HomeMy WebLinkAboutENGINEERINGGENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4.. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM I WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: D 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 2b TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: L PORTLAND CEMENT TYPE I - ASTM C 150 11. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 Ill. AIR ENTRAINING +/- 1% - ASTM C 260 IV. WATER REDUCING AGENT - ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: 1. REINFORCING BARS - ASTM A615, GRADE 60 I[. WELDED WIRE FABRIC - ASTM Al 85 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR -BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. -UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #1 4X2-3/4"- WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #I-QX1 -1 /2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM coARSE-AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 6-0" IN HEIGHT. MISCELLANEOUS: 4CAMM MY Sthimponimfil 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. LEGEND: (ALL MAY NOT APPLY) SCR = SCREEN KP KICK PLATE PW PICTURE WINDOW X = HORIZ. SLIDING WINDOW 0 = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP SOLID INSULATED PANEL CT CABLE TIE SG SUPER GUTTER CS CLEAR SPAN KB KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2"x0.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"4.044" 2 x 5: 2"x5"x0.050" OPEN BACK SECTIONS 1 x 2: 1 "x2"xO. 044" 1 x 3: 1 "0"4.044" SNAP SECTIONS 2 x 2 SNAP: 2"x2"x0.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"x0.045" SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0. 100" 2 x 5 SMB: 2"x5"x0.050"x0. 100". 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SM B: 2"x7x0. 057"xO. 120" 2 x 8 SMB: 2"x8"x0.072"x0. 124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"xl 0"0.092"4.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. (D z 0� LLI LLI z (D z LLI 0 _j L.L z D L0 lqT Iq q c:) co 0') cy) cy) < E 0 0 c:) ci 0 00 J 0-) LL L0 c: - I L_ LLI --- cy.) F-- "- 0) 0 -r-- c: (< 0 0- c\l 0 0 co uj 00 0 en a) _0 (D Ld 6i 2m F- C14 OD r- C) cl) Lu c 6 or) oo T_ 0 z 0 w 0 0 _j _j z U) w w (r w 0 < W Of 6 U) z _j LL o U) w w w I— W W (f) z < _j < c:) ZD 0 co 04 �- IL L9 0 cy) u) DESIGN DATE: 05/25/2018 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS 1 WALL HEIGHT PER 0- 0 p- M 0 0 m m i X 0 411 41t '111 81-1011 3X2 C? 2X7SMB 2X7SMB X X X 2X7SMB C? 2X7SMB 3X2 21-811 -n o 0 Z 0 co M m >< X X co cq M G) cn m --j m X co 0 ;u m ;o m o m CONTRACTOR: > r, m < — S2 < — T G) PIONEER SCREEN LLC o z 0 z z z c, 0 PROJECT ADDRESS: m m Q N) z N) 0 Z� CARLSTON 3280 SE SLATER ST, STUART, FL �—&-6 -L 2 6-6 -L 2 - 6-6 -L �1� 2 6-6 -L --� 2 IX3 >< X cq 2X3 o X w X Ul cn X c" co N) X CA cn c- c- cu IX3 co -------------- 261-211 ...... ............................... . 