HomeMy WebLinkAboutPLAN REVIEW FORM -10 0 1,35
SAINT LUCIE COUNTY FIRE DISTRICT
�ruOUNTy;, PLAN REVIEW FORM
5�160 N.W.Milner Drive
Port Saint Lucie,FL 34983
x' 'K Telephone: 772-621-3322
FDIS � Fax: 772-621-3604
Web Address: www.slcfd.com
• Building Dept. SLC FMO Permit# B-17-207
Project Name WA WA BLDG Permit# 1704-0135
M I
Address 260 SE Prima Vista Blvd City PSL
Contractor TBD
Address City
State Zip Telephone
Architect/Engineer Cuhaci&Peterson Telephone (407)661-9100
Occupancy Type Mercantile.(class B) Construction Type VB Square Feet 7945
Occupant Load 164 per plans Number of Stories I1 Access Box Required Access Key Switch
AFS Permit FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required.The file format shall be.pdf only.
2.All revisions,including the electronic copy must be received prior to permitting.
3.The Fire Marshal requires 24 hour notice on all Inspections.
4.The respective Building Department shall schedule all final Inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers,Fire Alarms,and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE,2010 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
Notes:
1.Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.HVAC duct smoke detector shall
be tied into the fire alarm system.
2.The Installation or Alteration of Fire Alarm Systems require a separate review and permit.
3.Panic Hardware is required on all exit doors.
Page f 1 of Reviewed by Tony Jerger Date 08/15/2017
COMcheck Software Version 4.0.5.1
Envelope Compliance Certificate
CANNEL)
Project Information BY
Energy Code: 2014 Florida Building CoRtIALJ Ue^n fit'lion
Project Title: Wawa-FLO-F85FB-2150151
Location: Port Saint Lucie, Florida F1COPY
Climate Zone: 2a IFILE Project Type: New Constriction
Vertical Glazing/Wall Area: 22%
Construction Site: Owner/Agent: Designer/Contractor:
SW Corner of NE Prima Vista Blvd. Cuhaci Peterson Architects, Cuhaci&Peterson Architects
&SE Floresta Drive Engineers, Planners Engineers and Planners
Port Saint Lucie, FL 34983 1925 Prospect Ave. 1925 Prospect Ave.
Orlandd, FL 32814 Orlando, FL 32814
407-661-9100 407-661-9100
Building Area Floor Area
1-Retail : Nonresidential 5831
Additional Efficiency Package
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Envelope Assemblies
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factory.)
Perimeter
Roof 1:Insulation Entirely Above Deck:High Albedo Roof Required,3- 5836 — 40.0 0.025 0.048
Year-Aged Solar Reflectance=0.68,Thermal Emittance=0J83(d),
[Bldg.Use 1 -Retail]
Exterior Wall-Front:Steel-Framed,16"o.c.,[Bldg.Use 1 -Retail] 1607 30.0 0.0 0.079 0.077
Storefront windows-front left:Metal Frame with Thermal BreaIk:Fixed, 330 -- -- 0.270 0.500
Perf.Specs.:Product ID N/A,SHGC 0.40,PF 0.55,[Bldg.Use 1 -
Retail](b)
Storefront spandrel-front left:Metal Frame with Thermal Break:Fixed, 28 -- — 0.270 0.500
Perf.Specs.:Product ID N/A,SHGC 0.00,PF 0.55,[Bldg.Use 1 -
Retail](b)
Storefront windows-front right:Metal Frame with Thermal Break:Fixed, 220 — -- 0.270 0.500
Perf.Specs.:Product ID N/A,SHGC 0.40,PF 1.98,[Bldg.Use 1 -
Retail](b)
• Storefront windows-front clerestory:Metal Frame with Thermal 165 -- -- 0.270 0.500
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,[Bldg.Use 1-
• Retail](b)
Storefront Entry Door:Glass(>50%glazing):Metal Frame,Entrance 42 — — 0.270 0.830
Door,Perf.Specs.:Product ID N/A,SHGC 0.40,PF 0.55,[Bldg.Use 1 -
Retail](b)
Exterior Wall-Left:Steel-Framed, 16"o.c.,[Bldg.Use 1 -Retail] 1230 30.0 0.0 0.079 0.077
Storefront windows-left side:Metal Frame with Thermal Break:Fixed, 14 — -- 0.270 0.500
Perf.Specs.:Product ID N/A,SHGC 0.40,[Bldg.Use 1 -Retail](b)
Exterior door type 1:Insulated Metal,Swinging,[Bldg.Use 1 -Retail] 28 -- -- 0.550 0.610
Exterior door type 3:Insulated Metal,Swinging,[Bldg.Use 1 ,Retail] 42 -- -- 0.550 0.610
Exterior Wall-Rear:Steel-Framed, 16"o.c.,[Bldg.Use 1-Retail] 1520 30.0 0.0 0.079 0.077
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 1 of 10
` I
w
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factoli•)
Perimeter
Storefront windows-rear:Metal Frame with Thermal Break:Fixed,Perf. 57 — — 0.270 0.500
Specs.:Product ID N/A,SHGC 0.40,PF 0.36,[Bldg.Use 1 -Retail](b)
Exterior Wall-Right:Steel-Framed,16"o.c.,[Bldg.Use 1'-Retail] 1185 30.0 0.0 0.079 0.077
Storefront windows-right side-left:Metal Frame with Thermal 99 -- -- 0.270. 0.500
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,PF 4.72,[Bldg.
Use 1-Retail](b)
Storefront windows-right side-right:Metal Frame with Thermal 156 -- -- 0.270 0.500 _
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,PF 1.22,[Bldg. ,
Use 1 -Retail](b)
Storefront spandrel-right side-right:Metal Frame with Thermal 43 — — 0.270 0.500
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.00,PF 1.22,[Bldg. -
Use 1 -Retail](b) '
Storefront windows-right side-clerestory:Metal Frame with Thermal 56 -- — 0.270 0.500
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,[Bldg.Use 1 -
Retail](b)
Exterior door type 2:Insulated Metal,Swinging,[Bldg.Use 1-Retail] 21 — -- 0.550 0.610
Exterior Wall-Angled front/right:Steel-Framed,16"o.c.,[Bldg.Use 1 - 63 30.0 0.0 0.079 0.077
Retail]
Storefront windows-Angled front/right:Metal Frame with Thermal 36 — — 0.270 0.500
Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,PF 1.80,[Bldg. •
Use 1-Retail](b)
Storefront windows-Angled front/right-clerestory:Metal Frame with 10 -- — 0.270 0.500
Thermal Break:Fixed,Perf.Specs.:Product ID N/A,SHGC 0.40,[Bldg.
