HomeMy WebLinkAboutENGINEERINGGENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 ,j WIND LOADS: -.1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: D 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 ,'I CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: 1. PORTLAND CEMENT TYPE 1 - ASTM C 150 11. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 111. AIR ENTRAINING +/- 1% - ASTM C 260 IV. WATER REDUCING AGENT - ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: 1. REINFORCING BARS - ASTM A615, GRADE 60 11. WELDED WIRE FABRIC - ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. ALUMINUM SPECIFICATIONS: SCANNW Eff 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS st r, OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE. GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #1 4X2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10XI-1/2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE 1'X2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 190b.PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 6-0" IN HEIGHT. MISCELLANEOUS: 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK W/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. LEGEND: (ALL MAY NOT APPIL SCR = SCREEN KP KICK PLATE __PW PIC�17UREWNDOW X = HORIZ. SLIDING WINDOW 0 = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP SOLID INSULATED PANEL CT CABLE TIE SG SUPER GUTTER CS CLEAR SPAN KB KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2"x0.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"x0.044" 2 x 5: 2"x5"x0.050" OPEN BACK SECTIONS 1 x 2: 1 "xZ'0. 044" 1 x 3: 1 "xT'0. 044" SNAP SECTIONS 2 x 2 SNAP: 2"x2"4.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"x0.045" SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0.l 00" 2 x 5 SMB: 2"x5"x0.050"x0.1 00" 2 x 6 SMB: 2"x6"x0.050"x0.1 20" 2 x 7 SM B: 2"x7x0.057x0. 120" 2 x 8 S M B: 2"ff'xO. 072"xO. 124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SM B: 2"xl 0"x0.092"x0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. 04 (D uj 0 c: QA tn uj - . 2'-0" ................ ....... WALL HEIGHT PER PLA 0 90 ........... .......... ;0 0 0 C) m 0 m IX3 ;U X X X 1X3 co -101-011 121-011 3X2 3X2 2X5SMB 2X4SMB 0 'ZZ, X Zzz",Zzzzz, X C/) 'ZZ'\ c) CA) C.0 X IQ X Z """Zz, zz"zzz" "zz , \1 Z'z 0 "zz' 2X5SMB 'z \z 2X4SMB z C/) zzzl zz" Z" 'zz"Z, G) C Z' m 2X4SMB 2X5SMB 0 2X4SMB Z' 2X4SMB "Z zzz\", z 'Z'\ m X zz\z\""""""\\""\' c/) 'Z' zz\,, 2X4SMB z Z' G), "\,\"",Z",, 'ZZ "Z 0 "Z'ZZ m 0"I""o z Zzz, 2X4SMB > Z'Z' 'ZZ' Z'ZZ" "Z""Zz, 'Z'ZZ, 3X2 51-0" 6-0"—� 141-011 0 IX3 X > x CA) 6 X X 2X3 c— c— IX3 4'-0"-4— 6-0" 1 4'4'—� cn x