HomeMy WebLinkAboutCONSTRUCTION PLANSLOCATION MAP
N.T.S.
VICINITY MAP
N.T.S.
I W. F. McCAIN & ASSOCIATES, INC. I
REVISIONS
OCEAN TOWERS BUILDING
DESIGNED WFM
DRAWN BJK
CHECKED WFM
DATE OCTOBER 2016
PROJECT # 14-169-B
BUILDING ADDITION
SECTION 35, TOWNSHIP 36 S, RANGE 41 E
CITY OF JENSEN BEACH
ST. LUCIE COUNTY, FLORIDA
OCTOBER 2016
CIVIL AND STRUCTURAL ENGINEER
W. F. McCAIN & ASSOCIATES, INC
CERTIFICATE OF AUTHORIZATION #8221
1171 19TH STREET
VERO BEACH, FLORIDA 32960
PHONE 772-770-1093
FAX 772-770-1508
OWNER
OCEAN TOWERS CONDOMINIUM ASSOCIATION
C/O MR. ED DULBS, TREASURER
9400 SOUTH OCEAN DRIVE
JENSEN BEACH, FLORIDA 34957
PHONE 772-341-1989
ELECTRICAL ENGINEER
BAILEY ENGINEERING CONSULTANTS, INC.
10620 GRIFFIN ROAD, SUITE 202
COOPER CITY, FLORIDA 33328
PHONE 954-448-7930
MECHANICAL ENGINEER
FORT PIERCE ENGINEERING, INC.
315 SOUTH 7TH STREET
FORT PIERCE, FLORIDA 34950
PHONE 772-672-4636
REQUIRED PERMITS
PERMITTING AGENCY
PERMIT NUMBER
PERMIT STATUS
FDEP
0081062-377—DSGP
RECIEVED 8-4-16
FDEP
COASTAL CONSTRUCTION
EXEMPTION RECEIVED 4-26-16
SLC
SITE PLAN APPROVAL
EXEMPTION RECIEVED 7-27-16
SLC
BUILDING PERMIT
CODE ANALYSIS
1. APPLICABLE CODES
A. 2014 FLORIDA BUILDING CODE
B. 2014 NATIONAL ELECTRIC CODE
C. 2014 FLORIDA PLUMBING CODE
D. 2014 FLORIDA MECHANICAL CODE
E. 2014 FLORIDA FIRE PREVENTION CODE
2. OCCUPANCY TYPE
1) GROUP "U" - UTILITY AND MISCELLANEOUS
(F.B.C. 312)
3. CONSTRUCTION TYPE
A. TYPE II B - UNSPRINKLED
B. STRUCTURAL FIRE RATINGS (F.B.C. TABLE 601
& 602)
1) EXTERIOR BEARING WALLS -CMU WALLS
ALL SIDES (FIRE SEPARATION >30' ALL
SIDES, NO FIRE HOUR RATED REQUIRED)
2) ROOF/CEILING ASSEMBLY - LIGHT
NON-COMBUSTIBLE STEEL
4. BUILDING HEIGHT AND AREA
A. HEIGHT
1) ALLOWABLE - 55' (F.B.C. TABLE 503)
2) ACTUAL PEAK HEIGHT - 8'
B. AREA
1) ALLOWABLE - 8,500 SF / UNIT- GROUP "U"
2) ACTUAL SQUARE FOOTAGE
326 SF
S. OCCUPANT LOAD (F.B.C. 1004.1.2)
ACCESSORY STORAGE AREA, MECHANICAL
EQUIPMENT ROOM, 1 PERSON PER 300 SF -
326 SF / 300 = 1 OCCUPANT
6. EXIT CAPACITY (F.B.C.1005)
A. NUMBER OF EXITS REQUIRED: 2 (F.B.C.
1004.2,2.)
B. NUMBER OF EXITS PROVIDED: 2
C. EGRESS WIDTH REQUIRED (LARGEST UNIT -
3,400 SF)
1) .2" (PER UTILITY OCCUPANT) X 1 = .2"
D. EGRESS WIDTH PROVIDED
1) 2 @ 36" = 72"
E. EXIT MIN. WIDTH: 36" CLEAR OPENING (F.B.C.
11-4.13.5)
7. ARRANGEMENT OF EXITS (F.B.C. 1016)
A. GROUP "U" = 300' MAX. TRAVEL DISTANCE TO
EXIT
ENGINEER'S PROJECT NO. 14-169-B
INDEX OF
COVER SHEET
DRAWINGS
G-1 EXISTING CONDITIONS/DEMOLITION PLAN
G-2 PROPOSED SITE LAYOUT
G-3 DETAILS
S-1 STRUCTURAL PLAN
S-2 STRUCTURAL ELEVATIONS
S-3 STRUCTURAL DETAILS
S-4 STRUCTURAL SPECIFICATIONS AND DETAILS
E-01 ELECTRICAL SITE PLAN AND LEGEND
E-02 EXISTING SINGLE LINE DIAGRAM
E-03 PROPOSED SINGLE LINE DIAGRAM
E-04 ELECTRICAL DEMOLITION PLAN
E-05 ELECTRICAL PLAN VIEW
E-06 LIGHTING PLAN VIEW
E-07 PANEL SCHEDULES
E-08 ELECTRICAL DETAILS
H-01 HVAC LEGEND & DETAILS
H-02 HVAC PLAN
P-1 PLUMBING LEGEND, NOTES, SCHEDULES AND DETAILS
P-2 PLUMBING FLOOR PLAN
SCRfYNEL�
B:
RECEIVED
SEP 13 2017
PERMI ITING
St. Lucie County, FL
NOT VALID WITHOUT THE ORIGINAL SIGNATURE
AND EMBOSSED SEAL OF THE ENGINEER
ENSF •e
WILLPAM F. MdCAIN,
DATA 9'A(TT(�2��7:.
_mac • �.OR10,.
■
■
M
INTAKE
A/C UNIT =__= STANDBY
-- GENERAT
5' ABOVE
GRADE
- UGE-P
FUEL
FILL FFU
SEE SHEET E-04 FOR
GENERATOR ROOM d)EMO
STEEL DOOR
7'-1"
OVE0OAD
EXHAUST CONTROL
PA
NEL
OVERHEAD
ELECTRICAL
-N EXISTING 4"
FRAME WALL
12'-6Y" 1 70 5'-3Y"
STANDBY L
L GENERATOR
EXHAUSfi
BRICK PAVERS
18" OVERHANG
1 R'-1l1
TO BE DEMOLISHED
33'-6"
vV - W------- W--- W W W— W
W
W
EXISTING
BUBLDING
EXISTING IMPERVIOUS
AREA=127.3 qn FT
PLIGHT—'- 4' T- ' ---r- SKYLIGH
—1/2" OVERHANG
W _ W-- W---4— W W W
�3'-{0"
LOCK WALL
7'-3n
W
TO BE DEMOLISHED
EX. DOOR
18" OVERHANG
ICK PA
3' METAL FENCE
W
U ERGROUND
PL BING(TO D
BE ELOCATED P z
38'-7°
►'i9
W W W
FL - FL FL
W W
FL
2
K
w
N
UZ
Z w
— w
w
�Z
� W
ga
w
Ci w
OZ2
z
co g
Q w
o
Z
Q �
U
U�
U z
0
LL o
0
z
z
w-- w—
FL FL
o
M M
Q o 0
LL n
XU" r
a, w X
� Lu
m o
O a
w
Z
Q
C/) Z
Z�
00-
i::z
❑0
z H
0 J
rn 0
V
z LIJ
I— 0
U)
X
Lu
Z
0
0
� Q
Z (7
Q Z
w
0 J
0=
In
PROJECT NO
14-169B
R
UGE-P
0
C 04 ■
18'-2"
O
m STO RAG E
I16"x618,1
REPLACE EXISTING 72"x82.5" ROLLUP DOOR
WITH TRUDOOR 600 SERIES HOLLOW METAL
FRAME LOUVER DOUBLE DOORS OR APPROVED EQUAL
4.5'x4' EXAUST LOUVER
RUSKIN MODEL # ELF6375DXD
OR APPROVED EQUAL
SEE SHEET S-3 FOR
WALL OPENING DETAIL
PROPOSED GENERATOR
SEE ELECTRICAL DRAWINGS
FOR SPECIFICATIONS
ELECTRICAL PANELS
SEE ELECTRICAL DRAWINGS
TANKLESS-
WATER
--� HEATER
18"
OVERHAN'
°
�.
a10
18-10"
a'
2'X4' INTAKE
LOUVER
STE ;� AND
.4
4 c4
USKIN
MODEL # ELF6375DXD
C
/OR
APPROVED
EQUAL
SEE SHEET S-3
FOR
W
.4
WALL OPENING
DETAIL
` `" + :.•.;;
- 8"X8" EXAUST
FAN LOUVER
RUSKIN MODEL
# ELF6375DXD
•
OR APPROVED
EQUAL
SEE
WALL PENETRATION
lXIL
SEE SHEET S-3
FOR
SHEET
WV '
WALL OPENING
DETAIL
W
w____
W _...,.,.
