E E E E E • ❑ POLE MOUNTED LIGHT (TYPE DENOTED) PER SCHED E E E E �iJ WALL MOUNTED LIGHT (TYPE DENOTED) AS NOTED E E E E (2) RECESSED LIGHT (TYPE DENOTED) E E E E 0 SURFACE LIGHT (TYPE DENOTED) E E E E P1 O0' P2 SUSPENDED OR PENDANT LIGHT (TYPE DENOTED) E E E E INDUSTRIAL LIGHT (TYPE DENOTED) E E E E n TRACK AND TRACK LIGHT (TYPES DENOTED) AS NOTED E E E E EMERGENCY DOUBLE HEAD WALL LIGHT (TYPE DENOTED) 96" EXIT SIGN (TYPE DENOTED) 12" LIGHT FIXTURE ON (EM) LIFE SAFETY OR CRITICAL BRANCH AS NOTED E E E E E E E E Q n 0/ _ V V a z z wLo z rn d E W PL U w s uV a a L) > m y. -• uj o Q w 3 Z 3 01 >w �m 0 �t LU Ir �� 0 # M ^� 1 CO �. a , Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02106/2019 Revisions No. Date Description t rel J LU LU ULO LO U� rY J J Q U_ OfU LU Of 2 LU OD U~ o� v0 V D- If this document is sealed and signed in a digital - 9 or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of P 9 tY the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability liabili associated with it where the. authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title ELECTRICAL NOTES AND ABBREVIATIONS Sheet Number RnOl J u I COMcheck Software Version 4.1.:1.0 Interior Lighting Compliance Certificate Project Information Energy Code. 2017 Florida Building Code, Energy Conservation Project Title: DELIVERY STATION - DVB1 Project Type: Alteration Construction Site: OwneriAgent: 7440 Commercial Circle Fort Pierce, FL 34951 Allowed Interior Lighting Power A Area Category 1-100 - VESTIBULE (Common Space Types:Lobby - General) 2-101 - EMPLOYEE STORAGE (Common Space Types:Locker Room) 3-102 - BREAKROOM (Common Space Types:LcungeiBreakroom) 4-103 - CONTEMPLATION (Common Space Types:LoungeSreakroom) 5-104 - MOTHERS (Common Space Typewl-oungetBreakroom) 6-105 - WOMEN'S VESTIBULE (Common Space Types:Corrldor(Transitlon >=8 fl wide) 7-1 USA - WOMEN'S RR (Common Space Types:Resirooms) 8-1051B - WOMEN'S RR (Common Space Types:Restrooms) 9-106 - MEN'S VESTIBULE (Common Space Types:Corridor7ransdion >=8 it wide) 10-106A - MEN'S RR (Common Space Types:Restrooms) 11-1068 - MEN'S RR (Common Space Types:Restrooms) 12-107 - TRAINING (Common Space Types:Classroom/Lecture/Training) 13-108 - STORAGE (Common Space Types:Storage >---50 - 4=1000 sq.ft.) 14-109 - JANITOR (Common Space Types:Storage >=50 - <=1000 sq.ft.) 15-110 - ELECTRICAL (Common Space Types:Eleciroal/Mechanical) 16-111 - CONFERENCE ROOM (Common Space Types:Coherence/Meeting/Muaipurpose) 17-112 - OPEN OFFICE (Common Space Types:Office - Open Plan) 18-113 - OFFICE (Common Space Types:Offiee - Enclosed) 19-114 - STATION MANAGER (Common Space Types:Office - Enclosed) 20-115 - HR OFFICE (Common Space Types:Office - Enclosed) 21-150 - WAREHOUSE (Warshouse:Fine Material Storage) Proposed Interior Lighting Power Project Title: DELIVERY STATION - DVB1 Data filename: P:\83460006\WIP 11RAWINGSNElec\Ughting\DVB1 - COMcheck.cck. Designer/Contractor: Dave Herscher Progressive AE 18114 Mile Rd, NE Grand Rapids, MI 49525 616.447.3386 hersched@progressiveae.com B or Area (ft2) 228 450 2882 52 50 67 274 274 67 274 274 910 324 107 97 296 537 101 149 107 51975 C D Allowed Allowed Watts Watts i ft2 (B X C) 0,90 206 0,75 338 o.73 2104 0.73 38 0.73 36 0.66 44 0,98 269 0.98 269 0,66 44 0.98 269 0,98 259 1.24 1128 0.63 204 0.63 67 0.96 92 1.23 364 0.98 526 1.11 112 1.11 165 1.11 119 rotal Allowed Watts . 55373 Report date: 02/25/19 Page 1 of 10 COMched Software Version 4.110 Exterio, Lighting Compliance Certificate Project Information Energy Code: 2017 Florida Building Code, Energy Cons rvation Project Title: DELIVERY STATION - DVB1 Project Type: Alteration Exterior Lighting Zone 2 (Light industrial area with limited nighttia a use) Construction Site: Owner/Agent: 7440 Commercial Circle Fort Pierce, FL 34951 Allowed Exterior Lighting Pow Designer/Contractor: Dave Herscher Progressive AE 18114 Mile Rd. NE Grand Rapids, MI 49525 616.447.3386 h e rsc h e d Q p ro g ressi vea e. c om A B C D E Area;Surface Categv Quantity Allowed Tradable Allowed Watts Watts ; Unit Wattage (B X C) MAIN DOOR (Main entry) 3 It of door 20 Yes 60 OTHER DOORS (Other door (not main ry)) 12 ft of door 20 Yes 240 LOADING DOCK (Parking area) 3250 ft2 + 0.06 Yes 195 VAN LOADING AREA (Parking area) 4900 IQ I 0.06 Yes 294 EGRESS PATH ( Walkway < 10 feet wid 600 It of 0.7 Yes 420 PARKING (Parking area) 108000 ft2 0.06 Yes 6480 Total Tradable Watts (a) . 7689 Total Allowed Walls = 7689 Total Allo, ad Supplemental Watts (b) � 600 (a) Wattage tradeoffs are only alloweltween tradable areas/surfaces. (b) A supplemental allowance equal 00 watts may be applied toward compliance of bot non -tradable and tradable areas/surfaces. Proposed Exterior Lighting Por A B C D E Fixture ID : Descriptioramp i Wattage Per Lamp), Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt, MAIN DOOR( Main entry 3 ft of doaith)' Tradable Wattage EC - RECESSED DOWNLIGHT: Metsllde: Standard: 1 2 70 140 OTHER DOORS (Other door (not rentry) 12 It of door width) • Tradable Waltag0. W2 - LED WALL PACK: LED Panel 3f 1 3 34 102 LOADING • DOCK (Parking area el: Tradable Wattaoe W1 - LED WALL PACK: LED Panel 6( 1 2 59 118 VAN LOADING AREA ( Parking are00 ftM: Tradable Wattage VI - LED PARKING GARAGE LIGHT) Panel 33W: 1 4 32 128 EGRESS PATH I Walkway < 10 feels 600 ft of walkway lenyth)t : Tradable Walte W 1 - LED WALL PACK: LED Panel 6C PARKING ( Parking area 108000 1123dable Wattage 1 S 59 854 Project Title: DELIVERY STATION 81 Data filename: PA83460006\WIP DBdGS\E1ec\Llghting0VB1 - COMcheck.cck Report date: 02/25/19 Page 4 of 10 I A B I C D E Fixture ID : Description / Lamp i Wattage Per Lamp / Ballast Lempal Not Fixture (C X D) Fixture Fixtures Watt. 100 -VESTIBULE ( Common Space T e obby General 228 sa ft ) R1 -2X4 LED TROFFER: LED Panel 41 W: 1 4 42 168 101 - EMPLOYEE STORAGE (Common Spec TyneseLocker Room 450 so ft ) R1 iRi E - 2X4 LED TROFFER: LED Panel 41 W: 1 8 42 336 102 - BREAKROOM ( Common Space Tyoes-Lounge/Breakroom 2882 sq.ft 1 R1181 E - 2X4 LED TROFFER: LED Pane141 W: 1 29 42 1218 103 CONTEMPLATION ( Common Space T e o nge/Breakroom 52 sa tt.l R1 -2X4 LED TROFFER: LED Panel 41 W: 1 2 42 84 104 - MOTHERS f Crimmgn Space Ty�es:Lounae/Breakroom 50 so.f11 R1 -2X4 LED TROFFER: LED Panel 41 W: 1 2 42 84 105 WOMEN'S VESTIBULE ( Common Space Types-Corridor/Transition > 8 H wide 67 sn 1I1 R1 E - 2X4 LED TROFFER: LED Panel 41 W: 1 1 42 42 105A WOMEN'S RR (Common Space Type Tl str am 74 sg tt l 82 - 2X2 LED TROFFER: LED Panel 33W: 1 5 30 150 1058 - WOMEN'S BR? Common Space TyoasrRecfrn_n_ms 274 sn fj 1 S2.2X2 LED TROFFER: LED Panel 33W: 1 5 30 150 106 MEN'S VESTIBULE ( Common Space Type&Corridor/Transition > S It wide 67 Sq ft,] R1 E - 2X4 LED TROFFER: LED Panel 41 W: 1 1 42 42 106A - MEN'S RR ( Common Space Tyoes•Restrooms 274 sa ft V S2-2X2 LED TROFFER: LED Panel 33W: 1 5 30 150 106E - MEWS RR ( Common Spann Tyaes Restroams 274 so.ft.4 S2.2X2 LED TROFFER: LED Panel 33W: 1 5 30 150 107 - TRAINING ( Common Space Types Classroom/Lecture/Trainin og 1 n eM e t RI lR1E - 2X4 LED TROFFER: LED Panel 41 W: 1 12 42 504 R2.2X2 LED TROFFER: LED Panel 33W: 1 4 30 120 108 STORAGE ( Common Space Types'Storage >-50 < 1000 scift 324 stift ) R1IR1 E - 2X4 LED TROFFER: LED Panel 41 W: 1 4 42 168 109 - JANITOR ( Common Space Tye :tor a >=50 - <=1000 sa ft 107 sa ft 1 Si - 2X4 LED TROFFER: LED Panel 41 W: 1 2 42 84 110 - ELECTRICAL ( Common Space Tyoes:Eiectrical/Ma hsni al 97 sq.ft ) R1 -2X.4 LED TROFFER: LED Panel 41 W: 1 2 42 84 111 - CONFERENCE ROOM ( Common Space Typ s 7ConlerencelluteetinVMultipurpose 296 sa ft ) R1 - 2X4 LED TROFFER: LED Panel 41 W: 1 4 42 168 112 OPEN OFFICE ( Common S=e Types•Office Open Plan 537 ca ft ) RVR1E - 2X4 LED TROFFER: LED Panel 4l W: t 11 42 462 113 - OFFICE ( Common SpaceL%igs:Offico - Enclosed 101 so„ ft) R1 -2X4 LED TROFFER: LED Paned 41 W: 1 2 42 84 114 - STATION MANAGER ( Common Space Type<7Office - Enclosed 149 sa ft 1 R2 - 2X2 LED TROFFER: LED Panel 33W: 1 4 30 120 115 - HR OFFICE ( Common Sups TTypesDffice - Enclosed 107 sq.) R1 - 2X4 LED TROFFER: LED Panel 41 W: 1 2 42 84 1.50 - WAREHOUSE (Warehouse:Fine Material Storage 51275 sq,ft-) P1/PIE - LED HIGHBAY: LED Panel 110W; 1 101 213 21613 Total Proposed Watts = 25965 Interior Lighting PASSES Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented In this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2017 Florida Building Code, Energy Conservation requirements In COMcheck Version 4.1.1,0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist, Project Title: DELIVERY STATION - DVB1 Report date: 02/25/19 Data filename: P:\83460006\WIP DRAWINGSNEIec\Llghting\DVB1 - COMcheck.cck Page 2 of 10 A B C D E Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lampsi # of Fixture (C X D) Fixture Fixtures Watt. VI � LED PARKING GARAGE LIGHT: LED Panel 33W: 1 3 32 96 PL20JPL2BIPL5 - LED POLE MOUNT: LED Panel 84W: 2 14 166 2324 Total Tradable Proposed Watts . 3262 - Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting building plans, specifications, and other calculations su systems have been designed to meet the 2017 Florida 4.1,14.knel to comply] with any applictable mandatory r, Naltrf-Title — i - I Si Project Title: DELIVERY STATION -DVB1 Data filename: P:183460006\WIP DRAWINGS\Elec\LlghtinglDVB1 - COMcheck.cck is consistent with the sad exterior lighting its In COMEheck%ersion Z/ ZII Date Signatuee Project Title: DELIVERY STATION - DVB1 Report date: 02125/19 Data filename: P:\83460006\WIP DRAWINGS\Eiec\Lighting\DVBI - COMcheck.cck Page 3 of 10 COMcheck software Version 4.1. 1.0 inspection Checklist Energy Code: 2017 Florida Building Code, Energy Conservation Requirements: 100.0% Were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. section --------- ---------- ' 4 ! .Plan Review. Complies? Comments/Assumptions &_Req.1D C405.6 Plans, specifications, andlor ❑Complies Requirement will be met. [PR17]1 calculations provide all tnformatlon ❑Does Not with which compliance can be ;❑Not Observable determined for the electrical systems and equipment and document where ❑Not Applicable exceptions are claimed. Provisions are made for metering individual tenant units. Feeder connectors (for feeder and branch circuits) sized in accordance with approved plans with maximum drop of 5% voltage drop total. C103.2 Plans, specifications, and/or [Compiles Requirement will be met. [PR411 calculations provide all information ❑Does Not with which compliance can be determined for the interior lighting ❑Not Observable and electrical systems and equipment ;❑Not Applicable and document where exceptions to the standard are claimed Information provided should Include Interior ;lighting power calculations, wattage of 'bulbs and ballasts, transformers and _ control devices. C103.2 Plans, specifications, and/or !❑Complies Requirement will be met. [PR811 calculations provide all information ❑Does Not with which compliance can be determined for the exterior lighting ❑Not Observable and electrical systems and equipment ;ONot Applicable and document where exceptions to the standard are claimed. Information provided should include exterior ; lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Additional Comments/Assumptions: 1 Hlgh Impact (Tier 1) Medium Impact (Tier 2) M@Lcw Impact (Ter-3- Report date: 02125/19 Project Tftle: DELIVERY STATION - DVB1 Report date: 02/Ali9 Page 5 of 10 Data filename: P:\834600061WIP DRAWINGS\Elec\Llghting\DVBI - COMcheck.cck Page 6 of 10 G/ o a Z z LU G W Z_ C7 E W o e� - ^ W � ro V - v co> Ir ^ _ F c W = 0 a iT Lu Lu Z 3 - v .2 O to 't [r _m co Q 00 co a °D co sommom Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description ZW o J r UG) U r') Q J Q LL �W WU �Lu W Cl) M _ n- / U� o0 O LL `W W If this document is sealed and signed in a digital or electronic format and is received fromsomeone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title ELECTRICAL ENERGY CODE COMPLIANCE FORMS Sheet Number E0a02 J S ectla n—�_,__---- Rough -in Electrical Inspection Complies. Comments/Assumptions i �:&Req.iDj--- C4052,1 Lighting controls installed to uniformly ❑Complies Requirement will be met. '[EL1511 reduce the lighting load by at least ❑Does Not 50%.❑Not Observable ❑Not Applicable', C405.2.1 Occupancy sensors installed in i0complies Requirement will be met. [EL1811 required spaces. ',13DIbes Not ❑Not Observable' :[Not Applicable '. C405.2.1, independent lighting controls installed❑Compiles Requirement will be met, xC405.2.2.. per approved lighting plans and all ❑Does Not i3 CEL2311 manual controls readily accessible and visible to occupants. . ❑Not Observable ❑Not Applicable pS,2 2. Automatic controls to shut off all ❑Complies °,Requirement will be met. building lighting installed in all ❑Does Not CEL2212 buildings.©Not Observable! ❑Not Applicable ¢- 5.23 Daylight zones provided with ❑Complies Exception: Requirement does not apply. [EL1611 individual controls that control the ❑Does Not lights Independent of general area Observable lighting.❑Not ❑Not Applicable C405.2.3, Prltnary sidelighted areas are ❑Complies ", Exception: Requirement does not apply. C405.2.3. ! equipped with required lighting ❑Does Not 1,.controls. C405,2 3. ❑Not Observable', 2 ❑Not Applicable j [EL2011 C405.2.3, Entlosed spaces with daylight area Complies Exception: Requirement does not apply. C405.2.3. I under skylights and rooftop monitors =[ Does Not 1, are equipped with required lighting®Not Observable' C405.2.3. 3©Not controls. Applicable [EL2111 C405.2.4 Separate lighting control devices for :❑Complies Requirement will be met. [EL411 specific uses installed per approved❑Does Not .lighting plans. ❑Not Observable ❑Not Applicable C405.2.4 ':Additional interior lighting power I❑Complies Requirement will be met. [EL8[1 allowed for special functions per the j❑Does Not approved lighting plans and is automatically controlled and []Not Observable separated from general lighting. IONat Applicable j _ C405.2.5 Automatic lighting controls for exterior'❑Complies Requirement will be met. [EL25]null lighting Installed. Controls will be []Does Not daylight controlled, set based on ❑Not Observable business operation time -of -day, or ❑Not Applicable reduce connected lighting > 30%. C405.3 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met. [EL611 face.❑Does Not ,ONot Observable ! ��.........___.._._...__.._......__r._.-.__.__...._..�._ [Not Applicable Additional Comments/Assumptions: 1 High Impact Wier 1) Medium Impact (Tier 2) _. Low Impact (Tier 3) Project Title: DELIVERY STATION - DVBI Report date: 02125119 Data filename: P:1834600061WIP DRAWINGSOEIecWghtinglDVB1 - COMcheck.cck Page 7 of 10 %`�'�.+� � &ft "�"r n ''pf„'}�`�x.rv'se ,�;#.+`, F-a^x� �. 