x o CONTRACTOR: 0 m m m > < < 0 Fn 5 PIONEER SCREEN LLC FLORIDA ENGINEERING LLC 5 z z z 0 !q -� � 4456 TAMIAM.1 TRAIL, UNIT B14 0 rp PORT CHARLOTTE, FLORIDA 33980 z , > CD --i PROJECTADDRESS: (941) 391-5980 M www.fiengineeringllc.com iz) ALEXANDER 13054 NW GILSON RD bl�Cg E. Gunderson, P.E. #60102 m PALM CITY, FL PROJECT NO. 1813832 CA CERT. #30782 DATE: 5/23/2018 FLASHING C) *HORIZONTAL OR SLOPED CD VxZ' FASTEN TO COL. (INTERNAL) W/(2) #1I SMS, FASTEN TO (2) #1 OxW SMS INTO SCREW uj EAVE RAILS ABOVE W/ #IOXI-1/2" SMS BOSSES FOR EDGE MEMBER 0� ci 00 0 24" D.C. AND 6" FROM END. TABLE D BEAM CITY EACH SIDEISIZE 2x3 4/12 2x4 8/10 2x5 8/10 2x6 10/10 2x7 12/10 2x8 8/14 2x9 9114 2x10 9/14 0 0 ALUMINUM INTERNAL OR EXTERNAL 0 EDGE MEMBER 0 0 RECEIVING CHANNEL w/(4) #11 Uj OR PURLIN 0 0 INTO GIRT OR PURLIN & (2) #14x75" o INTO BEAM OR UPRIGHT 0.062 ANGLE 0 BEAM PER PLAN CLIPS MAYB E USED L NOTCHED TO RECI COLUMN WITHIN (2) #1 OX2" INTO BEAM EDGE MEMBE R c14 OR PURLIN PURLIN I MEMBER C) 00 SMS, (EACH SIDE) BEAM BF E — -- --------- ------------- 00 C) QTY PER TABLE D 0.0625" 601 FLAT PLATE _j ----------- w/(8) #1104/4" SMS, MIN. 112" INSTALL BRACI�,� I EDGE DISTANCE, PLATE MAY BE 1 I ce) (4)#10 'SMSINTO co F_: NOTCH PROFILE MAY VARY TO PERMIT CORRECT # SMS TO CORNER FASTENED INTERNALLY TO BRACE 1 SCREW BOSSES (D.Z E UPRIGHT, BEAM -SNAP, < N SELF MATING, OR HOLLOW z o e 'i C) cj MAINTAIN MIN, OF 5/8" SEPERATION 0 00 FROM EDGE OF BEAM SMS D.C. w — —1 0") DETAIL E - UPRIGHT TO BEAM ui < LL Lo CONNECTION SCALE:NTS DETAIL "D" - ROOF BRACING CONNECTION DETAJL "C" - GIRT OR PURLIN TO BEAM� z 1r, - ,-- DETAIL SCALE:NTS; OR POST DETAIL SCALE:NTS LLI 0-) (1) o cy) c Z 0 < uj < *ALL MEMBERS PER PLAN 2"x2" .063" - DIM. TO MATCH PURLIN PURL N < SIZEXRECEIVING CHANNEL NOTE: WHERE PAVERS ARE PRESENT USE 5/16" *MEMBERS VARY PER PLAN (2) #12 SMS INTERNAL TO EAVE TAPCON XL (RED HEAD MFG.) MASONRY -- -------------------------- -- -------- RAIL (3) #12 EACH SIDE INTO PURLIN CONCRETE FOOTING 2-1/4" (MIN.) cv) S_� --------- ----------- Lo co ANCHORS TO PENETRATE UNDERLYING IY- co cq -ALTERNATELY 5" x 1/4" QUICKSETS 2-1/4" EMBEDMENT - ------------------ 0 0 ;T 0 Ce) �NTERS�ECTING o FASTEN TOP OF HEADER TO I _j MEMBER W/(2) #10 SMS w/1" o LL co PENETRATION INTO SCREW BOSS OF EAVE RAJ L - SEE P SELF -MATING OR MEMBER - TYP. BOTH SIDES 1/8"x2"x2 ANGLE SNA I P SECTION TYP. 1x2 OPEN BACK 5032 H-3'2'xANGLE PER PLAN EXTRUSION UPRIGHT 2-#12SMSINTOCOLUMN 11"&' O.B. BASE PLATE-TYP. DOOR JAMB PER PLAN 1/4" MASONRY ANCHOR EACH (2) #1104" SMS THRU 1x2 INTO ANGLE - EACH SIDE COL. 2-1/4" MIN. CONC. EAVE RAIL EACH SIDE OF COLUMN ANCHOR EMBEDMENT ------------ ------------ -------------- w 2" MIN. INCREASE DISTANCE WHEN GREATER THAN 2x4 ----------- MIN 4" SLAB 3000 PSI -__, \ ­ - \ \ \ \ IL4111 0 CONC.w/FIBERMESH UPRIGHT IS USED ... V,V ...... FASTEN HEADER w/(2) #10x3" ',,,,<NTO SCREW BOSS OF HEADER DETAIL 11G" - SLOPED PURLIN CONNECTION SCAI E: NITS ALTERNATE HEADER CONNECTION WHEN Z-BAR IS USED - FASTEN CONC. F SIDE VIEW Z-BAR TO COL/HEADER AT EACH lilt CORNER AND 18" O/C 1-1/2"x 1/16" PLATE (12) #12xl" SM� (TOP OR BOTTOM) @ V SPACING 1/4 .'MASONRY ANCHOR 0 AT EACH ANGLE __TI _1j1__1I 2 - #12 SMS 2"xZ' EDGE BEAM ALTERNATE BASE PLATE CONNECTION ATTACH MEMBER TO BASE PLATE 1/4" TAPCON XL (RED HEAD MFG. OR EQUAL) (INTERNAL) w1(2) #1 Ox2- SMS 2 @ W BASE z z 2 @ SLAB (BEYOND) w 0 ATTACH BASE PLATE TO MEMBER (2)#10x3"SMS w 0) INTO SCREW BOSSES _j w/(2) #1 0x3" SMS INTO SCREW _j LL CONNECTING EDGE BOSS OF BASE PLATE C) BEAM TO PURLIN 1 N2" FASTENED TO COLUMN LL, 0 1"x2" BASE PLATE ANCHORED it 11 w/(2) #10xl-1/2" SMS INTO 11 11 cn 0 3: 0 CONG w/ 1/4" MASONRY E SCREW BOSS S FOR SMB w CHOR 6" MAX EACH SIDE OR SNAP COLUMN z AN x w z C.) OF POST AND 24" D.C. MAX W 0 z o ........ < 0 VxZ' SNAP w _j V, 0 0 C:11 _j cf) < \'\'\\""V\ ..... NOTCH COLUMN AS REUD. w < IL FRONT VIEW % % % % CONC. FOOTING BELOWL____� COLUMN PER PLAN z 0 0 1 DETAIL "B" - 2"x4" TO 2'W" SELF MATING 0 IL 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN I OF DESIGN DATE: 5/21/2018 UPRIGHT TO DECK DETAILS SCALE:NTS COLUMN 1-1/2" PENETRATION INTO UNDERLYING FOOTING ALTERNATE DETAIL "G" SLOPED REVISION 1: 05/23/2018 PAGE: DETAIL 'T" - DOORJAMB & HEADER PURLIN CONNECTION SCALE: NTS REVISION 2: DATE CONNECTION SCALE:NTs SCALE: NTS 3 GIRT FASTENED INTERNALLY AT EACH END w/ #1 Oxl.5" EACH SCREW GROOVE. FASTEN TO BEAM wl 2x2xl25 ANGLE (2) #12 SMS INTO BEAM & (2) #10xl-1/2" THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY TO GUTTER - 2"x2"xl/8" ANGLE W/(2) #12 SMS-�_ EACH LEG FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION ___lL 0 9— BEAM (2) #142" WOOD L��lm #12 SMS �� V�I_SCREW 18" O.C. 0 0 F CLOSE BOTTOM 0 o o BEAM WHEN TRIMMED .044 RECEIVING CHANNEL, FASTEN W/(2) #12 SMS EACH SIDE OF BEI� #10 SMS WITHI OF BEAM & 24" 2x2xl/8" AN( EA. SIDE OF W/(2) #12 SN EACH LEG E 'FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER INTERNALLY w/(2)#12 SMS ALTERNATELY 2x2xl/8" ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW TOP VIEW DETAIL "H" � SCALE:NTS NOTE F INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 3/8" MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTEN GUTTER TO FASCIAw/#14x2" WOOD SCREW 18" O.C. (2) #12 SMS (2)#l4x2" WOOD SCREW FASCIA (2"x6" MIN. EXISTING) STRUCTURAL GUTTER —ALTERNATELY SEE PAGE 5 5052-1-132 GUSSET TABLE B-1 BEAM SIZE COL. TO BEAM QTY SIMS/ SIDE OF COL. BEAM TO BEAM QTY SMS/ FACE/SIDE 2x4 (5) #12 (9) #12 2x5 (5) #12 (9) #12 2x6 (7) #12 (9) #12 2x7 (10) #12 (10) #12 x 8 (12) #12 (14) #12 2X9 F2 (14) #14 (14) #14 2 x10 (16) #14 (15) #14 IDETAIL "K" GUSSET CONNECTION SCALE:NTS .050" GUTTER STIFFNER FASTEN TO FASIA %?v(2) #12x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS z-- -ALTERNATELY SEE PAGE 5 __v — DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE:NTS (2) #12 SMS 2x2xl/8" ANGLE W/(2) GIRT #12 SMS EA. LEG "_�\ 0 0 SMB 1/8"&'x4" STRAP BEAM (2) #12 SMS I MTO (2) #12 SMS INTO GUTTER GIRT 1/9'4"x4" STRAP (2) #12 SMS INTO BEAM (2) #12 SMS INTO GUTTER 2x2xl/81' ANGLE w/(2) #12SMSEA.LEG I SMB 1/8"xTW" STRAP (2) #12 SMS INTO BEAM (2) #12 SMS INTO GUTTER o 0 WHEN BEAM & PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM & PURLIN w/ 1/8"xZW" ANGLE & (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (BEAM TO PURLIN) wl 1/8"4"4" ANGLE w/(2) #12 SMS INTO EA MEMBER (BEAM & PURLIN) #14 WOOD SCREWS "0 FASCIA 18" D.C. GIRT - STRUCTURAL GUTTER SIDE VIEW (2) GUTTER BRACES EACH W/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA GIRT (2) GUTTER BRACES EACH W/(2) #12 SMS FASCIA INTO GUTTER & (2) #14 � ji WOOD SCREWS INTO FASCIA GIRT (2) #12 SMS TOP VIEW DETAIL "L" CORNER CONNECTION SCALE:NTS GUTTER (9) #10x2" SIV 1/8" PLATE ON 45* ANGLE OR 1/8"xZW" ANGLE wl(4) #12 SMS INTO EACH INTERSECTING MEMBER PERIMETE FRAMING DETAIL 1-2" CABLE CONNECTION AT CORNER SCALE:NTS 1/8" STAINLESS STEEL 40* M[�N BRAIDED CABLE 6 A 0* MAX. YEBOLT FOR ABLETENSION 10STAINLESS STEEL BRAIDED CABLE ................. ....... ............. ..... 4" MIN. S�LAB IIN_ wIFOOTING 3/8" DIA x 3" EMBED CONG. SCREW ANCHOR (TAPCON OR EQUAL) 0�0 PS CONG. 0 40- MIN�\ WWM OR FIBERMESH 60* MAX. \ 36X loxl' "I - "I ........... ................ \ 0 ............... O�, ...... ) ............ ........ . . ........... . ............. . ........... 4" MIN. SLAB WFOOTING 1.5"x5.5" ALUM. STRAP wl(2) 1/4" DIA x 2-1/4" MASONRY ANCHOR (TAPCON OR EQUAL) DETAIL 1-1" CABLE CONNECTION AT FOUNDATION SCALE: NTS 3000 PSI CONC. 6x6-lOxlO WWMORFIBERMESH- 04 0 0 (D 4t 00 I kn Uj W20 0) wo ,ia c) 00 0 0) co co Z Z E 10 C) 6 w-jo — 00 5 W < c� _j 0') U_ Lo z -,, LU M c) co c: z2 W < 0 T--- c: i < < < X: 0 0 LO 0 LL CINI 00 r_ c:) w 0 04 cf) 00 CIO V_ 00 z w 0 0 cl z w z 0 U-1 0f U) _j _j LL C) 0 (0 Of 6 U) 3: w z z 0 z 0 < 0 w u) —i c:) —1 ce) < IL w < � IL DESIGN DATE: 5/21/2018 REVISION 1: 05/23/2018 PAGE: REVISION 2: DATE SCALE: NTS 4_ 04 1 1� C) 3/16" 5052-H32 GUSSET V X 