W W
— W.
W -- W-
GENERATOR SHALL LIE ON
4" THIICK 4000 PSI CONCRETE PAD
WITH #4 N & S 10" O.C.
AND #3 E & W 10" O.C.
aEIME
Rm
EXISTING
E UILDING
SEE BOOSTER PUMP DETAILS
AND SPECIFICATIONS
SHEETS P-1 &2
17 �ii,��
°
14'
o.4 Ur
4 �2'-411
Y
—1y2 z-i'
PUMP PAD LOCATIONS
SCALE: 3/8"=1'
NOTE: SEE SHEET S-4 FOR PROPOSED
P OPOSED DOOR DETAILS AND SPECS
DOOR
7 0 7 -3
11 EX. DOOR --
°
Q
°
SEE FLOOR PENETRATION -�
A. 4 DETAIL SHEET G-2
(TYP I CAL)
W .4 W W___L
W
1. ., .0
III 7'-9Y"
a 5%
w 91-91
o
«I•� �'y. I Mi
it
J
a �
V-0"
CID
W
W.
gUgNw
g
�
Z
w
9
0
W
In
ILL!
O
0
U
g
FLOOR PENETRATION LOCATIONS
SCALE: 3/8"=1'
s u x u I It 18" OVERHANG
HYDRO- i ( 4 -
cumu—
TANK \
38'-711
— I 22'-7" — 0
FIRE ALARIM PANEL
a
mot
PROPOSED AD ITION W W W W
2 X6 2 HOUR
FIRE WALL Q{.___ 3
SEE DETAIL SHEET G-3 0 - - ' - W
W W W W x J _... _. .
p� PROPOSED 4' IDE RI K
�.. PAVER SIDEW K
W W— W
V 1131.
SCALE: 3/8"=1' D':
® COPYRIGHT 2015 W.F. McCAIN k ASSOCIATES, INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANY WAY WITHOUT THE WRITTEN PERMISSION OF THE ENGINER. CHANGES TO THE DRAWINGS MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFESSIONAL ENGINEER SHALL ADHERE TO THE PROCEDURES OF 61G15-27 F.A.C. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER
W W
Us
Z�
L
�
Oco
c
<L
Z
=
cU
C •
F
u_
I
�E
N
N
p
f0
o
M M
cj z
aoo
ow0�
o��
N�
LLn�
H U LU
WWz
a
o
CO
wonL
�LU
LU
LL
W
IU
Z
O_
w ~
OQ
Z O
Q Z
w a
(.) J
0=
m
SHEET
OF '3
FL# 50046 PROJECT NO
THE INTEGRITY OF THE ENGINEERING DESIGN. 14-169B
L
SEE NOTE
SEE SHEET G-
FOR DEMOLITIOI
OF WALKWAY R001
ROOF PLAN
SCALE: 1/4 )I=i'-o
10
5
2 6" FROM FPUA 11 in 1IMI;
10
1" SPRINKLER SUPPLY
2
�J
12
I:7
6" TEST HEADER f
5
'::
1Y4" JOCKEY PUMP SUPPLY
\r0
FIRE PIPING SIDE VIEW
SCALE: 3/811=1'-0'L
FASTEN TRACK
® 12" O.C. MAX.
(SIZE AND GAUGE
SHALL MATCH STUDS)
ROOFING NOTES
1.) ROOFING MATERIAL SHALL BE 2-PLY SBS POLYGLASS ROOF SYSTEM OR APPROVED EQUAL
2.) A TAPER PICKAGE SHALL BE INSTALLED IN ORDER TO MAINTAIN PROPOSED ROOF SLOPES AND SHALL BE
SUBMITTED Tq THE ENGINEER OF RECORD FOR APPROVAL.
3.) ROOFING CKAGE SHALL BE SUBMITTED FOR APPROVAL BY THE ENGINEER OF RECORD AT THE TIME OF BID.
4.) 8"X6" ALUMINUM GUTTER WITH KAYNER COATING AND 6" ALUMINUNM DOUWNSPOUT WITH KAYNER COATING
ANCHORED TO EXTERIOR OF BUILDING AS PER MANUFACTURER SPECIFICATIONS AND CURRENT FBC.
5.) 4"X6" SCUPPER DRAIN THROUGH TOP BEAM. APPLY ROOF SYSTEM AS PER MANUFACTURER SPECIFICATIONS z
g
AND CURRENT FBC a
6.) CONSTRUCT CRICKET PER ROOF SYSTEM MANUFACTURER SPECIFICATIONS AND CURRENT FBC. w
LL
7.) NO CHANGES SHALL BE MADE WITHOUT WRITTEN APPROVAL OF THE ENGINEER. In
w
8.) ALL MATERIAL SHALL BE INSTALLED AS PER MANUFACTURER SPECIFICATIONS AND IN ACCORDANCE WITH THE Q
CURRENT FLORIDA BUILDING CODE. >
NOTE 4
REINFORCED
ETE TOP
IRUCTURAL
AND DETAILS
AL)
1. 6" TAMPERED B VALVE
2. 6" CHECK VALVE
3. 6" OS&Y VALVE WITH OS&Y TAMPER
4. FIRE PUMP
5. 1 Y4" TAMPERED BF VALVE
6. JOCKEY PUMP
7. 1Y4" CHECK VALVE
8. 1" TAMPERED BF VALVE
9. 1" FLOW SWITCH
10. SIDE WALL SPR14KLER
c=, COPYRIGHT 2015 W.F. McCAiN & ASSOCIATES, INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANY WAY WITHOUT THE WRITTEN PERMISSION OF THE
1/4" RED HEAD SLEEVE ANCHOR 0 48"
O.C.. TYP. CONNECTION FOR PARTITION TO
SIDEWALL, ROOF, OR FLOOR
(SIZE AND GAUGE SHALL MATCH STUDS)
)f GAP BETWEEN
TOP OF STUDS AND
BOTTOM OF ROOF DECK
METAL ROOF PAN
SEE STRUCTURAL PLANS
CAULK BOTH SIDES TOP AND
BOTTOM WITH HILTI 606 PER
MANUFACTURER SPECIFICATION
SEE HILTI SUBMITTAL PACKAGE
2 LAYERS 1/2" TYPE "X" GYPSUM WALLBOARD
APPLIED TO EA. SIDE OF STUDS PER
UL U419 AS PER RATING REQUIRED.
STEEL STUDS ® 24" O.C.
- D=6", Bf=1-5/8", 20 GA. OR
D=3-5/8", Bf=1-5/8", 20 GA.
5 }'2" GLASS FIBER FRICTION FIT INSULATION
MIN. R-21 RATING
PROPOSED
CONCRETE FLOOR
d d. la d a a Is as
INTERIOR NON -LOAD BRG. 2 HOUR FIRE -RATED AREA
SEPARATION WALL DETAILWITH STC 59 SOUND RATING
GALVANIZED STEEL
PIPE SLEEVE. DIAMETER
AS RECOMMENDED BY
SEAL MANUFACTURER -
GROOVED COUPLING
SHOWN. OTHER
CONNECTIONS
AS APPROPRIATE
11
1/2T 1/2T
MECHANICAL SEAL. WHERE PIPE V
PASSES THROUGH FIRE RATED ;..
WALLS, MECHANICAL SEALS
SHALL BE FIRE RATED •�•s,
ASSEMBLIES
NOTE:
INSULATED PIPING:
INTERRUPT INSULATION AT
BOTH SIDES OF WALL. INSTALL
INSULATION FLUSH WITH WALL
AFTER WATER TIGHT INSTALLATION
OF MECHANICAL SEAL.
SCALE'. N.T.S.
INTERMEDIATE
FLANGE/WATER STOP
PIPE DIAMETER
AND MATERIAL VARIES.
INTERMEDIATE FLANGE/WATER STOP
NOT REQUIRED FOR SLEEVES
INSTALLED IN CMU, BRICK OR
CAVITY WALLS.
WALL SLEEVES INSTALLED IN BRICK, CMU OR
CAVITY WALLS SHALL BE GROUTED IN PLACE
WITH NON -SHRINK GROUT. APPLY BONDING
AGENT TO CLEAN DRY SURFACES BEFORE
PLACING GROUT.
1 /2" 1 /2"
R
HOLLOW METAL DOOR DETAILS
E
1 1 /4" MIN. EMBED.