Use 1 -Retail](b)
Floor 1:Slab-On-Grade:Unheated,[Bldg.Use 1 -Retail](c) 324 -- -- 0.730 0.730
(a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
(d)High albedo roof requirement options:1)3-year aged solar reflectance>=0.55 thermal emittance>=0.75,2)3-year aged solar reflectance
index—64.0,3)Initial year aged solar reflectance>=0.70 thermal emittance>=0.75,4)Initial year aged solar reflectance index>=82.0.
Envelope PASSES: Destgn,JL%better than,code
Envelope Compliance Statement
Compliance Statement. The proposed envelope design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this per applicat' The proposed envelope systems have been
designed to meet the 2014 Florida Building Code, Energy C e ation equi ements in COMcheck Version 4.0.5.1 and to comply
with any applicable mandatory requirements listed in the p tion C ecklist
Rick Zane Smith, R.A. 03/17/2017
Name-Title Si nature Date
�Q•<<G Of
F`OR�O
CO..
CKZANE Sly/Ty 9
AR0010527
RED AR
•
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 2 of 10
Q
i
COMcheck Software Version 4.0.5.1
Inspection Checklist
Energy Code: 2014 Florida Building Code, Energy Conservation
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#' Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 !Plans and/or specifications provide all ;❑Complies ;
[PR1]1 �information with which compliance 1ODoes Not
:can be determined for the building I❑Not Observable;
envelope and document where
exceptions to the standard are QNot Applicable
;claimed.
C402.3.1 ;The vertical fenestration area <=30 ❑Complies
[PR10]1 !percent of the gross above-grade wall 1❑Does Not
;area. �❑I Not Observable
❑Not Applicable
C402.3.1 ;The skylight area <=3 percent of the ;❑Complies
[PR1111 Igross roof area. :,❑Does Not
EjNot Observable;
❑Not Applicable
C402.3.2 I In enclosed spaces> 10,000 ft2 ;E]Complies
[PR14]1 directly under a roof with ceiling E❑Does Not
heights>15 ft. and used as an office,
j lobby, atrium, concourse, corridor, :❑Not Observable
• storage,gymnasium/exercise center, �E]Not Applicable
convention center,automotive
service, manufacturing, non-
(refrigerated warehouse, retail store, I
distribution/sorting area,
transportation, or workshop,the
`following requirements apply: (a)the
daylight zone under skylights is>=
half the floor area; (b)the skylight
area to daylight zone is>=3 percent
with a skylight VT>=0.40; or a
minimum skylight effective aperture
>= 1 percent.
C402.3.2. ;Skylights in office,storage, ;❑Complies
2 !automotive service, manufacturing, :❑Does Not
[PR15]1 in on-refri ge rated warehouse, retail
;store,and distribution/sorting area Not Observable
have a measured haze value>90 ;E]Not Applicable
percent unless designed to exclude
;direct sunlight.
11 High Impact(Tier 1) 12,1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO- F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 3 of 10
.t
Section
• Plan Review A Complies? Comments/Assumptions
&:Req.ID
C402.4.9 ,Ceilings with vented dropped ceiling ;❑Complies ,
[PR16]1 cavities over conditioned spaces have E❑Does Not
a continuous air barrier between the
conditioned space and the vented I❑Not Observable
1 unconditioned space and are sealed to;❑Not Applicable
the air barrier of the walls. Unvented
dropped ceiling cavities over
{conditioned spaces without air barrier I I
between the conditioned and
unconditioned space are sealed from
the exterior environment and adjacent! I
spaces by a continuous air barrier and
is sealed to the air barrier of the walls.
,Unconditioned spaces above separate 1 I
;tenancies contain dividing partitions
between the tenancies to form a
continuous air barrier that is sealed at I
;the ceiling and roof. Building cavities
I designed to be air distribution system
components are sealed according to I
the criteria for air ducts, plenums, etc. ;
in Section C403.2.7. ;
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 4 of 10
a
I
I
Section .,'
• # Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID l
C402.2.6 ,Slab edge insulation R-value. ;❑Complies ;See the Envelope Assemblies table for values.
[FO3]2 ElDoes Not I
;❑Not Observable;
❑Not Applicable
'C303.2' {Slab edge insulation installed per ;❑Complies ;
[FO4]2 .!manufacturer's instructions. ElDoes Not
;❑Not Observable
j❑Not Applicable
C402.2.6 ;Slab edge insulation depth/length. I❑'Complies ;See the Envelope Assemblies table for values.
[FO5]zSlab insulation extending away from ;Oboes Not
• building is covered by pavement or 1❑Not Observable
>= 10 inches of soil.
❑Not Applicable
C408.2.8, I Exterior insulation protected against ;❑Complies
C404.5 !damage,sunlight, moisture,wind, ElDoes Not
[FO6]1 I landscaping and equipment ❑Not Observable;
maintenance activities.
❑Not Applicable
Additional Comments/Assumptions:
I
I
' I
I
I
I
1 High Impact(Tier 1) 1 ,2 IMedium Impact(Tier 2) 13 1 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 5 of 10
I ,
Section
# Framing/Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C402.4.3, ;Factory-built fenestration and doors ;❑Complies
C402.4.4 are labeled as meeting air leakage :❑Does Not
[FR18]3 j requirements.
i ❑Not Observable;
❑Not Applicable
C402.3.3, ;Vertical fenestration U-Factor. ;❑Complies See the Envelope Assemblies table for values.
C402.3.4 ;❑Does Not
[FR8]1 j :[-]Not Observable;
❑Not Applicable
C402.3.3 ;Vertical fenestration SHGC value. ❑Complies ;See the Envelope Assemblies table for values.