'a�""s.s-. a8�q"MOgg, . -. .rr"'_,.',, �a C303 3 Furnished O&M Instructions for❑Complies Requirement will be met. C408.2.5; :, systems and equipment to the :©Does Not building owner or designated 1713 ❑Not Observable representative. �=•>❑Not Applicable C405 4.1 Interior installed lamp and fixture _ ❑Complies Seethe interior Lighting fixture schedule for values. [FI1811 lighting power is consistent with what ❑Does Not is shown on the approved lighting ❑Not Observable plans, demonstrating proposed watts ❑Not Applicable are less than or equal to allowed watts, C405.5.1 Exterior lighting power is consistent []Complies see the Exterior Lighting fixture schedule for values. [F11911 with what is shown on the approved ❑Does Not lighting plans, demonstrating ❑Nat Observable' proposed watts are less than or equal ❑Not Applicable to allowed watts. Cana 2.5.'Furnished as -bunt drawings for ❑Compiles Requirement will be met. L electric power systems within 90 days ❑Does Not _[Fl1611 it system acceptance, ©Nat Observable ❑Not Applicable �:.408.3 Lighting systems have been tested to ❑Complies : Requirement will be met. [F:13311 :ensure proper calibration, adjustment, ❑Does Not programming, and operation. ❑Not Observable I ❑Not Applicable Additional Comments/Assumptions: 1 Hr h Im act Tler 1 T Medium Impact ITler 2� Low Impact (Tier 3) G_.I. �. ? ( ) 7 ] Project Title: DELIVERY STATION -DVB1 Data filename: P:1834600061WIP DRAWINGS1ElecILlghting\DVB1 - COMcheck.cck 1 I High Impact (Tier 1) 014HMedium Impact (f[er 2) Low Impact (Tier 3)� Project Title: DELIVERY STATION - DVB1 Report date: 02/25/19 Data filename: P:1834600061WIP DRAWINGS1Elec5Lighting\DVB1- COMcheck.cck Page 8 of 10 Report date: 02/25/19 Project Title: DELIVERY STATION - DVB1 Page 9 of 10 Data filename: P:1834600061WIP DRAWINGSNEleclLlghbng\DVB1 - COMcheck.cck Report date: 02125/19 Page 10 of 10 U a Z z R w w z Z Z w Issuances PERMITS: 02/27/2019 m LO rn vE 2 U N N a a> � N c m (7 a w 3 z 3 �-7 r # M 00 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description Z O TF I J W 0 W J UG) C) J J Q LL XU W W W_ O� UIX 00 LL If this document is sealed and signed in a digit or electronic format and Is received from some other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity e the document. The sealing professional disclai the seal and signature and shall not be liable fi any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated in this marine Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title MMKIANCE FORMS Sheet Number K03 1 J NAIL 16' ' 18t 1s• . III lil PIL C 18' C2� 18 18" PL5 T III s PL2B — FOUNDIRON ' 13' OFFSET 12' tz 12^ E a -6I COMMERCIAL CIRCLE (60' R.O,W.) S 00'29'21" W ' U rs•0• 1- STORY COMMERCIAL BUILDING FIFE =18.8 Y• � 777 16' . 16" PROVIDE FUSES IN CIRCUIT TO FIXTURE BALLAST. FUSES SHALL BE IN "BUSS" TYPE "HEB" OLDER (WP) LIGHT POLE 3'-0" BACK FROM CURB 1" CHAMFER NOTE: DO NOT SET ANCHOR "SONOTUBE" BOLTS PRIOR TO MANUF FORM SHOP DRAWINGS SHOWING BUILT CIRCLE OF FINISH GRADE 0� POLE BASE. PAVEMENT SURFACE CONCRETE BASE #4 REBARSUIT r SPACED EVENLY ON 20" DIA CIRCLE (4 REQ'D) #4 TIE RODS IN 20" DIA CIRCLE 2-0" DIA POLE BASE DETAIL PI-5 PROPOSED CANOPY LOCATION #6 BARE GROUND WIRE CONNECT TO GROUNDING LUG FURNISHED BY E.C. BASE COVER ANCHOR BOLTS TO BE /— FURN & INSTALLED BY E.C. INSTALL TRUE & SQUARE WITH PARKING LOT �— PROVIDE DOUBLE NUTS ON EACH ANCHOR BOLT FOR LEVELING UNIT. PROVIDE ONE ABOVE & ONE BELOW BASE FLANGE. 2-6" (6" MAX IN GRASS ARE1 PVC CONDUIT m LONG SWEEP ELLS 4 CONDUIT & #6 GAD WIRE — CADWELD OR DOUBLE LUG CONNECTION 3/4"OU-0" GROUND ROD NOT TO SCALE 18" 2P \ ( 16' 7" 8' l spy V 18. SITE GENERAL NOTES A. ALL LIGHTING AND POWER CONDUCTORS SHALL BE INSTALLED BETWEEN 24" (MINIMUM) AND 36" (MAXIMUM) BELOW FINISHED GRADE. B. ALL COMMUNICATIONS CONDUIT AND CABLES SHALL BE INSTALLED 36" (MINIMUM) BELOW FINISHED GRADE. C. ALL CONDUCTORS FOR EXTERIOR LIGHTING AND POWER CIRCUITS SHALL BE #10 AWG MINIMUM. FOUND NAIL ELECTRICAL SITE PLAN 1" = 40141 Q0 U ro a z o-s � — LU a W� Z 0 m a E W ^2 U W N j a> F � N U � N Z xM O of) do w ,_ M Ir a O '(0 Issuances PERMITS: 02127/2019 SITE PLAN REVIEW: 02106/2019 Revisions No, Date Description im 0 ZW O J� U6 Uc- J I" E 270.' Q LL_ ULL Of . LU 2E U aLL n O F UC o� �LL N h W J W 0 11. EF ea If this document is sealed and signed in a or electronic format and is received from s other than the sealing professional identifi the document, you must contact the sealir professional in writing to validate authentic the document. The sealing professional di the seal and signature and shall not be Ila any liability associated with it where the authenticity of any digital or electronic sea signature has not been validated in this In Job Number 83460( Drawn By S App/d By SI Sheet Title FIL ELECTRICAL SIT PLAN Sheet Number KIM o w� h 0 0 o_ ow s � - y U oZ w� �a z 2 y eu� y a a� z� 0 � w¢ Z > co 0 wS y W S ri INU cd w z w � m Wo y o- a o w� ww m Q� 7t O 11 12 f3 I o L1A-42 75cd LIB a MEN'S RR 16B MEN'S VESTIBULE L1A-40 w 106 1_1A-41 w 0 0 MEN'S RR to6A L1A-42 75 V 0 O L1A-48 75cd WOMEN'S RR a 10E B - I � 0 0 � 0 0 WOMEN'S VESTIBULE uA•as W �� 105 L1A-50 0 0 0 0 WOME 'S RR 10 L1A-48 75cd 4 ® r —I — — I — I I L1A-65 1A-64 � L1A-59 C L1A-64 C )Ad OR WATT N MANAGES OFFICE:{� LIA-65 114 L1A-65 113 TIA-64 0 C L1A-59 109 (� L1A-68,70,72 Far'il L1A-60 99 UA-SJ _,S7V(p L1A-65 L1A-64 . -= C 300d EF-2 L1A,% V /� WH-1 15cd 41A-7 L1A-67 1A 75,ft V LIA-51 L1A- IL// L1A-66 OPEN OFFIC A —A H1 STORAGE v C L1A-66 112I LIA 58 108 L1A-66HR FFICE o L1A 115 �I L1A-73 L1A-66 L1A-57 A-56 L15 75C'L LL1A L1A-53 1 3 L1A-66 Mr Vv I V CU-1 r - - - _ L1A-74,761 I I ELECTR16AL I I I III. II I uo I I I I 104 C U L1A-35 I L1A-35 L1A35 C L1A-19 CONTEMPLATION L1A-35 L1A 103 C L1A-35 CONF RENCE OOM 111 0 L1A-47 L1A•6 I C L1A-69 .1A-47 L1A-44 tY L1A-44 L1A4 O 0 L1A-43 L1A-43 ( 9 P) ❑ ® �LA46 _ 6 L1A-45 LIIA•45 TRAINING p tY U E U .1A-4 I; ® L1A-47 EXy L1A-79 C 75cd L1A-47 L1A-32 },. lA-29 C VESTIBULE u 100 LiA-30 L1A-32 PLOY ST RA 01 4 L1A-31 diiII14 8 C L1A-24 L1A-28 L1A-2 L1A-32 L1A-16 C -�� zu � I "^-`" ( L1A-27 L1A-21 L1A-22 L1A-25 L1A-16 LI U - L1A-61 - - - - - uuuuuu ... .. :,. U I IJ 0 _o L1A-13 O is L1B-26UjUUU L1A-18 i Lib_27.29 . L1B 28,30 1 L1 31,33 LIA-14 L1B-32,34 n n n n n- 17 J � i 1� L1B-35Q= ?9 L1A-15 uluuuuu L1A-16 BREAKROOM _ L1A-17 U L1A-61 L1A-39 U1UUU U - - L1A-7 L1A-10 L1A-38 L1A-37 L1A-36 I L1A-9I L1A-12 ILL11 1. L1A-2 L1A-3.,IIL1A 4 L1A-5 L1A-6 66, 68" gg ® L1 L1A�� -1� 1 ENLARGED POWER PLAN I fle ® ENLARGED POWER PLAN KEY NOTES r iQ a 1, (2) 2" CONDUITS FROM DEMARCATION UP TO T-6" BELOW STRUCTURE - PROVIDE D z BUSHINGS ON EACH END OF CONDUITS. 2 - W N 2, 4" CONDUIT TO TELEPHONE PEDESTAL TO DEMARCATION. COORDINATE WITH SERVICE PROVIDER. v E 3. FIRE RETARDANT 4' X 8' X 3/4" PLYWOOD BACKBOARD. n w W g q t- > 4. FURNISH AND INSTALL POWER JUNCTION BOX FOR DOOR ACCESS CONTROLS AND V ^ _ U w DOOR ALARM. COORDINATE POWER REQUIREMENTS AND FINAL LOCATION WITH ^. Lu EQUIPMENT INSTALLER. W U a 5. FURNISH AND INSTALL POWER JUNCTION BOX FOR DETEX DOOR ALARM. MOUNT ¢ z JUNCTION BOX AT 12" ABOVE DOOR FRAME. COORDINATE FINAL LOCATION WITH u • Lu EQUIPMENT INSTALLER. rn 6. CEILING MOUNT POWER AND DATA RECEPTACLE FOR CEILING MOUNTED PROJECTOR O ��t SCREEN. COORDINATE FINAL LOCATION AND ADDITIONAL REQUIREMENTS WITH - C! PROJECT CONSTRUCTION MANAGER. a a m 7. RECESSED TV RECEPTACLE WITH SURGE PROTECTIVE AND LOW VOLTAGE KIT. RECEPTACLE SHALL BE PASS & SEYMOUR #TV1WTVSSW AND SHALL INCLUDE DUPLEX Issuances OUTLET, CAT 5E JACK, AND F-CONNECTORS. PERMITS: 02127/2019 8. ONE SINGLE DATA PORT FOR IP CLOCK. COORDINATE FINAL LOCATION WITH START UP SITE PLAN REVIEW: 02/06/2019 PROJECT MANAGER. Revisions 9. FLUSH FLOOR BOX (CAST IRON) WITH (3) DUPLEX RECEPTACLES AND (3) PHONEIDATA No. Date Description OUTLETS. FURNISH AND INSTALL 1" CONDUIT FOR POWER AND 1-1/4" CONDUIT WITH PULL STRING FOR PHONE/DATA. (PLASTIC BOX / BOX COVERS SHALL NOT BE ACCEPTABLE). COORDINATE FINAL LOCATION OF FLOOR BOX WITH OWNER PRIOR TO INSTALLATION. PROVIDE ALTERNATE PRICE FOR TWO CHANNEL POWER POLE CONNECTION. 10. FLOOR SCRUBBER RECEPTACLE; COORDINATE PLUG CONFIGURATION AND FINAL 0000000000 POWER REQUIREMENTS WITH SUPPLIED EQUIPMENT AND PROJECT CONSTRUCTION MANAGER. 11. DOORBELL. COORDINATE MANUFACTURER AND LOCATION OF CHIME WITH OWNER. 12. NOT USED. C O 13. NOT USED. r 14. CONTRACTOR TO INSTALL JUNCTION BOX FOR CEILING FAN, MUST SUPPORT WEIGHT M OF CEILING FAN. COORDINATE TYPE OF CEILING FAN WITH OWNER. \� M 4CONTRACTOR TO INSTALL (6) RECEPTACLES TOTAL FOR MICROWAVE OVENS. COORDINATE LOCATION WITH OWNER PRIOR TO ROUGH -IN WORK. Q 16, INSTALL RECEPTACLES ON WALL ABOVE AEN CABINET. RECEPTACLES SHALL BE (3) L6-20R AND (1) L6-30R TWIST LOCK RECEPTACLES INSTALLED IN T030IN MARINE ENCLOSURE. COORDINATE FINAL LOCATION AND REQUIREMENTS WITH I.T. EQUIPMENT/ EQUIPMENT INSTALLER AND PROJECT CONSTRUCTION MANAGER. z W U 17. FURNISH AND INSTALL (2) 4" CONDUITS FROM AEN EQUIPMENT TO 16" BELOW O a STRUCTURE STEEL. COORDINATE EXACT REQUIREMENTS WITH I.T. EQUIPMENT/ C)EQUIPMENT INSTALLER AND PROJECT CONSTRUCTION MANAGER. PENETRATIONS THRU I.T. CLOSET WALL SHALL BE FIRE RATED WITH WIREMOLD FS4R FIRE STOP OR J - Q LL EQUAL. /' LU 18, INSTALL RECEPTACLES ON PLYWOOD BACKBOARD NEXT TO INTRUSION DETECTION a EQUIPMENT ENCLOSURE. RECEPTACLES SHALL BE 5-20R MOUNTED AT 6'-0" ABOVE LL FINISHED FLOOR. COORDINATE FINAL LOCATION AND REQUIREMENTS WITH I.T. O n EQUIPMENT/ EQUIPMENT INSTALLER AND PROJECT CONSTRUCTION MANAGER. O AL �� C If this document is sealed and signed in a c or electronic format and is received from s( other than the sealing professional identifie the document, you must contact the sealing professional in writing to validate authentic the document The sealing professional dis the seal and signature and shall not be liah any liability associated with it where the authenticity of any digital or electronic seal signature has not been validated in this ma Job Number 834600i Drawn By S\ App/d By SD Sheet Title ENLARGED POWER PLAN Sheet Number El ml PROPOSED CANOPY LOCATION N OO O O O �7 �8 O9 10 11 12 13 14 15 0 JANITOR CLOSET ELECTRICALI `✓ 1 W19 116 W1 OW19 W-19 4 - MDP W . IL; DP _.� �� _ PIE ��� �� �Q D dLCP Pi ❑ PIE Pi 1 W1a EM 1 W 34=-- - W-34 EM-5 W-35 EM-5 W-34 EM-5 -ru r W-38 ❑ , - �EM I I ❑ POE � I Pp � �-� p W-39 � W1y� O EM LTG INVERTER) W-19 W-19 I I II I P1 P1 PIE PIE P1 - PIE P1 PIE P1 iJ 0 9 0 PIE P1 PIE � 0 0 ❑ to W-34 W-35 I EM-5 I EM-5 W-36 I EMIT W-37 EM-5 I W-36 EM-5 W- i _ I 39 EM 5 hi I - — - P1 — —PIE — P1- PIE— — - P1— - PIE - 01 - EM��X2 El PIE 0 W❑37 � EM�3 W❑36 EM�3 W❑37 EM�3 � W3fi � � ��� I � � P1 P1 CW1� W-35 EM-1 W-34 I W❑38 O9 W-19 I 1 I V1 PIE P1 O ID 0 W-19 EM-I W-34 P1 P1 W-34 W-35 v1 I I E) P1 PIE 0In 5 E V1 W-19 PIE P1 ® 0 EM-I _ W-34 - P1 PI V1 0 0 9 W-34 W-35 W-19 P1 PIE 0 In W-35 EM-1 - W1 W-19 O PIE 0 EM-1 P1 -0- W-35 P1 0 W-34 PIE ID EM-1 P1 0 W-35 P1 0 W-34 PIE P1 P1 - P1 -I 0 EM-1 W-38 W-39 - 8 P1 0 W-38 PIE 0 EM-1 P1 PIE P1 0 0 ❑ W-39 EM-1 W-35 P1 P1 0 0 W-35 W-34 W2 W-21 PIE 0. EM-1 --0 - - —O FIRST FLOOR LIGHTING PLAN 1/16" = T-0" LIGHTING GENERAL NOTES CL A, ALL RECESSED LIGHTING FIXTURES IN LAY -IN CEILINGS SHALL BE INSTALLED WITH 6' z LONG FLEXIBLE METAL CONDUIT. aj B, ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE ` Z LO 0 FIXTURES UNLESS INDICATED OTHERWISE. / O E C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR W x 0 a MW LIGHTING FIXTURES. LP w F- a.? D. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS u . n U Lu m INDICATED ON PLAN BY DASHED CONDUIT. , W ° C0 CL � 3 E. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND ¢ Z SWITCHING SHOWN. w F CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE O � w �rn PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE (D m CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL O EQUIPMENT SCHEDULE. CL a G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE Issuances REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT. PERMITS: 02/27/2019 H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER SITE PLAN REVIEW: 02I06/2019 THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE Revisions REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT. No, Date Description 0 LIGHTING KEYNOTES 1. LIGHT FIXTURE TO REPLACE EXISTING FIXTURE IN SAME LOCATION 2. 2-BUTTON OVERRIDE SWITCH FOR WAREHOUSE LIGHTING, A. BUTTON ONE: ALL ON B. BUTTON TWO: HALF ON C. BUTTON THREE: ALL OFF W ZLU ® J F' M Q LL U u.f LLLI o O U� o0 O 1Z �LL � ti LLI W 0 LU If this document is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where. the authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title r r-.7 v WAREHOUSE LIGHTING PLAN Sheet Number EU N E z W a ii 1 ENE20LARGED LIGHTING PLAN O ENLARGED LIGHTING KEYNOTES I 1. 2-POLE COMBINATION DIMMER AND OCCUPANCY SENSOR SWITCH FOR PLUG LOAD CONTROL RECEPTACLES. 2, PROVIDE ADDITIONAL POWER PACK FOR PLUG LOAD CONTROL RECEPTACLES IN THIS AREA. 3. 0.10V DIMMER. U TCl) V d U z ^_ w w {.i� z v E IZ o •— p� w ro Lu W S r` o 33a333 z 3 w 3 C31W afrn C/) O w `t `� U M CIL a- ro m Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description I z O 1111111111 U-I J W U� J J Q LL �U wci� �w Oa U~ 00 vw v If this document is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional In writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated In this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title ENLARGED LIGHTING PLAN Sheet Number Hall -i R W-34 W-35 W-36 W-37 W-38 W-39 EM-1 EM-3 EM-5 H1-54 L1A-71 W-19 W-21 W-18 W-20 LIGHTING CONTROL RELAY PANEL ACQUITY BLUE BOX WITH TIME CLOCK AND OUTDOOR PHOTOSENSOR CONTROL LIGHTING CONTROL RELA TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO WAREHOUSE LIGHTING TO SIGN CONNECTION TO OUTDOOR AREA LIGHTING TO OUTDOOR AREA LIGHTING TO PARKING LOT LIGHTING TO PARKING LOT LIGHTING NOT TO SCALE PANEL C PANEL D 208V/120-V, PANEL L1A 208V/120-V, 3-PH, 4 W 208/120-V, 3-PH, 4 W 225-A MILO 3-PH, 4 W 225-A MLO (TO BE 225-A MLO (EXISTING) REMOVED) (NEW) i I r ( r � r i i i `------------f 4 #3/0, #6 GND, 2"C. OR 4 #250KCMIL AL, #4 AL GND, 21/2"C. PANEL CDP 208/120-V, 3-PH, 4 W 600-A MLO LUMINAIRE SCHEDULE TYPE DESCRIPTION MOUNTING VOLT WATT MANUFACTURER CATALOG NUMBER NOTE EC EXISTING RECESSED DOWNLIGHT RECESSED 277 V 70 W EXISTING EXISTING 3 EM EXTERIOR REMOTE HEADS MULLION 277 V 3 W DUAL-LITE EVO-D-B P1 LED HIGH BAY WITH OCCUPANCY SENSOR PENDANT @ IT-0" AFF 277 V 213 W METALUX VHBLED-LD1-24-W-UNV-L840-CD1-SVPD3-U 1 & 2 PIE LED HIGH BAY WITH OCCUPANCY SENSOR POWERED THROUGH INVERTER PENDANT @ IT-0" AFF 277 V 213 W METALUX VHBLED-LD1-24-W-UNV-L840-CD1-SVPD3-U 1 & 2 PL2A POLE MOUNTED AREA LIGHT 25' POLE 277 V 166 W MCGRAW-EDISON GLEON-AF-03-LED-El-T2 1 PL2B POLE MOUNTED AREA LIGHT 20' POLE 277 V 166 W MCGRAW-EDISON GLEON-AF-03-LED-E1-SL2 1 PL5 POLE MOUNTED AREA LIGHT 25' POLE 277 V 166 W MCGRAW-EDISON GLEON-AF-03-LED-El-5MQ 1 R1 2X4 LED TROFFER RECESSED 277 V 42 W METALUX 24AC-LD5-48-UNV-L835-CD1-U 1 R1E 2X4 LED TROFFER WITH EMERGENCY BATTERY BACKUP RECESSED 277 V 42 W METALUX 24AC-LD5-48-UNV-EL14W-L835-CD1-U 1 R2 2X2 LED TROFFER RECESSED 277 V 30 W METALUX 22AC-LD5-34-UNV-L835-CD1-U 1 S1 2X4 LED TROFFER WITH DRYWALL FRAME T RECESSED 277 V 42 W METALUX 24AC-LD5-48-UNV-L835-CD1-U-DF-22-W 1 S2 2X2 LED TROFFER WITH DRYWALL FRAME T RECESSED 277 V 30 W METALUX 22AC-LD5-34-UNV-L835-CD1-U-DF-22-W 1 S2E 2X2 LED TROFFER WITH DRYWALL FRAME T & EMERGENCY BATTERY BACKUP RECESSED 277 V 30 W METALUX 22AC-LD5-34-UNV-EL14W-L835-CD1-U-DF-22-W 1 V1 SURFACE MOUNT EXTERIOR LIGHT SURFACE 277 V 34 W MCGRAW-EDISON TT-C2-LED-E1-MQ 1 W1 LED WALL MOUNTED AREA LIGHT WALL MT @ X'-X" AFF 277 V 59 W MCGRAW-EDISON GWC-AF-01-LED-El-T4W 1 W2 LED WALL PACK WITH EMERGENCY BATTE BACK-UP WALL MT @ 8'-0" AFF 277 V 34 W MCGRAW-EDISON GWC-AF-01-LED-E1-T4W-600-CB 1 X1 LED EXIT SIGN WITH EMERGENCY BATTER BACK-UP UNIVERSAL 277 V 3 W DUAL-LITE EVE-U-G-W-E-1 X2 LED EXIT SIGN COMBO WITH EMERGENCY BATTERY BACK-UP AND REMOTE CAPABILITY UNIVERSAL 277 V 3 W I DUAL-LITE EVE-U-G-W-D4-I SCHEDULE NOTES: 1. LUMINAIRE TO BE ORDERED THROUGH CITY LIGHTING -CONTACT: GARY MAGRENI, gmagreni@citylighting.com, 704-235-31133. 