HomeMy WebLinkAbout22020536-REVISED RESPONSES TO COMMENTSA v charlan-6roch a associates inc. charlan brock portwood architects / planners October 16th 2002 Tony Liento St. Lucie County Fire District Bureau of Fire Prevention 2300 Virginia Avenue Ft. Pierce, Florida 34982 Re: Grand Isle condominiums CBA Project #1771.01 Permit # 22020536 To Whom it Concerns: 4iANW�D St Luc eCounty The following are our revised responses to! comments from your office on September 10, 2002 regarding the above referenced project: I 3. COMMENT: All Stairs: Maximumi riser height is 7 inches. Minimum tread depth is 11 inches. I RESPONSE: Egress stairs are designed with 7 risers and 11" treads as required by code. Stair at roof to elevator equipment room has been revised to meet egress stair requirements. Please refer to sheets A6.1, A6.2 and A4.6 for revised drawings. 4. COMMENT: The 2-hr stair enclosure indicates window openings. There shall be no window openings in the 2-hr stair enclosures. RESPONSE: Will comply. Please refer to revised sheets A1.2, A1.3, A1.4, A1.5, A2.1, A4.4, A4.5, A6.1, A6.2, and A7.2. 7. COMMENT: The Fire Control Room shall be separated from the remainder of the structure by not less than 1-hr construction. i RESPONSE: Fire Control room to be 1-hr rated with 45 minute door. Sheets Al. 1 and A4.3 revised and resubmitted. I If there are questions regarding these responses, please feel free to contact me directly. Sincerely, Allen Daps co/ Douglas Anderson Project Manager Charlan Brock & Associates, Inc. k,