[FR10]1 I❑Does Not
;❑Not Observable! -
❑Not Applicable
C303.1.3 'Fenestration products rated in ;❑Complies
[FR12]? accordance with NFRC. ;❑Does Not
;❑Not Observable;
❑Not Applicable
C303.1.3 I Fenestration products are certified as ;❑Complies
[FR13]1 Ito performance labels or certificates :❑Does Not
;provided. I❑Not Observable
❑Not Applicable
C402.2.7 U-factor of opaque doors associated I❑Complies ;See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ElDoes Not
I meets requirements.
❑Not Observable;
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 6 of 10,
f
-Section_.
* # Mechanical Rough-In Inspection Complies? Comments/Assumptions
&Req.ID
'C402.4.5. ,Stair and elevator shaft vents have ;OComplies
1 I motorized dampers that automatically ElDoes Not
[ME3]3 jclose. ;pNotObservable
IE ;ENot Applicable
Additional Comments/Assumptions:
I
I
i
I
I
I
i
•
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy CaICs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 7 of 10
Section
# Insulation Inspection Complies? Comments/Assumptions
&Req.ID
C402.4.1. All sources of air leakage in the I❑Complies ; k +
1 �building thermal envelope are sealed, !❑Does Not
[IN1]1 ;caulked,gasketed,weather stripped 1
or wrapped with moisture vapor- ❑Not Observable
!permeable wrapping material to ,❑Not Applicable
minimize air leakage.
C402.4.2. ;Roof R-value. For some ceiling ;❑Complies ;See the Envelope Assemblies table for values.
1 systems,verification may need to :❑Does Not
[IN2]1 ;occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C303.2, ,Roof insulation installed per ;❑Complies
C407.2.1 !manufacturer's instructions. Blown or E❑Does Not
[IN3]1 ;poured loose-fill insulation is installed
only where the roof slope is <=3 in ❑Not Observable
12. Roof/ceiling insulated to an R- ;❑Not Applicable ;
jvalue of at least R-10. Multiple-family
;residential roofs/ceilings insulated to
an R-value of at least R-19.Where 1
cavities beneath a roof deck are
ventilated,the ceiling is considered
:the envelope component. I I
C402.2.1. ,High-albedo roofs satisfy one of the 1❑Complies
1 1following:3-year-aged solar UDoes Not
[IN5]3 reflectance>=0.55 and thermal
emittance>=0.75,3-year-aged solar ;❑Not Observable
reflectance index>=64.0, initial year :❑Not Applicable
;solar reflectance>=0.70 and thermal
emittance>=0.75, or initial year
solar reflectance index >=82.0. I
C303.2 ;Above-grade wall insulation installed ;❑Complies
[IN7]1 :per manufacturer's instructions. :❑Does Not
❑Not Observable;
❑Not Applicable
C402.2.5 Floor Insulation R-value. ;❑Complies ;See the Envelope Assemblies table for values.
[IN8]2 ;❑Does Not
i ;❑Not Observable I
j❑Not Applicable
C303.1 ;Building envelope insulation is labeled ;❑Complies
[IN10]2 .with R-value or insulation certificate I❑Does Not
providing R-value and other relevant
{data. I❑Not Observable;
I ;❑Not Applicable
C303.2.1 ;Exterior insulation is protected from ;❑Complies
[I1\114]? jdamage with a protective material. !❑Does Not
Verification for exposed foundation
insulation may need to occur during ;❑Not Observable
Foundation Inspection. ;❑Not Applicable
C402.2.1 Insulation intended to meet the roof ;❑Complies
[IN17]3 insulation requirements cannot be PDoes Not
installed on top of a suspended
ceiling. Mark this requirement ❑Not Observable
compliant if insulation is installed 1❑Not Applicable
jaccordingly.
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 12 1 Medium Impact(Tier 2) 13 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 8 of 10.
Section
# Final Inspection _T7__Complies? Comments/Assumptions
& Req.ID
C402.4.6 ;Weatherseals installed on all loading ;❑Complies
[FI37]1 dock cargo doors. ;❑Does Not
❑Not Observable;
❑Not Applicable
C402.4.8 i Recessed luminaires in thermal ;❑Complies
[FI26]3 envelope to limit infiltration and be IC PDoes Not
rated and labeled.Seal between
i interior finish and luminaire housing. ;❑Not Observable
❑Not Applicable
C406 !Efficient HVAC performance,efficient ;❑Complies
[FI34]1 !lighting system,or on-site supply of :❑Does Not
renewable energy consistent with
(what is shown the approved plans. ON
Observable I
❑Not Applicable ;
Additional Comments/Assumptions:
I
i
i
i
I
I
i
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 9 of 10
i
COMcheck Software Version 4.0.5.1
• Interior Lighting Compliance Certificate
Project Information
Energy Code: 2014 Floridal Building Code, Energy Conservation
Project Title: Wawa-FLOC,-F85FB-2150151
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
SW Corner of NE Prima Vista Blvd. Cuhaci Peterson Architects, Cuhaci&Peterson Architects
&SE Floresta Drive Engineers, Planners Engineers and Planners
Port Saint Lucie, FL 34983 1925 Prospect Ave. 1925 Prospect Ave.