2. FACTORY INSTALLED SENSOR TO BESET SO THAT AFTER 10 MINUTE TIME DELAY AFTER VACANCY, THE LIGHTING FIXTURE WILL DIM TO 20% OF FULL OUTPUT. 3. EXISTING RECESSED DOWNLIGHT IN CANOPY. E.C. TO VERIFY EXISTING CONDITIONS AND RECONNECT LIGHTS TO NOTED CIRCUIT. MECHANICAL EQUIPMENT CONNECTION SCHEDULE TAG DESCRIPTION POWER VOLTAGE PHASE FEEDER DISCONNECTING MEANS DISC FURNISHIINSTALL AC-1 AIR CONDITIONER 208 VA 208 V 1 3 #12, #12 GND, 3/4" C. FURNISHED WITH UNIT MC AHU-1 AIR HANDLING UNIT 31592 VA 480 V 3 3 #8, #10 GND, 3/4" C. FURNISHED WITH UNIT MC AHU-2 AIR HANDLING UNIT 11639 VA 480 V 3 3 #12, #12 GND, 3/4"C. FURNISHED WITH UNIT MC AHU-3 AIR HANDLING UNIT 11639 VA 480 V 3 3 #12, #12 GND, 3/4"C. FURNISHED WITH UNIT MC BAF-1 HIGH VOLUME LOW SPEED FAN 2827 VA 480 V 3 3 #12, #12 GND, 3/4" C. 3P30A FUSED DISCONNECT EC BAF-2 HIGH VOLUME LOW SPEED FAN 2827 VA 480 V 3 3 #12, #12 GND, 3/4" C. 3P30A FUSED DISCONNECT EC BAF-3 HIGH VOLUME LOW SPEED FAN 2827 VA 480 V 3 3 #12, #12 GND, 3/4" C. 3P30A FUSED DISCONNECT EC CU-1 CONDENSING UNIT 2933 VA 208 V 1 3 #10, #12 GND, 3/4" C. FURNISHED WITH UNIT MC DH-1 VAV W/ 10KW HEAT 10000 VA 480 V 1 2 #10, #10 GND, 3/4"C. EXISTING TO BE RELOCATED EXISTING EF-1 EXHAUST FAN 180 VA 120 V 1 2 #12, #12 GND, 3/4" C. FURNISHED WITH UNIT MC EF-2 EXHAUST FAN 180 VA 120 V 1 2 #12, #12 GND, 3/4" C. FURNISHED WITH UNIT MC WH-1 WATER HEATER 3000 VA 208 V 1 3 #10. #10 GND; 3/4" C. 2P30A DISCONNECT EC STARTER TYPES: FVNR FULL VOLTAGE NON -REVERSING FVR FULL VOLTAGE REVERSING 2-SPD TWO SPEED VFD VARIABLE FREQUENCY DRIVE RVS REDUCED VOLTAGE COMBINATION DISCONNECT TYPES: FS FUSED SWITCH NFS NON -FUSED SWITCH MCP MOTOR CIRCUIT PROTECTOR CB CIRCUIT BREAKER CONTROL DEVICES: HOA HAND -OFF -AUTO SWITCH RP RED (RUN) PILOT LIGHT GP GREEN (POWER) PILOT LIGHT 0/0 ON -OFF SELECTOR SWITCH S/S STOP -START PUSHBUTTONS PANEL B PANEL A PANELL1B 208V/120-V, 208V/120-V, 208/120-V, 3-PH, 4 W 3-PH, 4 W 3-PH, 4 W 225-A MLO 225-A MLO 225-A MILO (TO BE (TO BE PANEL N 240/120-V, 3-PH, 4 W 600-A MLO (TO BE,REMOb 4 #4/0, #4 GND, 21/2"C. OR 4 #300KCMIL AL, #2 AL GND, 21/2"C. PANEL M 240/120-V, 3-PH, 4 W 225-A MLO (TO BE REMOi i PANEL EM 480Y/277V LJ(NEW) 3PH,4W -1-� 100A MLO 3P600 FUSED i ,% . FJ PANEL H1 PANEL Z PANEL Y DISCONNECT 'Z -j 480/277-V, 480/277-V, 480/277-V, (TO BE REMOVED))) 3-PH, 4 W 3-PH, 4 W 3-PH, 4 W 225-A MILO 225-A MLO 225-A MILO 4 #10 #10 GND, 3/4"C. (NEW) (TO BE REMOVED) PANEL MOP (TO BE REMOVE[ 480/277-V, 3-PH, 4 W i EMERGENCY LTG 800-A MAIN FUSED INVERTER-SURE-LITES ) i DISCONNECT #C3FT-012-277.277 WITH i (EXISTING) i i11 OUTPUT BREAKER 11i ---------- 225KVA `c"_�r�u's 30 1480.208/120V i 4 i �- i 4 1480-240/120V ------ (EXISTING) i (TO BE REMOVED) 3P200 4 #3/0, #6 GND, 2"C. 3P400 3P200 OR 4 #250KCMIL AL, #4 AL GND, 2112"C. 3P400 3P200 3P800 EXISTING FEEDS FROM EXISTING UTILITY PADMOUNTED TRANSFORMER EXISTING METERS AND CT CABIN PANEL W PANEL AC 480/277-V, 480/277-V, 3-PH, 4 W 3-PH, 4 W 225-A MILO 600-A MLO I i ELECTRICAL SPECIFICATIONS a I Z 260501 Minor Electrical Demolition 260923 Lighting Control Devices w M A. Verify field measurements and circuiting arrangements are as shown on Drawings. A, Acceptable occupancy sensor manufacturers: Steinel Professional, Hubbell Building Automation, -- 126111 W z rn B. Verify that abandoned wiring and equipment serve only abandoned facilities. Sensor Switch, and WattStopper. c0 E > C. Report discrepancies to Owner before disturbing existing installation. B. Ceiling occupancy sensors to be low -voltage, dual technology type for use with power packs. w D. Disconnect electrical systems in walls, floors, and ceilings to be removed. Each room controlled with ceiling sensors to also have momentary contact switches tied to the e� w rn m E. Coordinate utility service outages with utility company and owner. power pack for manual lighting control. X a > F. Provide temporary wiring and connections to maintain existing systems in service during C. Wall switch style occupancy sensors to be line -voltage, dual technology type with integral 0-10V . �i l- N construction. When work must be performed on energized equipment or circuits, use personnel dimming capability. v uJ a E' experienced in such operations. D. Power packs to plenum rated, self-contained relay compatible with selected occupancy sensor for00 G. Remove, relocate, and extend existing installations to accommodate new construction. switching on line voltage loads. Power packs to be dual rated-1201277-V. `� C7 4 H. Remove abandoned wiring to source of supply. w I. Remove exposed abandoned conduit, including abandoned conduit above accessible ceiling 262200 Low -Voltage Transformers CP w Z finishes. Cut conduit flush with walls and floors, and patch surfaces. A. Enclosed dry -type general purpose. > r� J. Disconnect abandoned outlets and remove devices. Remove abandoned outlets if conduit B. 480-V, 3-phase primary, 208Y/120-V, 3-phase, 4-wire secondary. o � A v servicing them is abandoned and removed. Provide blank cover for abandoned outlets that are C. 150-degree C temperature rise. LU not removed. D. 220-degree C insulation system. K. Disconnect and remove abandoned panelboards and distribution equipment. E, Aluminum windings. d a L. Disconnect and remove electrical devices and equipment serving utilization equipment that has F. DOE 2016 compliant. co cto been removed. G. Sizes 15-KVA through 75-KVA to be suitable for wall, floor, or trapeze mounting; sizes over 75- 4onow., M. Disconnect and remove abandoned luminaires. Remove brackets, stems, hangers, and other KVA to be suitable for floor mounting. Issuances accessories. H. Manufacturers: Square-D, Eaton, Siemens. PERMITS: 0227/2019 N. Repair adjacent construction and finishes damaged during demolition and extension work. 0. Maintain access to existing electrical installations that remain active. Modify installation or provide 262413 Switchboards SITE PLAN REVIEW: 02/06/2019 access panel as appropriate. A. Front connected, front only accessible. Revisions P. Extend existing installations using materials and methods compatible with existing electrical B. Individually mounted main breaker - electronic trip type. installations, or as specified. C. Group mounted feeder breakers. No. Date Description Q. Remove exposed abandoned grounding and bonding components, fasteners and supports, and D, Feeder breakers 400-A or less to be thermomagnetic trip type, electrical identification components, including abandoned components above accessible ceiling E, Feeder breakers larger than 400-A to be electronic trip type. finishes. Cut embedded support elements flush with walls and floors. F. Main switchboard to have surge protection device. R. Clean and repair existing equipment to remain or to be reinstalled. G. Arc -flash energy mitigation for breakers greater than 1200-A. S. Protect and retain power to existing active equipment remaining. H. Electronic power metering. T. Cap abandoned empty conduit at both ends. I. Manufacturers: Basis of Design is Square-D QED-2; Eaton and Siemens also acceptable. 260519 Low -Voltage Electrical Power Conductors and Cables 262416 Panelboards A. Conductors will be sized per National Electrical Code (NEC) requirements. A. Power distribution panelboards to be I -line type. B. Copper conductors will be used for ampacities lower than 100-A, when used as branch circuits, B. Lighting and branch circuit panelboards to be NF type (480/277-V) or NO type (208/120-V), and when feeding mechanical equipment. C. Load centers not permitted. C. Aluminum or copper conductors will be used for feeders with ampacities of 100-A or greater. D. NEMA 1 enclosures for dry indoor locations. D. Conductors #12 AWG and smaller to be solid, all others to be stranded. E. NEMA 3R enclosures for panels located in outdoors or wet locations. E. Conductor insulation for conductors #6 and smaller to be THHN/THWN-2 or XHHW-2. F, Breakers to be bolt -on type. F. Conductor insulation for conductors #4 and larger to be XHHW-2. G. Arc -flash energy mitigation for breakers greater than 1200-A. G. Insulation voltage rating to be 600V. H. Manufacturers: Basis of Design is Square-D; Eaton and Siemens also acceptable. r� H. All conductors will be required to be in conduit except where concealed by finished walls or M ceilings where MC cable will be permitted. 262717 EciuinmentWiring W I. #12 AWG is minimum allowable size for power circuits. #14 AWG is minimum allowable size for A. Verify that equipment is ready for electrical connection, wiring, and energization. control circuits. Increase minimum conductor size to #10 AWG for 20-A, 120-V circuits longer B, Make electrical connections in accordance with equipment manufacturer's instructions. than 75-feet, to #8 AWG for 20-A, 120-V circuits longer than 150-feet, and to #10 AWG for 20-A, C. Make conduit connections to equipment using flexible conduit. Use liquid tight flexible conduit 277-V circuits longer than 150. with watertight connectors in damp or wet locations. D. Connect heat producing equipment using wire and cable with insulation suitable for temperatures 260526 Grounding and Bonding for Electrical Systems encountered. A. A grounding electrode system will be comprised of a concrete encased electrode, three driven E. Provide receptacle outlet to accommodate connection with attachment plug. ground rods (minimum), the building steel, and the water service pipe. F, Provide cord and cap where field -supplied attachment plug is required. Z B. Maximum allowable impedance to ground will be 5-ohms. G, Install suitable strain -relief clamps and fittings for cord connections at outlet boxes and equipment W � r C. Equipment grounding conductors will be required in all raceways where line -voltage conductors connection boxes. ® U are located. H. Install disconnect switches, controllers, control stations, and control devices to complete �_ D. Ground bus bar will be located next to the main house service switchboard, meter centers, and in equipment wiring requirements. U o"> each IT room. I. Install terminal block jumpers to complete equipment wiring requirements. Q E. Accessible bonding connections in non -corrosive locations will be by mechanical connections. J. Install interconnecting conduit and wiring between devices and equipment to complete equipment LL F. Banding connections that are not in accessible locations or are in corrosive environments will be wiring requirements. a U made by exothermic connections. LULU W U � 262726 Wiring Devices W 26 0534 Conduit A. Receptacles: Cn d A. Underground conduits will schedule 40 polyvinyl chloride (PVC). 1. Standard receptacles: Industrial specification grade, NEMA 5-20R. O B. Above ground conduits where not subject to damage will be electrical metallic tubing (EMT). EMT 2. GFCI receptacles: Industrial specification grade, NEMA 5-20R (in weather proof enclosure ` U Of fittings to be steel or malleable iron. when used outdoors). O O C. Above ground conduits where subject to damage will be intermediate metallic conduit (IMC) or rigid galvanized steel. IMC or rigid fittings shall be threaded type. B) 3. USB charger type receptacles: Commercial grade, two 120-V ports and two USB ports. Switches: Industrial specification grade, 20-A. ILL D. Final connections to transformers, mechanical equipment, etc: will be with flexible metal conduit in C) Cover plates: Nylon or stainless steel (coordinate with owner). dry areas and liquid -tight flexible metal conduit in wet or outdoor locations. D) Manufacturers: Hubbell, Leviton, Pass & Seymour. UJ E. F. Provide fire stopping to preserve fire resistance rating of partitions and other elements. Where conduits penetrate waterproof membrane, seal as required to maintain integrity of 262813 Fuses membrane. A) Class RK1, time -delay. G. Secure and support conduits in accordance with NFPA 70 and Section 26 0529 using suitable B) Provide products listed, classified, and labeled as suitable for the purpose intended. supports and methods approved by the authority having jurisdiction. C) Unless specifically indicated to be excluded, provide fuses for all fusible equipment as required for mmi H. Provide independent support from building structure. Do not provide support from piping, a complete operating system. W ductwork, or other systems. D) Voltage Rating: Suitable for circuit voltage. E) Manufacturers: Bussmann, Littelfuse, Mersen. 260538 TelenhonelDatalLowVoltage Raceway System A. The Electrical Contractor shall install the required conduit, raceway, fittings, boxes, outlets, etc., 262818 Enclosed Switches as required for the telephone/data/low voltage systems. Actual installation of the telephone/data A. Heavy duty type quick-make/quick-break safety switches. equipment and necessary wiring is not included in this contract. B. Fusible type to have fuse clips for Class R fuses. B. The Contractor shall install all conduits as called for on the drawings. Each run of conduit shall C. Indoor locations to be NEMA 1, outdoor locations and where exposed to moisture to be NEMA contain not more than (2) 90-degree bends, and no run shall exceed 100 feet in length. Minimum 3R. radii for bends shall be 8-1/2 inches for 3/4-inch conduit, 10-1/2 inches for 1-inch conduit, and D. Manufacturers: Square-D, Eaton, Siemens. equivalent of long radius factory bends for larger sizes. C. A 3/4-inch conduit shall be run to serve 1 outlet with 314 inch between outlets and a 1-inch home 262923 Variable Frequency Motor Controllers run. A. Microprocessor -based inverter logic. D. All conduits from outlets shall be stubbed into joist space as indicated on the drawings for B. Pulse width modulated system. Seal accessible ceilings or to back board or cabinet for nonaccessible ceilings. Provide bushings on C. Indoor locations to be NEMA 1, outdoor locations to be NEMA 3R with internal heater. ends of conduit. D. Manufacturers: Square-D, Eaton, Siemens. E. All conduits shall be provided with fish wire. F. Provide 3/4-inch fire rated plywood, good on 1 side, for backboards at locations indicated on 264300 Surge Protective Devices drawings. Paint exposed surface matte grey. A. Devices to comply with most current edition of UL 1449 and use individually fused metal oxide = 0 G. All outlets shall have blank plates. varistors. =v i B. B. Service entrance SPD: Type 1, approximately 200kA per phase protection. _, 260553 Identification for Electrical Systems C, Branch panelboards: Type 2, approximately 100kA per phase protection. e®`, ATf A. Provide labeling for each panel board that includes voltage, bus rating, AIC rating, arc flash D, Manufacturer to be same as electrical distribution equipment and to be integral to equipment it is /* :•� ., ° �g '�" hazard warning label, and power source feeding panel. Also provide type written circuit directory protecting. o� •• OR3Fs1. �` �� to identifyeach load fed from oriel. p . i d "�" """ � �� B. Provide labeling for each transformer that included primary and secondary voltage, KVA rating, 283100 Fire Detection and Alarm r I and power source feeding the transformer. A, Provide design and installation for extension and modification of existing fire alarm system. If no 11 C. Conductors shall be color coded to identify voltage, phase, neutral or ground. existing fire alarm system in building, provide new. Contractor responsible to providing all necessary components. B. Fire alarm system to comply with all applicable codes and standards. C. Fire alarm system to be microprocessor controlled addressable type. D. Fire alarm to be EST iO Series or equivalent by Simplex or Honeywell. 