TYP. JAMB DETAIL
3/811 X 3.5" HILTI SLEEVE
ANCHORS OR APPROVED
EQUAL 3 EACH SIDE
STEEL DOOR
DOOR FRAME AND JAMB DETAIL
WOOD BUCK
N.T.S.
1D
V
N
a
F-
z
UU
Z
U
0
w
y
2
W
w
C]
O
U
LU
C1
K
w
U0
Z
Z m
W
fn ?
W z
F. LU
QF
UZ
w
O i
�0
Q Lu
cla
Q0
U
to
U�
Uz
St
o
LU
1
a
0
z
z
0
E
m
M co
O)
Q CO)ODp
LU M LUI--o
O
U LL r r
X 3f
F� UQ UJ
Z C
LUO
DOLL
0UU
a
I
3 WALL SLEEVE WITH MECHANICAL SEAL FOR CONCRETE, BLOCK,
G-3 CMU, OR CAVITY WALLS N.T.S.
WORK SCOPE: EXISTING WOOD ROOF AND PROPOSED GALVANIZED NEW CONCRETE BUILDING ROOF
1.) REMOVED EXISTING ROOFING AND RELATED DEBRIS TO THE WOOD DECK. DISCARD ALL DEBRIS LEGALLY OFFSITE J
2.) RE -FASTEN THE EXISTING WOOD DECK TO CODE. <
3.) FURNISH AND INSTALL A PRESSURE TREATED WOOD NAILER AT THE PERIMETER EDGE OF THE ROOF TO W
ACCOMMODATE THE INSTALLATION OF THE SHEET METAL (040 KINAR PAINTED ALUMINUM).
4.) AT THE WOOD DECK AREA WE WILL FURNISH AND INSTALL A 1.5" POLYISOCYANU RATE RIGID ROOF INSULATION
WITH AN LTTTR R VALUE OF 8.6. ALL BOARDS ARE TO BE MECHANICALLY ATTACHED AS PER FLORIDA BUILDING
CODE APPROVAL.
5.) FURNISH AND INSTALL'%!' PER FOOT TAPERED ISO CRICKETS, AS PER DRAWINGS PROVIDED.
6.)ATTHE OUTER EXTERIOR CONCRETE ROOF DECK WE WILL FURNISH AND INSTALL PER PLAN TAPERED ISO SYSTEM,
AS PER DRAWING. ALL BOARDS ARE TO BE ADHERED IN INSULATION ADHESIVE.
7.) FURNISH AND INSTALL POLYGLASS TWO PLY MODIFIED BITUMEN ROOF SYSTEM. THE BASE PLY WILL BE THE
ELASTOFLEX SAV AND THE WHITE GRANULAR CAP WILL BE ELASTOFLEX SAP AND/OR POLYFLEX G OR APPROVED
EQUAL.
CEMENT GROUT -
CAULKED DRY 8.) FURNISH AND INSTALL POLYGLASS TWO PLY POLYGLASS MODIFIED BITUMEN WALL FLASHING ON ALL WALLS
INTEGRALTO THE ROOFING SYSTEM.
9.) FURNISH AND INSTALL 16 GAUGE PREFINISHED ALUMINUM ONE PIECE COUNTER FLASHING METAL TO Z
- FINISH FLOOR TERMINATE THE WALL FLASHING. O
10.)FURNISH AND INSTALL 16 GAUGE PREFINISHED ALUMINUM EDGE METAL. SAME TO BE COMPLETED WITH A W
CONTINUOUS CLEAT WITH 6" WIDE JOINT UNDER PLATES.
=1 e
11.)FURNISH AND INSTALL 16 GAUGE PREFINISHED ALUMINUM COPING METAL. SAME TO BE COMPLETED WITH A OQ
CONTINUOUS CLEAT WITH 6" WIDE JOINT UNDER PLATES. 17-
FLANGER WEEP 12.)FURNISH LEAD STACK FLASHING OR ALSANS FLASHING ON ALL OTHER PENETRATIONS AND SCUPPERS. Q Z
Lu
GALV. STEEL PIPE 13.)FURNISH TWENTY (20) YEAR POLYGLASS NO DOLLAR LIMIT WARRANTY. U J
SLEEVE (TYP PROVIDE FLEXIBLE COUPLING
(SCH 10 MIN3 WITHIN 6'-0" OF FLOOR M
4 PIPE SLEEVE W/GROUT INTERMEDIATE FLOOR PENETRATION ;;;;';J'4.""""",'^ . SHEET
G-3 N.T.S.
YCENg� yL FILE
.5 046 OF 3
WIL ,0 F644P N, j . L# 50046 PROJECT NO
DA'
CHANGES TO THE DRAWINGS MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFESSIONAL ENGINEER SHALL ADHERE TO THE PROCEDURES OF 61G15-27 F.A.C. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER
THE INTEGRITY OF THE ENGINEERING DESIGN. I 14-169B
ROOF FRAMING PLAN
SCALE. / �\
NOFTH �
ROOF DECK SPECIFICATIONS
TYPE B-H5B-36 GALVANIZED STEEL ROOF DECK, 36" WIDE PANELS, a-1/2" DEI
RIBS SPACED @ 6 O.C., 20 ga, WEIGHT = 2.3 PSF, + S =-.235 IN ,
MANUFACTURED BY VERCO OR APPROVED ALTERNATE. STEEL DECK SHALL BE
FASTENED TO ALL STEEL SUPPORTS W/ 3/4"0 SPOT WELDS @ 6" O.C. & SIDE
OVERLAP SEAMS BUTTON WELDED @ 12" O.C.
VARIES
SEE PLANS SMOOTH LEVEL SURFACE
14" LAP SPLICE MIN
-FORMED SIDES
I -#4 @ 8" Q.C. MAX
I I
o I' #4 @ 8" O.C.
N I I -ROUGH SURFACE
I" "I
-STD. 90' HOOK
--J L -
CONCRETE FLOOR SLAB
REFERENCE SHT S-4 FOR CONCRETE SPECIFICATIONS.
REFERENCE MECHANICAL DWGS FOR ANCHOR BOLTS.
PUMP BASE — TYPICAL SECTION
SCALE: 3/4"=1'- 0"
UGE-P
DOOR AND WINDOW SCHEDULE
MARK
SIZE
DESCRIPTION
10
4'-0" X 6'-8"
EXTERIOR STEEL DOOR
02
3'-0$$ X 6'-8"
INTERIOR/EXTERIOR
STEEL DOOR
03
4'-0" X 4'-0"
BRONZE FRAME SINGLE HUNG
WITH MIRROR GLAZE
TRUDOOR 600 SERIES
®
(2) 3'-0" X 6'-8"
HOLLOW METAL
FRAME LOUVER DOUBLE
DOORS
EXISTING BLOCK WALL —
EDGE OF NEW FLOOR SLAB
20" X 20" CONCRETE GRADE
AM
— — — — — — —
—
14"0 AUGER CAST CONCRETE
��� _�
_
PILE SEE SPEC/NOTES FOR
/
Q
w
M
v
10
CO
In
00
CAPACITY, DEPTH & OTHER RFQ'S I
I p
N
s3
83
I I
w
.-
o
DO
a
m
N
Z
N
N
I
00
w
w
W
w
o
(D
a
I
V5
ILL
20" X 20" CONCRETE
00
I
Lu
U
GRADE BEAM CENTERED
UNDER EXTERIOR CMU WALL
I
_
j/
M
7'-9"
7'-1"
co
w
w
FOUNDATION PLAN
Z�
SCALE: 1 /4"=1'-0"
uS
Lu =Ui
" o
s N
NORTH
Q
z
Z o
U2ow06o
H- c
Z
r¢ 0_ ^'
co
K
N LL n r
N
��p
Q
w
22r
U w C
��
ZX
T.
z
<
a
Q
o
.0�Oa
r w
Uar
>
V
20
z
E
K
S
U
O
N
1§
z
NEW 30 x 68 DOOR IN EXISTING WALL
PROVIDE NEW 8" X 8" PS CONCRETE
HEADER BEAM
SEE DOOR JAMB DETAIL - TYP 2, SHEET S-3
EXISTING
BUILDING
EXISTING
DOOR
ELECTRICAL EXISTING 8"
I
J
PANELS CMU WALL
3' 10'
<
0
EXISTING ROOF OVERHANG �-att-arirr I v-1 rvn L
_ CONCRETE PUMP NEW BX12 — — -
PADS AND PIPING CMU COLUMN
m 0 P Pp 6" PARTITION NON BEARING
° q D
EXISTING • °� \ SEE SHEET G 2
BRICK PAVERS
•
NEW 8 I PROPOSED \ NEW 8
SEE SHEET G-1 FOR CMU WALL
CONCRETE LANDING CMU WALL I PUMP \°sr
ROOM
PUMP SEE NOTE 9 e47/z
PAD. PROPOSED \
ADDITION PROPOSED
°O STORAGE 2 E
FFE = 9.55 ROOM
— DISTANCE TO EXIT 2
NEW 8"
EXISTING LANDSCAPED AREA CMU WALL
EXISTING LANDSCAPED AREA
SCALE: 1/4 =1 0
NORTH
74
RICHARD A. KELLNER, PE - FL#8774
DATE: - :�v _ :2
u COPYRIGHT 2015 W.F. McCAIN & ASSOCIATES, INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANYWAY WITHOUT THE WRITTEN PERMISSION OF THE ENGINEER. CHANGES TO THE DRAWINGS MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFESSIONAL ENGINEER SHALLADHERE TO THE PROCEDURES OF 61G15-27 FAC. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER RESERVED RIGHTS AND MAY VOID THE INTEGRITY OF THE ENGINEERING DESIGN.