3X2 2X8SMB 2X8SMB IM 10 1 cl) X w X X io r,j w w i cn 2X8SMB 1c: im ix 2X8SMB 3X2 .. ......... lX3 X X 00 X cn cn co X 2X3 c- lX3 H �-6-6 1" 616 11' 41-1111� 2 2 r1i x w x C) cn C) ca m FLORIDA ENGINEERING LLC 4456 TAMIAMI TRAIL, UNIT B14 PORT CHARLOTTE, FLORIDA 33980 (941) 391-5980 www.fiengineeringllc.com PROJECT NO. 1814319 CA CERT. #30782 Ckig E. Gun'W'rson, P.E. #60102 DATE: 05/25/2018 FLASHING 1")g' FASTEN TO COL. (INTERNAL) W/(2) #10xl-1/2" SMS, FASTEN TO EAVE RAILS ABOVE W/ #lOX1-1/2" SMS 24" O.C. AND 6" FROM END. —_ TABLE D BEAM OTY EACH SIDEJSIZE 2x3 4/12 2x4 8/10 2x5 8/10 2x6 10/10 2x7 12/10 2x8 8/14 2x9 9/14 2x`10 9114 MAINTAJN MIN, OF 518" SEPERATION FROM EDGE OF BEAM SMS O.C. DETAIL E - UPRIGHT TO BEAM CONNECTION SCALE:NTS NOTE: IF PAVERS ARE PRESENT,CONCRETE ANCHORS SHALL PENETRATEINTO FOOTING 2-1/4'MIN. (TYP-) NOTE: WHEN FASTENING TO WOOD USE 114" GALV. LAG SCREW IN LIEU OF CONIC. ANCHORS AND ENSURE PENETRATION MIN 2-1/4" INTO STRUCTURAL FRAMING BENEATH (TYP.) *HORIZONTAL OR SLOPED BEAM PER PLAN NOTCHED TO RECEIVE COLUMN WITHIN SMS, (EACH SIDE) QTY PER TABLE D NOTCH PROFILE MAY VARY TO PERMIT CORRECT # SMS COLUMN PER PLANS TABLE "B" UPRIGHT OTY. TAPCON/ SCREW 2X3 0 2X4 1/2 2X5 1/2 2X6 2/4 2X7 2/4 2X8 3/6 2X9 3/6 2X10 4/8 1/8")05a"x ANGLE v 5032 H-32 ANGL 2 - #12 SMS INTO COLUMN 1/4" MASONRY ANCHOR EACH ANGLE - EACH SIDE COJ�� MIN 4" SLAB 3000 PSI CONC. W/FIBERMESR--- (2) #1 Ox2" INTO BEAM BEAM — INSTALL BRX TO CORNER SELF-MATING OR SNAP SECTION TYP. PER PLAN 1"x2" O.B. BASE PLATE-TYP. 0 0 V"� oll 2-1/4" MIN. CONC. ANCHOR EMBEDMENT " MIN. WHEN GREATER THAN 2X4 UPRIGHT IS USED SEE TABLE "B" 3000 PSI CONC. SLAB/ FTG. 6x6-10x&------- SIDE VIEW WWM OR FIBERMESH 1/4" MASONRY ANCHOR AT EACH ANGLE,,.— 2-#12SMS /4�TAPCON XL (RED HEAD MFG. OR EQUAL) lx2 BASE 2 SLAB (BEYOND) 1 'W" BASE PLATE ANCHORED TO CONC w/ 1/4�'MASONRY ANCHOR 6" MAX EACH SIDE OF POST AND 24" O.C. MAX 6. 3000 PSI CONIC. SLAB/ FTG. 6x6-1 0 FRONT VIEW WWM OR FIBERMESH DETAIL "B" 2"x4" OR LARGER UPRIGHT TO DECK DETAILS SCALE: N.T.S. (2) #1 Ox3" SMS INTO SCREW BOSSES FOR EDGE MEMBER DETAIL "ID" - ROOF BRACING CONNECTION DETAIL SCALE:NTS 11 --- EDGE MEMBER III A I OR PURLIN 0.0625" 6063-T6 FLAT PLATE w/(8) #10x3/4" SMS, MIN. 1/2" EDGE DISTANCE, PLATE MAY -BE FASTENED INTERNALLY TO BRACE *ALL MEMBERS PER PLAN *MEMBERS VARY PER PLAN FASTEN TOP OF HEADER TO INTERSECTING MEMBER wl(2) #10 SMS w/1" PENETRATION INTO SCREW BOSS OF MEMBER - TYP. BOTH SIDES ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL wl(4) #10x75" INTO GIRT OR PURLIN & (2) #14x75" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED > PURLIN ly, UPRIGHT ' BEAM -SNAP SELF MATING, OR HOLLOW DOORJAMB