3P600 =USED DISCONNECT ;EXISTING) ELECTRICAL ONE -LINE DIAGRAM NOT TO SCALE I I I I I 15 If this document Is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writingto validate authenticity of the document. The sealing. professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seat or signature has not been validated In this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title AILLECTRIC' ONE -LINE & SCHEDULES Sheet Number E4s0 0 s w >ti h �� o'- z a c� `ci z S � • N 2 O w �w aw ¢C' o_ c� o z w m W � � N J �g LL � N J J � Q LLLy w a� T d � J m J o as o w aZ wW m W a m o Vj U 8 C GJ U � Q DI LOCATION: ELECTR MAIN DEVICE: 600 A BUS AMPS: , RIBUTION PANEL: AC AL - 116 VOLTAGE: 480Y/277 V. 3 a 4 W. A.I.C.... EXISTING SPECIAL: EXISTING PANEL CKT POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES 1 3 40 0.0 kVA CHILLER (EXISING TO REMAIN) 2 3 10 0.0 kVA 40 HP AHU FAN (EXISTING TO REMAIN) 3 3 50 0.0 kVA 20 HP CIRC PUMPS (EXISTING TO REMAIN) 4 3 50 0.0 kVA 20 HP CIRC PUMPS (EXISTING TO REMAIN) 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS CONN. LOAD: OVA EST. DEMAND LOAD: 0 VA CONN. CURRENT: 10 A EST. DEMAND... 0 A NOTES: DISTRIBUTION PANEL: MDP LOCATION: ELECTRICAL -116 VOLTAGE: 480Y/277 V. 3 0 4 W. MAIN DEVICE: 800 A A.I.C.... EXISTING BUS AMPS: SPECIAL: EXISTING FUSEABLE SWITCH PANEL POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES 3 400 A 140.9 kVA CDP VIA T2 3 200 A 69.7 kVA W P2CKT 3 200 A 59.3 kVA H1 3 200 A 0.0 kVA Spare 3 400 A 0.0 kVA Spare 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS Lighting 29147 VA 125.00% 36434 VA Motor 93279 VA 100.00% 93279 VA Other 107400 VA 100.00% 107400 VA LITES 3 VA 125.00% 4 VA CONN. LOAD: 269849 VA EST. DEMAND LOAD: 262126 VA CONN. CURRENT: 325 A EST. DEMAND... 315 A NOTES: E.C. TO VERIFY FUSES AND DISCONNECTS ARE IN GOOD WORKING ORDER. W U a z V z W ao w < z z A W w _ u. U i- F- I U A� ~ 2 W r Q i W ' ? I OU) W r7 CLIY a 4111� Issuances asp PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/0612 DISTRIBUTION PANEL: CDP LOCATION: ELECTRICAL - 116 VOLTAGE: 208Y/120 V. 3 a 4 W. MAIN DEVICE: 600 A A.I.C.... EXISTING BUS AMPS: SPECIAL: EXISTING PANEL CKT POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES 1 — 0.0 kVA Space 2 — 0.0 kVA Space 3 — — — 0.0 kVA Space — 4 — 0.0 kVA Space -- 5 — — — 0.0 kVA Space -- — — — 0.0 kVA Space — — 0.0 kVA Space 3 200 A 57.3 kVA PANEL L1A (EXISTING BREAKER) P12 3 225 A 67.6 kVA PANEL LIB (REPLACE EXISTING BREAKER) 3 200 A 16.1 kVA PANEL D (EXISTING) 13 14 15 16 17 18 19 20 21 22 23 24 25 26 LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS Motor 3501 VA 100.00% 3501 VA Other 97400 VA 100.00% 97400 VA CONN. LOAD: 140921 VA EST. DEMAND LOAD: 125911 VA CONN. CURRENT: 391 A EST. DEMAND.., 349 A NOTES: REMOVE ALL BREAKERS NOT BEING REUSED AND REPLACE WITH SPACE FILLER. Revisions No. Date Descd �M z O J LLI 1111141, i ad6•, S, O iiy4�^;+ RQORtdI I If this document is sealed and s or electronic format and is race! other than the sealing professlo the document, you mustcontac professional In writing to validat the document. The sealing prof the seal and signature and shal any liability associated with It w authenticity of any digital or ele signature has not been validata Job Number Drawn By App/d By Sheet Title FILELE (l PANE SCHEDULE Sheet Number EM I I.�:; I;I _ J F. PANELBOARD: L1A LOCATION: ELECTRICAL -110 PANEL TYPE: MOUNTING: SURFACE NEMA1 VOLTAGE: 208Y1120V 13 o / 4W FED FROM: CDP BUS AMPS: 225 AMPS FEEDER: SEE ONE -LINE DIAGRAM MAIN DEVICE: 225 A MLO A.I.C. RATING: 10,000 AMPS SYMMETRICAL SPECIAL: LOAD DESCRIPTION LTS RCPTS MTRS OTHER P AMP CIRCUIT BKR AMP P OTHER MTRS RCPTS LTS LOAD DESCRIPTION VENDING MACHINE (G) 1600 1 20 A 1 .. . ... .. . . .. . . ... . . . . . ... . 2 20 A 1 1600 VENDING MACHINE (G) VENDING MACHINE (G) 1600 1 20 A 3 4 20 A 1 180 COUNTERTIOP GFCI COUNTERTOP GFCI 180 1 20 A 5 6 20 A 1 180 COUNTERTOP GFCI MICROWAVE (G) 1100 1 20 A 7 8 20 A 1 1100 MICROWAVE (G) MICROWAVE (G) 1100 1 20 A 1 9 10 20 A 1 1100 MICROWAVE (G) MICROWAVE (G) 1100 1 20 A 11 12 20A 1 1100 MICROWAVE (G) FUTURE ERC 1100 1 20 A 13 14 20A 1 1100 FUTURE ERC FUTURE ERC 1100 1 20 A 15 16 20 A 1 720 GENERAL RECEPTACLES TV RECEPTACLE 450 1 1 20 A 17 18 20 A 1 450 TV RECEPTACLE WATER COOLER (G) 500 1 20 A 19 20 20 A 1 1600 VENDING MACHINE (G) ICE MACHINE (G) 1200 1 20A 21 22 20 A 1 180 COUNTERTOP GFCI MICROWAVE (G) 1100 1 20A 23 24 20 A 1 1 1100 MICROWAVE (G) MICROWAVE (G) 1100 1 20A 25 26 20 A 1 1100 MICROWAVE (G) MICROWAVE (G) 1100 1 20A 27 28 20 A 1 1100 MICROWAVE (G) COUNTERTOP RECEPT 180 1 20 A 29 30 20 A 1 180 COUNTERTOP RECEPT COUNTERTOP RECEPT 180 1 20 A 31 32 20 A 1 540 ENTRY RECEPTACLES MOTHERS RM RECEPT 180 1 20A 33 34 20 A 1 600 MOTHERS ROOM FRIDGE (G) MOTHERS /_ 900 1 20 A 35 36 20 A 1 1200 REFRIGERATOR (G) REFRIGERATOR (G) 1200 1 20 A 37 38 20 A 1 1200 REFRIGERATOR (G) REFRIGERATOR (G) 1200 1 20 A 39 40 20 A 1 1200 1 EWC EWC 1200 1 20 A 41 42 20A 1 360 GENERAL RECEPTACLE TRAING RM FLOOR RECEPT 400 1 20 A 43 44 20 A 1 400 TRAINING RM FLOOR RECEPT TRAING RM FLOOR RECEPT 400 1 20 A 45 46 20 A 1 200 TRAINING RM FLOOR RECEPT TRAINING RM RECEPTS 1080 1 20A 47 48 20A 1 360 GENERAL RECEPTACLE EWC 1200 1 20 A 49 50 20A 1 1200 EWC OPEN OFFICE RECEPTS 360 1 20 A 51 52 20A 1 360 OPEN OFFICE RECEPTS OPEN OFFICE RECEPTS 360 1 20 A 53 54 20 A 1 360 OPEN OFFICE RECEPTS OPEN OFFICE RECEPTS 360 1 20 A 55 56 20 A 1 500 PRINTER PRINTER 500 1 20 A 57 58 20 A 1 180 ELECTRICAL RM RECEPT CONFERENCE RM RECEPTS 720 1 20 A 59 60 20 A 1 180 MECH ROOM RECEPT CUSTOMER PICKUP RECEPT 360 1 20A 61 62 20 A 1 Spare Spare 1 20A 63 64 20 A 1 720 OPTIONAL OFFICE RECEPT STATION MANAGER RECEPT 720 1 20A 65 66 20 A 1 900 HR ROOM RECEPTS STORAGE RECEPTS 360 1 20A 67 68 20A 3 1000 0 1 WATER HEATER TRAINING RECEPTS 360 1 20A 69 70 -- 1000 0 — SIGN CONNECTION 600 1 20 A 71 72 -- 1000 0 — DEMARC RECEPTACLE 360 1 20 A 73 74 20 A 2 1467 CU-1 AC-1 104 2 20 A 75 76 — 1467 104I - 77 78 20 A 1 180 EF-1 EF-2 180 1 20 A 79 80 20 A 1 Spare Spare 1 20 A 81 82 20 A 1 Spare Spare 1 20 A 83 84 20A 1 Spare LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED PANELTOTALS Motor 3501 VA 100.00% 3501 VA Other 33600 VA 100.00% 33600 VA CONNECTED LOAD: 57261 VA Receptacle 20160 VA 74.80% 15080 VA EST. DEMAND LOAD: 152181 VA CONNECTED CURRENT: 159 A EST. DEMAND CURRENT: 145 A NOTES: (G)- GFCIBREAKER PANELBOARD: EM LOCATION: WAREHOUSE -119 PANEL TYPE: MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 o / 4W FED FROM: EM LTG INVERTER BUS AMPS: 100 AMPS FEEDER: SEE ONE -LINE DIAGRAM MAIN DEVICE: 100 A MLO A.I.C. RATING: MATCH PANEL W SPECIAL: LOAD DESCRIPTION LTS RCPTS MTRS OTHER P AMP CIRCUIT AMPBK p OTHER MTRS RCPTS LTS LOAD DESCRIPTION WAREHOUSE EM LIGHTING 2556 1 20 A 1 ... ... ... 2 20 A 1 Spare WAREHOUSE EM LIGHTING 2556 1 20 A 3 4 20 A 1 Spare WAREHOUSE EM LIGHTING 2130 1 20 A 5 6 20 A 1 Spare Space — 7 8 — — Space Space — 9 10 - — Space Space — — 11 12 — — Space Space — — 13 14 — — Space Space 15 16 — — Space Space — 17 18 LOAD CLASSIFICATION CONNECTED DEMANDFACTOR CALCULATED PANELTOTALS Lighting 7242 VA 125.00% 9053 VA CONNECTED LOAD: 7242 VA EST. DEMAND LOAD: 19053 VA CONNECTED CURRENT: 9 A EST. DEMAND CURRENT: 111 A NOTES: PANELBOARD: LOCATION: WAREHOUSE -119 PANEL TYPE: MOUNTING: SURFACE NEMA1 VOLTAGE: FED FROM: CDP BUS AMPS: FEEDER: SEE ONE -LINE DIAGRAM MAIN DEVICE: A.I.C. RATING: SPECIAL: L1 B 208Y/120V / 3 o / 4W 225 AMPS 225 A MLO 10,000 AMPS SYMMETRICAL LOAD DESCRIPTION LTS RCPTS MTRS OTHER P BKR AMP CIRCUIT BKR AMPP OTHER MTRS RCPTS LTS LOAD DESCRIPTION JEM RECEPTACLE 2500 1 30A 1 ... ... . ... . ... . ... . ... . 2 30A 1 2500 MHE RECEPTACLE RECEPTACLE 2500 1 30A 3 4 30 A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 30A 5 6 30A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 30A 7 8 30A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 30 A 9 10 30 A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 30A 11 12 30A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 1 1 30A 13 14 30A 1 2500 MHE RECEPTACLE MHE RECEPTACLE 2500 1 30A 15 16 30A 1 2500 MHE RECEPTACLE PRE VENDING 360 1 20 A 17 18 20 A 1 360 DOCK RECEPTACLE D K RECEPTACLE 360 1 20 A 19 20 20 A 1 360 DOCK RECEPTACLE D K RECEPTACLE 360 1 20 A 21 22 20 A 1 360 DOCK RECEPTACLE H OH DOOR OPERATOR 500 1 20 A 23 24 20A 1 500 HS OH DOOR OPERATOR E ERIOR RECEPTACLE 360 1 20A 25 26 20A 1 360 AEN RECEPTACLE A 208-V, 30-A 2300 1 2 1 30 A 27 28 20A 2 1500 AEN 208-V, 20-A - 2300 - - 29 30 - - 1500 AEN 208-V, 20-A 1500 2 20 A 31 32 20A 2 1500 AEN 208-V, 20-A 1500 - - 33 34 - 1500 AEN RECEPTACLE 180 1 20A 35 36 30 A 2 2300 OF 208-V, 30-A IDF RECEPTACLE 360 1 20A 37 38 - 2300 IDF RECEPTACLE 360 1 20A 39 40 30 A 2 2300 OF 208-V, 30-A Spare 1 1 20A 41 42 - 2300 LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED PANEL TOTALS Other 63800 VA 100.00% 63800 VA R eptacle 3780 VA 100.00% 3780 VA CONNECTED LOAD: 67580 VA EST. DEMAND LOAD: 167580 VA CONNECTED CURRENT: 1188 A EST. DEMAND CURRENT: 1188 A N ES: LOCATION: MOUNTING: FED FROM: FEEDER: PANELBOARD: D ELECTRICAL -116 PANEL TYPE: SURFACE NEMA1 VOLTAGE: 208Y/120V/ 3 o / 4W CDP BUS AMPS: 225 AMPS SEE ONE -LINE DIAGRAM MAIN DEVICE: 225 A MLO A.I.C. RATING: EXISTING SPECIAL: EXISTING PANEL LOAD DESCRIPTION LTS RCPTS MTRS OTHER P AMP CIRCUIT BKR AMP P OTHER MTRS RCPTS LTS LOAD DESCRIPTION 11 17 POWER DROP 360 1 20 A 1 ... ... . . ... . ... . ... . 2 20 A 1 360 1177 POWER DROP 111 POWER DROP 360 1 20 A 3 4 20A 1 360 1171 POWER DROP 11,7 POWER DROP 360 1 20 A 5 6 20A 1 360 1171 POWER DROP 1171 POWER DROP 360 1 20A 7 8 20 A 1 360 1177 POWER DROP 11 '1 POWER DROP 360 1 20A 9 10 20 A 1 1 1 360 11156 POWER DROP 1166 POWER DROP 360 1 20A 11 12 20 A 1 360 1177 POWER DROP 1171 POWER DROP 360 1 20 A 13 14 20 A 1 360 1171 POWER DROP 117 POWER DROP 360 1 1 20 A 15 16 20 A 1 360 1171 POWER DROP 11,7 POWER DROP 360 1 20 A 17 18 20 A 1 360 1177 POWER DROP 11 '1 POWER DROP 360 1 20 A 19 20 20 A 1 360 1148 POWER DROP 11,18 POWER DROP 1 360 1 20 A 21 22 20 A 1 360 2207 POWER DROP 2168 POWER DROP 720 1 20 A 23 24 20 A 1 1 360 2125 POWER DROP 11''3 POWER DROP 360 1 20 A 25 26 20 A 1 360 1173 POWER DROP 11 i'3 POWER DROP 360 1 20 A 27 28 20A 1 480 1173 POWER DROP 1173 POWER DROP 360 1 20 A 29 30 20A 1 360 1173 POWER DROP 11, 3 POWER DROP 360 1 20 A 31 32 20 A 1 360 1173 POWER DROP 1151 POWER DROP 360 1 20 A 33 34 20A 1 360 2524 POWER DROP 251)2 POWER DROP 360 1 20A 35 36 20A 1 360 7507 POWER DROP 2502 POWER DROP 360 1 20 A 37 38 20 A 1 360 7507 POWER DROP 2507 POWER DROP 360 1 20A 39 40 20 A 1 360 11175 POWER DROP 111i4 POWER DROP 480 1 20A 1 41 42 20 A 1 720 11168 POWER DROP LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED PANEL TOTALS R eptacle 16080 VA 81.09% 13040 VA CONNECTED LOAD: 16080 VA EST. DEMAND LOAD: 13040 VA CONNECTED CURRENT: 45 A EST. DEMAND CURRENT: 36 A N ES: I PANELBOARD: LOCATION: ELECTRICAL -110 PANEL TYPE: MOUNTING: SURFACE NEMA 1 VOLTAGE: FED FROM: MDP BUS AMPS: FEEDER: SEE ONE -LINE DIAGRAM MAIN DEVICE: A.I.C. RATING: SPECIAL: H1 480Y/277V 13 o / 4W 225 AMPS 225 A MLO MATCH PANEL W LOAD DESCRIPTION LTS RCPTS MTRS OTHER P BK AMP CIRCUIT AMPBK p OTHER MTRS RCPTS LTS LOAD DESCRIPTION AHU-1 10531 3 50 A 1 ... ... . . ... . ... .. . ... . ... . ... . 2 15 A 3 3880 AHU-2 10531 — 3 4 — 3880 10531 5 6 3880 — AHU-3 3880 3 15A 7 8 20A 1 3135 OFFICE LIGHTING 3880 — 9 10 20A 1 1 1 1 1257 OFFICE LIGHTING 3880 — 11 12 20A 1 Spare Spare 1 1 20 A 13 14 20A 1 Spare Spare 1 20 A 15 16 20A 1 Spare Spare 1 20 A 17 18 20 A 1 Spare Spare 1 20 A 19 20 20 A 1 Spare Spare 1 20 A 21 22 20 A 1 Spare Spare 1 20A 23 24 20 A 1 Spare Spare 1 20 A 25 26 20 A 1 Spare Spare 1 20A 27 28 20 A 1 Spare Spare 1 20A 29 30 20 A 1 Spare Spare 1 20 A 31 32 20 A 1 Spare Spare 1 20 A 33 34 20 A 1 Spare Spare 1 20 A 35 36 20 A 1 Spare Spare 1 20 A 37 38 20 A 1 Spare Spare 1 20 A 39 40 20 A 1 Spare Spare 1 20 A 41 42 20 A 1 Spare LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED PANELTOTALS LITES 3 VA 125.00% 4 VA Lighting 4392 VA 125.00% 5490 VA CONNECTED LOAD: 59265 VA Motor 54870 VA 100.00% 54870 VA EST, DEMAND LOAD: 160364 VA CONNECTED CURRENT: 171 A EST. DEMAND CURRENT: 173 A NOTES: LOCATION: ELECTRICAL -116 MOUNTING: SURFACE NEMA 1 FED FROM: MOP FEEDER: SEE ONE -LINE DIAGRAM PANELBOARD: PANEL TYPE: VOLTAGE: BUS AMPS: MAIN DEVICE: A.I.C. RATING: SPECIAL: W 480YI277V / 3 o / 4W 225 AMPS 225 A MLO EXISTING EXISTING PANEL LOAD DESCRIPTION LTS RCPTS MTRS OTHER P AMP CIRCUIT BKR AMP P OTHER MTRS RCPTS LTS LOAD DESCRIPTION DOCK DOOR LEVELER 2770 3 20 A 1 ... ... ... . ... . ... ... . ... ... . 