Please be advised that the following items are in response to plan review comments for the above referenced
project dated 6/4/2018
1. Please complete the climatic and geographic design criteria in accordance with table 301.2 (1).
Response: See Sheet A-4
2. Please show fire blocking in accordance with section 302.11 of the 2617 Florida Residential Code.
Response: See Sheet A-4
3. Please provide detail and location of the a/c pad in accordance with 107.2.1 of the 2017 Florida Building Code
Sixth Edition.
Response: See Sheet A-2
4. Please provide type of treatment protection against termite see section R318 of the 2017 Florida Building Code
Sixth Edition.
Response: See Sheet A-3
5. Please provide details showing that the structure was designed in compliance with section
R322 of the 2017 Florida Building Code 61' Edition.
Response: See Sheet A-1
6. Please provide site specific detail of the roof covering components 107.2.1 of the 2017 Florida Building Code
Sixth Edition.
Response: See Sheet A-4
7. Please provide wall separation detail of garage wall separation from living area R302.6 of the 2017 Florida
Residential Building Code Sixth Edition.
Response: See Sheet A-4
8. Please show on the plan the wood framed separation wall insulation type and R value 107.2.1 of the 2017
Florida Building Code Sixth Edition.
Response: See Sheet A-4
806 Delaware Avenue
Tel:
772 460 7751
www.architectonicinc.com
Fort Pierce, Florida 34950
Fax:
772 460 4244
FL Reg #AA26003348 1 of 2
ArchitectOnic Inc
9. Please provide site specific document regarding the type of insulation for the attic area type Chapter 1, Section
107 subsection 107.1 of the 2017 Florida Building Code Sixth Edition.
Response: See Sheet A-4
10. The cubic volume of the energy calcs does not match the plan please review and correct accordingly. See
Chapter 1 Section 107 of the 2017 Florida Building Code.
Response: Contractor to provide
$CC /l2u/
11. The energy calcs submitted are incomplete nOot signedby the owner/agent of the project.
Response: Contractor to provide See- n e u.)
12. Please provide detail for the exterior finish. of the chimney 107.2.1 of the 2017 Florida Building Code Sixth
Edition.
Response: See Sheet A-Z
13. Detail for the chimney is incomplete no dimensions shown on plans.
Response: Contractor to provide