Orlando)FL 32814 Orlando, FL 32814
407-661i 9100 407-661-9100
Additional Efficiency Package
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts 1 ft2 (B X C)
1-Retail 5831 1.30 7580
Total Allowed Wafts= 7580
Proposed Interior Lighting Power
A B C D E
Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Retail
AL1/AL1 E:AL1/AL1 E:Wet Loc.Sfc.Mnt.Linear LED:LED Linear 15W: 1 5 15 75
DL1/DL1E:DL1/DL1E:Recessed 6"LED Downlight:LED Other Fixture Unit 28W: 1 22 30 660
DL3/DL3E:DL3/DL3E:Recessed 4"LED Downlight:LED Other Fixture Unit 28W: 1 9 30 270
GL1/GL1 E:GL1/GL1 E:Recessed 2x2 LED:LED Other Fixture Unit 36W: 1 57 37 2109
GL3/GL3E:GL3/GL3E:Recessed 2x4 LED:LED Other Fixture Unit 40W- 1 15 40 600
GL5/GL5E:GL5/GL5E:Recessed 2x6 LED:LED Other Fixture Unit 46W: 1 1 44 44
HL:HL:Vapor Tight LED Sfc.Mnt.:LED Other Fixture Unit 28W: 1 2 30 60
LL1:1-1-1:4'Rec.linear LED wallwasher:LED Other Fixture Unit 36W: 1 7 38 266
P1:P1:Pendant with(1)LED:LED PAR 15W: 1 3 14 43
P2:P2:Pendant with(3)compact fluor.:Twin Tube 18W:Electronic: 3 4 80 320
P3:PI 48"Pendant with(3)CFL bulbs:Twin Tube 24/26/27W:Electronic: 3 1 80 80
SH/SHE:SH/SHE:4'Vaportight linear LED:LED Linear 33W:, 1 7 49 343
SL1:SL1:4'LED Wall Grazer:LED Other Fixture Unit 6.5W: 4 6 34 204
Total Proposed Watts= 5074
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 1 of 9
:Interioro a ■- be e -
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2014 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.0.5.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
jaison P. Moras, P.E. 03/17/2017
Name-Title Signature �����I��ti Date
`��``
,���. �'\G E N SF!Llp�,�'
��;• No 76 •�,yN
:cc=
�:• ST E OF •:4U
%
not
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 2 of 9
, I
i
A COMcheck Software Version 4.0.5.1
• Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2014 Florida,Building Code, Energy Conservation
Project Title: Wawa-FLO'-F85FB-2150151
Project Type: New Construction
Exterior Lighting zone .4(High activity metropolitan commercial district)
Construction Site: Owner/Agent: Designer/Contractor:
SW Corner of NE Prima Vista Blvd. .Cuhaci Peterson Architects, Cuhaci&Peterson Architects
&SE Floresta Drive Engineers, Planners Engineers and Planners
Port Saint Lucie, FL 34983 1925 Prospect Ave. 1925 Prospect Ave.
Orlando,IFL 32814 Orlando, FL 32814
Allowed Exterior Lighting Power 407-661-I9100 407-661-9100
A II B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts/Unit Wattage (B X C)
Overhangs at entry doors and seating area(Entry canopy) 1136 ft2 0.4 Yes 454
Exterior wall lighting(illuminated area of facade wall or surface) 2463 ft2 0.2 No 493
Total Tradable Watts(a)= 454
Total Allowed Watts= 947
Total Allowed Supplemental Watts(b)= 1300
(a)Wattage tradeoffs are only allowed between tradable are
(b)A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
Fixture ID: Description I Lamp I Wattage Per Lamp I Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Overhangs at entry doors and seating area(Entry canopy 1136 ft2):Tradable Wattage
DL2/DL2E:DL2/DL2E:Recessed 4.5"LED Downlight:LED PAR 20W: 1 5 20 100
DL7/DL7E:DL7/DL7E:Wet Loc.Rec.6"LED Downlight:LEDI Other Fixture Unit 28W. 1 28 30 840
Exterior wall lighting(Illuminated area of facade wall or surface 2463 ft2): Non-tradable Wattage
EL1:EL1:Wet Loc.LED string 1.5 w/ft:LED Other Fixture Unit 95W: 1 100 2 150
EL2:EL2:Wet Loc.LED Strip:LED Other Fixture Unit 6.5W: 1 6 8 45
EL3:EL3:Wet Loc.LED Strip:LED Other Fixture Unit 6.5W: 1 1 23 8 172
WC1:WC1:Decorative LED Wall Sconce:LED Other Fixture Unit 13W: 1 4 13 52
Z1:Z1:Wall Mtd.Ext.Area LED:Other: 1 5 35 175
Total Tradable Proposed Watts= 940
Exterior- . . -A Desigm 43% better than cocle
Exterior Lighting Compliance Statement
Compliance Statement. The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed exterior lighting systems have been
designed to meet the 2014 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.0.5.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calc's\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 3 of 9
t
I
I
I
Jaison P. Moras, P.E. 03/17/2017
Name-Title Signature 011111111i111 Date
%%% QF\ApEEP i���i
`.`\ Ns1p9�'
No 17
:O•.• ATE OF •:��/
nn
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 4 of 9.
i
f
COMcheck Software Version 4.0.5.1
' - Inspection .Checklist
8/1 1
Energy Code: 2014 Florida Building Code, Energy Conservation
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is'provided by the user in the COMcheck Requirements screen. For each
requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
A Re .ID
C103.2 !Plans,specifications,and/or ;❑Complies
[PR4]1 calculations provide all information !❑Does Not
with which compliance can be
determined for the interior lighting j❑Not Observable
land electrical systems and equipment 1❑Not Applicable
land document where exceptions to
;the standard are claimed. Information ;
provided should include interior I I
lighting power calculations,wattage of I
bulbs and ballasts,transformers and I
I control devices. I
C103.2 Plans,specifications, and/or ;❑Complies I
[PR8]1 !calculations provide all information ;❑Does Not
with which compliance can be I
determined for the exterior lighting ❑Not Observable
.and electrical systems and equipment IF-]Not Applicable
and document where exceptions to
;the standard are claimed. Information
I provided should include exterior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
I control devices.