2 20 A 3 2770 DOCK DOOR LEVELERS 2770 3 4 — — 2770 2770 5 6 2770 DOCK DOOR LEVELER 1385 3 20 A 7 8 20A 3 942 HS OH DOOR MOTOR — 1385 — — 9 10 942 — 1385 — — 11 12 942 HS OH DOOR MOTOR 942 3 20 A 13 14 30A 2 5000 VAV W/ 1OKW HEAT — 942 — — 15 16 5000 — 942 — — 17 18 20A 1 1596 PARKING LOT LIGHTING EXTERIOR WALL PACKS 748 1 20A 19 20 20 A 1 830 Lighting EXTERIOR DOOR LIGHTING 68 1 20A 21 22 25 A 3 2556 EM LTG INVERTER BAF-1 942 3 20 A 23 24 — 2556 -- 942 25 26 — — 2130 942 27 28 20 A 3 942 BAF-2 BAF-3 942 3 20 A 29 30 — — 942 — 942 31 32 — — 942 942 33 34 20 A 1 2556 WAREHOUSE LIGHTING WAREHOUSE LIGHTING 2343 1 20 A 35 36 20A 1 2343 WAREHOUSE LIGHTING WAREHOUSE LIGHTING 2343 1 20 A 37 38 20A 1 2130 WAREHOUSE LIGHTING WAREHOUSE LIGHTING 2556 1 20 A 39 L40 I 20A 1 ispare Spare 1 26-A—, 41 42 20 A 1 Spare LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED PANELTOTALS Lighting 24755 VA 125.00% 30944 VA Motor 34908 VA 100.00% 34908 VA CONNECTED LOAD: 166663 VA Other 10000 VA 100.00% 10000 VA EST. DEMAND LOAD: 175852 VA CONNECTED CURRENT: 184 A EST. DEMAND CURRENT: 191 A NOTES: U a z z ^ W n _ W z 0) os v E W _ T2 U ®� LU LP W m uj W122 c l— or Q Q W z W �.t ® w 'tm ^` Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No, Date Description ZUU o J r IY 0') m J J Q u-. Lli �U W O o U~ o0 �O LL r` J LLJ 0 ti r tM1 TA,''C+F a, If this document is sealed and signed in a digit or electronic format and is received from some other than the sealing professional identified it the document, you must contact the sealing professional In writing to validate authenticity c the document. The sealing professional disclai the seal and signature and shall not be liable f, any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated in this manne Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title PANEL SCHEDULES Sheet Number E5ml .J N Statistics Description Symbol ISLE WAREHOUSE Ci rc] C,J lei C in > �� �1 w2 Cis) �da 16 I i f 1.3 6 2.5 '42.3 34.6 406.6 4.6 46.1 4.6 46.1 5.5 48.2 + 4.3 44.9 36.1 49.5 4.1 44.2 36 34.2 '44.3 + 36.0 4�9.4 34.5 45.3 5.5 48.0 0 5.0 46.8 34.8 46.5 35.6 -48.4 33.6 44.2 0 32.7 �45.4 29.2 31.9 36.2 36.8 37.3 38.6 + 37.0 +39.4 36 .7 '36.8 39.4 '37.3 + 38.7 38.1 '37.9 39.1 36.7 '36.2 '18iL 4 32.4 35.5 36.5 - 38.0 36.5 '38.8 36.3 '36.3 38.8 36.8 + 38.2 : '.6 37.4 3II.6 +3 6.3 '35.7 4.6 +21.8 22.7 040.8 2.2 45.1 5.4 46.3 6.6 -_ 48.9 7.8 45.7 6.9 +50.5 38.5 45.1 6.8 LI+ +45.3 36.9 0 60.4 38.6 46.3 37.2 + 49.0 38.1 0 47.8 37.7 + 47.5 37.8 + 49.5 38.8 45.4 7.6 0 '46.4 5.5 '34.4 36.4 41.5 43.3 4 .1 5 45. 45. +45. 3 45.9 '46. 45. 5 '45.3 45.5 �46.0 44.4 46 0 48. +43. 0 0 ICI k 153.3 0 +43.4 '32.7 +44.8 37.6 49.8 '44.5 31 3 2 32 54.9 51.6 33.3 - 32 9 i '55.0 51.8 0 �' 8 48 2 �� �.I. I . 55.6 �50.6 , 4(.3 48 8 .I 51 9 --- �39.7 '41.7 2.2 +33.0 0 +44.6 3.9 39.0 '�2 8 47.7 '51.2 45 1 45.1' III I 45 4 �57.8 1.2 '56.9 146,2 I n , I .4 I 4i '58.0 51.1 57,5 i i 46.1 '. 4ti 4 �I 4�' G �IIL �� I . ILd 55.2 5o.1 56.2 1 I �.. 27�3 • 44.3 li I I196 � 4J_ 5 22 4 34.3 �48--.6 A 41 1 4. B 5.2 47.9 15.2 8 7 '51 5 -10 'B 8 51.8 103 ' 8 �I 14 i 51.2 --' 1' '39.6 '43.2 __ 51.7 4 3 4 8 4 8 57.0 45,5 44 8 i 57.0 0 � r 3 � 0 5 I �� � 55.4 II 47.3 4.0 4 .5 +36.9 `36.2 45.7 0 39.0 +46.7 '41.2 '40.3 '46.9 45.3 51.2 +48.6 46.3_ '52.4 31 N {' 9 `II i� li 91",I o 3 I 7.3,. �.i. m 137 9 AK 53.5 '54.1 54.4 52.0 56.4 11.4 .'� 8 4 3 8 � / 2 � 2 S -... 53A 55.2 55.2 ',2.4 56.2 � 42 5 � I 42,8 V'I'. 42.6 ., ��:0+t�� I „4:,� � +50.9 -52.5 54A �49.6 51.4 0 I 0 II 124 9. I -7 9 44.3 - - 71-.2 �21.7 8.8 - -° 40.7 + - 4.1 38.3 32.6 ,3 4 33 1.0 336 34 0 ' 3 6 --. '. '51.3 � 12 3 10„4 15 6 ,•�� �45.3 +38.0 +40 8 ' 9 + I 4�6. 45'. 53.5 46.1 E I 5-.0 153.4 I, 45.8 45.5 1 4�.7 '48.9 0 - +42.0 +39.1 +34.6 +32.9 32.5 32.5 '34.2 33.3 33 5 33.1 '34.5 + 33.2 33.0 32.5 +31.5 - +29.6 '29. +26. 25. 25. 25. I 25.6 +26.5 2 .1 8 26.8 +26.1 26.5 25.8 25.7 +24.6 + -,i 18.2 - +38.9 38.7 '41.3 +40.3 39.9 41.6 3 .8 '44.2 4 .3 4 .99.746. 4(.5 4 .3 4 .0 4 .8 +4 .1 + 34.9 +39.5 +39.7 42.9 +42.1 + 41.6 '29.2 30.6 +32.4 +32.0 31.1 +40. 32 +40.0 � 32. +43.3 +35. +4 4 . +40. +37.1 +40.1 '37.7 + + 43.0 40.6 42.9 40.2 42.7 40.1 + + 42.6_ 26.6 +' 36.7 29. I - + 44.6 41.5 + 41.5 39.3 011 +45.8 '42.3 40.8 38.8 + + 37.1 16.3 +1 + 19.1 16. a a , , 42.6 '40.9 38.9 45.9 42.2 41.9 39.5 44.3 41.3 0 -- a �LJI- _ 43.2 +40.5 42.7 + 40.2 44.3 41.3 40.3 38.2 0 41.3 '38.1 - -14 I I7 Avg Max Max/Min I 10.1 fc ! 12.6 fc 1.4:1 38.5 fc 58.0 fc 13.5:1 I Avg/Min Min I 1.1:1 8.9 fc 9.0:1 4.3 fc (Schedule Symbol Label Quantity Manufacturer 67-{EATON- METALUX (FORMER COOPER LIGHTING) 34 EATON- METALUX (FORMER COOPER LIGHTING) Plan View Scale - 1/16" = 1' Lamps - -- - p Lumens Per Light Loss g p Lam Number Filename Lamp Factor Catalog Number 'Description VHBLED-LD1-24-W-L840- METALUX VALUE HIGH BAY (168)3500K CCT, 85 CRI 216 VHBLED-LD1-24- 109.2407 0.9 CD1-C6-SVPD3-U LINEAR LED ABSOLUTE LEDs ABSOLUTE W-L840-CD1- PHOTOMETRY IS BASED ON PHOTOMETRY IS BASED U.IE'S CALIBRATION FACTORS CREATED ON CALIBRATION USING LAB LUMEN STANDARDS I FACTORS CREATED IN GONIOPHOTOMETER WITH I USING LAB LUMEN TEST DISTANCE OF 28.75 FEET iSTANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 24 FEET VHBLED-LD1-24-W-L840- METALUX VALUE HIGH BAY (168)3500K CCT, 85 CRI 216 VHBLED-LD1-24- CD1-C6-SVPD3-U LINEAR LED ABSOLUTE LEDs ABSOLUTE IW-L840-CD1- PHOTOMETRY IS BASED ON PHOTOMETRY IS BASED U.I@S CALIBRATION FACTORS CREATED ON CALIBRATION USING LAB LUMEN STANDARDS FACTORS CREATED IN GONIOPHOTOMETER WITH USING LAB LUMEN (TEST DISTANCE OF 28.75 FEET STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 24 FEET I I I 109.2407 0.9 Wattage 213 213 2/11 /2018 kale lot to Scale lrawina No. 1 of 1 a z _ ^- W IN W z C) � E Z ILLI o •- L m j a o j U m d m o Qj 2 < a ul z 01 W �J_ a' M O N T� t11 � T `^. v (0C1 a O o Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description Z W O J �- C)0) UM J Q Q LL U LLj �W O� Uof '1O vLL I.L � W W 0 ®� llli - i AT OF //llldifiill„AI�� (� If this document is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the - authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SVH App/d By Sheet Title t E PHOTOMORIC PLAN Sheet Number E7.0 SDW J zQ 32.� +26.3 '9.2 4.4 2.6 'i'3.9 16.9 '8.4 13.2 30.3 0 32.2 15.6 -8.6 '8.5 19.3 +16.4 25.8 110.1 7.3 11.4 27.8 I '33.6 14.8 '4.9 3.0 '3.7 '5.0 $ 3 -_ -- '35.6'31.421.512A*7.5 24.8 20.1 '8.3 5.2 5.5 11.0 14.8 12.2 13.5 15.6 15.3 25.4 28.9 21.0 '13.6 10.3 19.0 '34.4 27.4 12.2 '9.3 15.5 29533.1 29 2 +12 9 '4 9 3 8 16.7 12.1 11.3 31.2 6.8 _ �6.1 10.9 9.8 '6.9 6.8 8.6 mo 31.1 21.6 +25.8 30.0 18.8 17.5 24.8 34.0 23.3 13.2 18.0 34.4 '32.1 16.0 12.5 23.1 M. 32.8 22.9 18.9 4.3 4.5 11.5 27.1 -'23.2 J �2g' F - � '5.4 I] 33 _� JI 3 55 3 5.6 +11 A �9.0 12.0 '22.2 29 5 '37 0 '33.7 1 35 1 27 8 21 7 13.3 16 9 14 2 22.4 27.6 3612 34 8 '27.7 16 4 '15.2 9 9 17.1 20.5 32.1 38 1 35.9 25.5 �1 4.9 6.0 6.7 8.9 12.4 12.6 '20.1 29.4 20.7 24.6 1 i. '1 1 6 � 5 2� !1 A 1 '13.8 � � � � � I -13.9 � ''19. '2 16.9 +6.6 t 3.7 '4.3 +10.9 25.0 21.6 20.5 4.4 6.1 7.6 15.4 27.2 '20.4 114.1 '15.3 12A 13.3 1118 �19 90 � ' 11.5 2 .9 � '2.� .0 ' '3.0 - I 3.3 3.6 6.0 10.4 9.8 n 9.9 11.g1 8.6 4.7 3.7 5.0 7.6 '8.5 9.4 12.2 '19.0 28.1 33.5 31.0 22.7 'l5.7 113.1 '12.9 -12.6 1'1.6 '10.3 19.7 10.2� � F + 3.6 1 13.5 13.5 10.5 8.9 7.9 18 ' 7.3 1.5 -2 3 3.1 3.6 10.1 11.3 17.9 31.1 22.4 � � �--- -- �i � � --- - -- L - I 5.2 5 9 5.2 -'4.0 3.4 3.2 3.3 4.3 14.0 - - 3.6 : 7.6 -.... 3.6 3.5 3.3 2.5 2-7 3.0 3.3 �3_. 22 1 23.1 •20.5 13.9 16.1 '14 3 8.4 '24.7 15.8 9.7 9.5 9.5 11.0 13.1 10.5 8.8 9.8 13.3 12.4 9.1 9.1 11.8 13.2 10.2 8.2 6.0 4.5 -4 3 41 2 2 2 1 2 2 11.4 54 l l 1 32.5 26.3 11.3 18.9 '9.9 1.6 33.5 '20.6 )5.1 I 56 3 9 5 F, 4.4 6'.0 I � 4 7 4. 1 10. �1�4.� 10.0 16.7 7.9 '1 15 21 3 18.1 '15.3 8.3 6.9 '7.5 I 13.2 18.6 16.2 24.8 29.Ei 2 2 2:4 2.6 �5.9 '3.� + 18.3 30.0 19. 29. 17.3 10.9 18.3 '32 1 I I +27.5 +8.2 -8.0 -7.5 8.2 ..'77 7.8 9.2 '22.327.3 -_ 3 7 - - 31.9 1.8 20 J L J 1 7 L1 2.I 1.4 18.3 .3.4 29.9i _ L 31.7 5.9 6.8 '11.2 16.8 13.0 .5 11 7A 11.3 It 2.8 12.3 7.9 6.6 1 ' '- '- - 0 5 17.2 21 4 32.3 - 27.5 18.0 17.8 26.7 - 31.5 *19.5 It .3 9.9 9.9 19. �3.2 9.1 I -14 8 7.2 8.7 -17.7 � 2.2 22.0 '1.8 8.0 7.0 '7 1 7.4 '6 1 rt r _ _-, '3.1 3.5 '5 3 '4 ...Q 5.6 '5.9 7.8 ,8.9 7.1 � S7 14.0 14.1 16.3 24.9 18.7 -13.7 15.0 11.0 8.2 3.1 2 -1 5 3.1 °�.5 5 5 2.1- - +5.4 4.3 +4.0 4.'1 I, 10.4 1 : 3.2 29.5 24.7 12.7 12.0 -11.9 0.7 30.7 19.4 14.615.0 u )144021 35� 1 1)y91 --_ -_. l 9_I2.5 8.9 4.4 '2.92.7 ----- -- -... 22.2 a . 2.5 27.7 22.6 10.0 7.6 8.6 18.7 '28.7 +20.7 25 7 30.4 -29.9 14.0 8.8 10.3 +14.9 111.8 7.3 -'10.7 25.8 27.0 11.2 '8.0 '18.9 '29.3 15.8 +5.2 2.7 2.3 34I Q* ir- L p 2.2 9 F1 � _I F I 12.6 11.1 7.3 '6.7 '6.9 0.1 'l 3.4 13.9 +24 0 2, . 28 0 '10 15 5 '2. '26.3 11.2 18.3 18.0 '27.2 F '15.0 '4._9 2 4 2.0 2 .2 26.3 21.9 14.0 9.5 7.8 8.6 12.2 118.0 22.8 22.9 18.1. 11.6 6.6 4.1 2.9 2.1 22.9 + + + * 1 2, _1 7 15 t� 39.6 '2.; ' 5.4 6.3 8.0 10.2 8.8 6.8 7.4 9.3 16 1 1 � 2 � 19.5 "TT:6 --- �T5 --G' .5-�J,7 i2-.2----`�8.-5-- $.1 1.8 2 21.1 3.6 5.6 -13.3 23.1 16.4 7.1 '6.1 �9.1 '20 7 24,7 24.ZJ _-_J L �-J14.P_J 26.7 1 _ _-J 2._ I�: 26.7 3,1.9 33.3 j 2.9 5.6 )7.1 Statistics Description Symbol Avg Max Min I Av /Min Max/Min 1 g ISLE 13.4 fc 4.7 fc 3.0 fic 1.1:1 1.6:1 PATH OF EGRESS 15.8 fc 34.3 fc 2.0 fc 7.9:1 17.2:1 I i ,PATH OF EGRESS 16.7 fc 38.1 fc 2.1 fc 8.0:1 18.1:1 WAREHOUSE 13.2 fc 36.4 fc 0.8 fc 16.5:1 45.5:1 Schedule Symbol Label �I cm�ur www.Cltylighting.com 00 U V a z ^ W C _ W Z 'n C_-5 v E W cG U w M m _V^ CO> U w _ a � CIO � o CO a w Z w Xrn O w Lu �r tY � to to (7 , a00 d '(0 Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description W n ZW 0 O J r g C)° J ,J z Q QLj- ( Q W of W 2 W W D- W 00 �LL 0 f� W Uj W i J W LU Of O Q 0 ILL m Z O Q i1_ fl Ifthis document is sealed and signed in a digital Quantity Manufacturer �Catalo Number Number Lumens Per Light Loss or electronic format and is received from someone g (Description Lamp Lamps (Filename g Wattage other than the sealing professional identified in - - the document, you must contact the sealing p Lamp Factor 1 professional in writing to validate authenticity of 34 EATON - VHBLED-LD1-24- METALUX VALUE HIGH BAY (168)3500K CCT, 85 CRI 216 VHBLED-LD1-24- 109.2407 0.9 213 the document. The sealing professional disclaims METALUX IW-L840-CD1-C6- LINEAR LED ABSOLUTE LEDs ABSOLUTE the seal and signature and shall not be liablefor W-L840-CD1- (FORMER any liability associated with it where the SVPD3-U PHOTOMETRY IS BASED ON PHOTOMETRY IS BASED U.ies authenticity ofany digital orelectronic seal or signature has not been validatedinthis manner. COOPER CALIBRATION FACTORS ON CALIBRATION jLIGHTING) CREATED USING LAB FACTORS CREATED Job Number 83460006 LUMEN STANDARDS IN USING LAB LUMEN Drawn By SVI1 GONIOPHOTOMETER WITH 'STANDARDS IN App/dey sow TEST DISTANCE OF 28.75 GONIOPHOTOMETER Sheet Title 1 FEET WITH TEST DISTANCE OF 124 FEET W ,Designer AREHOUSE �MTf� Dat " I nyL,' iScale Tk AS NOTED IPLAN!Drawing No. Sheet Number (Summary 1 of 1 E7. J z Schedule Symbol Label IQuantity (Manufacturer 83 EATON- METALUX (FORMER COOPER R 1>`JS' 1 LIGHTING) R 2/S 2 Statistics Description BREAKROOM Calc Zone #20 Calc Zone #21 CONFERENCE CONTEMPLATION CUSTOMER PICKUP ELECTRICAL ENTRY HR OFFICE JANITOR MOTHERS OFFICE OPEN OFFICE STATION MANAGER TRAINING 27 EATON - METALUX (FORMER COOPER LIGHTING) Catalog Number Description 24AC-LD5-48-UNV-L835- METALUX Accord 2X4 LED CD1-U ,TROFFER !22AC-LD5-34-UNV-L835- METALUX Accord 2X2 LED ICD1-U TROFFER Lamp (168)3500K CCT, 85 CRI LEDs ABSOLUTE PHOTOMETRY IS BASED ON CALIBRATION FACTORS CREATED USING LAB LUMEN STANDARDSIN GONIOPHOTOMETER WITH TEST DISTANCE OF 24 FEET (84)3500K CCT, 85 CRI LEDs ABSOLUTE Number Filename Lamps 168 24AC-LD5-48- UNV-L835-C D 1- U.ies 84 22AC-LD5-34- UNV-L835-CD1- Lumens Per Light Loss i Lamp Factor Wattage 29.11734 0 9 41.88 41.25591 0.9 30.2 IPHOTOMETRY IS BASED U.ies ON CALIBRATION - FACTORS CREATED USING LAB LUMEN 23.827.227.427.52.E 20.E+25.82.12 66.4+26.1+24 5 2y 031.132.333 033.633 733.132.231.1'29.426.92 .0 STANDARDS IN 2 73 .132 033.1'3 633.832.732.3324'".8+29 5 + re4.243.4`42.2_4 +GONIOPHOTOMETER 3 437.8'38 63738.937.73 531.02 .0 +27.631.028.935.43�.038.136.636.036335.632$ - WITH TEST DISTANCE OF Ii �3 .33 .741.3�42.245+42.6+41.44 .13.9+24 FEET 26.928. 18.28.437.740.039.438.137.637.837.134 d)6+34 + 3 241 942 94 .52 .7 24.825.617 28.23 434.334.134.234 35 839 140.941 942 843 142 441 239 837 533.8+2 .4 Imo: ,---ram + + r.336 633 6 126 2277'21 26.53 + � 0+31 4 35 538 640.441 642.442 641 940.839.236.933.32 3 2 8'2 .624 . ` . ` . ' . + . ` ` . ' :3 +36.7+40.041.9'43 043.944.1+43.342.1'40.5+38.034.33 .0 + ri f -�: '2 33C�.224I 24.728.130 431.030.730.831.130 628 5 + + -_ 4 04 .945:947.14.14 .547.646.2 36.131.2. 3 444.4'45.54 845 944.54 .3 27.529.322. 27.3311.634.435.034.734 935,.434.932 1 - � + 11 + � -.. 4 .64 .037.53 1 ymbol Avg Max Min Max/Min Avg/Min fr:6.718.+28.5+33.z+36.337.537.3+37237.6+37.033 1 + .047.145.84 .737.23 A 41.7 fc 55.1 fc 15.4 fc 3.6:1 2.7:1 - - 28.329.8)2 . 28.435.339.3+39.3F38.137.737.837.134 38 241 7+43 745 045.946.245 544.242.640.136.031.4 -- 2 .73.0+29.635.137.5'38,6'37.636.135.635.835.132 + '$ 7.741.143.244.545.346.644.943.641 9 39.3 35.4 31.1 - - 31.3 fc 40.1 fC 18.4 fc 2.21 1.71 26.229.330.931.833.2�34.432.731.831.431.430.828 + i 38.942.644.846.147.047.346.545.1'43.340.636.531.8 - + + , ,24 .447.E+4$.95.1.5 .4+49.5+48.04 . - .338.63 .1 -22326-:4-25-�2§�5'L5.9-3-}:024-8-2r.�.925fi25z'-23: + I 24 728 028 327 83 ..�3 .633.732.632.232:334,.729 4 42 947.649.851.25 55Y 9+52 0+50.44 64 .640.434.4 31.1 fc 40.0 fc 17.9 fc 1.6:1 1.3.1 a 2.2:1 2 8 20.625.726.026.226.024 35.1 fc 41.7 fc 26.1 fc + 46.4 fC 50.5 fc 42.1 fc 1.2:1 1.1:1 28.631.]29435.537939.138.136.fi36.036335.5327 43.247.950.331853.053.5'52.751.24 341.03 .7 l ! 1 42 547.149.550 952.152 752.050.E+48 845.740.53 .3 -_ - 27.828. - 18 28.5+38.140 039 4i38.137.6`37.837.1+34 4 343.744 846. 750.0+48.64 4 939.03 .1 27.228.322. 26.63 . .534.534.4 34.534. .231 17..-9,4.11 34.0 fc 36.8 fc 30.4 fc 1.2.1 1.1:1 25.826.318.128.23 + 138.337.537.237r436 733 4 347.548 85Q 645.8�44.34 .33603 .8 34.3 fc 40.9 fc 25.3 fc I L� + 40.0 fc 45.4 fC 31.9 fc iI 1.4:1 1.11 28 629.924 34.638.140.240.940.037 33.035 336.135.333. + '38.4Z8�45.54645.342 80 1142.141.1382s73o.oa 23.326.28.429.028.9.029.328.82E 1.5:1 1.21 32.8 fc 39.3 fc 26.E fc I 41.346.349.350.2+49.045 4345. 44027 428.522 126.33 3.033.833.733.83 3 .631 1 -� ! 1.4:1 1.2:1 - +43.248.4+51.652.551.147.-40.644.045.144.040. 32.9 fc 38.3 fc 26.8 fc 26 226 36 537 737.23E 937.236.533 618 528 032.E + + + + '44.e49.853.1+53.9+52.448 39 1 �42 043.042.038. 46.3 fc 150.5 fc 41.E fc III 1.2:1 1.1:1 I 28.42s.7�12a.437s40.139.538.137.637.837.134 - - ' + , '45.750.7+53.9164.8+53.2+49 38 841 041 940.938A 2 .93 .029.535.73 .23 338.336.836.23 .53 .832 - 34.5 fC 40.0 fc 29.7 fc 1.3:1 1.2:1 '46.250.6'54.055.152.948, 39.342.143.042.038. 27.932 733.535. .034.233.132.732.832.229 �- 50.7 fc 63.4 fc 30.9 fc 2.11 1 .6: 1 - - - -27 - - +45.951.353.954.652.1.47 410. 44 044. 43. 40. 94 + 46.1 '4 .9 +49.1+51.252.052.1350.345 3 40. 3.844, 43. 40.1 39.3 fc 48.3 fc 28.9 fc 1.7:1 1.4:1 6.1' 0 4 0.5' .8 +34.736 836.336.938.1'38.739.542.146.547.848.649.250.148.044 q 37 540 241.040.037. 0.2 5 135.337 535.937.138.4+39.440.442.6'44.444.945.0+44.4+44.7+44.741 � 32.334.234.834A31. --- 41.7 fc 53.5 fc 24.0 fc III 2.2:1 1.7:1 ,4 33.532. _ ..._:..._...._.. _ 37.338.333.323.220.018.216.715i.4 - 4 .3 29.627. 