HomeMy WebLinkAbout1508-0155 ENERGY EFFICIENCY CODE 8-31-15FORM R405-2014
919014S
FLORIDA ENERGY EFFICIEI
Florida Department of Business and
DE FOR BUILDING CONSTRUCTION
al Regulation - Residential Performance Method
Project Name: Markee Residence
Builder Name: De La Hoz Builders Inc.
Street: 4904 Seagrape Or
Permit Office: St Lucie
City, State, Zip: Fort Pierce , FL , 34982
Permit Number:
Owner: Markee Residence
Jurisdiction: 611000
Design Location: FL, Fort Pierce
1. New construction or existing New (From Plan)
9. Wall Types (1344.0 sgft.) Insulation Area
2. Single family or multiple family Single-family
a_ Concrete Block - Int Insul, Exterior R=6,0 1344.00 It'
3. Number of units. if multiple family 1
b. NIA R= ft'
c. N/A
4. Number of Bedrooms 3
R= fI'
d, N/A R= fl'
5. Is this a worst case? No
10. Ceiling Types (1.285.0 sgft.) Insulation Area
a. Under Attic (Vented) R=38.0 1285.00 W
6. Conditioned floor area above grade (ft) 1285
b. NIA R= fta
Conditioned floor area below grade (ft') 0
c. NIA R= ft'
7. Windows(85.8 sgft.) Description Area
11. Ducts R IF
a. Sup: Attic; Ret: Attic, AH: Maur 6 267
a. U-Factor: Dbl, U=0.45 85.76
'
SHGC: SHGC=0.22
b. U-Factor. N/A
2
12. Cooling systems kBtumr Efficiency
SHGC:
a. Central Unit 24:0 SEER:16.00
c. U-Factor: NIA I
SHGC:
d. U-Factor: NIA
'
13, Healing systems kBtu/hr Efficiency
SHGC:
a. Electric Strip Heat 16.0 CQP:1.00
Area Weighted Average Overhang Depth: 3.600
t.
Area Weighted Average SHGC: 0.220
14. Hot water systems
8. Floor Types (1285.0 sgft.) Insulation Area
a. Electric Cap: 40 gallons
a. Slab -On -Grade Edge Insulation R=0,0 1285.00
EF: 0,980
b. Conservation features
b. N/A R= �7
None
c. NIA R= ft'
.J
15. Credits CF, Pstat
Total Proposed)
Modified Loads: 37.98
Glass/Floor Area: 0,067
Total
L
Baseline Loads: PASS
38:79
I hereby ce'rtify that the plans and specifications covered 4y
Review of the plans and t TEiE S�,l•9
this calculation are in compliance with the Florida Energy
Code.
specifications covered by this
calculation indicates compliance
with the Florida
PREPARED BY:
DATE: �_
Energy Code.
Before construction is completed
_ .__.,'' �i►,s �_.
this building will be inspected for '
9 P csa_�,�
I hereby
c .
compliance with Section 553.908 ; � &.
Florida Statutes.~'j"
certify that this as d, is in compliance
the Florida En"
with C e,
Cp v
U SV'E'C
BUILDING OFFICIAL:
DATE: _..?_.g _ _
DATE:
- Compliance requires certification by We air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.2.2.1 ,
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
- Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors,
tested in accordance with Section 803 of RESNET Standards, is not greater than 0.000 On for whole house.
8/31/2015 8:38 AMEnergyGaugeO USA - FlaRes2014 Section R405,41 Compliant Software C
1
FORM R405-2014
PROJECT
Title:
Markee Residence
Bedroo
s: 3
Address Type:
Street Address
Building Type:
User
Conditioned
Area: 1285
Lot #
Owner:
Markee Residence
Total SIodes:
1
Block/SubDivision:
# of Units:
1
Worst case:
No
PlatBook:
Builder Name:
De La Hoz Builders Inc,
Rotate
Angle: 0
Street:
4904 Seagrape Dr
Permit Office;
St Lucie
Cross ventilation:
County:
st. lucie
Jurisdiction:
611000
Whole
House Fan:
City, State, Zip:
Fort Pierce ,
Family Type:
Single-family
FL, 34982
New/Existing:
New (From Plans)
Comment:
CLIMATE
MECC Design Temp
Int Design Temp Heating
Design Daily Temp
V Design Location
TMY Site
! one 97.5 % 2.5 %
Winter
Summer Degree Days Moisture Range
FL, Fort Pierce FL_ST LUCIE COINTL
2 39 90
70
75 722
62 Low
BLOCKS
Number
Name
Area Volume
1
Blockl
1285 10780
SPACES
Number
Name
Area Volume
Kitchen Occupants
Bedrooms
InfilID Finished Cooled Heated
1
Main
1285 10280
Yes 4
3
1 Yes
Yes Yes
_
FLOORS
# _Floor
�1
Type _ _
Space_ P+erim_eter
R-Value
Y.._ ! --- --- ""
_ Area
_
_..�..-.--
Tile Wood Carpet
....._-'-._.�..-
Slab -On -Grade Edge Insulatio
Main168
ft 0
I
1285 ft�_4__...
