This letter is in reference to the review comments for the above referenced project. Please see
responses below to comments:
1. Revised energy calcs & Man J included herewith.
✓2. Sheet CVR has been revised to indicate the centerline anchors for the head and sill for
/ product approval FL15225.5
�✓ 3. The installation instructions for the Wayne Dalton garage door shall be provided.
vO'4. Sheet CVR has been revised to indicate the (2) anchors per location for product approval
FL15332.6.
✓5. Sheet CVR has been revised to indicate the fin mount requirements for windows E, F and
H.
V6. Sheet CVR has been revised to indicate the model for the shingles manufactured -by
Tamco Building Products for product approval FL18355.1.
V*7'. Sheet A2.0 has been revised to indicate the hatch patterns for the wall types in the Wall
Legend.
A. Sheet A3.0 has been revised to indicate the gable end on the side elevations.
,/9-. Sheet A4.0 has been revised to indicate a note referring to the truss engineering for
information on truss bracing.
./10. Sheet A6.0 has been revised to indicate the 8d ring shank nails to be used for roof
sheathing attachment.
vI1. Sheet A6.1 has been revised to indicate the corrected method of roof underlayment
attachment.
L,012. Sheet A6.1 has been revised to indicate the attachment of the stair kick plate to the slab.
13. Sheet A2.0 has been revised to indicate the door from the garage to the house to be self -
closing.
vOq'4. Sheet A1.0 has been revised to indicate the soil design load bearing value.
✓f5. Sheet A1.0 has been revised to indicate the soil density by proctor.
Vl'6. Sheet A2.0 has been revised to indicate the ceramic tile to be in accordance with R702.4
of the 2014 FRC.
V'17. Sheet A2.0 has been revised to indicate the gypsum board to be in accordance with
R702.3.1 of the 2014 FRC.
'001'8. Sheet A6.0 has been revised to indicate the interior non bearing wall detail.
✓19. Sheet A2.0 has been revised to indicate the fire blocking location on the stair detail.
20. Truss engineering shall be provided.
✓21. Sheet A3.0 has been revised to indicate the bable end showing the ladder framing detail.
Please call if you have questions.