PER PLAN ------------ FASTEN HEADER wl(2) #lOx3" "�,�TO SCREW BOSS OF HEADER ALTERNATE HEADER CONNECTION 10, WHEN Z-BAR IS USED - FASTEN I Z-BAR TO COLlHEADER AT EACH 11 11 CORNER AND 18" O/C ALTERNATE BASE PLATE CONNECTION ATTACH MEMBER TO BASE PLATE (INTERNAL) w/(2) #I Ox2" SMS ATTACH BASE PLATE TO MEMBER W/(2) #104" SMS INTO SCREW BOSS OF BASE PLATE -� III I MEMBER I DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE:NTS ..... . . . . . . .............................. .......... ............. .... ................................................................... .... 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF COLUMN 1-1/2" PENETRATION INTO UNDERLYING FOOTING DETAIL 7" - DOOR JAMB & HEADER CONNECTION SCALE:NTS #10x2" SMS INTO REW BOSSES 2"x2" )(' 063" - DIM. TO MATCH PURLIN SIZE RECEIVING CHANNEL (2) #12 SMS INTERNAL TO EAVE RAJL (3) #12 EACH SIDE INTO PURLIN EAVE RAIL - SEE PLAN-- lx2 OPEN BACK EXTRUSION (2) #10x2" SMS THRU lx2 INTO EAVE RAJ LEACH SIDE OF COLUMN DETAIL "G" -SLOPED PURLIN CONNECTION SCALE: INTS (12) #12xl' SMS @ 1" SPACING, 2")2" EDGE BEAM (2)#lOx3"SMS — INTO SCREW BOSSES CONNECTING EDGE BEAM TO PURLIN ALTERNATE DETAIL "G" SLOPED PURLIN CONNECTION SCALE: NTS 0 0 0 PURLIN UPRIGHT 1-1/2"x 1/16" PLATE (TOP OR BOTTOM) 1 "x2" FASTENED TO COLUMN w/(2) #10xl-112" SMS INTO SCREW BOSSES FOR SMB OR SNAP COLUMN V.&I SNAP NOTCH COLUMN AS REQ'D. COLUMN PER PLAN 04 0 (D 4t uj 00 C) Q) s 0 uj C) 00 c\I 00 r- C) ce) ZZ< 2 E 0-) cll� C:) c LLI 0 Do Lij _j m LL U.) Z LU M a) a) co c: 0) z 0 w < _j CF) < 0 F- of 0 0 (y) LL 00 V_ b z w 0 z U) Ill Lu w , w C.) W < z _j LL 0 cl) - w w F— W F— W U) X z 0 < F_ —i < 0� 0 00 0 < C-4 a_ C.) cy) U) DESIGN DATE: 05/25/2018 REVISION 1: DATE PAGE: 3 REVISION 2: DATE SCALE: NTS GIRT FASTENED INTERNALLY AT EACH END wl #1 Oxl.5" EACH SCREW GROOVE. FASTEN TO BEAM w/ 2x2xl25 ANGLE (2) #12 SMS INTO BEAM & (2) #10xl-1/2" THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY TO GUTTER - 2"x2"xl/8" ANGLE w/(2)#12SMS-._ EACH LEG __­1 FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION __L 0 BEAM (2) #14x2" WOOD ��/m #12 SMS SCREW 18" D.C. o o 0___ o CLOSE BOTTOM OF BEAM WHEN TRIMMED .044 RECEIVING CHANNEL, FASTEN w/(2) #12 SMS EACH SIDE OF BE�� #10SMSWITHI OF BEAM & 24" 2x2xl/8" ANI EA SIDE OF w/(2)#12SN EACH LEG E FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL*FASTEN TO STRUCTURAL GUTTER INTERNALLY w/(2) #12 SMS ALTERNATELY 2x2xl/8" ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW TOP VIEW DETAIL "H" SCALE: NTS NOTE F INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 3/8" MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTEN GUTTER TO FASCIAw/#14x2" WOOD SCREW 18" D.C. (2) #12 SMS (2) #14x2" WOOD SCREW FASCIA (2"x6" MIN. EXISTING) STRUCTURAL