Additional Comments/Assumptions: I
• 1 High Impact(Tier 1) 12 .1 M'edium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 i Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 5 of 9
Section
# Rough-In Electrical Inspection. Complies? Comments/Assumptions
&.Req.lp
C405.2.2. ;Automatic controls to shut off all I❑Complies
'1 1 building lighting installed in all ElDoes Not
[EL22]2 , !buildings. ;❑Not Observable
i( ;❑Not Applicable
C405.2.1. ;Independent lighting controls installed ;❑Complies ;
1 per approved lighting plans and all ❑Does Not '
[EL23]? manual controls readily accessible and;❑Not Observable;
visible to occupants. ;
;❑Not Applicable ;
C405.2.1. ;Lighting controls installed to uniformly ❑Complies ; +
2 reduce the lighting load by at least ❑Does Not
[EL15]1 50%. ;❑Not Observable
❑Not Applicable
C405.2.2. Daylight zones provided with ;❑Complies ;
3 individual controls that control the E❑Does Not
[EL16]z lights independent of general area ; ;
lighting. :❑Not Observable
;❑Not Applicable
C405.2.3 Sleeping units have at least one ;❑Complies ;
[EL17]3 master switch at the main entry door :❑Does Not
(that controls wired luminaires and I
;switched receptacles. ❑Not Observable
;❑Not Applicable ;
C405.2.2. ;Occupancy sensors installed in ;❑Complies
2 required spaces. ;❑Does Not
[EL18]1 I;❑Not Observable;
❑Not Applicable
C405.2.2. !,Primary sidelighted areas are 1❑Complies ;
3 !equipped with required lighting ;❑Does Not
[EL20]1 'controls. , I
;❑Not Observable;
I ;❑Not Applicable
C405.2.2. I Enclosed spaces with daylight area '❑Complies ;
3 under skylights and rooftop monitors :❑Does Not _
[EL21]1 ;are equipped with required lighting ❑Not Observable;
controls. I
;❑Not Applicable
C405.2.4 ,Automatic lighting controls for exterior;❑Complies ;
[EL25]2 I lighting installed. UDoes Not
1 I I
i ;❑Not Observable
❑Not Applicable
C405.2.3 ;Separate lighting control devices for ;❑Complies
[EL4]1 ispecific uses installed per approved :❑Does Not
11ighting plans.
;❑Not Observable;
❑Not Applicable
C405.3 ;Fluorescent luminaires with odd I❑Complies ;
[EL19]3 !'numbered lamp configurations that !❑Does Not
I are within 10 feet center to center(if
recess mounted)or are within 1 foot �❑Not Observable
edge to edge(if pendant or surface ❑Not Applicable
mounted)shall be tandem wired. ;
C405.4 Exit signs do not exceed 5 watts per '❑Complies ;
[EL6]1 'face. 1❑Does Not
❑Not Observable;
❑Not Applicable
1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 13 1 Low Impact(Tier 3) -y
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 6 of 9,
' K
Section
# I Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
` C405.6 ;Exterior grounds lighting over 100 W IElComplies
[EL24]1 provides>60 Im/W unless on motion ElDoes Not
sensor or fixture is exempt from scope
of code or from external LPD. ❑Not Observable I
❑Not Applicable
C405.2.3 ;Additional interior lighting power ;❑Complies
[EL8]1 allowed for special functions per the :❑Does Not
approved lighting plans and is :[-]Not Observable
;automatically controlled and
separated from general lighting. ;❑Not Applicable
Additional Comments/Assumptions:
I
i
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 7 of 9
Section
# Final Inspection Complies? . Comments/Assumptions -
&Req.113
C408.2.5. ,Furnished as-built drawings for ;❑Complies i .
1 electric power systems within 30 days UDoes Not
{FI16]3 of system acceptance.
❑Not Observable
j ;❑Not Applicable
C303.3, Furnished O&M instructions for ;❑Complies
C408.2.5. !systems and equipment to the T❑Does Not
2 I building owner or designated
[F[17]3 representative. I❑Not Observable
❑Not Applicable
C405.5.2 Interior installed lamp and fixture ;❑Complies ;See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what :❑Does Not _
is shown on the approved lighting ;
plans, demonstrating proposed watts ❑Not Observable
,are less than or equal to allowed ;❑Not Applicable ;
watts.
C405.6.2 I Exterior lighting power is consistent ;❑Complies ;See the Interior lighting fixture schedule for values.
[FI19]1 :with what is shown on the approved ❑Does Not
!lighting plans,demonstrating
proposed watts are less than or equal ;❑Not Observable
Ito allowed watts. ;❑Not Applicable
C4083 !Lighting systems have been tested to ;❑Complies
[FI33]1 'ensure proper calibration,adjustment, !❑Does Not
programming,and operation. ;
❑Not Observable,
❑Not Applicable
C408.3 I Lighting systems have been tested to I❑Complies
[FI48]1 :ensure proper calibration,adjustment, 1❑Does Not
programming,and operation.
❑Not Observable;
El Not Applicable
C406 ;,Efficient HVAC performance,efficient ;❑Complies
[FI34]1 1 lighting system,or on-site supply of :❑Does Not
!renewable energy consistent with ;
;what is shown the approved plans. ❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 8 of 9.
r
I
COMcheck Software Version 4.0.5.1
• Mechanical Compliance Certificate
Project Information
I
Energy Code: 2014 Florida Building Code, Energy Conservation
Project Title: Wawa-FLO L F85FB-2150151
Location: Port Saint Lucie, Florida
Climate Zone: 2a
Project Type: New Construction
I
I
Construction Site: Owner/Agent: Designer/Contractor:
SW Corner of NE Prima Vista Blvd. Cuhaci Peterson Architects, Cuhaci&Peterson Architects
&SE Floresta Drive Engineers, Planners Engineers and Planners
Port Saint Lucie, FL 34983 1925 Prospect Ave. 1925 Prospect Ave.
Orlando, FL 32814 Orlando, FL 32814
407-661-9100 407-661-9100
Additional Efficiency Package
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Mechanical Systems List
Quantity System Type&Description
1 HVAC System RTU-1 (Single Zone):
Cooling:1 each-Single Package DX Unit,Capacity=72 kBtu/h,Air-Cooled Condenser,No Economizer,Economizer exception:
Humidity Requirements
_ Proposed Efficiency=12.00 EER,Required Efficiency: 11.20 EER(11.4 IEER)
Fan System: FAN SYSTEM 11 RTU-1 —Compliance(Motor nameplate HP method):Passes
Fans:
• FAN 1 Supply,Constant Volume,4185 CFM,3.0 imotor nameplate hp
I
1 HVAC System RTU-2(Single Zone): I
Cooling:1 each-Single Package DX Unit,Capacityl=102 kBtu/h,Air-Cooled Condenser,No Economizer,Economizer exception:
Humidity Requirements I
Proposed Efficiency=12.40 EER,Required Efficiency: 11.20 EER(11.4 IEER)
Fan System: FAN SYSTEM 2 1 RTU-2—Compliance(Motor nameplate HP method):Passes
i
Fans:
FAN 2 Supply,Constant Volume,4710 CFM,5.0 motor nameplate hp
EF 1 Exhaust,Constant Volume,590 CFM,0.1 motor nameplate hp
1 HVAC System RTU-3(Single Zone):
Cooling:1 each-Single Package DX Unit,Capacity 172 kBtu/h,Air-Cooled Condenser,No Economizer,Economizer exception:
• Humidity Requirements
Proposed Efficiency=12.00 EER,Required Efficiency: 11.20 EER(11.4 IEER)
Fan System: FAN SYSTEM 3 1 RTU-3—Compliance,(Motor nameplate HP method):Passes
Fans:
FAN 3 Supply,Constant Volume,4500 CFM,3.0 motor nameplate hp
EF 2 Exhaust,Constant Volume,60 CFM,0.0 motor nameplate hp
1 Water Heater 1:
Electric Storage Water Heater,Capacity:50 gallons w%Circulation Pump
Proposed Efficiency:0.86 EF,Required Efficiency:6.86 EF
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 1 of 12
i
Mechanical Compliance Statement
Compliance Statement. The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2014 Florida Building Code, Energy Conservation r ents in COMcheck Version 4.0.5.1 and to comply
with any applicable mandatory requirements listed in the Inspection ecklist.