to O
LLI
O®
� Q
Z
Z
U
05
m
o
� t
S-1
OF 4
PROJECT NO
14-169B
EXISTING ' NEW ADDITION EXISTING
It
Fr
i�
REAR
RCMR
*2'-0" 3'-3Y4
no
I
STANDBY GENERATOR EXHAUST
TO BE REMOVED
HIGH POINT
16'-1"-
17'-3Y2" — --
EXISTING FLAT ROOF ELEVATION
SCALE: 1/4 =1 0
HIGH POINT
16'-1 "
F11OPOSED ROOFLINE
WITH TAPER PACKAGE
SLOPE = V PER FOOT
FRONT
PROPOSED FLAT ROOF ELEVATION
SCALE: 1/4 ))=i'-o ))
EXISTING SOUTH ELEVATION
S(;ALE: 1/4 =1 0
II
II
PROPOSED DOOR
CBS AddITION
a.-N[M
v
u)fon0
WEST ELEVATION STUCCO OVER MASONRY WALL
Y
N
g
N
N
~
°z
TO MATCH EXISTING BUILDING FINISH
co
4"x6" SCUPPER
LU
w
INSTALL 2-PLY ROOF MATERIAL
PER MANUFACTURER SPECIFICATIONS
z
y
(.5
LU
Q
U
AND CURRENT FBC
W
=
o
V)
U
U
EXISTING BUILDING BUILDING ADDITION
L
FRONT
PROPOSED ROOFLINE OF NEW
BUILDING ADDITION
SLOPE = V PER FOOT
SEE STRUCTURAL DETAILS
14 -5V
WINDLOAD CALCULATION DATA
BUILDING HEIGHT
< OR = 60ft
RISK CATEGORY
II
Vult
170
WIND EXPOSURE
C
TOP OF NEW
ROOFING PACKAGE
8"X6" ALUMINUM GUTTER AND
6" DRAIN PIPE WAAYNER COATING
ANCHORED TO BUILDING EXTERIOR
PER MANUFACTURER SPECIFICATIONS
AND CURRENT FBC
DRAIN AWAY FROM
TOP OF WALL LEVEL
TOP OF ROOF/SLOPE 3/8/FT'
[*7
TOP OF NEW
INTERIOR
FLR. SLAB
STUCCO OVER MASONRY WALL
TO MATCH EXISTING BUILDING FINISH
NORTH ELEVATION
SCALE: 1/4 ))=I'-O"
4"x6° SCUPPER
INSTALL 2-PLY ROOF MATERIAL
PER MANUFACTURER SPECIFICATIONS
AND CURRENT FBC
w
U
0
w
m
CU z
z Z
^ 'w
v/ Z N 0
W w o '0)
p M CO
Q
Z F 0 a LOm
(� wz ul 0V7
O UJ 0 Iz rc
♦�/^ O N fY O N r-
V/ S N r
ctS z ¢ - DO 0
z w � C)
Q v `LU
(� Z8 >
Uca
z
LL J U
O
rn
zz
BUILDING ADDITION
EXISTING BUILDING
TOP OF NEW
TOP OF WALL LEVEL
TOP OF ROOF/SLOPE 3/8°/FT"
ROOFING PACKAGE
8"X6" ALUMINUM GUTTER AND
3'-0"
6" DRAIN PIPE W/KAYNER COATING
(n
ANCHORED TO BUILDING EXTERIOR
z
PER MANUFACTURER SPECIFICATIONS
AND CURRENT FBC
w
Q
TOP OF NEW
DRAIN AWAY FROM FOUNDATION
r
INTERIOR
FLRSLAB
/
w
I— STUCCO OVER MASONRY WALL
TO MATCH EXISTING BUILDING FINISH
SOUTH ELEVATION
SCALE: 1/4 )$=1 1-0);
BARREL TILE ROOF
2" DRIP RAIL
PEEL
ROOF
AND STICK
EXISTING ROOF DETAIL
SCALE: 6"=1'-0"
RICHARD A. KELLNER, PE--EL#8774
DATE
z
cn O
w-
O°
�a
z�
Q z
U®
03
m
S-2
OF 4,
PROJECT NO
© COPYRIGHT 2015 W.F. McCAIN k ASSOCIATES, INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANY WAY WITHOUT THE WRITTEN PERMISSION OF THE ENGINEER. CHANGES TO THE DRAWING% MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFESSIONAL ENGINEER SHALL ADHERE TO THE PROCEDURES OF 61G15-27 F.A.C. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER RESERVED RIGHTS AND MAY VOID THE INTEGRITY OF THE ENGINEERING DESIGN.
14-169B
EXISTING
ROOF NEW ROOF
NOTE 9
NOTE 8
7XISTING CMU
BLOCK WALL
Y8" X 4" STEEL PLATE
EXTEND 8" PAST NEW
OPENING
L NOTE 7
10 NOTE 2
NOT TILED
SEE ROOF
2.
8 X 1
I CONCRETE BEAM W/ (4) #5 CONT &
FRAMING
#3 TII
3 0 8" O.C., TAPER TOP TO SLOPE
PLAN
3.
2-PL
COMPOSITE ROOFING.
4.
2 1/
CONCRETE TOPPING OVER 1.5" DEEP
GALV
TL DECK.
5.
C6 X
.2 STL CHANNELLS ® 24" O.C.
6.
NEW I
CORING OVER FOAM TAPER PACKAGE
EL. 7'-2 1 4"
7.
STEE
ANGLE 3 X 3 X 1/4" W/ 3/4" STEEL
BOTTOM OF
ANCH
R BOLTS @ 24" O.C.
INTERIOR CEILING
8.
EXISTI
G 8" CMU WALL
9.
EXIST]
G ROOF STRUCTURE UNKNOWN,
CONT
CTOR TO EXPLORE PRIOR TO
CONS
UCTION
10.
HILTI
ASONRY BOLT 3/4" X 5" ® 24" O.C.
ROOF SECTION 'A'
SCALE:
14" 0 AUGER CAST PILE
EXTEND VERT. REINF.
UP INTO GRADE BEAM
10" 10'
GRADE BEAM
3/4"=1'-0"
FOUNDATION SECTION 'M'
SCALE: 3/4
EPDXY MIN. 16" #3 BARS
(TYPICAL EVERY OTHER COURSE)
INSTALL NEW 8" CMU
BLOCK AND FILL
rWITH STRUCTURAL GROUT
2 CELLS MIN
FILL EXISTING CP
WITH STRUCTURE
2 CELLS MIN
NEW ]OPENING FRAME
FILL WITH STRUCTURAL GROUT
2 CELLS MIN
EPDXY MIN. 16" #3 BARS
(TYPICAL EVERY OTHER COURSE)
IU BLOCK
_ GROUT
TYPICAL CMU MODIFICATION DETAIL _
SCALE: 3/8" = 1'— J"
ASPHALT ROOFING OVER
2 1/2" CONCRETE TOPPING
OVER 1 1/1' GALV SEE DECK
SEE ROOF
FRAMING
PLAN
EL. 7'-7 3/4"
BOTTOM OF
INTERIOR CEILING C6
O.C.
13 X 3 X 1/4" CONT. W/
3/4" HILTI STL ANCHOR BOLT
0 24" O.C.
SEE SHT G-2 FOR INT.
FINISH WALL
[HORIZONTAL
"IS" CONC. BM CONT.
T & " MID HEIGHT
S @ 8" O.C. TYP
EL. 8'-8'
REF.TOP Of FLRSLAB = 0'-0"
O OVER
U WALL — TYP
24" O.C. IN
GROUTED WALL
—WEB @ 16" O.C. IN
AL MORTAR JOINT
ROOF SECTION 'B'
SCALE:
3/4 „-1 0"
PILE
2--6-
#5 DOWEL @ 12" O.C. TOP
#5 X 6'-0° ® 12" O.C. TIC 1/2" EXP. JT. MATERIAL
#5 X 12" O.C. E.W. BOT
co
.t°�I !° •�' 20" X 20" GRADE
BEAM SEE SECT.
