HomeMy WebLinkAboutPROJECT INFORMATION-,&XUV.U419 - Fire -resistance Ratings - AN,SI/UL 263
Page 1 of 11 __ ,
Design No. U419
BXUV.U419
Fire -resistance Ratings - ANSI/UL 263
Page Bottom
Design/System/Construction/Assembly Usage Disclaimer
• Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL
Certified products, equipment, system, devices, and materials.
• Authorities Having Jurisdiction should be consulted before construction.
• Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with
applicable requirements. The published information cannot always address every construction nuance encountered In the field.
• When field issues arise, It is recommended the first contact for assistance be the technical service staff provided by the product
manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each
product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate
methods of construction.
• Only products which bear UL's Mark are considered Certified.
I
BXUV - Fire Resistance Ratings - ANSI/UL 263
BXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
See General Information for Fire -resistance Ratinos - ANSI/UL 263
See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
Design No. U419
October 10, 2017
Nonbearing Wall Ratings - 1, 2, 3 or 4 Hr (See Items 4 & 5 through 5K)
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such
as Canada), respectively.
q)4�k
I:k - \
11.
I
http://database.ul.com/cgi-binIXYVItemplatelLISEXT/1 FRAMElshowpage.html?name=B... 11/3/2017
. BXUV.U419 - Fire -resistance Ratings - A,NSI/UL 263
Page 6 .of 11
20. Framing Members* — Steel Studs — As an alternate to Item 2 — proprietary channel shaped steel studs, min
width as Indicated under Item 5, galy steel. Studs to be cut 3/8 to 3/4 in. less in lengths than assembly height. Spaced 24
in. OC max.
RONDO BUILDING SERVICES PTY LTD — Rondo Lipped Wall Stud
2P. Framing Members* — Steel Studs — As an alternate to Item 2 — proprietary channel shaped steel studs, min
width as indicated under Item 5, min 25 MSG galy steel. Studs to be cut 3/8 to 3/4 in. less in lengths than assembly
height. Spaced 24 in. OC max.
OEG BUILDING MATERIALS — OEG Stud
2Q. Framing Members* — Steel Studs — Not Shown — In lieu of Item 2 — For use with Item 10, proprietary channel
shaped steel studs, min depth as indicated under Item 5, spaced a max of 24 in. OC, fabricated from min 25 MSG (0.018
in. min. bare metal thickness). Studs cut 3/8 in. to 3/4 in. less in lengths than assembly heights.
CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper X
3. Wood Structural Panel Sheathing — (Optional, For use with Item 5 Only) — (Not Shown) — 4 ft wide, 7/16 In. thick
oriented strand board (OSB) or 15/32 in. thick structural 1 sheathing (plywood) complying with DOC PS1 or PS21 or APA
Standard PRP-108, manufactured with exterior glue, applied horizontally or vertically to the steel studs. Vertical joints
centered on studs, and staggered one stud space from wallboard joints. Attached to studs with flat -head self -drilling
tapping screws with a min. head diam. of 0.292 in. at maximum 6 in. OC. in the perimeter and 12 in. OC. in the field.
When used, gypsum panels attached over OSB or plywood panels and fastener lengths for gypsum panels increased by
min. 1/2 in.
4. Batts and Blankets* — (Required as indicated under Item 5) — Mineral wool batts, friction fitted between studs and
runners. Min nom thickness as indicated under Item S.
See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies.
4A. Batts and Blankets* — (Optional) — Placed in stud cavities, any glass fiber or mineral wool Insulation bearing the
UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance.
See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies.
4B. Batts and Blankets* — For use with Item 5K. Placed in stud cavities, any min. 3-1/2 In. thick glass fiber insulation
bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance.
See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies.
4C. Fiber, Sprayed* — (Optional) and as an alternate to Batts and Blankets (Item 4B) where insulation is required -
Spray applied granulated mineral fiber material. The fiber is applied with adhesive at a minimum density of 4.0 pcf to
completely fill the wall cavity in accordance with the application Instructions supplied with the product. See Fiber,
Sprayed (CCAZ).
AMERICAN ROCKWOOL MANUFACTURING, LLC — Type Rockwool Premium Plus
5. Gypsum Board* — Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. Vertical
joints centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints in adjacent layers
(multilayer systems) staggered one stud cavity. Horizontal joints need not be backed by steel framing. Horizontal edge
joints and horizontal butt joints on opposite sides of studs need not be staggered. Horizontal edge joints and horizontal
butt joints in adjacent layers (multilayer systems) staggered a min of 12 in. The thickness and number of layers for the
hr, 2 hr, 3 hr and 4 hr ratings are as follows:
Gypsum Board Protection on Each Side of Wall
Rating, Hr
Min
Stud
Depth, in.
Items 2, 2C, 2D, 2F, 2G, 20
No. of
Layers
& Thkns
of Panel
Min
Thkns of
Insulation
(Item 4)
1
3-1/2
1 layer, 5/8 in. thick
Optional
i
2-1/2
1 layer, 1/2 in. thick
1-1/2 in.
1
1-5/8
1 layer, 3/4 in. thick
Optional
2
1-5/8
2 layers, 1/2 in. thick
Optional
2
1-5/8
2 layers, 5/8 in. thick
Optional
2
3-1/2
1 layer, 3/4 in. thick
3 in.
