FL# FL1654-R22
Application Type Revision
Code Version 2017
Application Status Approved
Comments
Archived M,
Product Manufacturer POLYGLASS USA
Address/Phone/Email 150 Lyon Drive
Fernley,NV 89408
(570)384-1230 Ext 242
jakins@polyglass.com
Authorized Signature James Akins
jakins@polyglass.com
Technical Representative Maury Alpert
Address/Phone/Email 1111 W. Newport Center Drive
Deerfield Beach,FL 33442
(912)429-8610
MAlpert@polyglass.com
Quality Assurance Representative Ariel Lender
Address/Phone/Email 1111 W.Newport Center Drive
Deerfield Beach,FL 33442
(954)233-1230
ALender@polyglass.com
Category Roofing
Subcategory Modified Bitumen Roof System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed the Robert Nieminen
Evaluation Report
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 10/06/2018
Validated By John W. Knezevich,PE
Validation Checklist-Hardcopy Received
Certificate of Independence FL1654 R22 COI 2017 01 COI Nieminen pdf
Referenced Standard and Year(of Standard) Standard Year
ASTM D6162 2008
ASTM D6163 2008
ASTM D6164 2011
ASTM D6222 2011
ASTM D6509 2009
FM 4470 2012
FM 4474 2011
UL 1897 2012
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
Date Submitted 09/14/2017'
Date Validated 09/15/2017
Date Pending FBC Approval 09/22/2017
Date Approved 12/12/2017
Summary of Products
FL# Model,Number or Name Description
1654.1 Polyglass SBS and APP Modified' SBS and APP modified bitumen roof systems _
Bitumen Roof Systems
Limits of Use Installation Instructions
Approved for use in HVHZ:No FL1654 R22 II 2017 09 FINAL Al ER POLYG ASS MODBIT FL3654
Approved for use outside HVHZ:Yes R22.Ddf
Impact Resistant:N/A Verified By: Robert Nieminen PE-59166
Design Pressure:+N/A/-622.5 Created by Independent Third Party:Yes
Other:1.)The design pressure in this application Evaluation Reports
relates to one particular assembly over concrete FL1654 R22 AE 2017 09 FINAL ER PO Yr'I ASS MODBIT FL¢54
deck.Refer to the ER Appendix for other systems and
deck types. 2.)Refer to ER,Section 5 for other Limits 2R 2.Ddf
of Use. Created by Independent Third Party:Yes
Back McKI -
contact Us::2601 Blair Stone Road.Tallahass 3 399 phone:BS -487-.1824
The State of Florida is an AAJEEO employer.Copyright 2007-2013 State of Florida >:Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you,do not want your e-mail address released in response to a public-records request,do not send electronic
mall to this entity.instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to Section
455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address If they have
one.The emails provided may be used far official communication with the licensee.However email addresses are public record.If you do not wish to supply a personal
address,please provide the Department with an email address which can be made available to the public.To determine If you are a licensee under Chapter 455,F.S.,
please dick here.
Product Approval Accepts:
M w ®Ed
Credit Card
Safe
i
TFUNIIY'JERD
Table Deck Application Type Description ri Page
SA Wood New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 5
1B-1 Wood New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 5-9
1B-2 Wood New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 10-11
1C Wood New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 11
lD Wood New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 12-13
lE Wood New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover 14-15
1F-1 Wood New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet(nails),Bonded Roof Cover 16-18
1F-2 Wood New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet(screws&plates),Bonded Roof Cover 19-21
1G Wood New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 21
2A Steel or Structural concrete New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover - 22-24
2B Steel or Structural concrete New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 25-28
2C Steel or Structural concrete New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover 29-31
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 32-40
3B Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 40
4A LWIC New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 41-42
4B LWIC New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 43
4C LWIC New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 44-46
5A CWF New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 47
5B CWF New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 48
5C CWF New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 49
5D CWF New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 49
5E CWF New,Reroof(Tear-Off)or Recover E Non-insulated,Mech.Attached Base Sheet,Bonded Roof Cover 49
iA Gypsum Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 50-52
A'iB Gypsum Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 52
6C Gypsum Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 53
6D Gypsum Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 53
7A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 54-58
7B Various Recover F Non-insulated,Bonded Base Sheet,Bonded Roof Cover 58
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation/base sheet fasteners shall be of sufficient length for the following deck engagement:
➢ Wood: Minimum 0.75-inch penetration.