35.5+36.z+34.129.025.322.420.018.3 421`45.545.5 479L0.5�0.3' 8+30.632828.429.030.130.931.331.5+31.731.8+31.8+31.431.238.9+38.4+36.232.329.626.523420I.8 47 9p0.5 0.3{l..8 32.2I35 236.934.335.436.31136.837.037.137.4I37.336.936.9+41.3+41.239.4�36.533.630.426 723.2 42 145.545.54 .3 33.9�i7.3 �39.638.739 740.7p1.341.441.6p1.9�V1.8+41.4'42.243.9t4.741341,938.534.9-30.626.1 3.742.239.937 033.529 225.0 18 620.324.128.334.5 8.3 0.941.642.1+43.2�p3.743.8'44.0k14.3�p4.243.844 5+45.1 21.7+23.726.431.d35.038.641.042.342.6 43.744.344.444.E 44.E 44.744.344.644.844.242.941.038.434.930, 726.5 +24.1+26.429.132.936.1+39.041.242.543.2'43.944.444.644.744.944.8+44.4+44.644.443.742.340.5'38.034.630.626.7 26.929.7 32.4 35.638.2'40.642.443.644.4+45.045.445.545.7 45.845.7+45.345.3+44.444.142.740.938.4 35.131.0 27.0 -29.7�33.2 �36.2'38.9+41.143.2I+44.745.646.4++47.1J47.4+47.447.5J47.7+47.6'47.1+47.0146.6'45.744.2 42.439.436.3 32.0 27.7 +32.0�i5.9�39.1i�41.643.6�15.5�}6.847.548.2IW8.9�19.249.149.2 9.4�t9.3+48.848.5W8.1�7.245.7'43.741 237.532 928.3 33.1 7.1 0.442.644.5 6.3 7.448.148.749.4 9.649.649.6F9.8 9 649.148.8148.4147.445.843.9+41 437.733 128.5 33.1'36.9'40.642.244.045.7+46.747.3+47.948.d48.8+48.7+48.8 48.948.748.247.84Z3+46.3+44.842.8+40.436.832.528.2 32.8+36.539.541.E 43.444.945.9+46.547.147.6'47.947.847.847.947.7�47.346.8'46.245.343.741.8+39.336.031.9271.8 33 236.839.841.943.745.246.146.747.347.848.148 048.048 147.947.446.946.345.343.841.939.436.032.027.9 + + + a + + + 34 138.141.143.245.046.547.548.048.649.249.449 349.349 449.248.648.147.E+46.645.043.0+40.537.032.72 .3 35.OD9.242.444.546.37.98.849.349.90.50.750.550 550.750.449.949.348.847 946.244.241.738.033.42 .7 35.1 9.342.544.646.4 7.948.949.449.9 0.5 0.750 650 650.750.549.949.3 8.9{47.9�46.244.241.738,633.4+2 .7 + - ,- , ,- , + ,- + - +. +'' + - + 34 438.3'41.4`43.545.346 847.748.248.849.349.549.449.449.549.248.748.247.646.645. 29.93 -04(y 843.04 .84 .235.12 .9+29.734.0+33'T34.029 7 26.129.'8'32 132.331.430.831.332 232.130 026 4 27.930.330.327.9 043.040.537.032.72 .3 +' '29.3' 4'2'37.1{{I�17.235.734.835.EI7.13Z1�J$�4A29. 31L53473 .831E '33.737.440.342.444.1�45.646.547.1+47.648.1+48.348.248.248.248.047.547.046.445.443.841.839.436.032.02 .9 32.539.845 447.046.843.837.93 7`31.8�036.931 6 ,31.6�7..240.540.5'38 637.638.540.4'40.537 431 `7 33.737 5�.6'33,Q + , , , + + , + 32.539.845.748.348.145.038.83 .432.637.940.037.932 6 33.737.3+40.242.444.145.546.547.047.548.048.248.248.148.247.947.446.946.345.343.741.839.335.931.92 .8 31.93 .14 747.3147.114 .138.13 932.0'37:139.2'37.132 0 32.433341 741.639.638.539.641 641.738 332: 34.438.338.334 34.338.341.343.445.146.E47.548.048.549.149.349.249.149.249.648.447.947.446.444.842.840.336.832.52 .1 + + ' + + + , , + + + F + + - 37 �640.�40 738 837.838 40.840,837 531. 33,.437: 3j.233.� 35.0 9.1 �42.344.446.1 7.7r38.649.049.5 0.1 0.350 150.150.350.049.448 9 8.447.445.843.841.337.633.12 .4 + , , I pp-- 3045+36638+340.443�45247'2500501{.851248142+9 0.929,934.937.837.736.135.336.337.837.734.729. 30.834.034.030.8--- 34.9 9.042.144.245.9 7.4N8.348.849.3'p9.8 0.049.949.8'S0.049.849.248.E 8.247.245.643.641.137.432.92 .3 35.03Z + {r - + + _ '3 63 . L + 1 , 4 i , + + + + , + + � 25.329.231.531.730 730.230.731.731.629 425.7 34.037.840.742.844.545.946.847.247.748.248.448.348.348.448.247.647.146.645.644.142.139.736.z32.02 .7 .539.541.644.748.551.654.957.257.455.452.2 ' '28.83373�536.55.034.135.036 636 633 828 9' r - + , , + , + + , + + 31634.634.230. ,I 33.036.539.3+41.342.944.z45.145.646.146.646.746.646.646.746.546.045.544.944.042.540.638.235.031.02.0 32.535.1'36.8+38.942.047.853.157.46.0_.66_1.560.258.2_5_6.8'56.054.753.752.751.449.747.745 44.2.037 532.kF _ , + ,__, --*- + 49.456 - + + , + + + + + + ! + + '- + 31.1.3 6 0 939:737 836.837.,839.739.936.631!0+32.636.038.840.742.3+43.6+44.444.945.345.8+46.045.945.945.945.745.244.844.343.341.940.137.734.530.62 .7 26.731.636.03 .031.726 8 .961.663 463.162 261.46.01,859.758_.857.956.554.6521449.8451.940.434.4 33 236.436.132 --� + _ , r. , + + + + 31.837.6'40.9�40.738 837.738.8i40.7+40.937.531;732.736.3+ .1'41.0+42.e43.944.74 .1�45. 4 . '4 .1'46. 46.046.1+4 4 44. '44. '4 .74 + + + 33.63E 836 532 39 5 5 6 0 E 0 5 9 5 4 9 5 3 2 240.,6 134.930.82 .6 28.434.238.238.334.428 7 43.153.259.2'62.1+63.163.363.363.062.261.460.659.157.1'54.952.147.942 035 5 „^ - r + , _�, � { { + + + 1 + + + + 11 + + + + + + + , + , 33 636 736 432. 31.136.739.939.837.936.837.839.739.93E 631;0 32.636.439.141.042A 3.844.544.845.2�F5.7. 5.945.745.7 5.945.745.144.7 4.4W3.642.240.538.334.930.72 .4 29.0351139:2'39.335.2292,7.62..3.62,.361.96L3fi0�59.257.255 ,24 .042135E ,_,-.,. + + + i-,.-, + + - + 1 '4 - - + 40.7 42Qfr5.6 59.4 6 0.9 61 ,636.635.034.235.036.636.633 828:9 - , + - ,- - i + '33.036.235:932. 29.033.83�Y 31.435.037.639.340.61.842.642.843.2'p3.7p3..843.643.6I43.8;43.643.142.72.41.740.438.836.866.729.72 .6 28.43 .238.23 .334.328 6 38.345 251 154.956.958L1�`3.959,1 58.958 457 856.654.852�.240.834.6 - 25.8+ + + + + + j 31 234.133 8+30. 29.431.631.730.830.230.831.731.629.425:7, 29.031.934.235.636.937.938.538.839.1'39.5'39.639.539.539.639.639.138.738.437.8'36.735.333.530.927.62 .1 5:Fi41:145$49,151,15� 35 . C u�Hriruls Pev®ut>s �Mpa� www.Cityllghting.com U TW z V Z W WLO Q0 Z V E OV w LZLA w To :20 U w � ~ c m o W U U a < ¢ w z Cr i Wn O rn cn T �_ v X �r U �m C1 3- r 3- r° D Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description RTMM ZW O LO �'LO 61 U rf) aQW 0w �w 0a 1-- (_5 o0 O N IT LL LLJ mmi LLI If this document is sealed and signed in a dig or electronic format and is received from soir other than the sealing professional identified the document, you must contact the sealing professional in writing to validate authenticity the document. The sealing professional discl the seal and signature and shall not be liable any liability associated with it where the authenticity of any digital or electronic seal of signature has not been validated in this manr Job Number 8346000E Drawn By SVI- App/d By SDN Sheet Title Designer Dates' Sc� {{011 12/1J201@ fJ Scale H bt Not to Scale PLAN Drawing No. Sheet Number ,Summary I I I I 10fl E71 Plan View Scale - 1" = 8' C J Schedule Symbol Y Label Quantity Manufacturer Y Catalog Number g _ Description Lamp Number Lamps Filename Lumens Per Lamp Light Loss Factor Wattage 13 EATON - 24AC-LD5-48-UNV-L835- METALUX Accord 2X4 LED (168)3500K CCT, 85 CRI 168 124AC-LD5-48- 29.11734 0.3 41.88 METALUX CD1-U TROFFER LEDs ABSOLUTE UNV-L835-CD1- (FORMER PHOTOMETRY IS BASED U.ies COOPER ON CALIBRATION 1 LIGHTING) FACTORS CREATED USING LAB LUMEN STANDARDSIN GONIOPHOTOMETER WITH TEST DISTANCE OF I24 FEET 4 EATON - 22AC-LD5-34-UNV-L835- METALUX Accord 2X2 LED (84)3500K CCT, 85 CRI 84 22AC-LD5-34- 41.25591 0.42 30.2 METALUX CD1-U TROFFER LEDs ABSOLUTE UNV-L835-CD1- (FORMER PHOTOMETRY IS BASED U.ies C2E (COOPER LIGHTING) :ON CALIBRATION FACTORS CREATED USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 24 FEET Statistics Description Symbol BREAKROOM + CUSTOMER PICKUP + (ENTRY + MEN'S BATHROOMS + OPEN OFFICE + TRAINING + WOMEN'S + BATHROOMS Avg Max Min Max/Min Avg/Min 2.0 fc 5.4fc 0.3fc 18.0:1 6.7:1 2.9 fc 6.6 fc 0.8 fc 8.3:1 3.6:1 3.3 fc 6.9 fc 0.9 fc 7.7:1 3.7:1 3.9 fc 7.7 fc 1.0 fc 7.7:1 3.9:1 3.3 fc 6.0 fc 0.6 fc 10.0:1 5.5:1 2.4 fc 6.6 fc 0.6 fc 11.0:1 4.0:1 3.9 fc 7.7 fc 1.0 fc 7.7:1 3.9:1 0.6 0.8 1.0 1.4'2.0'2.8'3.9 4.9 +5.5 5.6 5.1 4.2 3.1 0.6 0.8 1.1 1.5 2.1 3,0 4.1 5.2 +5.9 '6.0 5.5 4.6 -- - `0.610.8'1.1 1.42.0+2.83.94.95.645.75.24.5'3.83.43.23.23.23.02.72.4'2.01.71.5i1 3.64.34.84.9+4.6'4.1+3.83.613.73.83.93.83A'2.92.41.9+1.61 3.13.53.94.03.93.73.63.74.1+4.54.84.74.13A2.7'2.1+1.7`t '2.6+2.93.1'3.33.33.33.4'3.84.45.15.55.44.83.93.02.2 1.7+1 +2.2 2.4 2.6 2.7 2.8'2.9'3.2 3.7 4.515.3+5.8 5.7 5.0 4.0'3.1 2.31.71 +3.0 3.5 1 +4.6 +5. '2.7 +4.2 3 3 2.5 1.9 1. 4.1 4.8 +50463.83.b2.3181.41.210)+ .D. 45. 3.54.1.3.4+6. '6.35.1+3.8'2.82.0+1. +. 4.8 5.8 6 1 5.6 4.5 3.4 2.5 1.9 1.5 1.2 1.0 0. +4.04.6435.66. 6.75.4+3.92.82.1+1.16.6+ 6 _1 -- 5 1 6.2 5.9 4.8 3.6 2.6 1 9 15 '1.2 1.0 0. 4.7-�4.6 1.0. 5.4 16.0 16.4 +5.9 '4.8 3.6 2.7 20 +1 4.8 5.8 '61 +5.5,+4.5 3.4 2.5 1 9 +1.5 1.2 11,0 +1: 4Y'4.6-`5..5] +3.9 '4.6 4.8 4.5 +3.8 '3.0 +2.3 +1.8 IE + + + + 4.0 4.7 49 45 3.7 2.9 2.3 1.8 1.4 1.2 1 1 1 6.0t.66.52.93.2'3.43.22.82.41.91.61. + + + + , , + 32 3.6 3.6 34 2.9 24 20 1.6 1.4 1.2 + 1 1 +1. '6.9 7.6 7 3' .-2.4Z.37'rY9�6-'I . + , + + _ 2 4 2.$ 2 6 2.5 2.3 2 0 1 7 1.5 1.4 1.2 1.1 1. '. '7. 7.7 74'r2.2 2.5'2.6 2.5 23 2.0 1.7 +1.5 1 1.9 1,9 1.9 1.9'+1.8 1.7 1.�6 -1 5 -1.4 1.3 "131. +6.2+6.8�6.7i3.1+3.5+3.6+3.43.0 2.52.0+1.7 1. , 5 +'5 + + 1.4 1.5 15 15'1.5 1.5 1.5 1.5 15 1.5 15 1 +4.2 '4.9 '5.1 +4.7 +4.0 13.1 '2.4 +1.9 +11.1 '1.21.21.3'131.41.51.61.71.81.9+1.9-1 ! 4.54.4 5.66.36.76.14.93Y2.72.01. + 0 , +5 + + - ! 0.9 1.�0 '1.9 1.2. 1.4 1.5 +1.8 2.0 2.3 2.5 2.5 2 L41 '4.3 5.6 +6.�� 6.8 5.4 4.0 2.9 2.1 1. 9 1. 0 11 12 1.4 1.7 2.0 2.5 3.0 3.4 3.5 3'4.2 5.3+64�%7fl 6.2+5.0 382.82.11. ,1.2 ,+ -,_ 0.80.91.01.21.51.82.33.03.8'4.6484 3;8 �4:4 i5.3 �3:2=4 9-3 P- �2:5 + . + . � + ' + + + ' �- 5 1.9 2.6 3.5 4.6 5.6 6 0 5. 3.0 +3.5 4.0 4.6 5. 2.8 4.2 3.3 2.5 -1.9 1. 070.9101.21.520273.i+49'6.1'6.6`5 3.5+4.1 4.415.4'6.6.3+5.1 3.9+2.8 2.1 +1 0.7 0.810 1.21.5 19 2.6 3.5 4.6 5.7 61 `5 4.0 4.7 '2 4.3 5.6 +6.9�-r1. 4 +6.8''5.4 +4.0 '2.9 11 ''0.+ + + , 7 0.8 0.9 1.1 '1.4 1.7 .3 3.0 3.9 4.6 '5 0 4. 4.74.71.05.416.1 6.4'5.94.83.6'2.7+2.0+1- , + + + _ 0.7 0.7 0.9 1.0 1.2 1.5 1.9 2.4 3.0 3.5 3.7 3 4.9 5.1 5.6 4.0 4.6 4.8 4.5 3.8 '3.0 2.3 1.8 1. _ rO -0.7 '0.8 0.9 1.1 1.3 1.6 2.0 2:3 2.,6 2.7 2. '6.2'6.7+6.6+2.93.33.43.2 2.8 2.4+20'1.61.-- - 7.1 7. 732�+2.42.4232T19 Y�Y4 I5+0.5050.50.50.5 0.91.01.010107.1_'732.02.32.32.22.1'1.81.61.41.5'0.60.60.60.60.6 1.21.21.21212 6.26.76.6.2.83.2+3.3 3.1 2.7 2.3'1.9 1.6+1. '0.7'0.7'0.8'0.7'0.7+0.7 1.5 1.5 1.5 15 15 . -B. 5.6 3.84.54.7+4.4.+3.72.92.3+1.81. 0.90.90.9'0.9'0.9+08.i 2.02.12.01918 4.84.8+5.3+6.0+6.35.84.7+3.62.62.0+1. 1.21.2+12.1.1 1.010 2.82.82.72.4 2.1 4.0 4.6+4.3 5.6 6.y f, 6.75.4 +4.02.9 2.1 1. +1.7 1.7'1.61.41.3 11 3.9 39 36 31 26 7.�4. 3.44.1'4.45.6+6.'11D1'6.45.23.92.82.11. +222113 .4.3.01.8.6.3 5.2 5.34.783.0 * + �, I_;, � _„ t, + F j g fj 3.4 3.0 2.6 2.3 '1.9 +1.6 6A 116.4 15.6 4.4 3.4 4.4'3.93.1 2.8 2.2 1.8 6.816.9 &0 �47 36. 0.9 1.1 1.3 1.8 '2.4 3.2 4.1 5.0 15.4 +5.2 '4.4 +3.5 3.2 2.6 +2.1 6.3 6.4 5.6 4.5 3.5 10.9 1.1 1.31.8 2.4 3.2 4.1 4.9 5.4:5.2 4.5 3.62.7 2.9+2.41_5.3 5.4 4.8 4.03.2 '0.8 '0.6 l +2.6 '2.6 2.4 2.0 +1.6 1.3 1.1 11, 0.5 0.5 L. 2.5 2.5+2.5 22-+1.9 1.5 1.3 1. 0.7 0.70.8 0.8 0.91.0+1.1 1.2+1.5'1.8+2.2+2.7+3.2 3.4+3.43.0'2.5'2.11.7'1.4.1. 1 10.8b.9'0.91.01.01.1 1.21.411.62.02.53.2'3.94.3'4.33.7+3.0+2.31.811.4+1:2 '1.0 11 1.1+1.211.2+1.2+1.3+1.5 1.7+2.2+2.83.6 4.4 4.9 4.8 4.2 3.4+2.6 1.9.1.51. 1.0 1.1 1.2 1.3 1.3 1.4 1.4 1.4+1.4+1.4+1.5+1.6+1.8'2.2'2.9 3.6+4.45.04.9 4.2'3.4.2.6+1.9 151. 1.11.2 1.4 1.61.81.9 1.91.9.1.8 1.7 1.6 1.71.92.2 2.7 3.3.4.0+4.4'4.3 3.8 3.12.41.81.51. '1.3'1.5+1.8'2.1 2.4 2.6 +2.6 +2.4 2.2+2.0'1.8 1.8 -1.9 '2.1 2.4"2.9+3.3 3.63.5 3.2 2.6'2.1 +1.7 1.41:1 +1.4 +1.7 +2.1 2.6 '3.1 '3.5 3.5 3.2 '2.7 +2.3 +2.0 1.9 -'1.8 1.9 +2.2 +2.4 2.7 2.8 2.8 '2.5 2.2 1.8 1.5 -1.3 1. 1.5 -1.9 2.53.2 3.9 4.4 4.3 3.9 3.2 2.6 2.211.91.8 1.9+t.9 2.1 +2.2 2.32.2'2.1 +1L9 1.61.412 1. '1.6 +2.1 +2.7 '3.6 4.4 `5.0 �4.9 4.4 3.6 2.9 2.3 2.0 '1.8 '1.8 -1.8 1.9 +2.0 '2.0 +2.0 1.9 '1.7 11.5 '1.3 11.2 1; 1.62.1+2.8 3.6'4A 5.0',5.0 4A1,6 2.92.3+2.0+1.9'1.8 1.9 1.9.2.0 2.02.0+1.9+1.7+1.5.1.3'1.2+1. 1.63 2.02.6.34.0'4.44.44.03.3+2.7+2.32.0'1.91.9+2.0+2.1 2.22.3'2.32.1+1.91.6'1.41.2+1. 1.5 1.8 2.3+2.83.33.6 3.6+3.3 -2.9 '2.4 '2.1 '2.0 1.9 2.0+2.22.52.7 2.82.8 2.5+2.21.81.5+1,3;1. 1.41.6+2.02.3 2.62.82.8+2.7 2.4 2.2.2.0'1.9 2,0 2.22.52.93.43.6+3.6+3.2 2.72.11.71A1, 1.3-`1.5+1.7'1.9+2.2+2.3+2.3'2.2+2.1 2.01.91.9 2.0+2.3'2.8.+3.4 4.1 �I4.4 I4.4 3.8 11 2.41.91,51. 13 1.4 1.6-1.8 1.9.2.02.0 2.01.9'1.8+1.81.9+2.1 2.4 3.03.7 4.5 5.0 4.9 4.3+3.4 2.6+19+1..5 1 + 3 1.4 1.6 112 .8 .9 2.0 .0 2.0 1.9 1.8 1.8 1.9 2.0 2.4 3.0 3,.7 4.5 5.0 14.9 4.2 3.4 2.6 1.9 1.5 1 - -- '1.3 +1.5 '1.7 11.9 +2.1 2.3'2.3 2.2+2.11.911.8 1.8 2.0 2.3'2.7'3.3 4.04A 4.33.7'3.0+2.3 1.8 1.4'1.1 1.41.6'1.9 2.3 2.6 2.8 2.8 2.62.42.11.91.8 -1.9 2.1 2.4 18 3.2 3.5 3.4 102.5 2.0 1.61.31. 1.5 1.8 2.2 2.8'3.23.6 3.6 3.3 2.8 2.4'2.0'1.8 1.8+1.8 2.0+2.2+2.5+262.5'2.3+2.01.61.3+1.1 1. +1.6`2.0 2.5+3.23.9'4.4+4.4+3.9 3.2.2.E 2.1 1.81.71.6 1.7 1.8+t.9+1.9'1.9'1.71.5+1.311.11.0 `0: 1.62.1 2.73.5 4.4'4.9µ4.9+4.3 3.5+2.7 2.1 1.8 -1.5 '11.4 1.41.4+1.4 1.4 1.4 -1.3 -1.2 1.1 0.9 09 b. 1.6 -2.0 2.7 3.5'4.3 �4.9 4.8 4.3 3.42.7 2.11.7 1.41.31.211.21.1 1.1 '1. 1 1.0+0.9 0.9 0.810.7 +0. -_- 2.1 23 2.4 2.3 2.1 '1.8 1.5 1.3 .1.1 1.0 +0. 1.5 1.9'2.4 3.1 +3.8 4.3 +4.2 3.7 3.1 2.4 1.91.5'1.3 1.1 ,1.0 1.0 b.9 0.9 +0.9 +0.8 '0.8 V7 +0.7 +07 0. 1 2.9 3.1 +12+3.02.62.211.8 '1.41.21.0 0. 1.31.6 2.1 2.63.03.3 3.3'3.0+2.52.0++1.61.3+1.1 1.0+0.9.0.8'0.8+0.8+0.70.70.7+0.60.6 '0,661 3.7 4.2 4.3,4.0 +3 4 .2.-/ 2.1 -�1.6 '1.2 '1.0 10.. E +1.2 1.4 1.7 +2.0 2.3 2.5 2.5 +2.3 2.0 1.6 it 4 1.2 1.0 0.9 10.8 '0.7 '0.7 0.7 0.6 0.6 +0.6 '0.6 .0.5 0.5 10. 4.6535.68.1 4.212 2.3`1.7+1.31.00. 1.0'1.11.31.51.7..1.81.81.7+1. '51.31.11.00.90.80.70.7.0.6+0.60.60.5+0.50.50.50.5+0. 51'6.1 6.56.04.83.52.5'1.81.31.00.E +0.9'0.91.01.21.21.31.3`1.21.1 1.0.0.90.80.70.70.60.6+0.60.5'0.5+0.50.5`0.5+0.4+0.4+0.1 52 626.6.6.0 4.93.6 26 1.8-+1.3'1.0+0.+0.7'0.8+0.8+0.9+0.9'1.0+1.0'0.9+0.9 0.8+0.8'0.7-0.6 `0.6'0.610.5'0.5 0.5 0.5 0.4 0.4+0.4 0.4-04'0.1 Y t ' i 1 + + + k. + _ _ _ -0.7 _ -0. T 4.6 5.4 5.7 5.3 44.4 2.5 1.8 1.3 1.0 0. -0.6 -0.7 0.7 0.7'0.7 0.8 0.8 0.7 0.7 0.7 0.6 '0.6 0.6'0.5'0.5 0.5 0.5 0.4 0.4 0.4 0.4+0.4+0.4 0.4'0. Plan View Scale - 1" = 8' P.C9r vvww.Oryllghtingsom g W U LL LL W U X W a_ I- O' O U- m 0 Z O Q �ate� Scale Not to Scale (Drawing No. Summary 1 of 1 Q/ U ID a z ^ W Lo _ W N W Z � iN r d E W U W @ Of a W ,> /� d W = U N 2 (7 a �T iv- Q Lij Z ILL! � O U) w �rn � n . C4 # m ^` 1 �. a m m Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02/06/2019 Revisions No. Date Description qqrmm ZW O J� ULC) lY � U o� J a ¢� �w 2W O a U~ O0 O V W W 0 If this document is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated in this manner. Job Number 83460006 Drawn By SVH App/d By SDW Sheet Title ED PHOTOMETRIC PLAN Sheet Number E7.3 J 9 \iI U a C') z Ql ^_ LU n �L w z � W cG � allU u\/ 0 Z ~ � We ^ m _ W = P O 0 a L� ¢ w Z 01 w .9 p Vu LU a"o) �� IL C7 'r (0 00 u7 d °�° m Issuances PERMITS: 02/27/2019 SITE PLAN REVIEW: 02106/2019 Revisions No. Date Description /Re's�'all +o.o +o.o +o.o +o.o +o.o +o.o +o.o +o.o o.o o.o o.o o.0 0.0 0.0 o.o o.o o.o o.o Ow o.o 0.0 0.0 0.0 0.0 0. 0.0 .o 0.0 O.o 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1: o a 0. 00.0 0.0 0. o.o 00 o.o o.o o.o a.o o.o O.o o.o o.o o.o o.o o.o o.o o. o.0 0.0 0. 0.0 0,..0 0.0 0.0 0.0 o. / + + + + + + # + + + # + + + + + + + 'F # + + + + + + + + + + + + + + + + + + + F + + + + + + + + + + + + + + + + + + + + + + + t + + + + + + + + + + + + + + + + + + + + + + + + + + + + # + + + + + i + + + + + + + + + + + + + + a.o a.o o.o o.o a.o o.o 0.0 0.0 o.o o.o o.o o.o o.o o.a 0.0 0.a o.0 0.0 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.o a.o 0.0 0.0 .0 0.o 0.o o.o O.o 0.0 0.0 0.0 0.0 0.o 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.o a.o 0.0 0.0 0.0 0.0 0.0 0.0 0.o b.o o.o .o o.o o.o o.o o.o o.o o.o o.o o.o i.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o.o o. o.o o.o O.o o.o o.o .o o.o o.o o.o o.o o.o o.o o.o o.o 0.0 0.0 0.0 0.o O.o 0 0.0 0.0 0. 