-._0.__.._,.
0_
ROOF
/
Roof
Gable Roof
Solar
SA Emitt
Emitt Deck Pitch
V #
Type Materials Area
Area Color
Absor.
Tested
Tested Insul. (deg)
1
Hip Composition shingles 139
ft.Q ft! Medium
0.85
No 0.9
No 0 22,ti
ATTIC
V #
Type
�-^-
Ventilation
Vent Ratio (1 in)
Area
--
RBS IRCC
t
Full attic
Vented�M
300 1285 ft7. -
N __._..._.._. N
CEILING
#
_ W.._...
Ceiling Type
..q_ .
Space
R-Value Area
_ .
_ Framing Frac
Truss Type
_ _......
1
Under Attic (Vented)
Main
38 1285 fP
0.11
Wood
i
8/3112015 8:38 AM EnergyGauge® USA - Fi Res2014 Section R405.0 Compliant Software FILE 6—'aO Pt4y
FORM R405-2014
WALLS
__ _.#--Omt..._...__T.o.�:......._1NaUTypa.,.___...
Adjacent
Spac
_ _ce
Cavity Width Height Sheathing Framing Solar Below
,u.a.R-Value_._.FL—ln_—F-t__In_ —Area_.-.____ft:_Value._Fraction—Absor Gr_adela-.
,- _ 1 N
Exterior Concrete Block -
Int Insul Main
6 40 8 320.0 ft= 0 0.75
0
2 E
Exterior Concrete Block -
Int Insul Main
6 44 8 352.0 fi' 0 0.75
0
3 S
Exterior Concrete Block -
Int Insul Main
6 40 8 320.0 ft' 0 0.75
0
_,,,__ 4 W
Exterior Concrete Block - Int Insul Main
6 44 8 362.0 ftz 0 0.75
0
DOORS
#
Omt Door Type
Space
Storms U-Value Width Height
Area
�
rtoVW�
Ft In Ft in
1
Insulated
Main
None .4 3 - - � 6 �.�� 8
20 fP
2
E Insulated
Main
None .4 3 6 8
20 ftz
INFILTRATION
# Scope
Method
SLA
I FM 50 ELA EgLA ACH ACH 50
1 Wholehouse
Proposed ACH(50)
000254
856.7 47,03 _T 88.45 � .1855 ` 5
HEATING SYSTEM
�#
System Type __ �H�^
Subtype
W
Efficiency Capacity Block
Ducts
1
Electric Strip Heat
None
COP:1 16 kBtulhr 1
sys#1
COOLING SYSTEM.
#
System Type Subtype
~None
Efficiency Capacity Air Flow S_H_R Block
Ducts
1
Central Unit
_
SEER: 16 24 kBtuihr 720 cfm �0.75� _ 1
sys#1
HOOT
WATER. SYSTEM
#
System Type SubType Location
EF Cap, Use SetPnt Conservation
1
Electric None
Main
0.98 40 gal 60 gal 120 deg None
SOL 'R
HOT WATER SYSTEM
FSEC
Collector Storage
Cart #
,.b,.>.�.None
Company Name
ystem Model # Collector Model # Area Volume FEF
None._,.�...�,_____.�.,�._.�...,_.a.....�..