�. ��. L�• f 'M' FOR REINF:
' a 0 AUGERK14"
CAST PILE TYP
CMU WALL
DO NOT UNDERMINE
EXISTING FOUNDATION
FOUNDATION SECTION 'N'
SCALE:
EXISTING CMU
TO REMAIN
NEW DOOR OPENING
S-4 3/4"
NEAT SAW CUT
�� �►r
polvil"m
',AREFULLY REMOVE
MISTING BLOCK —
..J #5 VERT. REBAR
FULLY GROUT CELLS
0••' aing im I gjm I •
SCALE:
3/4"=1'-0"
EXISTING CMU
TO REMAIN
3/4"=1'-0"
ASPHALT ROOFING
SEE SPECIFICATIONS
2 1/2" CONCRETE TOPPING
OVER 1 1/2" GALV STL DECK
SEE S-4 FOR WELDING SPEC
C6 X 8.2
24" O.C.
C3X3X1/4"CONT. W/
3/4" HILTI STL ANCHOR BOLT
© 24" O.C.
8° SEE SECTION 'B' FOR
NOM REINFORCING
VARIES W/ ROOF HT
EL 8'-8"
�a
a• � z
-r8" CMU WALL
BEYOND
—DOOR OPENING
0
Y
co
1a
N
o
U,
~O
z
ROOF SECTION 'C'
o
Q
SCALE: 3/4"=1'-0"
0
W
0
LU
o
LU
O
O
U
8"
8" X 12" CONC.
COL. (4) #6 VERT _
#3 TIES, (1) @4" T& 6
#5 DOWEL @ 12" O.C. TO THEN @ 8" O.C.
(3) #5 X 6'-0" ® 6" O.C. �i r
CENTER ON COLUMN
#5 X 12" O.C. E.W. BOT
--L-------I'-F---' ==J
CMU WALL
ADO NOT UNDERMINE
•) di �� �f EXISTING FEN
xf
20" X 20" GRADE BM pq
14" 0 AUGER CAST PILE
SEE SECT 'M' FOR REINF. SEE SPEC NOTES ON S4
FOR LENGTH, CONC. MIX & REINF.
EL PILES &
GRADE BEAM
FOUNDATION SECTION 'O'
SCALE: 3/4
BEARING
W
NOII 9�
-o� '.�.
0
BEARING
S-4 3/4' 8
NOTE 1 INOTE 2
(1) #5 IN STRUCTURAL
NEAT SAW CUT I GROUT
I
I
I
I
I / #5 VERT IN FULLY
I, GROUTED CELL — TYP
NI
0�TING
�C� I
I
I
I
I
j \ I
/ I
I
I
CORE DRILL 3/4"0 X 6"
EPDXY FILL T & B —TYP
DOOR ELEVATION - TYP 'O'
SCALE: 1/2 "-1)—T
NOTE 1: PRECAST CONCRETE U-UNTEL
LL
f
N
- N O
o O
c N M
< 01
C O 00
' o LU I'
i i F- 0 n
11
i PUQLuC
DOXa
i 0 0 a
Lu
W
U i
LL
iw
U
u)
J
Q
LLu
0
J
Q
ry
D
co
W/ (1) #5 IN GROUTED CAVITY y SHEET
BY CAST CRETE CORP. W
NOTE 2: CONTRACTOR TO SHORE EXISTING �+ �'
cl
ROOF UNTIL LINTEL IS INSTALLED - `
OF 4
RICHARD A. KELC4Ef2, F E - FL#8774 PROJECT NO
DATE: _ z� } 76/•7
u COPYRIGHT 2015 W.F. McCAIN & ASSOCIATES. INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANY WAY WITHOUTTHE WRITTEN PERMISSION OF THE ENGINEER. CHANGE TO THE DRAWINGS MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFESSIONAL ENGINEER SHALL ADHERE TO THE PROCEDURES OF 61G15-27 F.A.C. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER RESERVED RIGHTS AND MAY VOID THE INTEGRITY OF THE ENGINEERING DESIGN. 14-169B
STRUCTURAL NOTES
Governing Code
The herein proposed structural design is certified to be
in accordance with the 2014 Florida Building Code, 5th
Edition.
Design Loads
* Basic Wind Speed = 170 mph (3-second gust)
* Fastest Mile Wind Speed = 132 mph
* Wind Importance Factor (1) = 1.15
* Category II Building
* Wind Exposure = C
* Internal Pressure Coefficient = t0.18
Dimensions and Design
The General Contractor and / or Subcontractor shall
verify all dimensions in the field with this construction
drawing prior to construction. The Engineer shall be
immediately notified of any discrepancies found.
The General Contractor and / or Subcontractor(s) shall
report any discrepancies, errors or omissions to the
Engineer for correction before construction begins.
Should any contractor choose to overlook or fail to
report any discrepancies, errors or omissions to the
Engineer, that contractor shall bear the expense
incurred as a result of such discrepancies, errors or
omissions.
Concrete and Masonry Construction
1.) All concrete materials shall attain the following
ultimate compressive strengths at 28 days:
a) 5,000 psi - piles below the 100-year storm surge
elevation.
b) 4,000 psi - all interior beams and colums
c) 4,000 psi - all exterior beams, colums, all grade
beams and structural slabs.
2.) All concrete shall be ready -mixed and in
accordance with ASTM Specification C 94. All concrete
work shall conform to ACI 318-02. Concrete
maximum slump shall be 3 to 5 inches.
3.) Reinforcing steel shall be deformed, new billet steel
ASTM A-615 Grade 60. All splices and hooks shall be
in accordance with ACI 318-02. Minimum splices shall
be 40 bar diameters (25 in. for # 5 bars). Splices
shall not be made at the points of greatest stress
(i.e.; supports in the case of top steel, and mid -span
in the case of bottom steel. Provide bent bars at
any change in direction or intersection of beams or
columns. Reinforcement partially embedded in
concrete shall not be field bent. Such reinforcement
is to be bent (cold) prior to embedment. The same
applies for masonry reinforcement.
4.) No changes shall be made without written approval
of the Engineer. Contractor is to notify the Engineer
24 hours prior to concrete placement.
5.) All concrete masonry units (CMU) shall have a
prism strength of 1,500 psi minimum.
6.) For walls that are to be grouted and reinforced
provide one (1) # 5 bar per cell for vertical
reinforcement as marked per plan. All masonry
construction shall conform with ACI 530-95/ASCE
5-95/TMS 402-95. All masonry units shall comply
with ASTM C 90-93; and are to be used with Type M
or S mortar adhering to ASTM C 270-92a, and with
grout attaining 2,000 psi at 28 days adhering to ASTM
C 476-91.
7.) For reinforced walls also provide standard 9 ga.
Truss Type horizontal joint reinforcing at 16 in. D.C. in
all walls combined with one (1) # 5 horizontal bar
placed 8 in. above the ground floor slab and one (1)
# 5 bar placed at mid -wall. Horizontal truss
reinforcing shall start at the top of the footing. Also,
it shall be placed at the top and bottom of all
openings, when applicable.
8.) Care shall be exercised during reinforced CMU wall
erection to ensure that cells to be grouted are
lined -up properly, providing a minimum clear area of
10 square inches and minimum clear dimension of 3
in.. Provide saw -cut clean -out hole in bottom course
and remove mortar droppings from cells at end of
each day the units are placed.
9.) Provide footing dowels to match wall reinforcing
size and spacing unless noted otherwise. Lap splice
foundation reinforcing at 48 bar diameters and
terminate reinforcing with standard ACI hooks to
provide continuous reinforcing from footings to
uppermost tie -beams.
10.) Lintels should be poured concrete as noted on the
plans and should be sized for 8 in. bearing on each
side. Provide hooks for # 5 bondbeam reinforcement
with 25 in. laps at all corners, changes in direction
and intersections.
11.) Cover requirements for reinforcing shall be as
follows:
a) 3 in. for piles, beams or columns exposed directly
to earth or weather,
b) 2 in. for concrete beams and columns not exposed
to earth or weather,
c) 1-1/2 in. for slabs exposed directly to earth or
weather, and
d) 3/4 in. for slabs not exposed to earth or weather.
AUGER -PLACED CONCRETE PILES
1.) This section specifies excavation and concrete
required for construction of auger -placed piles,
2.) Piling shall be 14" 0 cast -in -place grout augered
piles reinforced with (6) #6 bars in a circular cage with
#3 spiral ties spaced at 12" O.C. All piles shall have
top elevation as shown on plan and tip of pile elevation
at -16.0' from grade.
3.) Contract price for auger -placed piles will be based
upon total length of piles as measured.
4.) Contractor will submit certification that contractor
has technical qualifications, experience, trained personnel
and facilities to install auger placed concrete piles as
specified.