0.o o.o o.o o.o o.o 0. + + + + i + + + + + + + �. + + # + + + + + +. + + + + + + + ' ' + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +o.o o.o o.o o.o o.o o.o o.o o.o 0.0 o.o o.o o.o 0.0 0.o O.o o.o o.o o. o o 0.a o 0.0 o.o o.o o.o o.o o:o o.o o.o o.o o.o o.o o.o a.o o.o o.a o.o o.o 0.0 0.0 0.0 0.0 0.0 + o o.o 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0, o.o o.o 0.0 o.o o. o.o o.o 0.0 0.0 o. + + + + + + + + + + + + > + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + 'F + + + + + + + + + + + + + + + + + + + + + + + + + # + + + + + + + + + + + + + + + + + + + + + + + + # + + + + + + . . p 6 • . . .o o.o .o 0 0:06�°o 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.o a.o O.o o.o o.o o.o o:o o.0 0.o a.o 0.0 0.0 0.0 0.0 0.0 0.0 0.o o.o o.0 0.o o.o o.o o.o o.o o.o o.o O.o O.o 0.o o.o o:o o.o o.o o.o o.o o.o o.o o.o o.a o.a o.0 0.0 0.0 0.0 0.0 o.o o.o o.o o�o.o o.0 0.0 0.0 O.o o.o a. + + + + + + + + + + + 0 +0.0 +0.o +0.1 +0.1 +0.1 0.1 0.1 +0.1 +0.1 +0.1 �0.1 +0.1 +0.1 +0.1 +0.1 "6 1 W.o +0.o +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 `0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.0 +0.0 +0.0 +0.0 +0.o +0.o +0.0 +O.o +0.0 +0.0 +0.o +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 0.0 +0.0 �0.0 +0.0 +0.0 +0.0 +0.0 0.0 0 o 0.0 0.0 0.0 0.0 0.0 o.0 o.0 0.0 0.0 0.0 0.0 0.0 0.o 0.0 O.o 0.o Liz Oreu z LU -j _ LO 0.00.00.00. 0.o0.00.o0.00. .00.00.o0.00.00.00.00.1 0.1 .1 0.1 0.1 0.1'0.1 .1 0.1 0.1 0.00.00.o0.00.00.00.00.o0.00.00,00.1 0.1 @.3$20.. 0. 0.20.1 0.1 0.00.00.1 0.1 2 .2 2 20.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0,1 0.1 0.1 10.4Q.1 1 0.1 0.1fl.1 0.1 0.1 0 1 0:1 0.1 0.00.00.00.00.00.00.00.0 0.00.00.00. �� + + + + + + 2 + + 0+0 2 + 0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0.1 +0. +0.1 +0.1 +0.0 +0,0 + .0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0.0 +0. U t 1 0.0 +0.0 +0.0 .0 +0.0 +0.0 +0.0 0.0 0.0 0.1 0.1 0.1 0. 1 0.1 0.1 2 . 2 9 �.6 0. �.5 0. m6Mme9u 5 + + N ®®�mau.1 J J + pp�q + 2u` . O• + + + + + + + 0.3 0.3 0.3 0.2 0.1 0.1 0.1 0.1 01 0.0 LIM U.0 .U.U 0.0 0.0 0.0 0.0 0.0 0:0 0.0 0.0 0.0 0.1 0.1 4..3 .3' 0.3 .3 0 3 0.3 0�3 .3 4�1 0.1 0. 0.1 .8 b. 1: 01. 1.1 .0 0.8 0.7 1 0 .2 0. 0.8 1. L 0 0.8 0.7 0. pp 5 r1 Q LL + + + + + + +. + + + 5 + Q.5 + Q.5 + + + + Q + + + + + + + + O + + + + + + + 4 + + 5+ + + + + + + + + + +tl' +�I + ' + + ��' _ ,+. +0• + M�' + + + + + + .+ + °+� + + + + Q' + + + + + + + + + + + n + + + + + + 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 .1, 0.5 5 0. 0 0.1 2 0 1.8 1. 1.3 1.8 1. 0 ,as,0 1.5 1.5 1.4 .6 0. ?� 0.� 8 .3 1. 17 1 0.8 0.9 0.70.7 .7 0.7 .7 0. 0.7 0 -0 0.7 0. 0.6 0. 0.8 0.7 0 0.8 0.6 0.3 0. 0 0.1 0.0 .0 0.0 0. 0.0 .0 0.0 0.0 0.0 0.0 0.0 0. a W 5 1 + + + + + 1 + + + + . + + + + + + + w x s�75 ++++++ + + + + + +++++++++++D.0 0.0 0.0 0.0 0.0 0.0 0.0 0.o 0.0 1 0.3 .6 0:9 1.0 .1 1.4 1.5 .3 1. 0.9 0. .....1.1 1.2 1.3 1.6 17 1.4 1.1 11 1. 1 1.3 1.6 1.6 1.2 .1 1. 4 .6 1.6 1.3 1. 9 .8 .8 0.8 0. 0.4 0.3 0. 0.1 0.0 O.0 0.0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.++++++ + + + + + s s w a *** q, * 5 + + + + + + + + + + Cn 00.00.00.00.00.00.00.00.00.00 0. 1.1 1.1 1.31.31.3 .31.61.7 31. 1. L 1. 1. 25 I 0.25 41.61.92.1 1.1.41.51.8 .1 .1 .01.61.41.21.1 1.1 .00.8 0.3 0, 20.0O.tll .0 .00.00.00.00.00.00.00.00. Od a, t ° r< x s H + + . . * ° *1.6 ' * 0. , 0. 0.. 0. "1 g 1 g 11.5. .4 "1.5 ).7 ).8 1.8 1,9 1.9 12.0 12,0 1.9 1. 1.7 1. 8 1.9 2.1 1.1 2.0 1.9 1.9 2.0 1.2 2.3 2.3 2.2 .1 1.8 1.6 )A 1.2 1.1 b.8 0 4 0. 0. 1.2 1.4 1 2 .0 0.0 .0 0.0 0.0 0.0 0.0 0. 0.0 0,0 0.0 0. U 0.00.0 .00.00.00.00.0 .00.00. 0. 1.811:41.61.71.71.6 .51.@ 1.71.61.51.61.71.61.3 {l + + + + , 4. 2.8*1.9`1.6`1.8).911.1'r1.712.2'2.31L.312.2� .1'2.0 .0"1. .012.2 2.2 2 2.2 2.1 L.1 2.2 1.5 2.6 2.5 1.5 .3 2.0 1.9 1.7 1.4 1.1 0.8 § .�'�. II1.7 1.9 .0 0.1 .0 0.0 0.0 0.0 0.0 0. 0.0 0.0 0.0 0. / 0.0 0.0 .0 0.0 0.0 0.0 0.0 .0 0:0 0. 0. 1.3 1.6 1.8 1.4 1.9 7.8 .8 1.7 1.8 1.7 1.8 1.8 1.8 1.8 1.7 1.6 25 �U- + + + + + + + + + + + . "1 * s Vs12. . 'r * + + + + + + + + + + + + 0.0 0.0 .0 0.0 0.o 0.o 0.0 .o 0.1 0. 1.4 1.7 1. '�5 '2.3 1.9 .9 .8 1.8 .8 1.9 1.9 .4 .4 1.8 1.7 1.3 1. 4. .1 .1-1 .8 12.0 12. 2.6 13.0 2.5 2.6 2.5 L. 2.3 2.2 .3 1. 3 1.3 11.4 2.3 2. L.8 2.8 - 1.8 1.6 1. .9 411. 2.1 2.3 0. �51 0.1 .1 0.1 0.0 0.0 0.0 -0. 0.0 0.0 0.0 0. 0.00.0 .00.00.00.00.0 .00.1 0 ,�. 1.41.71.9 .4 .31.91.91.81.81.81.91 2.4 1.91.7 `1.9112.0d2.1 2.7 1 -- -1.8 -1.9 .3'F 4L.32.4�2.4Z. 8 12.82.9 1.81.61. .9 6�: 1. 2.22.7 .9 0.2 .1 0.1 0.1 0.00.00. �C� 0.00. 25 G9MNE�U � * x 0:0 0.0 .0 0.0 0.0 0.0 0.0 .0 0.1 0. 1.3 1.6 1.8 1.8 1.9 1.9 1.9 1,8 1.9 1.8 1.9 11.0 2.0 1.9 1.7 4: 1.8 1.9 2. 5 1.9 L.0 .1 3 2.4 2.5 2.4 2. 4 2.8 2.8 1.9 1.6 1.20'9 .6 1 7 1. 2.8 3.1 .8 0 .4 0.1 0.1 0.0 0.0 0. g QQ 0.0 0. + + + + + + + + + + 0'2 * x * V x x w +. + + + + + 5 + + + + + + + + + + 0.0 0.0 .0 0.0 0.o Vo b.0 .0 0.1 0 2 O 1.2 1.5 1.7 1.7 1.8 1.8 1.7 1.9 12.1 1.9 1.9 12 12.0 '2.0 1.9 1.7 P5 4. 3 112.3 ) 9 `1.8 1. 5° `1.9 1L.0 .1 d2. .3 2.5 2.5 2.5 12. 4 11.8 2.8 1.9 1.6 1.3 0 .7 .9 2. 3.0 3.3 .9 1 0. 0.4 0.1 0.1 0.0 0.0 0. 0.0 0.0 0.0 0. + + + + + + + + + + + * " II * * a-�`n�rt-ate + ' ' * + + + + + + + + + + + + + + J 0.0 0.0 .0 0.0 O.o 0.o 0.0 .0 0.1 2 .4 ' 1.3 1.4 1.5 1.6 1.8 1.6 1.7 12.1 11.4 12.3 'g2.1 '2.0 '2.0 1.9 1.8 1. 9 1.42.1 `1.9 2.0L.4 4.4 2.8 2,3 2.1 2.0 .1 3 2.8 d2.93.0 2. 43.0.1 1.9 1.7 1. 1. 8 �.9 2. 3.3 3.4 t1.0 �15r1 0.1 0.1 0.0 0.0 0. 0.0 0.0 0.0 0. 0.0 0.0 .0 0.@A pA 0.0 .0 0.4 .2 1.4 1.5 1.5 1.5 1.6 1.6 1.9 12.3 '11.7 � .6 11.2 12 11.0 *1.0 1.9 1.9 25 54➢VLP�® d. .5 � .6 � .1 12.0 "2.1 12.5 13. 9 '13.1 '2,7 12.3 '2.1 .1 � u .4 112.8 13.4 13.6 113. 3 d3.6 113.E 1.9 1.9 1.8 1.4 .9 .9 2. 3.1 3. 1 0. 0.4 0.1 0.1 �.0 0.0 0. 0.0 0.0 0.0 in o+o.0 .00.0Vb nb.0 .00.3 .2 1.41.51.51.5.61.61.8'2.212.51r2.31s2.0120'12.0'12.0"2.01.8 1. 4. 5 .6 .1 1.92.02.43. 3.1 2.62.142.0 .1 2. 3.23.32. 3 13.43.4 1.91.81.81. 9 .81 2.73.23.8 0:5 0.1 0.1 .00.00.00.00.00.00. + + . . s - .).9. + + + + 0.00.0 .00.00.00.00.0 .00. 1.31.41.51.E .61.61.71.9'2.1 .91:92012.02.02.01.81,71. 25 L.O`1.911.1 .5 4.4 .7 .21.9L.O .1 2 .4r2:5 .72.72. 4 1L.92.92 1.61.4 q1 .80. 1 2.32.93.20.4 .30`� 0.1 0.1�).00:00.00.00.00.00. rJ�a' J "' + . * * * + + + C �. 0.0 0.0 .0 0.0 0.0 0.0 0.0 .0 0.� .2 1 . 1.3 1.5 1.7 1 8 .8 1.7 1.6 1.7 1.8 1.9 2.0 2.1 .0 2.0 1.9 s4. 1.9 `1.9 2. 9 1.9 2.0 .1 12 .5 '11A '12. 3 2.8 2.8 .9 1.6 1.2 1.0 .8 .5 1 2.1 2. 0. �152 0.1 0.1 0.0.0 0:0 0.0 0.0 0.0 0.0 0. + + + + + + + + + + '25 * :r �: + + * + + + + + + + + " 0+ + + + + + + + + + + + + + 0.0 0.0 .0 0.0 OA 0.0 0.0 .0 0.1 0 1.4 1,7 1.8 1.9 .9 1.8 1.9 2.49 7 2.0 1.9 1.8 1. 4 z.1 `1.9 2.1 2.3 1.9 2.0 3 0 7 6 1.9 1.6 1. 1 �.9 .5 .4 1.9 2.0 1, 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0. 5 Q , ` ' pp 2 .3 "2. '2.4 '12.4 '12. 2.3 2.8�2� 2 2.8 2.8 7 2.6 13Pf1 �[.3 ) .8 ) .6 1 0.9 55 +0 r5+ 1.4 +1.6 .a Q 325DA +OA +0.0 +0.0 +0.0 +o.o +0.o +0.0 +0.0 +0.0 +0. + + . _ + * . x. 102v1 2. ° .02.22. 2 3.8 1.91.71.81.92: 3. 0.0 0.0 .0 0.0 0.0 0.0 0.0 .0 0.1 2 0 4 1 1.5 1. 2,5 2.3 1:9 7.7 1.7 1.7 1.9 1.9 '�L.3 '2.0 '2 0 ,1.9a 1.8 12 0 '1'15 _ q z v * + + + + + + + + + + + + + + + + + + 25 PL5 , , * » .12.211.7 1.8 L 3 2.3 d1.32.4 2.2 2.3 2.4 2.5 2.7 2.7 2.6 2.4 1.7 2.0 1.8 1.5 1 0.9 1 00 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0. 0.0 0.0 .0 0.0 0.0 0.0 0.0 .0 0.1 02 0. 1.9 1.9 1.8 1.8 1.7 1.8 1.9 1.9 1.8 18 1.7; 1.8 ,33 .7 + + 0'5 . . v * * * * * �5 . . * * + + + + 0.0 0.0 .0 0.0 0.0 O.0 O.o .0 0.1 0 2 .4 0. 1.1 1.4 1.7 1.9 1.5 12.0 1.9 1.9 1.7 1.8 1.7 1.6 1.6 1.7 1.7 1 6 :Q 1.7,'2.5v13.❑4 4.1 A 0 1.9 2. 2.0 2.0 2. ?P 2.2 12.3 12.2 12.1 1. 1. 1. i'0 12.1 12.1 12.1 `12.0 % n 2.1 % A "'1.4 12.4 SA '1.2 12.0 1.8 1.6 1.3 1. 0.8 �.3 0 1 0.0 0.0 0.0 0.0 0:0 0.0 0.0 0.0 0.0 0.0 0. + + Am + Seal 0.00.0 .00.00.00.00.0 00ic .$b 4 81.31.51.712.012.0�1.112.2312.1312.112.11E1.8'11.71E1.51`1.6`1.5"14.�`111��1°:6d2.5-1�.0�2.9�38 11.5+1.7+2.0 .9+17+1.71:81.81.81.82'.02A 1.7+1.5+1.5+1.5+1.51.72.02.1 1.91.71.71.82.02.22.22.1 1.9 .4 0.201 0.00.0 0.00.00:00.00.00.00.00.00. + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + x ' S ).4 : « n.O-4.6 * S S 1.5 2.0 2.2 5 1. 1, 4 1: 4 1. 5 1. 8 1, 9 1. 5 1: 1. 2 1. 4 1. 8 1. 9 1. 6 1. 3 1. 3 1. 4 1. 6 1. 9 2.0 1. 8 1. 5 1. 011. 0 1. 0 0 . 4 0.2 .2 O k1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -0.0 0.0 0.0 0. 0. 00.00.00.00.0 .00.1 0. 2.11.853.43.84.0 6'.211.51.81.4 11.4,41�1:13.1_30.0 0.0 o 0.O 0. 0. �. 1.4 2.0 12.9 4.2 4.7 .9 6.4 .9 2.5 1.8 110 7 �,T .Q 17 2.7 3.2 0 22 2.1 1.6 1 01 .2 1.4 .1 0.9 0.7 0.7 0.8 1.0 a.9 1 .1 0.9 0.8 0.7 0 .5 19 .1 0.1 0. 0 0. �.0 0.0 .0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0. + + 3 + * BS +1.4+1.7+1.7+1. +0.9 + 0.70.70.70- Otb50.4 .40. 0.1 0. 1 0.0000. 0.00.0 .0 .0 0.00.00.00.00.00.00. La 7 0.00.00.00.00.00.00.00.00.0Uu 5 0.00 $0.0 .00. 00.00 t:p.ou4wb.u0.00.00.00. 0.0 O.O O.O O.O O.O 0.0 0.0 0.0 0.0 Rai 2. 9 3. 5 Pf a 4 0.25 5 0. 0.00.00.00.00:00.00.1 1 0. 0. � � � � .60.8 .01.21.51.31. .91.81. 11.00.I�. �.[0.20.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 1s0. 1 0.10.1 0.1°0.00.00.00.00.00.00.0 0.00.00.00. 0.0 .00. 0.00.00.00,00.00. 40 Plan View Scale -V=40' rltfYllll/ J'1 � Statistics Description. Symbol Avg Max Min Max/Min Avg/Min Loading Dock Area IX 2.5 fc 7.3 to 0.4 fc 18.3:1 6.3:1 North Parking Lot X 1.6 fc 2.7 fc 0.6 fc 4.5:1 2.7:1 OVERALL T 0.9 fo 7.3 fc 0.0 fc N/A N/A South Parking Lot ` 2.2 to 5.8 to 0.4 fc 14.5:1 5.5:1 Lamp Symbol Label QTY Manufacturer Catalog Number Description Number Lamps Lumens per Lamp LLF Wattage Pole Height Ll 1 EATON - McGRAW- GLEON-AF-03-1-ED-EI-T2 GALLEON AREA AND ROADWAY LUMINAIRE (3) 70 CRI, 4000K, 1050mA LIGHTSQUARES WITH 16 LEDS EACH 48 371.6656 0.9 166 25' PL2A EDISON (FORMER AND TYPE II OPTICS Retail, Roadway, Sidewalk, Site, Street, Substation, Security, Corrosion Resistant, Vandal CREATED ° COOPER LIGHTING) Resistant, Wet Location ABSOLUTE PHOTOMETRY IS BASED ON CALIBRATION FACTORS USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 28.75 FEET 1 PATON - McGRAW- GLEON-AF-03-LED-E1- GALLEON AREA AND ROADWAY LUMINAIRE (3) 70 CRI, 4000K, 105l LIGHTSQUARES WITH 16 LEDS EACH 48 371,0736 0.9 166 20' ❑ EDISON (FORMER SL2 AND TYPE II SPILL LIGHT ELIMINATOR OPTICS Retail, Roadway, Sidewalk, Site, Street, Substation, Security, ° PL2 B COOPER LIGHTING) Corrosion Resistant, Vandal Resistant, Wet Location ABSOLUTE PHOTOMETRY IS BASED ON CALIBRATION FACTORS CREATED USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 28,75 FEET ❑ 12 EATON - MCGRAW- GLEON-AF-03-LED-E1- GALLEON AREA AND ROADWAY LUMINAIRE (3) 70 CRI, 4000K, 1050mA LIGHTSQUARES WITH 16 LEDS EACH 48 397.777 0.9 166 25' PL5 EDISON (FORMER 5MQ AND TYPE V MEDIUM OPTICS Retail, Roadway, Sidewalk, Site, Street, Substation, Security, Corrosion Resistant, CALIBRATION FACTORS ° COOPER LIGHTING) Vandal Resistant, Wet Location. ABSOLUTE PHOTOMETRY IS BASED ON CREATED USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 28.75 FEET 7 EATON-McGRAW- TT-C2-LED-EI-MQ TOPTIER LED PARKING GARAGE LUMINAIRE MEDIUM DISTRIBUTION 168 28 0.9 34 25' VI EDISON (FORMER COOPER LIGHTING) 8 PATON - McGRAW- GWC-AF-0I-LED-E1-T4W GALLEON WALL LUMINAIRE (1) 70 CRI, 4000K, 1050mA LIGHTSQUARE WITH 16 LEDS EACH AND TYPE IV WIDE 16 394.7684 0.9 59 NA EDISON (FORMER OPTICS Industrial, Landscape, Library, Office, Parking, Parks, Pathway, Pedestrian, Prison, Recreation, W 1 COOPER LIGHTING) Residential Retail, Roadway, Sidewalk, Site, Street, Substation, Security, Corrosion Resistant, Vandal Resistant, Wet Location ABSOLUTE PHOTOMETRY IS BASED ON CALIBRATION FACTORS CREATED USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 28.75 FEET 3 EATON-McGRAW- GWC-AF-0I-LED-El-T4W- GALLEON WALL LUMINAIRE (1) 70 CRI, 4000K, 615mA LIGHTSQUARE WITH 16 LEDS EACH. AND TYPE IV WIDE 16 260.0742 0.9 34 NA EDISON (FORMER -600 OPTICS Industrial, Landscape, Library, Office, Parking, Parks, Pathway, Pedestrian, Prison, Recreation, W2 COOPER LIGHTING) Residential Retail, Roadway, Sidewalk, Site, Street, Substation, Security, Corrosion Resistant, Vandal Resistant, Wet Location ABSOLUTE PHOTOMETRY IS BASED ON CALIBRATION FACTORS CREATED USING LAB LUMEN STANDARDS IN GONIOPHOTOMETER WITH TEST DISTANCE OF 28.75 FEET If this document is sealed and signed in a digital or electronic format and is received from someone other than the sealing professional identified in the document, you must contact the sealing professional in writing to validate authenticity of the document. The sealing professional disclaims the seal and signature and shall not be liable for any liability associated with it where the authenticity of any digital or electronic seal or signature has not been validated In this manner. Job Number 83460006 IDrawn By Author ' App/d By SDW Sheet Title rH E OTOMETRIC PLAN Sheet Number VIA GENERAL NOTES 1. NUMERICAL VALUES SHOWN WITHIN BRACKETS (ex. [1001) REPRESENT THE MILLIMETER VALUE OF THE PRECEDING IMPERIAL VALUE AS A DEFAULT. NUMBERS WITHIN BRACKETS FOLLOWED BY'm' (ex. [100m]) DENOTE A LENGTH IN METERS. 2. LOCATIONS OF RACEWAY, PATHWAY AND SIMILAR ITEMS ARE SHOWN SCHEMATICALLY. COORDINATE INSTALLATION, INCLUDING BUT NOT LIMITED TO CABLING, SECURITY PATHWAYS AND SPACES, AND EXACT LOCATION OF HORIZONTAL CABLING WITH LOCATIONS OF FIXED CASEWORK AND BUILDING CONDITIONS AFFECTING THE WORK OF THIS CONTRACT. 3. PERFORM WORK IN ACCORDANCE WITH APPLICABLE COUNTRY CODES AS AMENDED LOCALLY AND ENFORCED BY THE AHJ. 4. COORDINATE SECURITY WORK WITH THAT OF OTHER TRADES. REFER TO ARCHITECTURAL, ELECTRICAL AND TELECOMMUNICATIONS DRAWINGS AND SPECIFICATIONS. COORDINATION SHALL OCCUR PRIOR TO FABRICATION, PURCHASE, AND INSTALLATION OF WORK. 5. NEW CABLING INSTALLATIONS SHALL BE CONCEALED IN WALL AND CEILING SPACES UNLESS OTHERWISE NOTED ON THE DRAWINGS. CABLING IN ACCESSIBLE CEILING SPACES SHALL BE INSTALLED WITHIN OPEN CABLING SUPPORTS NEAR STRUCTURES AND WALLS OR AS SPECIFICALLY NOTED ON DRAWINGS. SEE SPECIFICATIONS FOR SUPPORT REQUIREMENTS. 6. PROVIDE FIRESTOPPING SYSTEMS FOR CONDUIT AND RACEWAY SYSTEMS AT PENETRATIONS, SLEEVES AND SLOTS OF FIRE RATED CONSTRUCTION FOR HORIZONTAL AND INTRABUILDING PATHWAYS AND SPACES. 7. MAINTAIN A MINIMUM SPACING OF 12" [305] FROM ELECTRICAL FEEDERS AND BRANCH CIRCUIT WIRING AND 12" [305] FROM AUXILIARY SYSTEM CABLING. 8. MINIMUM SPACING FROM ELECTRICAL APPARATUS SUCH AS MOTOR DRIVEN EQUIPMENT AND TRANSFORMERS SHALL BE 6-0" [1.83m]. SPACING REQUIREMENTS SHALL APPLY TO OPEN CABLING PATHWAYS WHERE EQUIPMENT IS LOCATED ON THE SAME FLOOR, FLOOR ABOVE, FLOOR BELOW OR IN ROOMS ADJACENT TO SUCH EQUIPMENT AS THOUGH WALLS AND FLOORS DID NOT EXIST. EXCEPTION: BUILDING CONSTRUCTION THAT RESULTS IN CONTINUOUS METALLIC BARRIER BETWEEN ELECTRICAL APPARATUS AND CABLE PATHWAYS SHALL BE CONSIDERED AS SUITABLE SEPARATION. 9. PRIOR TO STARTING SECURITY INSTALLATION, CAREFULLY INSPECT INSTALLED WORK OF OTHER TRADES AND VERIFY THAT SUCH WORK IS COMPLETE TO THE POINT WHERE WORK MAY PROPERLY COMMENCE. NOTIFY THE ARCHITECT AND ENGINEER IN WRITING OF CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK. 10. DO NOT BEGIN SECURITY INSTALLATION UNTIL ALL UNSATISFACTORY CONDITIONS ARE RESOLVED. BEGINNING WORK CONSTITUTES ACCEPTANCE OF CONDITIONS AS SATISFACTORY. 11. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, OUTLET BOXES, JUNCTION BOXES, RACEWAY SYSTEMS, ETC. FOR A COMPLETE AND OPERATIONAL PATHWAY SYSTEM FOR ALL SECURITY SYSTEMS PER THE SCOPE OF WORK INDICATED ON THE CONSTRUCTION DRAWINGS AND BID SPECIFICATIONS. 12. THE SECURITY CONTRACTOR SHALL PROVIDE ALL DEVICES, CABLING, PROGRAMMING, AND COMMISSIONING NECESSARY FOR A FULLY FUNCTIONING SECURITY INTRUSION DETECTION, VIDEO SURVEILLANCE AND ACCESS CONTROL SYSTEM AS SPECIFIED. 13. GENERAL CONTRACTOR SHALL PROVIDE ALL ELECTRIFIED DOOR HARDWARE INCLUDING ELECTRIFIED HINGES AND 24V POWER SUPPLIES FOR ANY 24V DOOR HARDWARE SUPPLIED AS INDICATED ON THE CONSTRUCTION DRAWINGS AND BID SPECIFICATIONS. 14. ALL SECURITY DEVICE CABLING SHALL BE PROVIDED IN COMPLIANCE WITH LOCALLY AMENDED CONSTRUCTION PRODUCTS REGULATIONS (CPR). SYSTEM SPECIFIC NOTES 1. PROVIDE TAMPER SWITCH FOR EACH SECURITY ENCLOSURE WITH CONNECTION TO AN AVAILABLE INPUT ON A B208 INPUT MODULE. BUILT IN ENCLOSURE INPUTS ON ALL LENEL MODULES SHALL BE JUMPERED OUT TO CLOSE THE CIRCUIT. DOUBLE TAMPER SWITCHES SHALL BE PROVIDED FOR ALL BOSCH INTRUSION DETECTION PANEL ENCLOSURES. TAMPER SWITCHES SHALL BE INSTALLED IN THE MANUFACTURER PROVIDED MOUNTING POINTS. AN ALARM SHALL BE GENERATED IF AN ENCLOSURE IS OPENED OR REMOVED FROM THE WALL REGARDLESS OF IF THE DOOR HAS BEEN OPENED. 2. PROVIDE CONNECTION TO B208 INPUT MODULE FROM POWER SUPPLIES WITH CAPABILITY TO INITIATE POWER FAIL SIGNAL. AN ALARM SHALL BE GENERATED UPON FAILURE OF ANY POWER SUPPLY. 3. ACCESS CONTROLLED DOORS, SECURITY DEVICE WIRING SHALL TERMINATE TO A LENEL 1320 DUAL READER INTERFACE MODULE. 4. ALL ACCESS CONTROLLED DOORS SHALL BE EQUIPPED WITH DOUBLE POLE, DOUBLE THROW (DPDT) MAGNETIC CONTACTS AND SHALL BE SUPERVISED BY BOTH THE BOSCH INTRUSION DETECTION SYSTEM AND BY THE LENEL ACCESS CONTROL SYSTEM. 5. PROVIDE MINIMUM 4-HOUR BATTERY BACKUP FOR SECONDARY POWER OF SECURITY DEVICES CONNECTED TO THE LENEL SYSTEM. PROVIDE P-TOUCH LABEL FOR EACH BATTERY WITH THE SITECODE AND BATTERY INSTALLATION DATE 6. PROVIDE UNDER VOLTAGE CUT OUT PROTECTORS FOR ALL POWER SUPPLIES WHICH SUPPORT SECURITY DEVICES. DURING A POWER INTERRUPTION, POWER SUPPORTING SECURITY DEVICES SHALL BE INTERRUPTED IF BATTERY VOLTAGE DROPS BELOW SECURITY DEVICE MANUFACTURERS RECOMMENDATIONS. 7. UNLESS OTHERWISE NOTED, ALL SECURITY DEVICE CABLING SHALL BE WITHIN CONDUIT TO 10'-O" [3m] ABOVE FINISHED FLOOR, EXCEPT WHERE CONCEALED WITHIN AN ACCESSIBLE CEILING SPACE. RIGID PLASTIC CONDUIT INSTALLED IN ACCORDANCE WITH LOCAL CODES AND REGULATIONS IS ACCEPTABLE. 8. PROVIDE ROLL UP DOOR CONTACTS BOLTED TO THE TRACK OR TO THE WALL AT +10'-O"[3.0m] ABOVE FINISHED FLOOR FOR ALL OVERHEAD ROLL UP DOORS AND VENTILATION SCREENS. 9. PROVIDE SECURITY CABLE LABEL AT EACH END OF EACH CABLE JACKET BASED ON THE DEVICE LABELING PROVIDED ON THE LAYOUT DRAWINGS. SECURITY CABLE LABEL SHALL BE WITHIN 6" [152] OF END OF CABLE. 10. SECURITY DEVICES SHALL BE LABELED IN ACCORDANCE WITH INSTRUCTIONS PROVIDED TO ON SHEET AC5.01 DETAIL 1. 11. AS BUILT DRAWINGS SHALL INCLUDE ANY ADDITIONAL DEVICE LABELS, CONTINUING THE LABELING SCHEME BASED ON THE NEXT HIGHEST AVAILABLE NUMBER. AS BUILT DRAWINGS SHOULD ALSO INCLUDE LOCATIONS OF ADDITIONAL IDPs (PULL BOXES) AS REQUIRED FOR THE PROJECT. 12. PROVIDE 6'-6" [2.OM] SERVICE LOOP AT DEVICE END AND 10'-0" [3.0m] SERVICE LOOP FOR TERMINATION AT HEADEND PANEL. 13. PROVIDE PULL -STRING IN ALL CONDUITS TO FACILITATE CABLING INSTALLATION. 14. PROVIDE WIRE AND CABLE INSTALLATION PER LOCAL CODES. 15. SPLICING OF CABLING IS NOT PERMITTED. 16. ALL DEVICES SHALL INCLUDE LINE SUPERVISION WITH RESISTOR PACKS INSTALLED. 17. INSTALLATION OF ALL WIRING, CABLING AND DEVICES SHALL BE PER MANUFACTURER'S RECOMMENDATIONS. 18. EMERGENCY DOOR RELEASE BUTTONS SHALL BE REQUIRED ON CARD IN/CARD OUT DOORS WHERE DOOR HARDWARE DOES NOT INCLUDE MECHANICAL DEFEAT. EMERGENCY DOOR RELEASE FUNCTIONALITY SHALL BE ACHIEVED VIA A HARDWIRED CONNECTION AND SHALL NOT BE ACHIEVED VIA SYSTEMATIC PROGRAMMING. 19. MAGNETIC LOCK KEYED SWITCH OVERRIDE DEVICES SHALL BE REQUIRED ON THE UNSECURED SIDE OF ALL DOORS WHERE DOOR HARDWARE INCLUDES MAGNETIC LOCKS. MAGNETIC LOCK KEYED SWITCH OVERRIDE FUNCTIONALITY SHALL BE ACHIEVED VIA A HARDWIRED CONNECTION AND SHALL NOT BE ACHIEVED VIA SYSTEMATIC PROGRAMMING. 20. PERIMETER INTRUSION DETECTION INCLUDING MOTION DETECTORS, AND MAGNETIC CONTACTS AT EMERGENCY EXIT DOORS, OVERHEAD DOORS, AND ACCESS CONTROLLED ENTRY DOORS SHALL TERMINATE TO AN INTRUSION DETECTION SYSTEM INPUT MODULE OR CONTROL PANEL. 21, UNLESS OTHERWISE NOTED, ACCESS CONTROLLED DOORS SHALL BE EQUIPPED WITH ELECTRIC DOOR HARDWARE THAT IS UNLOCKED IN THE DIRECTION OF EGRESS AT ALL TIMES (MECHANICAL DEFEAT). 22. PROVIDE GIMBAL MOUNT FOR MOTION DETECTORS WHERE REQUIRED TO PROVIDE UNIFORM COVERAGE OF AREA. GIMBAL MOUNTS SHALL NOT BE PROVIDED IN OFFICE AREAS UNLESS REQUIRED FOR UNIFORM COVERAGE OF AREA. 23. ALL LENEL LICENSES WILL BE PROVIDED BY AMAZON. DONGLE ID AVAILABLE UPON REQUEST AND BUSINESS JUSTIFICATION. 24. HORN STROBE (BLUE IN COLOR) IS ONLY USED FOR LOCAL NOTIFICATION/ANNUNCIATION OF DOOR HELD OR DOOR FORCED ALARMS AT ACCESS CONTROLLED DOORS. HORN STROBE HAS NO FUNCTIONAL INTERACTION WITH THE OPERATION OF THE DOOR, DOOR HARDWARE, ACCESS CONTROL SYSTEM OR FIRE ALARM SYSTEM. 25. ALL SUPERVISED DOORS SHALL BE EQUIPPED WITH A BURGLAR ALARM HORN AND CONFIGURED TO ALARM IN THE EVENT OF A DOOR FORCED CONDITION. BURGLAR ALARM HORNS AT ROLL UP DOORS SHALL BE STRATEGICALLY LOCATED AND ASSOCIATED WITH A GROUP OF DOORS I.E. 4-6 ROLL UP DOORS PER BURGLAR ALARM HORN. 26. ALARM HORNS SHALL BE CONFIGURED WITH A SOLID CONTINUOUS ALARM TONE. 27. RS-485 SECURITY BACKBONE CABLE GROUND CONNECTIONS SHALL BE BONDED TO THE ACCESS CONTROL PANEL BONDING POINT WITHIN THE HEADEND ENCLOSURE. TO AVOID GROUND FAULT ERRORS, THE FAR END OF RS-485 GROUND WIRING SHALL BE LEFT UN -TERMINATED AND SHALL BE CUT FLUSH WITH THE CABLE JACKET. 28. SECURITY CONTRACTOR SHALL PROVIDE COMPLETED SIG PROGRAMMING MATRIX FOR ENTIRE SECURITY SYSTEM TO AMAZON SECURITY PROJECT MANAGER FOR REVIEW AND APPROVAL AT LEAST 2 WEEKS PRIOR TO FIRST PLANNED COMMISSIONING MILESTONE. ALL SECURITY DEVICE CONNECTIONS SHALL BE MADE CONSISTENT WITH COMPLETED AND APPROVED SIG PROGRAMMING MATRIX, REPROGRAMMING OF THE SYSTEM TO CORRECT WIRING AND CONNECTION MISTAKES THAT ARE NOT CONSISTENT WITH THE APPROVED SIG PROGRAMMING MATRIX WILL NOT BE ALLOWED, CORRECTIONS SHALL BE MADE ON SITE BY THE SECURITY CONTRACTOR. 29. SECURITY CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL DOOR LABELING WITH CURRENT ARCHITECTURAL DRAWINGS PRIOR TO SUBMISSION OF COMPLETED SIG PROGRAMMING MATRIX TO AMAZON SECURITY PROJECT MANAGER. 30. VIDEO SURVEILLANCE CAMERAS SHALL BE PROVIDED WITH COVERAGE OF ALL PERIMETER OPENINGS. SEE SPECIFICATIONS FOR ADDITIONAL VIDEO SURVEILLANCE REQUIREMENTS. 31. LENEL ACCESS CONTROL SYSTEM SHALL BE CONFIGURED TO CHANGE READER STATUS TO "MANAGER MODE" WHEN BOSCH INTRUSION DETECTION SYSTEM IS ARMED, SEE SHEET AC5.02 FOR WIRING DIAGRAM. DELIVERY STATION - DVB1 FORT PIERCE, FL ACCESS CONTROL /VIDEO SURVEILLANCE PLANS ACCESS CONTROL SYSTEM LEGEND NCP ISC ACCESS CONTROL PANEL - -3300 INTELLIGENT SYSTEM CONTROLLER INTRUSION DETECTION PANEL - DP 0ka;, B#n12G BOSCH CONTROL PANEL - B8512G/B9512G FAR FIRE ALARM RELAY Es I CARD READER _lslLq CARD READER - MULLION MOUNT UCR-K CARD READER/KEYPAD COMBINATION TOUCH SCREEN KEYPAD AO AUTO OPERATOR ©rDD DOOR CONTACT DD=DPDT DOUBLE POLE DOUBLE THROW OH DOOR CONTACT - OVERHEAD RX REQUEST TO EXIT ❑� REQUEST TO EXIT BUTTON EL ELECTRIC LOCK ES ELECTRIC STRIKE IVL MAGNETIC LOCK ML K MAGNETIC LOCK KEYED SWITCH OVERRIDE N EMERGENCY DOOR RELEASE, PNEUMATICALLY CONTROLLED nCS ] 2uuu-L� CENTRAL SIREN - BOSCH D117 120dB HORN TIED TO BOSCH INTRUSION DETECTION PANEL, MOUNTED 2' UNDER STRUCTURE IN WAREHOUSE AREA H/S-B �DB LOCAL ALARM HORN STROBE (DOBERMAN) - B = TIED TO BOSCH INTRUSION DETECTION PANEL, DB = SOUND LEVEL H] H/S-L H LOCAL ALARM HORN STROBE (DOBERMAN) - DB L = TIED TO LENEL ACCESS CONTROL SYSTEM, DB = SOUND LEVEL P LOCAL SOUNDER - TIED TO BOSCH INTRUSION DETECTION PANEL 1 00-B P = PIEZO SOUNDER FOR AEN/IDF CABINETS, DB = 100 01 MOTION DETECTOR - WALL MOUNTED Iv1 LP MOTION DETECTOR - WALL MOUNTED, LONG RANGE - fJ' MOTION DETECTOR, CEILING MOUNTED, 360 DEGREE MOTION DETECTOR MOUNTED TO STRUCTURE, 360 DEGREE NXX XX=INSTALLATION HEIGHT LR=LONG RANGE - FOR WAREHOUSE SPACE SECURITY CAMERA SYSTEM LEGEND NVR NETWORK VIDEO RECORDER SON MONITOR DEC BOSCH VIDEOJET NETWORK VIDEO DECODER TELECOMMUNICATIONS, WALL MOUNTED IDF ENCLOSURE Do TELECOMMUNICATIONS, FLOOR MOUNTED IDF ENCLOSURE 0 11 TELECOMMUNICATIONS, FLOOR MOUNTED AEN CABINET S - C CAMERA, WALL MOUNTED, DOME :C�ITZ CAMERA, WALL MOUNTED, PTZ (PAN, TILT, ZOOM) CAMERA, 360° PANORAMIC - C X X = HEIGHT OR CLG (CEILING) �C D- CAMERA, CEILING MOUNTED, DOME �TZ CAMERA, CEILING MOUNTED, PTZ (PAN, TILT, ZOOM) rC D- CAMERA, EXTERIOR, CORNER MOUNTED, DOME > ©PTZ CAMERA, EXTERIOR, CORNER MOUNTED, PTZ (PAN, TILT, ZOOM) BASIS OF DESIGN NOTES 1. DRAWINGS INCLUDE MINIMUM REQUIREMENTS SPECIFIED WITHIN SECURITY DESIGN GUIDELINES REV 4.0 DATED JUNE 26, 2018. 2. CONFIRM REGIONAL SECURITY AND ACCESS CONTROL REQUIREMENTS WITH REGIONAL AMAZON PHYSICAL SECURITY PROJECT MANAGER. 3. DRAWINGS INCLUDE REQUIREMENTS SPECIFIED WITHIN WWRE DESIGN BULLETINS 1-28. SECURITY SYSTEM LABELING SCHEME SECURITY CABLE LABELING SCHEME ACP.Ox - A# - # - ## - ## -AA SECURITY CABLE IDENTIFIER DEVICE TYPE PORT NUMBER BOARD ADDRESS CONTROLLER PORT CONTROLLER ID ACP NUMBER SECURITY KEYPAD CABLE LABELING SCHEME ACP.Ox -A# - 3 - 31 -KP SECURITY CABLE LJ L[ L�_ IDENTIFIER DEVICE TYPE BOARD ADDRESS CONTROLLER PORT CONTROLLER ID ACP NUMBER INTRUSION SYSTEM CABLE LABELING SCHEME IDP.Ox - B# - 1 - ## - ## -AA INTRUSION CABLE L IDENTIFIER DEVICE TYPE PORT NUMBER BOARD ADDRESS SDI BUS NUMBER CONTROLLER ID OF NUMBER INTRUSION KEYPAD CABLE LABELING SCHEME IDP.Ox -B# - 2 - ## - KP INTRUSION CABLE L� IDENTIFIER -� DEVICE TYPE BOARD ADDRESS T SDI BUS NUMBER CONTROLLER ID IDP NUMBER INTERCOM & FIRE ALARM CABLE LABELING SCHEME ACP.Ox - ### AA SECURITY CABLE L IDENTIFIER T_ DEVICE TYPE DEVICE IDENTIFICATION ACP NUMBER PROGRAMMING DEVICE NAME LABELING SCHEME SITE - ## . ## - AAAA SECURITY DEVICE PROGRAM IDENTIFIER DEVICE DEVICE DESCRIPTION MODULE PORT NUMBER ALARM PANEL NUMBER SITE CODE PROGRAMMING MODULE NAME LABELING SCHEME SITE - ##. ## - AAAA SECURITY DEVICE L_�TTPROGRAM IDENTIFIER DEVICE DESCRIPTION MODULE PORT NUMBER ALARM PANEL NUMBER SITE CODE CCTV CAMERA LABELING SCHEME CCTV CAMERA LOGICAL X-)= - 0 - CXX IDENTIFIER CAMERA NUMBER FLOOR NUMBER -- SITE CODE se-oI SECURITY CABLE IDENTIFICATION TAG ACCESS CONTROL DEVICE LABELING SCHEME MD-001-00 �- FLOOR NUMBER DEVICE IDENTIFIER - - DEVICE TYPE SECURITY CAMERA DEVICE LABELING SCHEME AMZL- XXX -CXX �J L CAMERA NUMBER LOCATION -- -- SITE CODE WSO It,: COMMUNICATIONS 2801 S FAIR LANE TEMPE, AZ 85282 PHONE: (480) 379-6200 FAX: (480) 379-6205 www.iescomm.com SHEET INDEX SHEET DRAWING TITLE ACO.00 COVER SHEET AC1.00 ACCESS CONTROL AND INTRUSION DETECTION PLAN AC1.10 VIDEO SURVEILLANCE PLAN PROPRIETARY STATEMENT AC5.00 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS AC5.01 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS THESE DRAWINGS/DOCUMENTS HEREIN ATTACHED ARE THE PROPERT` AC5.02 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS OF IES CORPORATION ANY REUSE OR AC5.03 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS OF DOCUMENTSION WITH UTESE WRITTEN AC5.04 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS PERMISSION OF IES CORPORATION IS AC5.05 ACCESS CONTROL/VIDEO SURVEILLANCE DETAILS STRICTLY FORBIDDEN. ALL RIGHTS RESERVED. ABBREVIATIONS A AMPERE MPOE MAIN POINT OF ENTRANCE ABV ABOVE MPOP MAIN POINT OF PRESENCE AC AIR CONDITIONING MTD MOUNTED ACP ACCESS CONTROL PANEL (N) NEW ACH ABOVE COUNTER HEIGHT NEC NATIONAL ELECTRIC CODE AFF ABOVE FINISHED FLOOR NESC NATIONAL ELECTRICAL SAFETY CODE AG ABOVE GROUND NIC NOT IN CONTRACT AHJ AUTHORITY HAVING JURISDICTION NVR NETWORK VIDEO RECORDER ANSI AMERICAN NATIONAL STANDARD INSTITUTE AV AUDIO VISUAL OFC OPTICAL FIBER CABLE AWG AMERICAN WIRE GAUGE OFCI OWNER FURNISHED, CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED BAS BUILDING AUTOMATION SYSTEM OOBM OUT OF BAND MANAGEMENT BC BONDING CONDUCTOR OSP OUTSIDE PLANT BLDG BUILDING BKBD BACKBOARD PBX PRIVATE BRANCH EXCHANGE PDU POWER DISTRIBUTION UNIT C CONDUIT POE POWER OVER ETHERNET CAB CABINET POTS PLAIN OLD TELEPHONE SYSTEM CAT CATEGORY PP PATCH PANEL CATV COMMUNITY ANTENNA TELEVISION PSTN PUBLIC SWITCHED TELEPHONE NETWORK CCTV CLOSED CIRCUIT TELEVISION PVC POLYVINYL CHLORIDE CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED REC RECEPTACLE CLG CEILING RMFC RACK MOUNT FIBER CABINET CO CONDUIT ONLY RU RACK UNIT CP CONSOLIDATION POINT CU COPPER SIP SESSIONS INITIATION PROTOCOL CVD CONVERGED VOICE DATA SM SINGLEMODE SMFC SURFACE MOUNT FIBER CABINET DEC VIDEO DECODER SMR SURFACE METAL RACEWAY DEMARC DEMARCATION POINT SP SERVICE PROVIDER DSL DIGITAL SUBSCRIBER LINE STP SHIELDED TWISTED PAIR SW SWITCH (E) EXISTING EF ENTRANCE FACILITY TBB TELECOMMUNICATIONS BONDING BACKBONE EMT ELECTRICAL METALLIC TUBING TEL TELEPHONE ENCL ENCLOSURE TELCO TELEPHONE COMPANY O EPO EMERGENCY POWER OFF TGB TELECOMMUNICATIONS GROUNDING BUSBAR LLI ER EQUIPMENT ROOM TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION J TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR FACIE FIRE ALARM CONTROL PANEL TR TELECOMMUNICATIONS ROOM ul FBO FURNISHED BY OWNER IOTHERS TYP TYPICAL01, U FOIC FURNISHED BY OWNER INSTALLED BY J M CONTRACTOR UON UNLESS OTHERWISE NOTED Q FOIO FURNISHED BY OWNER INSTALLED BY OWNER UPS UNINTERRUPTIBLE POWER SUPPLY J u LL UTP UNSHIELDED TWISTED PAIR HC HORIZONTAL CROSS -CONNECT [„L LLI LLI HCM HORIZONTAL CABLE MANAGEMENT WAN WIDE AREA NETWORK w u WAP WIRELESS ACCESS POINT C INTERMEDIATE CROSS -CONNECT WLAN WIRELESS LOCAL AREA NETWORK O Lu IDF INTERMEDIATE DISTRIBUTION FRAME WP WEATHERPROOF I--1 r.[ U d IG ISOLATED GROUND J m IP INTERNET PROTOCOL V VOLTS W ISDN INTEGRATED SERVICES DIGITAL NETWORK VCM VERTICAL CABLE MANAGEMENT O ISO INTERNATIONAL ORGANIZATION FOR VMS VIDEO MANAGEMENT SYSTEM 0 6 ^ STANDARDIZATION VPN VIRTUAL PRIVATE NETWORK J-BOX JUNCTION BOX V) LF) w w KCMIL THOUSAND CIRCULAR MILS 0 0 a Q LAN LOCAL AREA NETWORK LOMMF LASER OPTIMIZED MULTIMODE FIBER MAC MEDIA ACCESS CONTROL REVISION: MAN METROPOLITAN AREA NETWORK DELTA DESCRIPTION MAX MAXIMUM _DATE MC MAIN CROSS -CONNECT -- ----- MDF MAIN DISTRIBUTION FRAME -- - MH MANHOLE MIN MINIMUM MM MULTIMODE MON MONITOR MPLS MULTIPROTOCOL LABEL SWITCHING SHEET MLE; COVER SHEET Designed By: Z.CAMPBELL - Drawn By: T.VOYTOVA Date: 01-09-19 Project # 2728196100 Web ID # 170414 `;gale: NONE AC0.00