Jose J. Diaz-Velazquez, P.E. r 03/17/2017
Name-Title Signature \\\\I\I I I I Date
-Oel
'.lam
No.78474 _
=13
STATE OF �to�
�ZORIDP . ' N
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 2 of 12.
I
_ COMcheck Software Version 4.0.5.1
Inspection Checklist
p , -
Energy Code: 2014 Florida Building Code, Energy Conservation
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review f Complies? Comments/Assumptions
& Reg.ID
C103.2 !Plans,specifications, and/or I❑Complies
[PR2)1 !calculations provide all information UDoes Not
with which compliance can be
determined for the mechanical �❑Not Observable
!systems and equipment and T❑Not Applicable
document where exceptions to the
standard are claimed. Load
i
calculations per acceptable
I engineering standards and
Ihandbooks.
C103.2 Plans,specifications, and/or I❑Complies
[PR3)1 !calculations provide all information I❑Does Not
jwith which compliance can be
determined for the service water ,❑Not Observable
heating systems and equipment and ❑ of Applicable
document where exceptions to the
standard are claimed. Hot water
:system sized per manufacturer's I
:sizing guide.
Additional Comments/Assumptions:
i
I
1 High Impact(Tier 1) 12 1 Medium Impact(Tier 2) 13 1 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 3 of 12
Section
# -Footing/Foundation Inspection Complies? Comments/Assumptions.
&,Req.ID "
C403.2.4. ;Freeze protection and snow/ice ;❑Complies
5 1 melting system sensors for future ;❑Does Not
[FO9]3 j connection to controls.
❑Not Observable;
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2. Medium Impact(Tier 2) 13'1 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 4 of 12.
Section
• # Plumbing.Rough-In Inspection I Complies? Comments/Assumptions
Req.ID
` C404.3 Temperature controls installed on ;❑Complies
[PL5]3 i service water heating systems(110 F �❑Does Not
.for dwelling units and lavatories in ONot Observable;
occupancies.)
public restrooms and 90 F for other ,�Not Applicable
I
C404.4 ;Automatic time switches installed to ;❑Complies
[PL3]1 automatically switch off the !❑Does Not
recirculating hot-water system or heat;
trace. :❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
I
I
I
1 High Impact(Tier 1) J 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 5 of 12
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
&Req.ID -
C403.2.3 ,HVAC equipment efficiency verified. ;❑Complies ;See the Mechanical Systems list for values.
[ME55]2' ;❑Does Not
;❑Not Observable
❑Not Applicable
C403.2.5. Demand control ventilation provided ;❑Complies ;
1 !for spaces>500 sq.ft. and >25 PDoes Not
[ME59]1 people/1000 sq.ft. occupant density {❑Not Observable
and served by systems with air side ;
economizer,auto modulating outside ;❑Not Applicable
air damper control,or design airflow
>3,000 cfm. ;
C403.2.7. HVAC ducts and plenums insulated 1❑Complies ;
1 and sealed according to Florida ❑Does Not
[ME60]2 ;Section C403.2.7,Table C403.2.7.1, ❑Not Observable
;Table C403.2.7.2. ;
❑Not Applicable ;
C403.2.7. All ducts,air handlers,filter boxes, ❑Complies ;
2 , building cavities, mechanical closets T❑Does Not
[ME79]2
and enclosed support platforms that
form the primary air containment I❑Not Observable
passageways for air distribution ;❑Not Applicable ;
systems are constructed and erected
j in accordance with Table C403.2.7.2
and with Chapter 6 of the Florida 1
Building Code, Mechanical. Ducts are
be constructed, braced, reinforced
and installed to provide structural I
;strength and durability.All transverse
joints, longitudinal seams and fitting
connections are securely fastened in
accordance with the applicable
i standards of this section. ;
C403.2.7. Duct insulation is protected from ;❑Complies ;
1.2 damage but not limited to the :❑Does Not
[ME80]2 following: 1. Insulation exposed to
weather is suitable for outdoor ❑Not Observable
service.Cellular foam insulation is ;❑Not Applicable ;
protected or painted with a coating
that is water retardant and provides
shielding from solar radiation. 2.
Insulation covering cooling ducts
located outside the conditioned space
is vapor retardant located outside the 1 ;
insulation,all penetrations and joints
of which shall be sealed.
C403.2.7.,,Additional insulation with vapor ;❑Complies ;
1.3 barrier is provided where the :❑Does Not
[ME81]2 , minimum duct insulation requirements;
of Section C403.2.7.1.1 are ❑Not Observable
I determined to be insufficient to 1❑Not Applicable
`prevent condensation. j
,
C403.2.8. Piping Insulation exposed to weather ;❑Complies
1 is protected from damage(due to sun,1❑Does Not
[ME7]3 !moisture,wind, etc.). i
;❑Not Observable;
El Not Applicable
C403.2.8 !Thermally ineffective panel surfaces of;❑Complies ;
[ME41]3 sensible heating panels have I❑Does Not
insulation >= R-3.5. ;❑Not Observable;
i ;❑Not Applicable
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3) -.
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Ca1cs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 6 of 12.