ft'
DUCTS
/
— Supply ,
- Return -- Air CFM 25 CFM25 HVAC #
v #
Location R-Value Area
v¢Attic _
�Y257
Location Area Leakage Type Handler TOT OUT ON RLF Heat
-� 'Attic x,64.25
Cool
6 ftx
ft Proposed On _ Main � — cfm 0.0 cfm MV 0.00 Y~ 0.60
1p� t�
""Y8/31/2015 8:38 AM EnergyGauge9 USA - ¢IaRes2014 Section R405.4.1 Compliant Software a e 4
FORMR408~2014
TEMPERATURES
Cooling Jan
Heati n J n
U 9 a
Ven ng Jan
Fe b
Feb
Feb
ar
M
Xj Mar
Mar
�JA
Aprr ay Jun
r ay Jun
A0pr I I May rl Jun
Jul
Jul
ri
Au
Aug'
rl
x
Se
Sep
Oct
Oct
Nov
Nov
HX
Dee
Dec
H
Jul
Aug
Sep
Oct
Nov
Dec
Thermostat Schedule:
HERS 2006
Reference
Hours
8131/2058�8AM EnorgymoouebUSA ' HaRes2014 Section n4oa�.1 Compliant Software
FILE CQP4ofY
'FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the Energyped,ormance Index, the more efficient the home.
4904 Seagrape Dr, Fort Pierce, FL, 34982
1. New construction or existing
New (From Plans)
2. Single family or multiple family
Single-family
3. Number of units, if multiple family
1
4. Number of Bedrooms
3
5. Is this a worst case?
No
6. Conditioned floor area (ft2)
1285
7. Windows— Description
Area
a. U-Factor: Dbl, U=0.45
85.76 ft'
SHGC: SHGC=0.22
b. U-Factor: NIA
ft2
SHGC.
c. U-Factor: N/A
ft'
SHGC:
_ d. U-Factor: N/A
W
SHGC:
Area Weighted Average overhang Depth:
3.600 ft.
Area Weighted Average SHGC:
0.220
8. Floor Types
Insulation
Area
a. Slab -On -Grade Edge Insulation
R=0.0
1285.00 ft2
b. NIA
R=
ft2
c. NIA
R=
ft2
I certify that this home has complied with the Florida Er
Construction through the abo ergy saving features
in this home before final in ection. therwise, a new
based on installed Cod m Eantrfs res.
Builder Signature:
Address of New Home: 49Qy : 1�0 E D
9, Wall Types
Insulation
Area
a. Concrete Block - Int Insul, Exterior
R=6.0
1344.00 ft'
b. NIA
R=
ft2
c, NIA
R=
ft'
d. N/A
R=
ft2
10. Celling Types
Insulation
Area
a. Under Attic (Vented)
R=38.0
1285.00 ft2
b. NIA
R=
ft2
c. N/A
R=
ft2
11. Ducts
R W
a. Sup: Attic, Ret: Attic, AH: Main
6 257
12. Cooling systems
kBtulhr
Efficiency
a. Central Unit
24.0 SEER:16,00
13. Heating systems
keluihr
Efficiency
a. Electric Strip Heat
16.0
COP:1.00
14. Hot water systems
a. Electric Cap: 40 gallons
EF: 0.98
b. Conservation features
None
15. Credits CF, Pstat
ay Efficiency Code for Building
iieh will be installed (or exceeded)
L Display Card will be completed
Date gv" (�
City/FL Zip: po2f pie-Qcc , i—r
*Note*'This is not a Building Energy Rating. If your, Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
6.38-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff. i
**Label required by Section R303.1,3 of the Florida Building. Code, Energy Conservation, if not DEFAULT.
8/31/2015 8:39 AM EnergyGaugeG USA - RaRCs2014 Section R405.4.1 Compliant Software C
e f
-P�F wrightso, t. Project Summary Date: June 29, 2015
Entire House By:
De La Hoz Builders, Inc.
