HomeMy WebLinkAbout22020536 PLAN REVIEWBOARD OF COUNTY
COMMISSIONERS
DATE:
PUBLIC WORKS
DEPARTMENT
TRANSMISSION COVER FORM 8AwFax # (561) 462-1148
1 BY
FAX #:
TO: n_.,,
COMPANY/DEPARTMENT:
NUMBER OF PAGES SENT (INCLUDING COVER):
lot C.4,flo,22-021
SENDER:
PHONE:
For
SPECIAL INSTRUCTIONS:
Your lnformadon
Original WiII Follow in Mail i ( -Take Appropriate ActionPerYourRequest ( ) Please Call on This
Please respond
ASAP ( ) RUSH ( )
COMMENTS:
HN D. ORUNN. D1,r No. 1 • DOUG COV AAD. DWrkr No. Z • PAUTA A. LEMS. Dbnkt No. 3 • FRAHMCotwvyAdmMWroror - DougWM M. And*,M HURRMON. DWft NO.,t • CUFF GAMES. DWec No. S2300VirginiaAvenue • Fr. Flence, FL U982
D+vWOn of WOft: (561) 462-1485 FAX ($61) 462-23629tneering: (561) 2-1707 Fox 462-2362 • DMslon of Rood G
DMsion of Build of Solid w ` CS61) 462-1768 FAX 46 7
561) 462-2511 FAX 462-2363
in9 ,Veciom C561) 462-1553 Fax.462-1735 • TDO (561) 462-1428
C . `
ST. LUCIE COUNTYJJ
CHECKLIST SfJMMARY
L*22020536*PLAN.BL
BUILDING DIVISION CHECKLIST
STATUS DATE OP ID DESCRIPTION / COMMENTS
YES 03/18/02 GTM19 1. Plans received in Building Division
COMMENT
Electrical - Van Whitaker
Page E-1.1A
SPECIFIES 2" CONDUIT RISERS - THIS CONFLICTS WITH
RISER DIAGRAM SHOWING SOME CONDUIT RISER SIZES AS
1&1/2"
Page E-4.8
GARAGE WALL OUTLETS TO BE GFCI PROTECTED
PAGE E-6
3. 1200 A MAIN (noted as 2 of 3) HAS 10 - 1&1/2 If
WITH 1/0 FEEDERS (150 A) BEING PROTECTED BY 200 A MCB
PAGE E- 6.1
4. THE 21/2" CONDUIT RISER TO HP2 IS TOO SMALL FOR (4)
500 MCM CU CONDUCTOR
5. PLEASE SHOW GROUNDING ELECTRODE SYSTEM AND SIZE
6. VOLTAGE DROPS CONSIDERED FOR LONG FEEDER RUNS? NO
MORE THAN 5% V.D. ALLOWED FOR COMPLETE SYSTEM
7. NOTE #5 FOR UNITS CALLS FOR A/C DISC SWITCH ABOVE
DOOR OVER - PLEASE MAKE SURE THAT SWITCH IS NOT
HIGHER THAN 617" MAX. HGHT.
GARAGE WALL OUTLETS TO BE GFCI PROTECTED
Plumbing - GEORGE BELLER
1. VENT STACKS ON RISERS S-1, S-2, S-3 S-4 FOR
WATER CLOSET AND S-5 TO BE 3" - MAZ FIXTURE UNITS
FOR 2" 20
2. NO RISER DIAGRAM FOR TRASH ROOM S-9
3. 2" HORIZONTAL WET VENT MAY HAVE A MAXIMUM OF 4
FIXTURES UNITS - RISERS S-3, S-4
WILLIAM HATCHER
1. NEED SPECS. ON PRODUCT COMPONETS AND CLADDING
AND ATTACHMENTS TO SAME
2. SMOKE EVACUATION FOR OPEN LOBBY THRU FLOORS 2
THRU 13 (code 1005.6.9.)
3. MANUAL J FOR A/C UNITS
4. A1.1 STORAGE AREA CORRIDOR TRAVEL DISTANCE TO
DEAD END TABLE 1004 OF CODE 20FT MAXIMUM LENGTH