'Section
• # Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C403.2.7. ;Ducts, air handlers,filter boxes, ;OComplies ;
3 I building cavities, mechanical closets 1ODoes Not
[ME10]2 and enclosed support platforms that 10Not Observable
form the primary air containment
passageways for air distribution ❑Not Applicable
systems are sealed in accordance with
• ;the applicable criteria of this section
and Table C403.2.7.2. I 1
C403.2.7. Air distribution systems are sized and I❑Complies ;
5 !designed in accordance with j❑Does Not
[ME76]2 jrecognized engineering standards. ❑Not Observable;
Refer to section details.
j;❑Not Applicable
C403.2.7. ,Air-handling units not installed in i 1❑Complies
6 attics of commercial buildings. :❑Does Not
[ME77]2 i I UNot Observable
;❑Not Applicable
C403.2.7. ;Cavities in framed spaces are not ; ;❑Complies
4 1 used to deliver air from or return air to I❑Does Not
[ME78]2 the conditioning system unless they I❑Not Observable
contain an air duct insert which is
I insulated in accordance with Section 1❑Not Applicable
C403.2.7.1 and constructed and
sealed in accordance with the
requirements of Section C403.2.7.2
i appropriate for the duct materials
;used.
C403.2.7. I Ductwork operating>3 in.water ;❑Complies ;
1.3 E column requires air leakage testing; E❑Does Not
[MEll]3 C ;❑Not Observable;
❑Not Applicable
C403.2.7. 'Ductwork operating >3 in.water ;❑Complies
1.3 i column requires air leakage testing. :❑Does Not
[ME11]3 ❑Not Observable
❑Not Applicable
C403.2.7. Ductwork operating >3 in. water ;❑Complies
1.3 column requires air leakage testing. !❑Does Not
[ME11]3 ;❑Not Observable;
j ;❑Not Applicable
C4033.1, ;Air economizers provided where 1❑Complies
C403.3.1. !required, meet the requirements for I❑Does Not
1 ;design capacity,control signal,
[ME62]1 ventilation controls, high-limit shut-off, ❑Not Observable
integrated economizer control, and ;❑Not Applicable ;
provide a means to relieve excess
outside air during operation.
C403.3.1, ;Air economizers provided where 10Complies 1
C403.3.1. !required, meet the requirements for :❑Does Not
1 ;design capacity, control signal, ❑Not Observable
[ME62]1 ventilation controls, high-limit shut-off,1❑Not Applicable
1 integrated economizer control,and I PP
provide a means to relieve excess
outside air during operation.
C403.3.1, ;Air economizers provided where ;❑Complies ;
C403.3.1. required, meet the requirements for :❑Does Not
1 :design capacity,control signal, ;❑Not Observable;
[ME62]1 ;ventilation controls, high-limit shut-off,;
integrated economizer control,and 10Not Applicable
provide a means to relieve excess
outside air during operation.
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 7 of 12
R
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions ,
& Req.ID
C408.2.2. ,Air outlets and zone terminal devices I❑Complies '
1 11 have means for air balancing. ;❑Does Not
[ME53]3 I ;❑Not Observable
;❑Not Applicable
C403.4.2 VAV fan motors>=7.5 hp to be driven;❑Complies
[ME66]2 i by variable speed drive, have a vane- I❑Does Not
axial fan with variable pitch blades,or
have controls to limit fan motor �❑Not Observable
demand. ;❑Not Applicable _
C403.4.2 ;VAV fan motors>=7.5 hp to be driven;❑Complies
[ME66]2 by variable speed drive, have a vane- ![:]Does Not
axial fan with variable pitch blades,or
have controls to limit fan motor ❑Not Observable
.demand. ;❑Not Applicable
C403.4.2 'VAV fan motors>=7.5 hp to be driven;❑Complies
[ME66]2 +by variable speed drive, have a vane- ElDoes Not
,axial fan with variable pitch blades,or,have controls to limit fan motor ;❑Not Observable
;demand. ❑Not Applicable
C403.4.2 VAV fan motors>=7.5 hp to be driven;❑Complies
[ME66]2 by variable speed drive, have a vane- :❑Does Not
axial fan with variable pitch blades, or
have controls to limit fan motor I❑Not Observable
demand. ;❑Not Applicable
C403.2.6 Exhaust air energy recovery on ❑Complies
[ME57]1 !systems meeting Table C403.2.6 El Does Not
1
❑Not Observable;
❑Not Applicable
C403.2.111 Unenclosed spaces that are heated ;❑Complies
[ME71]2 'use only radiant heat. ;❑Does Not
❑Not Observable;
❑Not Applicable
Additional Comments/Assumptions: ,
11 High Impact(Tier 1) 12 1 Medium Impact(Tier 2) 13 1 Low Impact(Tier 3) --
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 8 of 12.
