The following are our revised responses to! comments from your office on September 10, 2002 regarding the
above referenced project:
I
3. COMMENT: All Stairs: Maximumi riser height is 7 inches. Minimum tread depth is 11 inches.
I
RESPONSE: Egress stairs are designed with 7 risers and 11" treads as required by code. Stair at roof
to elevator equipment room has been revised to meet egress stair requirements. Please refer to
sheets A6.1, A6.2 and A4.6 for revised drawings.
4. COMMENT: The 2-hr stair enclosure indicates window openings. There shall be no window openings
in the 2-hr stair enclosures.
RESPONSE: Will comply. Please refer to revised sheets A1.2, A1.3, A1.4, A1.5, A2.1, A4.4, A4.5,
A6.1, A6.2, and A7.2.
7. COMMENT: The Fire Control Room shall be separated from the remainder of the structure by not less
than 1-hr construction.
i
RESPONSE: Fire Control room to be 1-hr rated with 45 minute door. Sheets Al. 1 and A4.3 revised
and resubmitted.
I
If there are questions regarding these responses, please feel free to contact me directly.