June 12, 2018
Saint Lucie County Building Department
Attn: Roof Permit Plan Review
2300 Virginia Avenue
Ft. Pierce, FL 34982
Re: Roofing specification prepared for the St. Lucie County Building Dept. for the structure
located at 7802 Belmont Avenue, St. Lucie County
Manufacturer:
Tri-Built Roofing Products
Profiles:
Tri "Built Modified, FL# 16027:1
Code:
FBC 2017I Section R 905.10
Wind Speed:
160 MPH; Ultimate Design Wind Speeds
Exposure:
B
Mean Roof Height:
30' Maximum
Pitch:
1.5%12 Main Residence
Required Design Pressure:
Zone1: -26 Zone 2: -41 Zone3: -57
Maximum Uplift Pressure:
=82.5
Base:
SBS-SA
Cap:
APP-SA
Roof Decking:
Existing 1 x 6 tongue and groove sheathing to be nailed w (3) 8d x 2"
ring shank nails per joist.
I
Manufacturer:
Profiles:
Code:
Wind Speed:
Exposure:
Mean Roof Height:
Pitch:
Required Design Pressure:
Maximum Uplift Pressure:
Base:
-Cap:
Insulation:
Roof Decking:
Tri-Built Roofing Products
Tri —Built Modified, FL# 16027.1
FBC 2017;;Section R 905.10
160 MPH;'Uitimate Design Wind Speeds
B
30' Maxim'um
1/4/12 Back Porch
Zone1: -26 Zone 2: -41 Zone3: -57
-82.5
SBS-SA
APP-TA
Minimum i.5" Energy 3 H-Shield or Roof Decking Polytherm,
Dekfast Galvalume Steel Hex with Dekfast #12 DP or TruFast MP-3
with TruFast DP, w/ (1) fastener per 1.33 square foot
Existing 1 x 6 tongue and groove sheathing to be nailed w (3) 8d x 2"
ring shank nails per joist.
806 Delaware Avenue Tel: 772 460 7751 www.architedtonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 2
�J TRINITY I ERD
t TABLE lE 2 WOOD DECKS NEIN CONSTRUCTION, RERO,QF ;EAR OFF OR RECOVER - "
SYSTEIVIrTYPE Ec NON'INSULATED, MECHANICALL*Y ATTACHED BA$E SHEET;BONREg RODF COVER ', i`
_.
System
Base Sheet
Roof Coverr(Note 15)
MDP
No.
Deck (Note 1)
Base
Fasteners
Attach
Base Ply
Cap Ply
(Psi
Min. 19/32-inch
Polyglass Elastobase, Polyglass Elastobase
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
(Optional) One or
W-1
plywood at max.
Poly, Polyglass G2 Base, CertainTeed
Roofgrip #14, Dekfast Hex with Dekfast #14
o.c. in two, equally spaced, staggered
more BP -AA or
SBS-AA, SBS-
-52.5
24-inch spans
Glasbase, Firestone MB Base,1M Perma-
or TruFast MP-3 with TruFast HD
center rows
APP-TA
TA,.APP-TA
Ply 28, Tamko Glass Base or GAFGLAS #75
Min. 19/32-inch
Polyglass Elastobase or Polyglass
Dekfast Hex with Dekfast #14 or TruFast MP-
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
W-2
plywood at max.
o.c. in two, equally spaced, staggered
SA, SBS-TA or
-52.5 *
24-inch spans
Elastobase Poly with poly top surface
3 with TruFast HD
center rows
SA
APP-TA
Min. 19/32-inch
Polyglass Elastobase or Polyglass`
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
(Optional) One or
SBS-AA, SBS-
W-3
plywood at max.
Elastobase Poly
Roofgrip #12
o.c. in two, equally spaced, staggered
more BP -AA or
TA, APP-TA
-60.0
24-inch spans
center rows
APP-TA
Min. 19/32-inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
W-4
plywood at max.
Elastobase Poly with poly top surface
Roofgrip #12
o.c. in two, equally spaced, staggered
SA
SA, SBS-TA or
-60.0*
24-inch spans
center rows
APP-TA
r rr_ .a. _-,..r._
TABLE 1F 4WOOD'DECKS `NEW CONSTRUCTION oRtEROOF:(TEAROFF)gi
r `'SYSTEM TYPE F NONrINSULATEb BONDEDROOF CO,UER,
System
Roof
Cover (Note 15)
MDP
— No: --
Deck
— --
Pruner
(Psf)
- Joint Treatment
�� z _
Non--.e'� :..
