Re: Residential Re -Roof
501 Nettles Blvd
Jensen Beach, FL
SCOPE OF WORK:
Install new Metal Roof (Extreme Metal Fabricators, LLC "5-V Crimp" (FL #17022.1) at above
referenced address over new underlayment, and existing plywood sheathing.
DESIGN CRITERIA:
FBC 2017
ASCE7-10
PROJECT DATA:
BUILDING HIEGHT = 10'-0"
A= 3'
MEAN ROOF HIEGHT = <20'
ROOF ANGLE = 4:12
SHAPE = PITCHED HIP / GABLE
ADJUSTMENT FACTOR =1.00
IMPROTANCE FACTOR = 1.00
WIND VELOCITY V ult = 165NMH
WIND VELOCITY V asd =128 MPH
EXPOSURE = D
ENCLOSURE CLASS = ENCLOSED BUILDING
INTERNAL PRESSURE COEFFICIENT = -0.18
APPLIED UPLIFT DESIGN PRESSURES PER ASCE (PSF):
ZONE 1 (Field) = -40.3
ZONE 2 (Perimeter/ Ridge) = -68.0
ZONE 3 (Comers) = -99.8 Paul Welch Inc.
Paul Welch P.E. Reg. No. 29945
June 6, 2018
501 Nettles Blvd Jensen Beach, FL 1 of 3
METAL ROOFING ATTACHMENT REQUIREMENTS:
Metal roofing to be attached with corrosion resistant Hex -Head wood screws #10 x 1 V2"
minimum with weather sealing washers (minimum 3/16" penetration through deck). Fasteners
shall be placed through the panel ribs at 12" on center across panel width and spacing along the
ribs as follows:
ZONE 1 (Field): FASTENER SPACING = 16" O.C.
ZONE 2 (Perimeter/ Ridge): FASTENER SPACING = 16" O.C.
ZONE 3 (Corners): FASTENER SPACING = 8" O.C.
NOTE: PROVIDE LAP SEALANT FOR ALL ROOF PANEL LAPS FOR ROOF
SLOPES UNDER 3 VERT.:12 HORZ.
Design uplift Pressure for attachment as per above:
Product Design Pressure: Zones 1 & 2:-93.5PSF / Zone 3:-10IPSF
Therefore O.K.
UNDERLAYMENT:
Underlayment shall be in accordance with manufacturer's guidelines, FBC 1507.4.5.1, and FBC
15074.5.2. Underlayment shall be Approved 30# Roofing Felt.
DECK INSTALLATION:
Re -nail all plywood sheathing (15/32" thick minimum) with 8D ring -shank nails at 4" O.C.
perimeter and 6" O.C. field for all zones.
All work to be in compliance with product approval (FL # 17022.1), manufacturer's
specifications, and the Florida Building Code 2017.
Paul Welch Inc.
Paul Welch P.E. Reg. No. 29945
June 6, 2018
501 Nettles Blvd Jensen. Beach, FL 2 of 3
rh ;�ti
4,
14
�A
ROOF ZONE PLAN
A 3'
Q, Q, ®= ZONE DESIGNATION (TYPICAL)
NOTE: PROVIDE LAP SEALANT FOR ALL ROOF PANEL LAPS FOR ROOF
SLOPES UNDER 3 VERT.:12 HORZ.
Paul Welch Inc.
Paul Welch P.E. Reg. No. 29945
June 6, 2018
501 Nettles Blvd Jensen Beach, FL 3 of 3