For:
Notes:
4904 seagrapedr 1
4904 seagrapedr, Fort Pierce, FI
Weather:
Winter Design Conditions
Outside db 42 OF
Inside db 70 OF
Design TD 28 OF
Heating Summary
Structure
12433
Btu
Ducts
3786
Btu
Central vent (0 cfm)
0
Btu
Humidification
0
Btu
Piping
0
Btu
Equipment load
16220
Btu
Infiltration
Method
Simpl
Construction quality
Avel
Fireplaces
Heating Cool
Area (ft� 1280 ill
Volume (it) 12672 12E
Air changes/hour 0.45 0
Equiv. AVF (cfm) 95
Heating Equipment Summary
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
Fort Pierce, FL, US
Summer Design Conditions
Outside db
90
OF
Inside db
75
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
61
gr/lb
Sensible Cooling Equipment Load Sizing
Structure
14010
Btuh
Ducts
6026
Btuh
Central vent (0 cfm)
0
Btuh
Blower
0
Btuh
Use manufacturer's data
n
Rate/swing multiplier
0.95
Equipment sensible load
19035
Btuh
d Latent Cooling Equipment Load Sizing
e
0 Structure
2829
Btuh
Ducts
1630
Btuh
g Central vent (0 cfm)
0
Btuh
0 Equipment latent load
4459
Btuh
2
3 Equipment total load
23493
Btuh
9 Req. total capacity at 0.70 SHR
2.3
ton
100 EFF
4.1
kW
14064
Btuh
50
OF
256
cfm
0.016
cfm/Btuh
0
in H2
Cooling Equipment Summary
Make
Ruud
Trade
Ruud
Cond
RA1624AJ2
Coil
RH1T24
AHRI ref
7940891
Efficiency
Sensible cooling
Latent cooling
Total cooling
Actual air flow
Air flow factor
Static pressure
Load sensible heat ratio
12.0 EER, 16 SEER
16800
Btuh
7200
Btuh
24000
Btuh
800
cfm
0.040
cfm/Btuh
0.10
in H2O
0.82
Calculations approved by ACCA to meet all requirements of Manual J
5 k.
2 ' fJ = 11:a 2
-f - wnightsoft` Right -Suite® lhiversal 201515.0.03 RSW8570 Page 1
.91. ...ansfeftManual J4904 seagrape dr-del la hoz.rup Calc = MJ8 Front Door faces: N
+ wrightsoft'
Right-J® Worksheet
Entire House
De La Hoz Builders, Inc.
Job:
Date: June 29, 2015
By:
1
Room name
Entire House
BATH 1
2
Exposed wall
168.0 ft
17.0 ft
3
Room height
9.9 ft
9.0 ft heatt000l
4
Room dimensions
1.0 x 62.0 ft
5
Room area
1280.0 ft2
62.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(BtuhffP-°F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Co01
Gross
NIP/S
Heat
Cool
Heat
Cool
6
W
13A-4ocs
" 0.143
n
4.00
2.55
360
360
. 1441
916
396
252
13A-40cs
0.143
a
4.00
2.55
444
394
1578
1003
T
216
137
4A4-2ov,
0.470
a
13.16
50.29
29
0
379
1448
0
0
l D
11 PO
0.290
a
8.12
8.41
21
21
171
177
0
0
11
W
13A-4ocs
.0.143
s
4.00
2.55
.360
360
.1441.
916
0
0
13A-4ocs
0.143
w
4.00
2.55
444
378
1515
963
0
0
0
0
1A-clom
1.270
w
35.56
38.97
13
12
459
503
0
0
0
0
1�2D
4A4-2ov
0.470
w
13.16
50.29
32
0
418
1599
0
0
0
0
11 PO
0.290
w
8.12
8.41
21
21
171
177.
0
0
0
0
C
16B-30ad
0:032
, -
0.90
1.68
1280
1280
1147:
2150
62
- 62
56
104
F
21A-28t
0.022
0.62
0.00
1280
1280
788
0
62
62
38
0
6
c) AED excursion
736
1 -41
Envelope loss/gain
9509
10589
706
452
12
a) Infiltration
2925
801
278
76
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
4
920
0
0
Appliances/other
1700
0
Subtotal (lines 6 to 13)
12433
14010
1
985
5291.
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
12433
14010
985
529
15
Duct loads
I
30%
43%
3786
6026
30%
43%
300
227
Total room load
16220
20036
1284
756
Air required (cfm)
256
600
20
30
A Z= -PP- wrightsa t' Right Suite® lhiversal 201515.0.03 RSU06570
ansfer\Manual J\4904 seagrape dr-del la hoz.rup Cale = MJ8 Front Door faces: N
+ wrightsoft-
Right-J® Worksheet
Entire House
De La Hoz Builders Inc.