_ — Ba
izSBStSA _
PI
�Optional)585'SP or =
BSSA1?AFP�
Min. 5/3 inch Inwood
tional);ASTM D41�
a max. s
- =
Plywood joints are covered with 4-inch wide strips of TriBuilt SA
APP-TA
(Optional) SBS-SA or
or APP-TA
SBS-SA, APP-SA, SBS-TA
Min. 15/32-inch plywood
W_6
(Optional) ASTM D41
TriBuilt SA SBS Base
97.5
at max. 24-inch spans
SBS Base, rolled into place to create continuous bond.
APP-TA
or APP-TA
Exterior Research and Design, I.I.C. d/b/a TrinityJERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-R2 for FL16027-R2
Revision 2: 09/25/2017 <
Appendix 1, Page 8 of 26
t
r '
NTINITY I ERD
1S. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
RooFyCoveRs ' ` t
_$TABLE 1$TRI=BUILT 1_
Reference
Layer
Material
Application
BP -AA
Base Ply
FBC Approved ASTM D4601, Type II
(Base and Ply sheets, Asphalt -Applied)
HA at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
SBS-AA
(SBS, Asphalt -Applied)
Cap Ply
TriBuilt SBS Granular
HA at 20-40 Ibs/square
SBS-TA
(SBS, Torch -Applied)
Cap Ply
TriBuilt SBS Granular
Torch -Applied
SBS-SA
Base Ply
TriBuilt SA SBS Base
(SBS, Self -Adhering)
Self -Adhering
Cap Ply
TriBuilt SA SBS Cap
APP-TA
Base Ply or Ply
TriBuilt APP Smooth
(APP, Torch -Applied)
Torch -Applied
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
APP-SA
(APP, Self -Adhering)
Cap Ply
TriBuilt SA APP Cap
Self -Adhering
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A
applies:
µ VAPOR BARRIER OPTIONS rSTRUCTURAL`GONCRETE,DECK,RDHERED (NSUlAT10N PER TABLEt3A _ . - k
Option #
Primer
Vapor Barrier
Insulation Adhesive
MDP (psf)
Type
Attach
VB-1.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Inta-Stik or CR-20, 12-inch o.c.
-60.0
VB-2.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Insta-Stik, 12-inch o.c.
-75.0
VB-3.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Millennium One Step Foamable Adhesive, 12-inch o.c.
-157.5
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20, 12-inch o.c.
-270.0
VB-5.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20, 12-inch o.c.
-290.0
17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for F1.16027-112
Certificate of Authorization #9503 6" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 3 of 26
C)o
�! I RININIERD
TABLE'1C: WOOD Di GKS = .. , _ . , Va ,>
N,R OF(,TEAR OFF)oR9RECOVER� . E . NEW CONSTRUCTIO ERO
SYSTEM TYPE C: MECHANICALLY=AITACFED'INSUTATIQN;:BONDED,ROOF'CQVER "w{,
,
....
System
Deck (Note 1)
Base Insulation
Top Insulation Layer
Roof Cover (Note 15)
MDP
Type
Fasteners
Attach
Base Ply
Ply
Cap Ply
No.
Layer
(Psf)
Min. 19 / 32-inch
(Optional)
Min. 0.5-inch Structodek High Density
Dekfast Galvalume
(Optional if
(Optional if using AA
W-8
plywood at max.
One or more layers,
Fiberboard Roof Insulation or min. 0.25-
Steel Hex with
1 per 1.33
using AA Ply)
Base) One or more BP -AA
SBS-AA, SBS-TA, APP-
82.5
24-inch spans
any combination,
inch Dens Deck, Dens Deck Prime or
Dekfast #12 DP
ftz
BP -AA
or APP-TA
TA
e ai
RM-6ypsur1q-Fa oof Board
(Optional)
�
Dekfast Galva _UM_E
W-9
Min. 19/32-inch
plywood at max.