GUTTER -ALTERNATELY SEE PAGE 5 5052-H32 GUSSET TABLE B-1 BEAM SIZE COL. TO BEAM QTYSMS/ SIDE OF COLa BEAM TO BEAM OTY SMS/ FACE/SIDE 2x4 (5) #12 (9) #12 2x5 (5) #12 (9) #12 2x6 (7) #12 (9) #12 2x7 (10)#12 (10)#12 (12)#12 (14)#12 (14)#14 (14) #14 (16)#14 (15) #14 JSSET CONNECTION CALE:NTS .050" GUTTER STIFFNER FASTEN TO FASIA w(2) #l2x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS �-_ -ALTERNATELY SEE PAGE 5 __v — DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE:NTS (2) #12 SMS baxlff' ANGLE wl(2) ��GIRT #12 SMS EA LEG _'� 0 SMB 0 0 J., 0 0 0 WHEN BEAM & PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM & PURLIN w/ 1/8"x2')Q" ANGLE & (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (BEAM TO PURLIN) w/ 118"x2"xZ' ANGLE w/(2) #12 SMS INTO EA, MEMBER (BEAM & PURLIN) #14 WOOD SCREWS '0 FASCIA 18" O.C. GIRT 1/8l'x2"x4" STRAP (2) #12 SMS INTO BEAM STRUCTURAL GUTTER (2) #12 SMS INTO GUTTER SIDE VIEW (2) GUTTER BRACES EACH W/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA GIRT 1/8"x2"x4�'STRAP GIRT (2) #12 SMS INTO BEAM (2) GUTTER BRACES (2) #12 SMS INTO GUTTER FASCIA EACH w/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA 2x2xl/8' ANGLE wl(2) o #12 SMS EA. LEG o (2) #12 SMS SMB 0 0 1/8"x2"x,f'STRAP (2) #12 SMS INTO BEAM GIRT \ (2) #12 SMS INTO STRUCTURAL GUTTER TOP VIEW DETAIL "L" CORNER CONNECTION SCALE:NTS (9)#lOx2"SN 1/8" PLATE ON 45'ANGLE OR 1/8"x2"x2" ANGLE wl(4) #12 SMS INTO EACH INTERSECTING MEMBER PERIMETE FRAMING DETAIL 1-2" CABLE CONNECTION AT CORNER SCALE:NTS 40* MIN��\\ BRAIDED CABLE 1/8"STAINLESSS EEL 60* MAX. \le (EBOLT FOR �BLE TENSION 1/&'STAJNLESS STEEL BRAIDED CABLE ....... . I .. .......... .... "I I I "I ........ .......... 4" MIN. SLAB WFOOTING 3/8" DIA x 3" EMBED' CONC. SCREW ANCHOR (TAPCON OR EQUAL) 3000 PSI CONC. 6x6-10xlO 40* MIN. WWM OR FIBERMESH 60* MAX. ........ ....... ..... ............... , , I I I , I I I I 1 0 ............... 0 A IN. SLAB )OTING 1.5"x5.5" ALUM. STRAP w/(2) 114!'DIA x 2-1/4" MASONRY ANCHOR (TAPCON OR EQUAL) DETAIL 14' CABLE CONNECTION AT FOUNDATION SCALE: NTS 3000 PSI CONC. 6x6-10xlO WWM OR FIBERMESH c"! 0 0 (D it Uj L 00 CF 0 a) =3 W, 0 00 c"I 00 o 0 0 cl) OZ ce) c) z Z) < 2 E 8 Lu 0� -of 0 C3 ('< W 0 00 w _j m LL U') z I LLi-rm- o.) cq ce) z o w < < 0 (.0 1- 0 Lo 0 ce) LL co z I-_ 0 w 0 0 z U) w LU Of w < (1) U) Z _j LL 0 U) - LU LU LLI 1--- W F— U) U) W z c:) < 0 0 00 < c,4 F- 0- w 0 ce) U) DESIGN DATE: 05/25/2018 REVISION 1: DATE PAGE: 4- REVISION 2: DATE SCALE: NTS 3/16" 5052-H32 GUSSET 2" X PURLINS ATTACH TO BEAM WITH MIN (4) #10 X 1 1/2" SMS PLACE WASHER UNDER SCREW IN GUSSET CORNER 1 114" (TYPICA��.. o ve #14 SMS @ 1 1/4" O.C. o o 0 o o 0 0 o o 0 \o 0 o 0 NOTES: 1. GUSSET DIMENSION ARE MINIMUM (2) REQ'D (1) EA SIDE OF BEAM - MAYBE INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1-1/4" C/C SPACING 3. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. 2"X2"XI/8" ANGLE X 4" LONG PROVIDE #14 X 1" INTO EACH MEMBER AS INDICATED BELOW PROVIDE INTERIOR ANGLE ABOVE AND BELOW CHAIRRAIL EXTERIOR PLATE GUSSET PLATE PER E-SERIES PURLIN ANGLE 1" INTO EACH DICATED BELOW CORNERPOST (2) #10 X 1 1/2" SMS THRU SCREW BOSSES M.M. 19 019119 1110 NOTES: SEE PLAN 1. CONNECTION DETAIL AT EAVE RAIL SIMILAR SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 X 2" SMS THRU BRACE INTO BEAM THRU GUSSET PLATE V X 2" O.B. FASTENED TO CORNER POST W1 #12 X 1 1/2" SMS AT 6" FROM TOP & BOTTOM RAILS TYPICALLY @ 24" O.C. 1/8" X 2" X 2" EXTRUDE ANGLE 5052 H-32 ALLOY EA CORNER W/ (2) #14 X 2" SMS INTO POST & (1) 3/8" DIA CONCRETE SCREW ANCHOR INTO CONCRETE 6" V", ________fiC0NC 21/4' M ............ ..... . . Ho ........... .... CHOR IBEDME .................... ................... SIDE VIEW CORNER K-BRACE DETAIL SCALE: N.T.S. (4) #14 X 3/4" SMS INTO POST 1 " X 2" BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C. MAX 7pi CORNER POST W/ 1" X 2" @ BACKSIDE 3/8" X LENGTH AS REQUIRED FOR 2 1/4" EMBED CONCRETE SCREWANCHOR INTO CONCRETE FRONT VIEW DETAIL #2 CP-1 CORNER POST TO CONCRETE DETAIL �b-4) SCALE:NTS CORNER POST EAVE RAIL CORNER POST 3" x 2-"x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) 1" x 2" O.B. PATIO SECTION (3) - #12 x 3/4" S.M.S., 6" x 5" x 0.050" COLUMN EACH SIDE AS SHOWN 6063-T6 ALLOY PLATE (1/2" MIN. PLATE EDGE K-BRACE R (ONE SIDE) OR STRONGER 2 x 2 x 0.093 2 x 2x 0093 DISTANCE & C-C BRACE �Yp. BRACE (TYP.) 3" x 3" x 0.050" MIN., 6063-T6 ALLOY FASTENER SPACING) PLATE DR STRONGER (ONE SIDE) WITH K-BRACE (3) - #12 x 3/4" S.M.S. EACH SIDE AS x 2 x 0.093 x 2 x 0 093 SHOWN (3/8" MIN. PLATE EDGE DISTANCE C Yp BRACE (TWY E (T 2 x 3 x 0.070 CHAIR RAIL & C-C FASTENER SPACING) 0 LBRA 0 2 x 2 x 0.0 ol 0 'o "I ____o ----- ---- P. ACE ( P. 0 0 0 0 0 0 GIRT(CHAIRRAIL) K-BRACE K-BRACE — ----------- A 0 0__-ll o 0 __ I LATERAL "W'-BRACING CONNECTION DETAILS 3/8" 0 CONCRETE ANCHOR (2 PLATES) FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "IC' -BRACING CONNECTION DETAILS 2 x 2 x 0.093 BRACE (TYP (11 TOTAL) - #12 x 3/4" (11 T( S.M.S. AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & LATERAL "IV' -BRACING C-C FASTENER SPACING) CONNECTION DETAILS C14 C) w j c� 0 0 iu c: -low-F uj 0 ca C) 00 C14 co C3 0-) M cv) Ce) zz< D E - _Q Zo cl� C) 6 W _J 000— 0) W < _j (3) LL U-) z - Tm- LU 0) 0 — cy.) c: �_ 'I- 0) z � w < ov- -i 't 0 � 00 < < Q < M 0 o LO 0 ce) LL 00 0 z I-_ 0 w 0 z ILL! w w C) U) < 6i z _J LL 0 co w U) w cr W W 0 U) z 0 < _j < cj� c:) L) 0 L) COD < C-4 F-- E-L w 0 m U) z 0 0 0� L) a. DESIGN DATE: 05/25/2018 REVISION 1: DATE PAGE: 5 REVISION 2: DATE SCALE: NTS