APPLICATION FOR BUILDING PERMIT REVISIONS
PROJECT INFORMATION
LOCATION/SITE
ADDRESS:
260 SE Prima Vista Blvd (SW corner SW Prima Vista Blvd and Floresta Drive)
DETAILED DESCRIPTION OF PROJECT
REVISIONS:
Signed and sealed shop drawings for structural steel members, reviewed by DP of Record
CONTRACTOR INFORMATION:
STATE of FL REG./CERT. #: CGCO61217
BUSINESS NAME: Hooks Construction Co
QUALIFIERS NAME: Steven C. Hooks
ADDRESS: 2211 S. Kanner Highway
CITY: Stuart STATE. FL
PHONE (DAYTIME): 772-419-8828
OWNER/BUILDER INFORMATION:
NAME: Wawa Florida LLC
ADDRESS: 7022 TPC Drive, Suite 200
CITY: Orlando
PHONE (DAYTIME: 610-358-8000
ST. LUCIE CO CERT. #:
ZIP: 34994
FAX: 772-237-3757
STATE: FL
FAX:
ARCHITECT/ENGINEER INFORMATION:
NAME: Cuhaci & Peterson
ADDRESS: 1925 Prospect Avenue
CITY: Orlando
PHONE (DAYTIME): 407-661-9100
SLCCC: 9123109
Revised 06130117
ZIP: 32822
STATE: FL ZIP: 32814
FAX: 407-661-9101
RFct7ft
MAR '6 Iola
Permitting be
St. Lucie cou � ent
STEELTEC
3901 Roswell Rd., Suite 111 SHT: CS page 1 of 5
Marietta, GA 30062 Date 3-23-18
770-505-5917 BY: RB
Client: Wawa #5220-FLO
Description: Wawa Canopy -Laminated Gutter Support Panel Structural
Calculations
Steeltec Job, Wawa #5220-FLO-Port ST. Lucie, ST. Lucie County, FL
Roof Load: 20 PSF Live Load
3 PSF Panel Dead Load
Wind Load: Risk Category II, 170 MPH, EXP. C, 3 Sec Gust
Steel Deck-ASTM A653 GR. 50- Fy-- 50.0 ksi
References:
-2017 Florida Building Code 6th Edition (2017 FBC)
-2015 International Building Code (2015 IBC)
-ASCE 7-10 Minimum Design Loads for Buildings and Other Structures
-AISC Manuel of Steel Construction — 14th Edition
-AISI Specification for the Design of Cold Formed Steel Structural Members-2007
Edition
(UReviewed, ❑ Furnish as Corrected
No Comments 0 Revise and Resubmit
❑ Rejected
❑ Submit Specific Item
This review is only ror general con1hrmance
with the desigit coma-pt or the prgjcet and
general compliance with the information
given in the Gmtrod Documents. Corrections
or comments made on the shop drawings
during the review do not relieve contractor
from complianve with the requirements or
the plans and specifications. Apprnval of a
specific item aludl not include approval or on
assembly of which ttxe item is a component.
Contractor is responxible for: dimensions to
be confirmed and correlated at the Jo�ite;
Information that pertains solely W the
fabrication procc"e,. or to the meets,
methods, techniques, sequences, and
procedures or construction; coordination of
the Work with that of all trades; and for
performing all work in a rife and satisfactory
CURACI & PETERSON ARCHITECTS, LLC
Date 3 u l8sy i"
_Z_
Z.No. 507 1 * =
� I
t', STATE OF
p��s,FLOR,OP,,C-4
161
MAR 2 3 `2010
STEELTEC-
SHT: 2 of 5
' DATE:3-23-18
BY: RB
Description: Wawa Canopy -Laminated Roof Panel
Laminated Panel Analysis
2" Laminated Panel @ Gutter Dead Load = 3 psf
Span = 6'-3"
Components & Cladding Wind Load for Open Building — Table 30.8-1
Step 1 : Risk Category II per Table 1.5-1
Step 2 : Charlotte County —170 mph wind speed per FBC
Step 3: Kd = 0.85 per table 26.6-1
Exposure "C" per Section 26.7
Kzt =1.0 per Figure 26.8-1
Gust Effect Factor G = 0.85 per Section 26.9
Step 4: Kz = 0.90 per Table 30.3-1
Step 5: Qh = (0.00256)(Kz)(Kd)(V)2 = Qh = (0.00256)(0.90)(1.0)(0.85) )(170)2= 56.6 Equation
30.3-1
Step 6:= Determine Factor Cn: Monoslope Roof per Fiqure 30.8-1.
Roof Slope = 2:12 = 9.46 degrees
By Extrapolation, Cn = +1.65 or -1.53
Step 7: Wind Pressure per Eq. 30.8-1 p= (Qh)(G)(Cn)
Positive Pressure: p=(56.6 pdf)(0.85)(1.65) = 79.4 psf
Negative Pressure: = p = (56.6)(0.85)(-1.53) _ -73.6 psf
n
STEELTEC
SHT: 3 OF 5
DATE: 3-23-18
BY: RB
DESCRIPTION: WAWA CANOPY -LAMINATED ROOF PANEL
LAMINATED PANEL ANALYSIS
2" Laminated Panel @ Gutter Dead Load = 3 psf
Span 6'-3"
Combination Loads: LL = 20 psf DL = 3 psf
Combination A: (0.6)(DL)+(0.6)WL)= (0.6)(3.Opsf)+(0.6)(-73.6psf)= -42.4 psf
Combination B: DL + (0.75) [(0.6)(LL)+WL]= 3 psf + (0.75)[ (0.6)(79.4 psf) + 20 psf] = 53.73
psf.
53.73 psf > 42.4 psf thus Combination B indicates:
Per Attached Tables, MAX. Allowable Pressure for 6'-3" is 54 psf.
Table is for "externally" imposed load, thus it does not include the DL
Dead Load + Table Load = 57 psf for 6'-3"
57 psf > 53.73 psf
Thus: 2" Laminated Panel is Satisfactory.
Sieel.
Engineered Composite Panels, INC
A member of the Image Resource Group
19
""ET COVERAGE�
24
GA F AC E —°
2" POLYSTYRENE
11
Sheet ' 4 ,of 5
iy
24-CA BACKER
CORE —STEEL LAMINATED PANEL
Drawn BY:
RB
Checked:
Date:
3-23-18
Laminated Panel
3'-9"
2" Foam Core Panel
Revised:
lark As:
Item:
Net Cov.
Notes:
Job No:
#5220
Engineering Composite Panels, INC.
SHT: 5 OF 5
J
DATE: 3-23-18
BY: RB
LOAD TABLE
(CLEAR SPAN LENGTH "L" IN BENDING)
ALLOWABLE SPANS BASED UPON L/180 DEFLECTION LIMIT
UNIFORM LOAD ALLOWABLE SPAN
"W" (PSF) "L" (FEET)
208.70
307.60
406.91
506.64
556.21
606.03
1. Panels are laminated polystyrene and steel bonded together with structural
Adhesives that conform to ICBO approval.
2. Facing Material: 24 GA. Steel Sheet Metal: Core: Polystyrene (EPS), Density=
1.0 pcf.
3. Steel sheets are considered continuously .bonded with an allowance for
unsupported edges.
4. Table shall be used in conjunction with the applicable requirements and load
combinations as specified in the International Building Code.