One or more layers,
an combination,
Y
Min. 1.5-inch ENRGY 3, H-Shield or
Pol herm
Steel Hex with
Dekfast #12 DP or
1 per 1.33
ftz
SBS-SA
(Optional) One or more
SBS-SA or APP-TA
SBS-SA A, SBS-
TA o AP -T
_82 5
24-inch spans
loose laid
TruFast MP-3 with
TruFast DP
n...
__7777w TAB E 1b wWA.OD-BECKf EW'COIU CTION' REROOFi TEAR OFF FOR REC V ` ' r: x
zi
15
S STEMITYPE D PRELIMINARILY ATTACHED INSULATION, IVIECHANICALL-Y ATTACHED,BASE SHEET, BONDED RO,C!F COVER
_ .. r ..
System
Deck (Note 1)
Insulation Layer(s)
Base Sheet
Roof Cover (Note 15)
MDP
No.
Type
Attach
Base
Fasteners
Attach
Base Ply
Cap Ply
(psf)
Polyglass Elastobase, Polyglass
OMG Flat Bottom Plates
Min. 19/32-inch
One or more layers,
Prelim.
Elastobase Poly, Polyglass G2 Base,
(square) with Roofgrip
12-inch o.c. in 4-inch lap and 12-
(Optional) One
SBS-AA,
W-10
plywood at max.
any combination
Attached
CertainTeed Glasbase, Firestone MB
#14, Dekfast Hex with
inch o.c, in two, equally spaced,
or more BP -AA
SBS-TA,
-52.5
24-inch spans
Base, JM Perma-Ply 28, Tamko Glass
Dekfast #14 or TruFast
staggered center rows
or APP-TA
AP-P-TA
-
Base or GAFGLAS #75 _
__MP_-3-with TruFast-HD
-- — --
Min. 19/32-inch
One or more layers,
Y
Prelim.
Polyglass Elastobase or Polyglass
Yg Yg
Dekfast Hex with Dekfast
12-inch o.c. in 4-inch lap and 12-
One or more
SBS-SA,
APP-SA,
W-11
plywood at max.
any combination
Attached
Elastobase Poly with poly top surface
TruFast MP-3 with
inch o.c. in two, equally spaced,
SBS-SA
SBS-TA
52.5 ,�
24-inch spans
2
asor
TruFast HD
Tru#14Fast
staggered center rows
or
APP-TA
W-12
Min. 19/32-inch
plywood at max.
One or more layers,
Prelim.
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates
12-inch o.c. in 4-inch lap and 12-
(Optional) One
SBS-AA,
24-inch
an combination
Y
Attached
Elastobase Poly
Y
(square) with Roofgrip #12
inch o.c. in two, equally spaced,
or more BP -AA
SBS-TA,
-60.0
spans
staggered center rows
or APP-TA
APP-TA
W-13
Min. 19/32-inch
at max.
One or more layers,
Prelim.
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates
12-inch o.c. in 4-inch lap and 12-
One or more
SBS-SA,
APP-SA,
plywood
24-inch spans
an combination
y
Attached
Elastobase Polywith of to surface
poly P
(square) with Roofgrip #12
inch o.c, in two, equally spaced,
SBS-SA
SBS-TA or
60.0
staggered center rows
APP-TA
Exterior Research and Design, LLC. d/b/a Trinity) ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
e EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-R2 for FL16027-R2
Revision 2: 09/25/2017
Appendix 1, Page 6 of 26
��TRINITYJERD
N GC1N5 TeA'`R.OFIS .'
t
�`; �`'�� * �`i
�t'.'.Y
'aI, �E* 2 yIECHA t<'A A C E • ANG 0 FSHE BO D D t S ON O DEDtRpd C01tER
�. _. � 13'A � .9;..,7.c 3j�
k§SYST, .
_J:t... wet t„-V . 1.id4.�?t, �i..+ r,wa-a..�s,w�»..a - ,L.+..'�-....x�.rwa.. ..�.•.aro.6. i.J.��
System
Deck
Anchor Sheet
Base Insulation
Top Insulation
Roof Cover (Note 15) m(p
No.
(Note 1)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply lPsfl
Min. 0.25-inch Dens
Polyglass G2 Base,
B-inch o.c. in 4-
Deck, Dens Deck Prime,
Min. 19/32-
CertainTeed Glasbase,
32 ga.,1-5/8-
inch lap and 8-
(Optional) FBC
SECUROCK Gypsum -
jp
inch I
plywood
Firestone MB Base, JM
inch diameter
inch o.c. in
Approved,
Fiber Roof Board, Min.