5.) Install piling with a maximum variation of 3 inches
of center of any pile from the location shown. Piles
shall not be out of plumb more than 2 percent.
6.) Contractor shall submit the following information:
description of the pile drilling and pumping equipment
to be utilized, proposed pile grout mix and description
of material to be used, a pile layout plan referenced to
the structural plans including a numbering system
capable of identifying each individual pile, record of
installation of each pile, pile location and plumbness,
total quantity of grout placed, load test report, design
mix (test reports and proportions) and contractor's
qualifications as specified.
7.) A representative from W.F. McCain and Associates
shall be present at time of pile installation for
verification of materials and installation.
8.) Materials
a) Portland Cement: ASTM C150, Type I.
b) Grout Fluidifler: U. S. Corps of Engineers CRD-C619.
Use Specrete-IP Intrusion -aid (or equivalent)
c) Water: Fresh, clean, and potable.
d) Mineral Admixture: Flyash conforming to C618, Class
C or Class F
e) Reinforcing Steel: ASTM A615, Grade 60.
f Fi
ne Aggregate: re ate: ASTM C33.
9.) The grout used shall consist of a mixture of
Portland cement, aggregate, fluidifier, and water so
proportioned and mixed to be pumped and to fill all
voids in the foundation material. Mixture shall be
proportioned to provide a minimum compressive strength
of 5,000 psi at 28 days with a water - cement ratio
not to exceed 0.40.
A testing laboratory, retained by Contractor, shall design
a mix to produce concrete as specified and perform
tests as required. Certified test reports (duplicate) shall
be submitted. Reports shall include proportions of
design mix.
yd. min.
a) Min.- grout per pile for resid. 1.2 cu.
10.) Execution
a) A Registered Professional Land Surveyor shall
establish lines and levels and stake pile locations.
b) After all auger -placed piles are in place, the
Registered Professional Land Surveyor shall make a field
survey of completed piles and shall submit a drawing to
the Engineer showing actual pile locations with respect
to planned pile locations and indicating plumbness of
piles.
c) Pile Record: Submit complete and accurate record of
oil auger -placed piles to the Engineer. Record shall
indicate the pile location, diameter, length, elevation of
bottom and top of pile, and the quantity of grout used
in each pile. Any unusual conditions encountered during
pile installation shall also be noted.
11.) The Contractor shall cooperate with the owners
geotechnical consultant to insure all installed piles
provide a 21 kip allowable bearing capacity and a 3 kip
allowable uplift capacity. See Note 14 for further quality
control specifications.
12.) Installation
a) The installation shall be performed in an orderly
sequence.
b) Advance the auger at a continuous rate that
prevents removal of excess soil. Stop advancement
after reaching the required depth or refusal criteria.
c) Auger refusal is defined as a rate of auger
penetration of less than 1 foot per minute of drilling.
d) The hole in the bottom of the auger shall be closed
while being advanced into the ground with a suitable
piug. The plug shall be removed by grout pressure or
with the reinforcing bar.
e) Reinforcing steel assemblies shall be detailed and
fabricated in accordance with the manual of Standard
Practice for Detailing Reinforced Concrete Structures
(ACI-318, latest edition). Pile reinforcing, as shown on
the structural drawings, shall be installed after the pile
is grouted by lowering the reinforcement down through
the freshly grouted pile (to the specified depth) before
the grout begins to set. Prior to installation of the
pile reinforcing, centralizers should be placed at the
bottom of the reinforcing and at about 20 foot centers
thereafter to the pile top to assure concentric
placement within the pile. Cage steel shall have 3
inches clearance to the outside of the pile.
f) At the start of pumping grout, raise the auger from
6 to 12 inches and after the grout pressure builds up
sufficiently, redrill the auger to the previously
established tip elevation.
g) Maintain at least ten feet of grout on the auger
flighting above the injection point during raising of the
auger. Positive rotation of the auger shall be
maintained throughout placement of the grout. Rate of
grout injection and rate of auger withdrawal from the
soil shall be coordinated as to maintain at all times
the minimum grout head and a positive pressure on the
gauges. The total volume of grout shall be at least
115 percent of the theoretical volume for each pile,
except, after grout is flowing at the ground surface
from the auger flighting, the rate of grout injection and
auger withdrawal shall be coordinated so that there is a
constant grout flow at the surface. If pumping of
grout is interrupted for any reason, the Contractor shall
reinsert the auger at least five feet into the pile and
regrou t.
h) Minimum volume of grout placed in hole shall be at
least nominal volume plus 15 percent of hole. Volume
of grout per linear foot of pile shall be not less than
volume of grout per foot of test pile. Make volume
measurements in the presence of the Engineer.
i) Auger hoisting equipment shall be provided that will
enable the auger to be rotated while being withdrawn
smoothly and steadily.
j) The spoil that accumulates around the auger during
injection of the grout shall be promptly cleared away
upon completion of the installation.
k) Materials shall be accurately measured by volume or
by weight as they are fed to the mixer. Order of
placing the materials in mixer shall be as follows: (1)
water, (2) fluidifier, and (3) other solids in order of
increasing particle size. Provide grout injection
equipment with a pressure gage in clear view of the
equipment operator. A second pressure gauge shall be
located near auger rig where it can be observed. Rate
of injection and rate of auger withdrawal from soil shall
be so coordinated as to maintain at all times a
positive pressure on gage which will indicate existence
of a removing pressure on bottom of auger flight.
Magnitude of this pressure and performance of other
augering and grouting procedures, such as rate of
augering, rate of grout injection, and control of grout
return around the auger flight, are dependent on soil
conditions, and equipment capability shall be at option
of Contractor, subject to approval of the Engineer.
Equipment for pumping grout shall be positive
displacement pump capable of developing a pressure at
pump not less than 350 psi. Pump shall be calibrated
by an approved method to verify accuracy of indicated
discharge. Remove oil or other rust inhibitors from
mixing drums and pumps. Auger hoisting equipment
shall be capable of withdrawing auger smoothly and at
a constant rate. If the auger jumps upward during
withdrawal, it shall be reinserted, and rate of withdrawal
decreased to prevent further jumping.
I) Locate piles as shown unless otherwise directed by
the Engineer. Do not place piles closer than 7 feet
center to center until grout in adjacent piles has set
for 24 hours. in locations where there are no concrete
slabs or other means of distributing load of the
equipment placing piles, the equipment shall be kept at
least 10 feet away from pile location, or upper 10 feet
of pile shall be cased.
m) Where pile top is near surface or above bottom of
excavation, Place metal sleeves of proper diameter
around pile top.
n) Cut off the tops of piles, square with pile axis and
at the elevations indicated by removing fresh grout
from the top of the pile or by cutting off hardened
grout down to final cutoff point at any time after initial
set has occurred. Where the pi
le cut-off is near the
surface or above the bottom of th excavation sleeves
or casing of the proper diameter d at least 18
inches in length shall be placed ar and the pile tops.
(Special conditions may require meal sleeves of
additional length).
o) Redrill the pile to the original depth at no
additional cost to the Owner if any of the following
occurs:
o1.) The design pile reinforcement cannot be placed
manually in the top of any pile following completion of
grouting.
o2.) The trap door at the bottom discharge outlet fails
to open completely, effectively creating a side discharge
condition.
o3.) Loss of grout head occurs for any reason during
pile installation.
o4.) There is more than a twenty -minute delay during
the grouting of any individual pile.
05.) There is a drop in grout level after completion of
the pile, which exceeds the average for the remainder
of the pile installations by more than two feet.
13.) In the event that non-augerable material is
encountered, such as cobbles, boulders, rock ledge,
metal timbers or debris which causes the rate of
penetration to be reduced to less than one foot per
minute above the desired tip elevation, or causes the
pile to drift from its location, then the pile shall be
completed to the depth of the non-ougeroble material
in accordance with these specifications. The length of
such short piles shall be included in the total linear
feet of pile for payment at the unit price. If required
by the Engineer, additional adjacent piles shall be
placed and the length of these additional piles shall
also be included in the total linear feet of piles for
payment.c
14.) Quality Control
a) Inspection: The Owner shall employ a Geotechnical
Consultant to provide inspection of all pile operations.
The Pile Contractor shall cooperate with the Inspector in
the performance of this work. The presence of Owner's
Geotechnical Consultant shall in no way relieve the Pile
Contractor of his obligation to perform the pile
installation in accordance with the Drawings and these
Specifications.
b) Grout Mix: The grout mix sha be tested by
making a minimum of six two-inc cubes for each day
during which piles are placed. A t of six cubes shall
consist of two cubes to be tested at seven days, and
two cubes to be tested at 28 da and two cubes held
in reserve. Test cubes shall be c ed and tested in
accordance with ASTM C 109. Cube specimens may be
restrained from expansion as descl bed in ASTM C 942.
c) Pile Acceptance: The Geotech>,ical Consultant
shall immediately notify the Contra :tor and Engineer if
any pile is not in conformance with these Specifications.