Job:
Date: June 29, 2015
By:
1
Room name
UTIL RM
WIC
2
3
4
5
Exposed wall
Room height
Room dimensions
Room area
7.0 ft
9.0 ft heat/cool
7.0 x 9.0 ft
63.0 ft2
0 ft
9.0 ft heat/cool
9.0 x 5.0 ft
45.0 ft'
Ty
Construction
number
U-value
(Btuhtf?-°F)
Or
HTM
(Btuhlf?)
Area (ft')
or perimeter (ft)
Load
(Btuh)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W
yJ
13A-4ocs '
13A-40cs
4A4-2ov
11 PO
13A-46cs
13A-4ocs
,A -clam
4A4-20v
11 PO
16131-30ad
0.143
0.143
0.470
0.290
0.143
0.143
1.270
OA70
0.290
0.032
n
a
a
a
;
w
w
w
w
-
4.00
4.00
13.16
8.12
4.00
4.00
35.56
13.16
8.12
0:90:
2.55
2.55
0.29
8.41
2.55
2.55
38.97
50.29
8.41
1.68
.0
63
0
0
0
0
0
0
0
.63'°.
0
63
0
0
0
0
0
0
0
63
0
252
0
0
- 0
0
0
0
0
56
0
160
0
0
0
0
0
0
0
,.. 106
0
0
0
0
0
0
0
0
0
45
0
0
0
0
0
0
0
0
0
45
0
0
0
0
0
0
0
0
0
40
0
0
0
0
0
0
0
0
0
76
L�--G
D
W
yyyJJJ
D
C
F
21A-28t
0.022
0.62
0.00
63
63
39.
0
45
45
28
0
6
c) AED excursion
-58
-5
Envelope loss/gain
I
348
209
68
70
12
a) Infiltration
115
31
0
0
b) Room ventilation
I
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
500
0
Subtotal (lines 6 to 13)
462
740
68
70
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
462
740
68
70
15
Duct loads
30%
43%
141
318
30%
43%1
21
30
Total room load
603
1058
89
100
Air required (cfm)
10
42
1
4
wrf ghtsOft" Right -Suite® lhiversal 201RSS 515.0.03 U0557D _ 1 �j 1 Pd�e 2
IZZIN...ansferlManual J14904 seagrape dr-del la hoz.rup Calc = MJ8 Front Door faces: N ��
wrl htsoft"
Right-J® Worksheet
Entire House
De La Hoz Builders, Inc.
Job:
Date: June 29, 2015
By:
1
Room name
MSTR BEDRM
KIT/DIN
2
3
4
5
Exposed wall
Room height
Room dimensions
Room area
42.0 ft
9.0 ft heat/cool
1.0 x 246.0 ft
246.0 ft'
16.0 ft
12.0 ft heat/cool
16.0 x 11.0 ft
176.0 ft'
Ty
Construction
number
U-value
(Btuh/fN-OF)
Or
I HTM
(Btuh/fN)
Area (f?)
or perimeter (ft)
Load I
(Btuh)
Area (ft')
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W
.13A-4ocs
13A-4ocs
4A4-2ov
11PO
13A-flocs -.
13A-4ocs
1A-clom
4A4-2ov
11P0
I613-30ad
'O.143
0.143
0.470
0.290
0.w
0.143
1.270
0.470
0.290
0.032
n
a
a
a
` s
w
w
w
w
4.00
4.00
13.16
8.12
4:00
4.00
35.56
13.16
8.12
0.90
12.55
50.29
3B.97
50.29
2.55
8A1
2.55
2.55
8.41
1.68
186
0
0
0
72
117
0
16
0
246.
189
0
0
0
72
101
0
0
0
246
' 757
0
0
0
- 288
405
0
209
0
220
481'
0
0
0
'- - ' 183
257
0
800
0
413.
: - 0
192
13
21
0
0
0
0
0
176
01,
158
0
21
' 0
0
0
0
0
176
0
633
170
171
0
0
0
0
0
158
0
402
649
177
0
0
0
0
0
296
D
W .
yyy!!!
D
C .