(Optional)
SBS-AA,
W-1
tin caps with 11
three, equally
ASTM C1289,
HA
0.75-inch FescoBoard
HA
BP -AA
SBS-TA, -60.0
max.
Tamko
ga. annular ring
spaced,
type II polyiso-
(homogeneous) or min.
BP
APP-TA
inch spans
in spans
Glass Base or
GlassPermBase or
shank nails
staggered
cyanurate
0.5-inch Structodek
GAFGLAS #75
center rows
High Density Fiberboard
Roof Insulation
Polyglass G2 Base,
8-inch o.c. in 4-
Min. 19/32-
CertainTeed Glasbase,
32 ga., 1-5/8-
inch lap and 8-
(Optional) FBC
Min. 0.25-inch Dens
(Optional)
S65-SA,
inch plywood
Firestone MB Base,
inch diameter
inch o.c. in
Approved,
Deck, Dens Deck Prime,
One or
APP-SA,
W 2
at max. 24
Perma-Ply 28, Tamko
tin caps with 11
three, equally
ASTM C1289,
HA
SECUROCK Gypsum-
HA
SBS-SA
more SBS-
-60.0
SBS-TA or
inch spans
Glass Base or
ga. annular ring
spaced,
type II polyiso-
Fiber Roof Board
SA or
APP-TA
GAFGLAS #75
shank nails
staggered
cyanurate
APP-TA
center rows
6-inch o.c. in 4-
Min. 2-inch
D-IS, OB500,
Min. 19/32-
32 ga., 1-5/8-
inch lap and 6-
ACFoam II, III,
CR-20 or M-
Min. 0.25-inch Dens
D-IS,
inch plywood
Polyglass Elastobase
inch diameter
inch o.c. in
H-Shield, H-
OSFA, atop
Deck, Dens Deck Prime
OB500,
(Optional)--
SBS-AA, _
W-3
at max. 24-
or Polyglass
tin caps with 12
four, equally
-
-fastener
—orSECUROCK-Gypsum-
- -
CR-20 or
BP-M-
BP -AA
36 -60.0•
--inch-spans- -
Elastobase Poly. _
-
ga. annular ring
spaced;
-Shield.CG,-
Multi -Max FA3
rows, 7-inch
Fiber Roof Board
M-OSFA
A
shank nails
staggered
center rows
orENRGY-3
oc
6-inch o.c. in 4-
Min. 2-inch
D-IS, OB500,
Min. 19/32-
32 ga., 1-5/8-
inch lap and 6-
ACFoam II, III,
CR-20 or M-
D-IS,
(Optional'
inch I
plywood
Polyglass Elastobase
inch diameter
inch o.c. in
H-Shor
atop
(Optional) Additional
OB5CR-2 0,
One or
W 4
Polyglass
tin caps with 12
four, equally
SBS-SA
more S
at max. 24-
Elastobase Poly
ga. annular ring
spaced,
Shield C ,
Shield CG,
fasteOSFAner
fastener
layers of base insulation
CR-20 or
SA or
inch spans
shank nails
staggered
Multi -Max FA3
rows, 7-inch
M-OSFA
APP
center rows
or ENRGY-3
oc
Exterior Research and Design, I.I.C. d/b/a Trinity) ERD
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVH2 EVP
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems;
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
TTRINITYIERD
Y 4"t iT L ....S 7 S. '" : 1 '�w-[^ F �S 3 t q1 -
n$: ,nF +C. .'��--n 'e'. `- •'R _
i1�BUILlaw H Co�Rs r
_
Material
_
'Application
Reference
Layer
BP -AA
(Base and Ply sheets, Asphalt -Applied)
Base Ply
FBC Approved ASTM D4601, Type II
HA at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
SBS-AA
(SBS, Asphalt -Applied)
Cap Ply
TriBuilt SBS Granular
l
HA at 20-40 Ibs /square
SBS-TA
(SBS, Torch -Applied)
Cap Ply
TriBuilt SBS Granular
Torch -Applied
SBS-SA
SBS, Self -Adhering) g)
Base Ply
TriBuilt SA SBS Base
Self -Adhering
Cap Ply
TriBuilt SA SBS Cap
APP-TA
(APP, Torch -Applied)
Base Ply or Ply
TriBuilt APP Smooth
Torch -Applied
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
APP-SA
(APP, Self -Adhering)
Cap Ply
TriBuilt SA APP Cap
Self -Adhering
g
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A
applies:
�VAPtlR;�ARR1EttOPT10NS
STRUCtURALCONCREI'��DECK�AtDHEaEDIN�ULA�[IO�IPE Tae�3A'� �'���k�, ��,� ��K;��`"�'�
� £�
Option #
Primer
Vapor Barrier
Insulation Adhesive
DP
M(Psf)
Type
Attach
VB-1.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Inta-Stik or CR-20, 12-inch o.c.