➢Steel: Minimum 0.75-inch penetration and engage the top Flute of the steel deck.
"v Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanu rate, polystyrene,wood fiberboard, perlite, gypsum-based roof board or mineral-wool roof board that meets the CA
requirements of F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover.
Exterior Research and Design,LLC.d/b/a Trinity(ERD Evaluation Report P9290.02.08-R20 for F1.3654-1122
Certificate of Authorization#9503 6'EDITION(2017)FBC NON-HVHZ EVALUATION Revision 20:09/12/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(570)394-1230 Appendix 1,Page 1 of 58
TRINITY I ERD
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D(mechanically attached base sheet,bonded roof cover),whereby the base
sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and
structural members shall•be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation. _
5. Preliminary insulation attachment for System Type D:Unless otherwise noted,refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29(January 2016).
5. Unless otherwise noted,insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application;the ribbons/beads shall expand as noted in the manufacturer's published instructions.
f ➢ Hot asphalt(HA): Full coverage at 25-30 Ibs/square.
➢ Dow INSTA STIK Quik Set Insulation Adhesive(D-I5): Continuous 0.75 to 1-inch wide ribbons,l2-inch o.c.
Y Millennium One Step Foamable Adhesive(M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c.
Y Millennium PG-1 Pump Grade Adhesive(M-PGl): Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c:
➢ OMG OlyBond 500(OB500): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c.(PaceCart or SpotShot). Nate: 01y8ond Green may be used where Olyoond 500 is referenced.
➢ OlyBond Classic(OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive&Sealants CR-20: Continuous 2.5=3.54nch wide ribbons,12-inch o.c.
➢Note: When multiple layers(s)of insulation and/or coverboard are installed in ribbon-applied adhesive,board joints shall be staggered.
Y Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted,all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum
Design Pressure(MDP)limitations. In no case shall these values be used to'increase'the MDP listings in the tables;rather if MDP listing below meets or exceeds that listed for a particular system in the tables,then
the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive(M-OSFA): MDP -157.5 psf (Min.0.5-inch thick)
➢ Millennium PG-1 Pump Grade Adhesive(M-PGl): MDP -157.5 psf (Min.0.5-inch thick)
➢ OMG OlyBond 500(OB500): MDP -45.0 psf (Min.0.5-inch thick Multi-Max FA-3)
➢OMG OlyBond 500(013500): MDP -187.5 psf (Min.0.5-inch thick ISO 95+GL)
),OMG OlyBond-500(06500): MDP -315.0 psf (Min.0.5-inch thick ENRGY 3)
➢OMG OlyBond 500(06500): MDP -487.5 psf (Min.0.5-inch thick ACFoam II)
➢ ICP Adhesives&Sealants CR-20: MDP -117.5 psf (Min.1.0-inch thick)
R. Bonded polyisocyanu rate insulation boards shall be maximum 4 x 4 ft.
i. For mechanically attached components or partially bonded insulation,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16,and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29,Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk*carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29(January 2016)for Zone 2/3 enhancements:
10. For fully bonded assemblies,the maximum design,pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16,and no rational analysis is permitted.
11. For mechanically attached components over existing decks,fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re-roof installation,the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive,and the existing
roof system(for recover)shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction,as documented through field uplift testing in accordance with
ANSI/SPRI IA-1,ASTM E907,FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D,the insulation is optional;however,the existing roof system shall be suitable for a recover application.
14. Lightweight Insulating Concrete(LWC)shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced,refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced,the minimum design mix shall be 300 psi. In all cases,the minimum top-coat thickness is 2-inches.