3
1-5/8
3 layers, 1/2 in. thick
Optional
3
1-5/8
2 layers, 3/4 in. thick
Optional
3
1-5/8
3 layers, 5/8 in. thick
Optional
http://database.ul.com/cgi-binIXYVItemplateALISEXT/1 FRAMElshowpage.html?name--B... 11 /3/2017
BXUV.U419 - Fire -resistance Ratings - ANSI/UL 263
Page 7.of 11
4
1-5/8
4 layers, 5/8 in. thick
Optional
4 _
1-5/8
4 layers, 1/2 in. thick
Optional
4
2-1/2
2 layers, 3/4 in. thick
2 in.
CGC INC — 1/2 in. thick Type C, IP-X2 or IPC-AR; WRC, 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX,
SHX, WRX or WRC; 3/4 in. thick Types IP-X3 or ULTRACODE
UNITED STATES GYPSUM CO — 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type SCX, SGX, SHX, WRX,
IP-X1, AR, C, WRC, FRX-G, IP-AR, IP-X2, IPC-AR; 3/4 in. thick Types IP-X3 or ULTRACODE
USG BORAL ZAWAWI DRYWALL L L C SFZ — 1/2 in. Type C; 5/8 in. Types C, SCX, SGX, ULTRACODE
USG MEXICO S A DE C V — 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2,
IPC-AR, SCX, SHX, WRX, WRC or; 3/4 in. thick Types IP-X3 or ULTRACODE
When Item 7B, Steel Framing Members*, is used, Nonbearing Wall Rating is limited to 1 Hr. Min. stud depth is 3-1/2
in., min. thickness of insulation (Item 4) is 3 in., and two layers of gypsum board panels (1/2 in. or 5/8 In. thick) shall be
attached to furcing channels as described in Item 6. One layer of gypsum board panels (1/2 in. or 5/8 in. thick) attached
to opposite side of stud without furring channels as described in Item 6.
5A. Gypsum Board* — (As an alternate to Item 5) — 5/8 in. thick, 24 to 54 in. wide, applied horizontally as the outer
layer to one side of the assembly. Secured as described in Item 6.
CGC INC — Type SHX.
UNITED STATES GYPSUM CO — Type FRX-G, SHX.
USG MEXICO S A DE C V — Type SHX.
5B. Gypsum Board* — (Not Shown) — As an alternate to Item 5 when used as the base layer on one or both sides of
wall when 5/8 in or 3/4 in. thick products are specified. For direct attachment only to steel studs Item 2A, (not to be used
with Item 3) — Nom 5/8 in. or 3/4 in. may be used as alternate to all 5/8 in. or 3/4 in. shown in Item 5, Wallboard
Protection on Each Side of Wall table. Nom 5/8 in. or 3/4 in. thick lead backed gypsum panels with beveled, square or
tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on opposite sides of
studs. Gypsum board secured to 20 MSG steel studs Item 2A with 1-1/4 in. long Type S-12 steel screws spaced 8 in. OC
at perimeter and 12 in. OC in the field. To be used with Lead Batten Strips (see Item 11) or Lead Discs or Tabs (see Item
12).
RAY -BAR ENGINEERING CORP — Type RB-LBG
5C. Gypsum Board* — (For Use With Item 2B) — Rating Limited to 1 Hour. 5/8 in. thick, 48 in. wide, Gypsum panels
with beveled, square or tapered edges, applied vertically or horizontally. (Vertical Application) - The gypsum board is to
be installed on each side of the studs with 1 in. long Type S coated steel screws spaced 8 in. OC starting 4 in. from the
edge of the board at the vertical edges and 12 in. OC starting 6 in. from the edge of the board at the center of each
board. Gypsum boards are to be secured to the top and bottom track with screws spaced 8 in. OC starting 4 in. from the
board edge. Fasteners shall not penetrate through both the stud and the track at the same time. Vertical joints are to be
centered over studs and staggered one stud cavity on opposite sides of studs. (Horizontal Application) - The gypsum
board is to be installed on each side of the studs with 1 in. long Type S coated steel screws spaced 8 in. OC starting 4 in.
from the edge of the board at the vertical edges and 12 in. OC starting 6 in. from the edge of the board at the center of
each board. Gypsum boards are to be secured to the top and bottom track with screws spaced 8 in. OC starting 4 in. from
the board edge. Fasteners shall not penetrate through both the stud and the track at the same time. All horizontal joints
are to be backed as outlined under section VI of Volume 1 in the Fire Resistive Directory.
CGC INC — Type SCX.
UNITED STATES GYPSUM CO — Type SCX, SGX.
USG BORAL ZAWAWI DRYWALL L L C SFZ — Type SCX
USG MEXICO S A DE C V — Type SCX
513. Gypsum Board* — (As an alternate to Item 5) — 5/8 in. thick, 48 in. wide, applied vertically or horizontally.
Secured as described in Item 6. For use with Items 1 and 2 only.
http://database.ul.com/cgi-binIXYVItemplate/LISEXT/1 FRAMElshowpage.html?name=B... 11 /3/2017