60.0
VB-2.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Insta-Stik, 12-inch o.c.
-75.0
VB-3.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Millennium One Step Foamable Adhesive, 12-inch o.c.
-157.5
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20, 12-inch o.c.
-270.0
VB-5.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20,12-inch o.c.
290.0
17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity ERD Evaluation Report A42970.10.12-R2 for F1.16027-112
Gertificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 3 of 26
4
Yk
!"K
CAI L C,--
NEW ot')
T Af M-G:V
535-5el-
S'�,t5T
ov�M-,
A
I't
oToo"
7-0 cr-F-,YI-TC
�5'132 ;PL.,-Iwo?pp
QOTRINITYIERD'
MIA1 t tAINOM DCDf%DT
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 Christian Street
Oxford, CT 06478
(203) 262-9245
TRI-BUILT Materials Group, LLC Lmaluation Keport H4471v.1V.11--nc
PO Box 70 FL16027-RZ
Rutherford, NJ 07070 Date of Issuance:10/23/2012
(800) 516-1485 Revision 2: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nleminen,
P.E. on 09/25/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
Q'*TRINITYIERD
Table
.Deck
Application
Type
Description
Page
1A-1
Wood
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
4
3A-2
Wood
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
5
1B
Wood
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
5
1C
Wood.
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
c
1D
Wood
New, Reroof (Tear -Off) or Recover
D
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
6
lE-1
Wood
New or Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
7
1E-2
Wood
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
8
1F
Wood
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
8
2A
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
9
28
2C
3A
Steel or Structural concrete
Steel or Structural concrete
Structural concrete
New, Reroof (Tear -Off) or Recover
New, Reroof (Tear -Off) or Recover
New or Reroof (Tear -Off)
C
D
A-1
Mech. Attached Insulation, Bonded Roof Cover
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
Bonded Insulation, Bonded Roof Cover
9
10
- 11-14
3B
Structural_ concrete
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
14
4A
LWIC
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
15-16
4B
LWIC
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
16
4C
LWIC
New or Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
17-19
5A
CWF
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
20
5B
CWF
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
21
5C
5D
CWF
CWF
New, Reroof (Tear -Off) or Recover
New, Reroof (Tear -Off) or Recover
B
C
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
Mech. Attached Insulation, Bonded Roof Cover
22
22
5E
CWF
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
22
6A
Gypsum
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
23
613
Gypsum
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
24
6C
Gypsum
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover'
24
% 6D
Gypsum
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
24
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
25-26
7B
Various
Recover
F
Non -Insulated, Bonded Base Sheet, Bonded Roof Cover
26
The followine notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
> Wood: Minimum 0.75-inch penetration.
Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.
v Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocya n u rate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the CIA
requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 andjor foam plastic, FBC Chapter 26, when installed with the roof cover.
Exterior Research and Design, LLC. d/b/a Trinity (ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization #9503 6"' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 A
ppendix 1, Page 1 of 26 l _,
s
QOTRINITYIERD
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base
sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and
structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ HA (HA): Full coverage at 25-30 Ibs/square.
➢ Dow INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c.
l ➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced.
➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick)
➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3)
➢ OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+GL)
➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3)
➢ OMG OlyBond 500 (OB500): MDP 487.5 psf (Min. 0.5-inch thick ACFoam II)
➢ ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min. 1.0-inch thick)
8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D, the insulation;is optional; however, the existing roof system shall be suitable for a recover application.
14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches.
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1.
Exterior Research and Design, I.I.C. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization #9503 67 EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 2 of 26