For LWC over structural concrete,reference is made to FBC Section 1917.4.1,Point 1.
Exterior Research and Design,LLC.d/b/a Trinity I ERD Evaluation Report P9290.02.08-R20 for FL1654-R22
Certificate of Authorization#9503 OH EDITION(2017)FBC NON-HVHZ EVALUATION Revision 20:09/12/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(570)384-1230 Appendix 1,Page 2 of 58
QOTRINITYIERD
15. Unless otherwise noted,refer to the following references for bonded base,ply or cap sheet applications.
3s- Y�1'r s#.b. _R'sr rn",., r.:.;. .•Cs k .�r+r..,,,;. �+.<x-:.«-.,v.++^, ter•,-::a,- .m�.n.,.i ':: � `«i*�..'..a,.�g`. 4 `JS « F "LY.t-h w.ka:°.:.;,.q.,
E:-z..... t _ : `ei ?O�YGU4SS��l"'OtdERS�+' '�, �.;. s'F
_ — b5, �'ML..Sf,�`.4
.a. ter. .�. � _ �. __♦. _ x»...,_, a. x_..-vx 6+S.A
Reference Layer Material Application
BP-AA Base Ply One or more plies Polyglass G2 Base,F8C Approved ASTM D4601,Type II Hot Asphalt at 20-40
(Base and Ply sheets,Asphalt- Ply One of more plies Polyglass Ply IV,Polyglass Ply VI,FBC Approved ASTM D2178,Type IV or VI Ibs/square
Applied) Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
Base Ply One ply Elastobase(sand/sand),Elastoflex V,Elastoflex 56,Elastoflex S6 Type II,Polyglass HT Base 650 PG350 at 1.5-2.0
SBS-CA1 Cap Ply Elastoflex VG,Elastoflex VG FR,Elastoflex 56,Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield gal/square
TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed)
Base Ply One ply Elastobase(sand/sand),Elastoflex V,Elastoflex S6,Elastoflex 56 Type II Polyplus 35 at 1.5-2.0
SBS CA2 Ca PI Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield
P y TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed) gal/square
Base Ply or Ply One or more plies Elastobase(sand/sand or poly/sand),Elastobase P(sand/sand or poly/sand),Elastoflex V,Elastoflex S6,Elastoflex
56 Type II,Polyglass HT Base 650
SBS-AA Elastoflex V,Elastoflex VG,Elastoflex VG FR,Elastoflex 56,Elastoflex S6 Type 11,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G, Hot Asphalt at 20.40
(SBS,Asphalt-Applied) Cap Ply Elastoshield TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed) Ibs/square
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
Base Ply or Ply 65U or more plies Elastobase(sand/poly),Elastobase(poly/poly),Elastoflex V,Elastoflex S6,Elastoflex 56 Type II,Polyglass HT Base
SBS-TA
(SBS,Torch-Applied) Cap Ply Elastoflex V,Elastoflex VG,Elastoflex VG FR,Elastoflex 56,Elastoflex 56 Type II,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G, Torch-Applied
Elastoshield TS-G FR,Polyfresko G SBS(poly-film backed),Polyfresko G SBS FR(poly-film backed)
Base Ply One or more plies Elastoflex SA V Base,Elastoflex SA V FR Base,Elastoflex SA V Plus,Elastoflex SA V Plus FR
SBS-SA Cap Ply Elastoflex SA P,Elastoflex SAP FR,Polyreflect Self-Adhering
(SBS,Self-Adhering) Unless otherwise noted,permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein,
Note: Elastobase of sand or of
(P Y/ 1 (P Y/PolY1•
APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0
gal/square
APP-TA Base Ply or Ply One or more plies Polyglass APP Base,Polyflex,Polybond
_. (APP,Torch-Applied) Cap Ply Polyflex,Polyflex G,Polyflex G FR,Polybond,Polybond G,Polyfresko G,Polyfresko G FR Torch-Applied
APP-SA Cap Ply Polyflex SA P,Polyflex SA P FR,Polyfresko G SA,Polykool
17 Unless otherwise noted,permissible membrane substrates for APP-SAare limited to the SBS-5A Base Ply options herein, Self-Adhering
(APP,Self-Adhering) Note: Elastobase of sand or Elastobase of
(P Y/ ) (P Y/PaIY)•
16. Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect on the system wind load performance. Refer to current Roofing Materials Directory for fire ratings
associated with coating usage.