2" O.B. FASTENED TO CORNER #14 SMS 1 1/4" O.C. POST W/ #12 X 1 1/2" SMS AT 6" FROM 2" X PURLINS ATTACH TO 2")(2" X 1/8" X 4" ANGLE TOP & BOTTOM RAILS TYPICALLY @ 24" O.C. uj BEAM WITH MIN (4) #10 X 1 1/2" SMS PROVIDE #14 X 1" INTO EACH 1/8" X 2" X 2" EXTRUDE ANGLE 5052 PLACE WASHER UNDER SCREW MEMBER AS INDICATED BELOW H-32 ALLOY EA CORNER W1 (2) #14 X 2" 0 IN GUSSET CORNER CORNER POST—\ SMS INTO POST & (1) 3/8" DIA E2 CONCRETE SCREW ANCHOR INTO Q o CONCRETE 0 o o 6 kn 0 0 uj o MS (2) #10 X 1 1/2" S 0 THRU SCREW BOSSES 1 1/4" (TYPICAL) 2 14�-MCONC ja- Q EYBEDMEN rr-n % % 1 1 1 1 .................. % )OTING co SLAB/F( r1l 00 NOTES: SEE PLAN ....... cy) NOTES: Ce) 1. CONNECTION DETAIL (y) _c AT EAVE RAIL SIMILAR SIDE VIEW Z Z < E LL 1. GUSSET DIMENSION ARE MINIMUM (2) c REQ'D (1) EA SIDE OF BEAM - MAYBE INTERNAL OR EXTERNAL 2. As BEAM SIZE CHANGES, ADD OR CORNER K-BRACE DETAIL C) cj SUBTRACT SCREWS TO MAINTAIN 1-1/4" C/C SPACING SCALE: N.T.S. W 0 co 7-- 3. GUSSET LENGTHS REMAIN CONSTANT _j 0) 0) WIDTHS CHANGE TO MATCH BEAM SIZE. LIJ Ll__ Lo - S 2"X2"Xl/8" ANGLE X 4" LONG PROVIDE #14 X 1" INTO EACH MEMBERAS NDICATED BELOW PROVIDE INTERIOR ANGLE ABOVE AND BELOW CHAIRRAIL I EXTERIOR PLATE CORNER POST EAVE RAIL 1 " x 2" O.B. PATIO SECTION 3" x 3" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) WITH ' (3) - #12 x 3/4" S.M.S. EACH SIDE AS o' SHOWN (318" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) 2 0.0 � x ACE (TYP. LATERAL "W'-BRACING CONNECTION DETAILS K-BRACE GUSSET PLATE PER E-SERIES PURLIN 3" x 2" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) (3) - #12 x 3/4" S.M.S., EACH SIDE AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 X 2" SMS THRU BRACE INTO BEAM THRU GUSSET PLATE DETAIL #2 CORNER POST K-BRACE x 2 x 0.093 P. BRACE (TY 0 , 0 0 0 o 0 i ,,,1 3/8" 0 CONCRETE ANCHOR (2 PLATES) FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "IV' -BRACING CONNECTION DETAILS (4) #14 X 3/4" SMS INTO POST 1 " X 2" BASE PLATE ANCHORED TO CONC Wl 1/4" CONCRETE SCREW ANCHOR (MIN. 1 114" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C. MAX .......... w ..................... 1 /CORN ER POST W/ 1 " X 2" @ A— BACKSIDE 3/8" X LENGTH AS REQUIRED FOR 2 1/4" EMBED CONCRETE SCREW ANCHOR INTO CONCRETE FRONT VIEW (CP-1 CORNER POST TO CONCRETE DETAIL � �4 SCALE:NTS 6" x 5" x 0.050" COLUMN 6063-T6 ALLOY PLATE (ONE SIDE) OR STRONGER 2 x 2 x 0.093 BRACE (TYP.) K-BRACE 2 x 3 x 0.070 CHAIR RAIL 0 0 0 0 0 0 0 GIRT (CHAIR RAIL) K-BRACE 0 2 x 2 x 0.093 (11 TOTAL) - #12 x 3/4" BRACE (TYP S.M.S. AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & LATERAL "IV' -BRACING C-C FASTENER SPACING) CONNECTION DETAILS