The volume of grout placed in eac'I pile shall be a
minimum of 115% of theoretical volume of the pile.
The amount of grout placed in eaJh five foot
increments of the pile shall be chdcked continuously
during installation. The cost of removing and replacing
Auger Cast Piles, which are not in conformance, shall
be borne by the Pile Contractor.
d) Reports: The Geotechnical Consultant shall maintain
an installation record of each pile. The record shall
note the project name and number, name of
Contractor, pile location, design pile capacity, pile tip
elevation, pile top elevation, depth of auger
advancement, (total and continuous) quantity of grout
placed, reinforcing steel placemenand any unusual
occurrences during the pile installi:pl ion. The grout
quantity shall be determined by recording grout pump
displacement or by other acceptable means. The
Geotechnical Consultant shall also maintain a daily
report, summarizing all work performed by the
Contractor.
15.) Corrections of Deficiencies
a) The contractor shall notify the Engineer in writing, of
the failure of a pile to meet any requirement of the
specification. Such written notification shall include all
information required for the evaluation of remedial
measures, including all information required for redesign.
b) Based on the survey provided, if a pile fails to
comply with the location or tolerance requirements, the
Engineer of record will calculate the load capacity
requirements of that pile, based on the actual,
"as -driven" locations and inclinations. If the calculation
indicates that the loading on that pile or, if in a pile
group, on any pile in that pile group, exceeds 110
percent of the design load, then the Contractor shall
perform such remedial work as the Engineer of record
in his sole discretion may require including but not
limited to furnishing and installing additional piles at
locations approved by the Engineer of record and
modifying concrete or reinforcement steel. These
corrective measures shall be performed solely at the
contractor's expense.
c) In the case of a pile with some deficiency that
affects load capacity, the Engineer of record will
calculate the load capacity of that pile, based on its
actual, "as -driven" tip elevation, location and inclination,
If the calculation indicates that the, loading on the pile
exceeds the load capacity, then the Contractor shall
perform such remedial work solely at his expense as
the Engineer of record in his sole discretion may
require, including but not limited installing additional
piles at locations approved by the Engineer and
modifying concrete or reinforceme steel.
d) If a pile fails to comply with t requirements of
this Section and the Engineer of cord determines that
modification to concrete or reinfo ement steel, or the
driving of additional piles is neces ry, the Engineer of
record will perform all required re nalysis, redesign and
detailing. All reanalysis, redesign and redetailing costs
will be the responsibility of the contractor and
reimbursed as a change to the contract.
e) The Contractor, at his option and at any time that
he determines that a pile will not satisfy the
requirements of this Section for a reason other than
encountering an underground obstruction, may, subject
to the provisions of this specification, abandon such
pile and replace it with a new pile or piles rather than
await direction or approval from the Engineer or
Engineer of record. However, the Contractor, in
exercising this option, assumes the risk that such
replacement pile or piles will be acceptable to the
Engineer.
f) Abandoned piles shall be cut off one foot below the
elevation of the bottom of the slab and will not be
paid for.
16.) Clean Up
a) All debris from excavation of objectionable material,
removal of obstructions, and any material not to remain
as part of the construction is to be removed and
disposed of by the subcontractor in a legal manner at
no additional cost to the Owner.
b) The site shall be cleaned at frequent intervals and
no material shall be stored on the site in a manner,
which would obstruct the easy access of equipment and
personnel.
17.) Refer to subsurface exploration report by KSM
Engineering dated 5/27/2016 for soil conditions and
pile recommendations.
*Steel Construction*
1.) All steel construction and fabrication
shall be in accordance with the 2005 edition of the AISC
"Specification for the Design, Fabrication and Erection of
Structural Steel for Buildings".
2.) All steel shapes and splicing plates and column bases and
top plates shall be A36 steel. Wide flange beams, W-shapes
shall meet ASTM A992 specifications. Steel tube columns shall
be fabricated from steel with a minimum yield strength of 46
ksi.
3.) All steel members shall be cleaned to remove loose rust and
mill scale, and given one shop coat of red oxide, air drying,
alkyd primer. Cleaning process shall meet or exceed Steel
Structures Paint Council specifications SSPC-SP2 for hand tool
cleaning. Primer shall be formulated to meet or exceed
performance, under laboratory conditions, requirements of U.S.
Federal specification TTP-636. The primer coat thickness shall
be a minimum of one (1) mil.
4.) All welds shall be performed with an E70 electrode, using
either submerged arc or gas metal arc or shielded process. All
welding shall be in accordance with the latest edition of the
AWS "Structural Welding Code".
5.) All bolts used for connections shall be A325 or conforming to
the structural specifications of ASTM A 325, with washers on the
nut and bolt, unless noted otherwise. All bolts shall have an
allowable tensile strength of 44 ksl and an allowable shear
strength of 17.5 ksi or greater. All nuts shall be hex nuts.
Anchor bolts for steel tube columns shall be A307 standard
anchor bolts embeded in concrete.
*General Notes*
1.) All backfill required on -site shall be clean, granular sand
material placed in lifts of maximum 16 in.. The backfill shall be
free from debris and organic material. Fill material shall be
compacted to 95% maximum dry density as determined by
ASTM D1557, All backfill under the slabs
shall be termite treated after compaction. Treatment shall be in
accordance with rules and laws established by the Florida
Department of Agriculture and Consumer Affairs. All areas,
under the building and five feet beyond, shall be cleared,
grubbed and stripped of all surface vegetation. Debris and
stumps shall be removed in their entirety and the exposed
surface shall be proof -rolled with sufficient passes to produce
the required compaction.
2.) The minimum allowable soil bearing capacity shall be 2,500
psf at 95% compaction. Sutability of bearing soils to support
foundations shall be approved soils testing laboratory.
3.) All windows, doors and attachments to be provided for this
project shall be certified by their respective manufacturer to
withstand all required wind loads for the 170 mph Exposure "C"
basic wind speed Induced pressures shown on the floor plans.
Window glass must withstand the Large Missile Impact Test.
Manufacturer's instructions shall be followed if they are more
stringent than the herein shown guidelines (see detail). Follow
manufacturer guidelines for proper sealing and waterproofing of
windows and door assemblies. All manufacturer certifications
shall be provided.
4.) In lieu of the mentioned windows with impact resistant
glass, the Owner/ Developer may opt for the installation of
hurricane shutters. The shutters must also comply with the
stated wind speed requirements. Note that the windows shall
at all times comply with the stated wind pressures.
5.) Soffit material shall be installed as per manufacturer
specifications to withstand the stated wind speeds.
6.) A vapor retarder consisting of 6 mil min. polyethylene with
joints lapped 6 in. and sealed shall be installed underneath all
concrete construction.
7.) All nails and metal hardware exposed to weather shall be
stainless steel. All nails shall be common wire nails unless
otherwise specified. Fill all nail holes in metal straps and
connectors except where noted.
B.) All exposed bolts shall be stainless steel bolts with a
minimum yield strength of 75,000 psi. Non -exposed bolts shall
conform as a minimum to ASTM A325.
9.) The Contractor shall lawfully dispose of all debris resulting
from this project.
10.) All connections not specifically covered herein shall be
made in accordance with the requirements of the Florida
Building Code.
11.) Any omissions made In this section, and in any section in
general, shall be built following standard safe construction
practices and principles and shall be in complete accordance
with all applicable sections of the Florida Building Code.
F6. NOT TO
EXCEED 14"rl
I I
" #10 "PHILLIPS HEAD" ST. STL. WOOD
SCREW W/ MIN. 1.25" FASTENER
PENETRATION INTO 2 x BUCK,
I
S„
HEAD, SILL & JAMBS
REFER TO DETAILS FOR 1 x OR 2 x
BUCKS. NO TO
EXCEED
PROVIDE NO LESS THAN (3) 14"
FASTENERS IN HEAD & (4) PER JAMB.
SEE BELOW. (TYP. NONE IN WINDOW
SILL/ DR. BOTTOM - OTHERWISE
PROVIDE SAME AS HEAD.)
FASTENER SPECIFICATIONS NOTED
ABOVE ARE TYPICAL. FOR ACTUAL
TYPE & NUMBER OF FASTENERS
PER WINDOW SIZE, REFER TO
PRODUCT CERTIFICATION SHEET
PROVIDED BY THE MANUFACTURER.
MANUFACTURER REQUIREMENTS
FOR BUCK ATTACHMENT ARE TO
BE USED IF MORE STRINGENT
THAN THOSE HEREIN SPECIFIED.