➢ PG200 Non Fibered Roof Coating;
➢ PG300 Fibered Roof Coating;
D PG600 Non-Fibered Aluminum Roof Coating;
➢ PG650 Fibered Aluminum Roof Coating;
➢ PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;
D PG70005(Quick Set)High Quality Elastomeric Roof Coating or KM Acryl ZS-QS(for granule-surfaced APP or SBS only);
➢ PG800 Asphalt Emulsion Roof Coating;
➢ Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;
➢ Polyplus 65 Premium Fibered Aluminum Roof Coating;
Y Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;
D Polybrite 70QS(Quick Set)Premium Grade Elastomeric Roof Coating or KM Acryl 15-OS(for granule-surfaced APP or SB5 only);
➢ Polybrite 90 High Solids Silicone Roof Coating or Polybrite 95 Silicone Roof Coating.
Exterior Research and Design,U.C.d/b/a Trinity)ERD Evaluation Report P9290.02.08-R20 for FL1654-RZZ
Certificate Of Authorization#9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION Revision 20:09/12/2017
Prepared by: Robert Nierninen,PE-59166 Polyglass Modified Bitumen Roof Systems;(570)384-1230 Appendix 1,Page 3 of 58
TMi-rY I ERD
17. Dens Deck shall be field-primed with PG100 prior to self-adhering membrane application. Refer to tables herein for other priming requirements.
18. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure(MDP)limitations. The lesser of the MDP listings below vs.those in Table 3A
applies:
a�tea; y-
YlIYOIt$A!tlllDkiJptlpNYTRtf4TU i�dfR1TE GC Eb. TWM 3dt gtr y
.m._ J���.., �
Option ft Primer Type A ttach
Vapor Barrier Insulation Adhesive MDP(psf)
.
VB4. PG100 Elastoflex SA V Plus Self-Adhering Inta-Stik or CR-20,12-inch o.c. -60.0
VB-2. PG100 Polyglass APP Base Torch-applied Inta-Stik or CR-20,12-inch o.c. -75.0
VB-3. PG100 Elastoflex SA _ Self-Adhering Insta-Stik,12-inch o.c. -75,0
VB-4. PG100 Elastoflex SA P Self-Adhering Millennium One Step Foamable Adhesive,12-inch o.c. -157.5
VB-5. PG100 Elastoflex SA P Self=Adhering CR'-20,12-inch o.c. -270.0
VB-6. PG100 Elastoflex SA V Base,Elastoflex SA V FIR Base, Self-Adhering Millennium'One Step Foamable Adhesive,Millennium PG-1 Pump Grade -290.0
Elastoflex SA V Plus,Elastoflex SA V Plus FIR Adhesive,OlyBond 500 or CR-20,12-inch o.c.
19. "MDP"=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads.Refer to FBC1609 for determination of design wind loads.
Exterior Research and Design,LLC.d/b/a Trinity(ERD Evaluation Report P9290.02.08-R20 for FL1654-RZZ
Certificate of Authorization#9503 6'EDITION(2017)FBC NON-HVHZ EVALUATION Revision 20:09/12/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(570)384-1230 Appendix 1,Page 4 of 59
TRINITY ERD
�
SWO,OD;REtKS:-HESA/C0(VSTRl1GT10NItERbF TIAt%t?FI -
] at
�iMOON
System Deck(Note i) Base Sheet Roof Cover(Note 15) MDP
No. Type Fasten Attach Base Ply Cap (Psf)
X` z
>,�Rir/I,OHEIII�Gg115t{�LY:3+•'<<av tzr a ..,�s�a �*..-#'ci P-.ie.:sz. ¢, .•.u.t, E ;.1tYe.a..,r s .,t, e a....,.,.�> as.:: - .f' }3. zT Y.t... ..r,Y r�:
._�:�•-...��_ rv� .-r...� ..cs_ �..,o _,_..... �.,d.,-..•, _..._aF.,#S+.Y s.A-y.._,.sSis s... fa�ek- u�`�YFl .�+.. � �4 f*i: �I.