Section ,
• # Final Inspection Complies? Comments/Assumptions
&Req.10
C403.2.4. !Heating and cooling to each zone is I❑Complies ;
1 controlled by a thermostat control. E❑Does Not
[FI47]3 i ;❑Not Observable
❑Not Applicable
C403.2.4. !,Heating and cooling to each zone is ;❑Complies
" 1 !controlled by a thermostat control. E❑Does Not
[F[47]3
;❑Not Observable;
❑Not Applicable
C403.2.4. !Heating and cooling to each zone is ❑Complies ;
1 controlled by a thermostat control. E❑Does Not
[FI47]3 I ❑Not Observable
❑Not Applicable
C403.2.4. ;Minimum one humidity control device ;❑Complies
3.4 1 per installed :❑Does Not
[FI51]3 I humidification/dehumidification
{system.Controls prevent !❑Not Observable;
!simultaneous operation of ;❑Not Applicable
;humidification and dehumidification
equipment. ;
C403.2.4. ;Minimum one humidity control device ;❑Complies
3.4 ;per installed :❑Does Not
[FI51]3 humidification/dehumidification t❑Not Observable
system.Controls prevent
Isimultaneous operation of ;❑Not Applicable ;
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device ;❑Complies
3.4 f per installed ;❑Does Not
[FI51]3 humidification/dehumidification
(system.Controls prevent ❑Not Observable
simultaneous operation of ❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. ,Thermostatic controls have a 5 "F ;❑Complies ;
2 i deadband. ;❑Does Not
[F[38]3
f ;❑Not Observable;
❑Not Applicable
C403.2.4. ;Temperature controls have setpoint ;❑Complies ;
2 1 overlap restrictions. 1❑Does Not
[FI20]3 I
;❑Not Observable;
❑Not Applicable
C403.2.4. I Each zone equipped with setback ;❑Complies ;
3 controls using automatic time clock or E❑Does Not
[FI39]3 ,programmable control system. ❑Not Observable;
El Not Applicable
C403.2.4. JAutomatic Controls: Setback to 55°F I❑Complies
3 f(heat)and 85°F (cool); 7-day clock, 2- 1ODoes Not
[F[40]3 ,hour occupant override, 10-hour
backup ,❑Not Observable
❑Not Applicable
C403.2.4. Systems include optimum start ;❑Complies ;
3.3 1 controls. ;❑Does Not
[FI41]3 ;❑Not Observable;
❑Not Applicable
1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 9 of 12
r �
Section
# Final Inspection Complies? Comments/Assumptions
&Req.ID
C403.2.4. ;Systems include optimum start ;❑Complies
3.3 controls. ;❑Does Not
[FI41]3 i
I❑Not Observable;
E ;❑Not Applicable
C403.2.4. ;Systems include optimum start ;❑Complies
3.3 (controls. ;❑Does Not
[F[41]3 I -
fE ❑Not Observable
❑Not Applicable
C408.2.5. ;Furnished HVAC as-built drawings. ;❑Complies ;
1 submitted within 90 days of system UDoes Not
[FI7]3 acceptance. -
❑Not Observable
❑Not Applicable
C303.3, ;Furnished O&M manuals for HVAC I❑Complies ;
C408.2.5. systems within 90 days of system ElDoes Not
3 !acceptance. i
[F[8]3 1❑Not Observable
;❑Not Applicable
C408.2.5. ;An air and/or hydronic system ❑Complies
3 1 balancing report is provided for HVAC I❑Does Not
(FI43]1 ;systems.
❑Not Observable
;❑Not Applicable
C408.2.3. ;HVAC control systems have been ;❑Complies
2 !tested to ensure proper operation, ❑Does Not
[FI10]1 ;calibration and adjustment of controls.
❑Not Observable
❑Not Applicable
C404.8.2. I Public lavatory facilities equipped with ❑Complies
[F[53]3 !outlet devices which limit the flow of ❑Does Not
hot water to a maximum of 0.5 gpm or; ;
are equipped with self-closing valves ;❑Not Observable
that limit delivery to a per cycle 1❑Not Applicable ;
III maximum of 0.25 gallons of hot water
;for recirculating systems and to a -
maximum of 0.50,gallons for non- 1
recirculating systems. ;
C404.8.2 ,Public lavatory water temperature I❑Complies
[FI11]3 <=110°F. ;❑Does Not
j ;❑Not Observable
❑Not Applicable
C404.8.1 !Showers used for non-safety reasons ;❑Complies
[F152]3 !equipped with flow control devices to T❑Does Not
limit the water discharge to a
maximum of 2.5 gpm per shower I❑Not Observable
I head. Flow restricting inserts used as I❑Not Applicable
a component part of a showerhead
;are mechanically retained at the point
of manufacture I I
C408.2.2 An air and/or hydronic system ;❑Complies
(F154]3 balancing report is provided for HVAC !❑Does Not
systems serving zones>5,000 ft2 of ; ;
conditioned area. Refer to section for ;❑Not Observable
full details. ;❑Not Applicable ;
C404.5 JAII piping in circulating system ;❑Complies
[FI25]2 insulated ;❑Does Not
❑Not Observable
❑Not Applicable
1 1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 10 of 12.
Section
- # Final Inspection Complies? Comments/Assumptions
&Req.ID
' C404.6 Controls are installed that limit the I❑Complies ;
[F[12]3 operation of a recirculation pump ElDoes Not
I installed to maintain temperature of a ; I ;
storage tank. UNot Observable
❑'Not Applicable
C403:2.1 I HVAC systems and equipment design ;❑Complies
(F150]3 loads calculated in accordance with ElDoes Not
ANSI/ASHRAE/ACCA Standard 183 or 1
183 or ACCA Manual N and shall be ❑Not Observable
attached to the code compliance form ❑Not Applicable ;
;submitted to the building department
when the building is permitted or, in ;
the event the mechanical permit is
obtained at a later time,the sizing
calculation shall be submitted with the
iapplication for the mechanical permit.
C403.2.2 HVAC systems and equipment ;❑Complies ;
[F127]3 capacity does not exceed calculated UlDoes Not
loads. 1
;❑Not Observable;
❑Not Applicable
C408.2.1 ;Commissioning plan developed by ;❑Complies ;
[FI28]1 registered design professional or :❑Does Not
;approved agency. ;
,❑Not Observable,
❑N'ot Applicable
C408.2.4 Preliminary commissioning report I❑Complies ;
[FI29]1 !completed and certified by registered {❑Does Not
;design professional or approved
❑Not Observable,
!agency. 1ONot Applicable
C408.2.5. !,Final commissioning report due to ;❑Complies ;
4 !building owner within 90 days of 1❑D6es Not
[F130]1 !receipt of certificate of occupancy.
! ,❑Not Observable,
;❑Not Applicable
C408.2.3. ;HVAC equipment has been tested to ;❑Complies
1 ensure proper operation. ;❑Does Not
[FI31]1 ;❑Not Observable;
❑Not Applicable
C408.2.3. ;Economizers have been tested to ;❑Complies ;
3 ensure proper operation. ;❑Does Not
[FI32]1 !
❑Not Observable
;❑Not Applicable
C406 !Efficient HVAC performance,efficient ;❑Complies ;
(F134]1 !lighting system, or on-site supply of 1❑Does Not
I renewable energy consistent with ❑Not Observable;
;what is shown the approved plans. ;
;❑Not Applicable
Additional Comments/Assumptions:
r
1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Wawa-FLO-F85FB-2150151 Report date: 03/15/17
Data filename: W:\2015\2150151\HVAC Calcs\Energy Calcs\F85-FB-v2017.01-(FL)_2014 IECC.cck Page 11 of 12