F
21A-28t
0.022
0.62
0.00
246
246
152
0
176
176
108
0
6
c) AED excursion
174
-104
Envelope loss/gain
2031
2308
1239
1420
12
a) Infiltration
687
188
349
96
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
2
460
0
0
Appliances/other
0
1200
Subtotal (lines 6 to 13)
2719
29571
1 1589
1 2715
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2719
2957
1589
2715
15
Duct loads
30%
43%
828
1272
30%
43%
484
1168
Total room load
3546
4228
2072
3883
Air required (cfm)
56
1691
1331
155
wrightsoft' Right -Suite® lhiversal 201515.0.031 FSU06570 0 1 9 1 PAbe 3
Aft, ...ansfer\Manual J44904 seagrape dr-del la hoz.rup Calc = MJ8 Front Door faces: N 67
+ W rightsoft"
Right-J® Worksheet
Entire House
De La Hoz Builders, Inc.
Job:
Date: June 29, 2015
By:
1
Room name
LIVING
BEDRM 3
2
3
Exposed wall
Room height
16.0 R
12.0 ft heat/cool
29.0 ft
9.0 ft heat/cool
4
5
Room dimensions
Room area
16.0 x 13.0 ft
208.0 ft2
15.0 x 14.0 ft
210.0 ft2
Ty
Construction
number
U-value
(Btuh/f?-°F)
Or
HTM
(Btuh/f?)
Area (f?)
or perimeter (ft)
Load
I (Btuh)
Area (ft')
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W.
V
13A flocs
13A-flocs
4A4-2ov
11170
.13A-4ocs
13A-4ocs
IA-clom
4A4-2ov
11 PO
-16&30ad
0:143'
0.143
0.470
0.290
--A 143
0.143
1.270
0.470
0.290
0.032
, , n'.
a
a
a
:
w
w
w
w
•. -
4.00
4.00
13.16
8.12
4.00
4.00
35.56
13.16
8.12
0.90.
2:55
2.55
50.29
8.41
2.55
2.55
38.97
50.29
8.41
1:68
0
0
0
0
. 0
192
13
0
.21
208
0
0
0
0
., . 0
158
12
0
21
208
p
0
0
0
0
633
459
0
171
' 186
, 0
0
0
0
. .:. : 0
402
503
0
177
349
0
135
16
0
126
0
0
0
0
210
.. 0
119
0
0
126
0
0
0
0
210
0
477
209
0
505
0
0
0
0
.: 188
0.
303
800
0
321
0
0
0
0
, 353
D
W.
VVV}}}JJJ
D
C. ..
F
21 A-28t -
0.022
0.62
0.00
208
208
128
0
210
210
- 129
0
61
c) AED excursion
613
31
Envelope loss/gain
15771
20441
1
1508
1745
12
a) Infiltration
349
96
475
130
b) Room ventilation
0
0
1
0
0
13
Internal gains: Occupants @ 230
0
0
1
230
Appliances/other
0
0
Subtotal (lines 6 to 13)
I
1926
2139
1 1983
2105
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
11
11
7
7
14
Subtotal
1937
2151
1990
2112
15
Duct loads
30%
43%
590
925
30%
43%
606
909
Total room load
2527
3076
2596
3021
Air required (cfm)
40
123
1
1 41
121
wrightsQft` Right Suite® thiversal 201515.0.03 RSU06570
..ansferlManual J\4904 seagrape dr-del la hoz.rup Calc = MJ8 kront Door faces: N
+ wrightsoft'
Right-J® Works eet
Entire House
De La Hoz Builders, Inc.
Job:
Date: June 29, 2015
By:
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
BATH 2
6.0 ft
9.0 ft heattcool
11.0 x 6.0 ft
66.0 ft2
BEDRM 2
35.0 ft
9.0 ft heat/cool
15.0 x 12.0 ft
180.0 ftz
Ty
Construction
number
U-value
(Btuhfif-°F)
Or
HTM
(Btuh/f?)
Area (f?)
or perimeter (ft)
Load
(Btuh)
Area (f?)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/PIS
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W
V�!