Min.19/32- Elastobase,Elastobase P Dekfast Hex(aka,Dekfast PLT-H-2-7/8)with Dekfast#14 12-inch o.c.in 4-inch lap and 12-inch o.c.in two SBS-SA,APP-SA,SBS-
W-136 inch plywood (poly-film to or Trufast 3"Metal Insulation Plate with Trufast HD SBS-SA I -52.5'
p yw (p y p} (2),equally spaced,staggered center rows TA,APP-TA
W-137 Min.19/32- Elastobase,Elastobase P Dekfast Hex(aka,Dekfast PLT-H-2-7/8)with Dekfast#14 12-inch o.c.In 4-inch lap and 12-inch o.c.in two Polyflex SA Base APP TA -52.5'
inch plywood (poly-film top) or Trufast 3"Metal Insulation Plate with Trufast HD (2),equally spaced,staggered center rows
W-138 Min.19/32- Elastobase,Elastobase P OMG Flat Bottom Plates(square)with Roofgrip 012 12-inch o.c.in 4-inch lap and 12-inch o.c.in two SBS-SA SBS-SA,APP-SA,SBS- -60.0'
inch plywood (poly-film top) (2),equally spaced,staggered center rows TA,APP-TA
W-139 Min.19/32- Elastobase,Elastobase P OMG Flat Bottom Plates(square)with Roofgrip#12 12-inch o.c,in 4-inch lap and 12-inch o.c.In two Polyflex SA Base APP-TA -60.0'
inch plywood (poly-film top) (2),equally spaced,staggered center rows
7ABCE 1Gt WgOD'DECKS—NEW CONS7RUCTIbNORitEFt •
�, §r'g 1( EM R :F:`,NON•1NSULATEO QELIRQQFCGIVER i'$}JE_ fi to
�kr$ .,a�Fsp�. 1�.�. _••Ci, .l.
System Deck(Note 1) Primer Roof Cover(Note 15)_. MDP(psf)
No. lointTreatm_ent Base Ply Ply Cap Ply
Min.15/32- (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS-
W-140 inch plywood None None SBS-SA TA,APP-TA TA,APP-TA 90.0
W-141 Min.15/32- (Optional) ex SA Base
inch plywood (O P )PG100 None Polyflex (Optional)APP-TA APP-TA 90.0
Min'15/32- (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS-
W-142 inch plywood PG100 None SBS-SA TA,APP-TA TA,APP-TA 97.5
W-143 Min.15/32- (Optional)PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Elastoflex SA V Base or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- 97 5
inch plywood place to create continuous bond. Elastoflex SA V FR Base TA,APP-TA TA,APP-TA
W-144 Min.15/32- WB 30DO None SBS-SA (Optional) SBS-SA,APP-SA,SBS- -105.0
inch plywood TA,APP-TA
Min.15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA-V Plus,rolled into Elastoflex SA V Plus or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS-
W-145 (Optional)PG100 135.0
inch plywood place to create continuous bond. Elastoflex SA V Plus FR TA,APP-TA TA,APP-TA
W-146 Min.15/32- tional(O PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Pol ex SA Base
inch plywood P } place to create continuous bond. yfl (Optional)APP-TA APP=TA -135.0
Exterior Research and Design,LLC.d/b/a Trinity ERD Evaluation Report P9290.02.08-R20 for FL1654-RZZ
Certificate of Authorization#9503 6'EDITION(2017)FBC NON-HVHZ EVALUATION Revision 20:09/12/2017
�, Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(570)384-1230 Appendix 1,Page 21 of 58