13A-4ocs
13A-4ocs
4A42ov
11PO
13A-4ocs
13A-4ocs
IA-clom
4A4-2ov
11 PO
168-30ad
0.143
0.143
0.470
0.29D
0.143
0.143
1.270
0.470
0.290
0.032
n
a
a
a
s'
w
w
w
w
4.00
4.00
13.16
8.12
4.00
4.00
35.56
13.16
8.12
0.90
-
I2.55
2.55
2.55
50.29
8.41
2.55
38.97
50.29
8.41
1.68
0
0
0
0
54
0
0
0
0
.66
0
0
0
0
54
0
0
0
0
66
0
0
0
0
216
0
0
0
0
59
0
0
0
0
137
0
0
0
0
111'
72
0
0
0
108
135
0
16
0
180
72
0
0
0
108
119
0
0
0
180
- 288
0
0
0
- 432
477
0
209
0
161
183
0
0
0
275
303
0
800
0
302
LL-G
D
w
VVVjjjJJJ
D
C
F
21A-28t
0.022
0.62
0.00
66
66
.41
0
180
180
111
0
6
c) AED excursion
-20
212
Envelope loss/gain
316
228
1679
2076
12
a) Infiltration
98
27
573
157
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
1
230
Appliances/other
0
0
Subtotal (lines 6 to 13)
414
255
2252
2462
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
11
11
7
7
14
Subtotal
425
267
2259
2470
15
Duct loads
30%
43%
129
115
30%
43%
688
1062
Total room load I
T555
381
I
2947
3532
Air required (cfm)
9
15l
47
141
1lC = Ad-Wrightsoft' Right Suite® lhiversal 201515.O03 RSU06570
ansfer\Manual J14904 seagrape dr-del la hoz.rup Cale = MJ8 Front Door faces: N
+ wrightsoft•
i
Right-J® Worksheet
Entire House
De La Hoz Builders, Inc.
Job:
Date: June 29, 2015
By:
1
Room name
H
2
3
Exposed wall
Room height
0 ft
9.0 ft heaUocol
4
Room dimensions
4.0 x 6.0 ft
5
Room area
24.0 ft'
Ty
Construction
number
U-value
(Btuh/f?-°F)
Or
HTM
(Btuh/fY)
Area (ft')
or perimeter (ft)
Load
(Btuh)
Area
or perimeter
Load
Heat I
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W -
13A-4ocs
13A-4ocs
4A4-2ov
0.143
0.143
0.470
n
a
a
4A0
4.00
13.16
2.55
2.55
50.29
0
0
0
0
0
0
- 0
0
0
0
0
0
D
11
11P0
.13A-4ocs
0.290
-0.143.
a
s ;
8.12
' 4.00
8.41
2.55
0
0
0
- 0
0
0
0
0
•
W .
VVV���JJJ
13A-4ocs
IA-c1om
4A4-2ov
0.143
1.270
0.470
w
w
w
4.00
35.56
13.16
2.55
38.97
50.29
0
0
0
0
0
0
0
0
0
0
0
0
D
c
11130
16&30ad
0.290
0.032
w
8.12
0.90,
8.41
1.68
0
24
0
24
0
22
0
40
F
21A-28t
0.022
0.62
0.00
24
24
15
0
61
c) AED excursion
-3
Envelope loss/gain
36
37
12
a) Infiltration
0
0
b) Room ventilation
0
0
13
Internal gains: Occupants @ 230
0
0
Appliances/other
0
Subtotal (lines 6 to 13)
36
37
Less external load
0
0
Less transfer
0
0
Redistribution
-36
-37
14
Subtotal
0
0
15
Duct loads
30%
43%
0
0
Total room load
0
0
Air required (cfm)
0
0
Calculations a roved by ACCA to meet all requirements of Manual J 8th Ed.
414- vurrightsoft° L201 Ju. 1 .AO
... ansferBNanual J14904 seagrapedr-del la hhoz.rup rCalc01MJ8, OFron Do rr faces: N a e 6
BATH 1
8x4
30 cfm
Sheet 1
8x4
42 cfm
• UTIL RM
1911
4" KIT/ 12x8
155 cfm
-i 0 x 10
7 '1
018x 1411 12x8
4 cfm ,
�20
x 20 123 cfm
a12x 9"
LWIN G
12x
169
MSTR BEDRM
Job #:
Performed for:
4904 seagrapedr
4904 seagrapedr
Fort Pierce. FI
0
BEDRM 3
10 x 10
711
De La Hoz Builders, Inc.
10x6
121 cfm
A
16 x 6 BATH 2
■ 8x4
15 cfm
6"
• 10x6
141 cfm
10 x 10
BEDRM 2
ag
g -S 10.. SUb6 10 y
2015-Jul-09 11:50:18
...\4904 seagrape dr-del la hoz.rup