MIN. 2 x 4 TREATED
SYP #2 BUCK
SHIMS CONFORMING TO
WINDOW MANUFACTURER
SPECIFICATIONS
C1
Re
-FRAMING OPENING ---I
OPTION 1: 2 x BUCK
3/16" DIA.. "PHILLIPS
HEAD" TAPCON SCREW
W/ MIN. 2" EMBEDMENT
INTO CMU INSTALLED
@ SHOWN SPACING
1 x TREATED SYP #2 BUCK
SHIMS CONFORMING TO
WINDOW MANUFACTURER
a SPECIFICATIONS
°°. TAPCON THRU FRAME
? & BUCK INTO CMU
II
3/16" DIA. TAPCON SCREW
W/ MIN. 2" EMBEDMENT
INTO CMU INSTALLED
@ SHOWN SPACING
DOOR NOTES: MASONRY WALLS
T" 1.) SWING DOOR BUCK ATTACHMENT IS
SIMILAR.
2.) PROVIDE @ EA. DOOR HINGE & @ EA.
STRIKE PLATE (2) SCREWS.
3.) PROVIDE FLASHING, WEATHERPROOFING,
SEALANTS & CAULKING IN STRICT
ACCORDANCE W/ DOOR MANUFACTURER
SPECIFICATIONS.
#10 "PHILLIPS HEAD" ST. STL.
WOOD SCREW W/ MIN. 1.25"
FASTENER PENETRATION INTO
2 x TREATED BUCK (OR FRAMING)
MIN. 2 x 4 TREATED SYP #2
BUCK (OR FRAMING) NEXT
TO 2 x 4 SYP #2 FRAMING
WINDOW WIDTH
RAMING OPENI
OPTION 1: 2 x BUCK
WINDOW �
1 x TREATED SYP #2 BUCK
SHIMS CONFORMING TO
WINDOW MANUFACTURER
SPECIFICATIONS
#10 "PHILLIPS HEAD" ST. STL.
WOOD SCREW W/ MIN. 1.25"
FASTENER PENETRATION INTO
2 x FRAMING THRU WINDOW
FRAME, SHIMS & 1 x BUCK
FRAMED WALLS
OPTION 2: 1 x BUCK
NOTE: REFER TO ARCH DWG'S FOR OTHER
DOOR & WINDOW FRAME DETAILS, NOTERFY
ARHC, WHEN CONFLICS ARE FOUND.
OPTION 2: 1 x BUCK
WINDOW NOTES:
1.) INSTALL WINDOWS PER MANUFACTURER
INSTRUCTIONS & PUBLISHED EVALUATION
REPORTS OR MIAMI-DADE NOTICE OF
APPROVAL.
2.) PROVIDE FLASHING, WEATHERPROOFING,
SEALANTS & CAULKING IN STRICT
ACCORDANCE
W/ MANUFACTURER SPECIFICATIONS.
3.) WINDOWS SHALL COMPLY WITH THE
PROVIDED WIND PRESSURES.
SCALE = N.T.S.
RL F
--
RICHARD A. KELLNER, PE-- FL#8774
DATE:'� - Z�/7
CD
p
QYQ
Q
T
N
col
w
~O
Z
o
Cl)
(
LU
0
_�ovvi
Iw-
Q
O
�
U
o
m
cli
M MM
z 0 U)
o w 0O r- o
U) LL n n
n
= I=-UwC
Q
W Z
m LL
a r O
o O a
�rLu
w
U
LL
UJ
w
U
LL1
O
Z
Q
U)
J
Q
LLl
0
J
F"
U
0
to O
LLI
® 'finn
Z V
W
0 -�
05
m
SHEET
W4
OF 4
PROJECT NO
COPYRIGHT 2015 W.F. MccAIN & ASSOCIATES, INC. THIS DRAWING AND ANY ELECTRONIC FILE IS PROTECTED BY COMMON LAW COPY RIGHTS AND MAY NOT BE REPRODUCED IN ANY WAY WITHOUT THE WRITTEN PERMISSION OF THE ENGINEER. CHANGES TO THE DRAWINGS MAY ONLY BE MADE BY THE ENGINEER; IF ANOTHER PROFESSIONAL ENGINEER ADOPTS THIS DRAWING AS HIS/HER OWN WORK, THE SUCCESSOR PROFEs§10NAL ENGINEER SHALLADHERE TO THE PROCEDURES OF 61G15-27 F.A.C. ANY OTHER CHANGES SHALL BE CONSTRUED AS AN INFRIGNMENT OF THE ENGINEER'S COPYRIGHT OR OTHER RESERVED RIGHTS AND MAY VOID THE INTEGRITY OF THE ENGINEERING DESIGN.
14-169B
FOIISHED GRADE
4°° POWER 24" MINIMUM
CONDUIT SECTION AA
SCALE: N.T.S. REFER TO SHEET
E-04 AND E-05 FOR
REQUIRED
MODIFICATIONS
ELECTRICAL SITE PLAN
SCALE: 1 "=10'-O"
10 5 0 10'
1 1 1
SITE ADDRESS
9400 S. OCEAN DRIVE
JENSEN BEACH, FL 34957
LEGEND
--
SYMBOLS:
CONDUIT CONCEALED UNDERGROUND.
120/208V PANELBOARD
HOME RUN TO PANELBOARD. NUMBER OF
ARROWS INDICATE NUMBER OF CIRCUITS.
HASH
MARKS INDICATE NUMBER OF #12 AWG.
15
DRY TYPE TRANSFORMER, NO
CONDUCTORS. NO HASH MARKS INDICATE
2#12
INDICATED KVA RATING.
CONDUCTORS OR AS NOTED.
SURFACE MOUNTED DUPLEX
RECEPTACLE 20A, 125V MOUNTED
®
PAD MOUNTED TRANSFORMER
12" ABOVE GRADE.
jig SURFACE MOUNTED GROUND
125
ELECTRIC A.C. MOTOR NO. INDICATES HORSEPOWER
FAULT DUPLEX WEATHERPROOF
RECEPTACLE 20A, 125V, 3W -
MOUNTED 18" ABOVE FINISHED
SERVICE OR EQUIPMENT GROUND
FLOOR RATED NEMA 4 WHILE IN
USE.
ABBREVIATIONS:
A AMPERES
MB
MAIN BREAKER
AC AIR CONDITOINER
MIN
MINIMUM
AFF ABOVE FINISHED FLOOR
MLO
MAIN LUGS ONLY
BKR BREAKER
NTS
NOT TO SCALE
CB CIRCUIT BREAKER
NEC
NATIONAL ELECTRICAL CODE
CU COPPER
P
POLE
FBC FLORIDA BUILDING CODE
PNL
PANEL
FPL FLORIDA POWER & LIGHT
SPD
SURGE PROTECTION DEVICE
FVNR FULL VOLTAGE NON -REVERSING
TYP
TYPICAL
GEN GENERATOR
V
VOLT
GND GROUND
WP
WEATHERPROOF
GRS GALVANIZED RIGID STEEL
GENERAL NOTES:
1. CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED.
2. CONTRACTOR SHALL VISIT JOB SITE AND FAMILIARIZE HIMSELF/HERSELF WITH ALL CONDITIONS
AFFECTING THE ELECTRICAL INSTALLATION AND MAKE PROVISIONS AS TO THE COST THEREOF.
3. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, FLORIDA
BUILDING CODE, CURRENT EDITION, AND SHALL COMPLY WITH ALL LOCAL ORDINANCES.
4. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
THE CONTRACTOR IS EXPECTED TO FURNISH AND !NSTALL ALL ITEMS FOR A COMPLETE
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR THE EQUIPMENT TO BE
PLACED IN PROPER WORKING ORDER.
5. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS.
6. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED
BY ENGINEER. LICENSED JOURNEYMAN SHALL BE PRESENT AT THE SITE DURING ALL ELECTRICAL
WORK.
7. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL
INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY
HAVE BEEN DAMAGED.
8. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE OF THE COMPLETED
PROJECT BY THE OWNER.
9. NO OPEN TRENCHES WILL BE ALLOWED TO REMAIN OPEN OVER NIGHT, UNLESS CIRCUMSTANCES
REQUIRE IT AND WRITTEN PERMISSION IS GRANTED BY THE OWNER. TRENCHING SHALL BE AS
PER THE FLORIDA TRENCH SAFETY ACT.
10. CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE CITY AND/OR COUNTY FOR ALL REQUIRED
INSPECTIONS.
11. SLANTED AND SHADED TEXT DENOTES EXISTING EQUIPMENT OR STRUCTURES. NON -SHADED TEXT
DENOTES NEW EQUIPMENT, STRUCTURES, & WORK.
12. ALL CONTROL PANELS SHALL BE UL LISTED AND SHALL COMPLY WITH ARTICLE 409 IN
ACCORDANCE WITH THE 2014 EDITION OF THE N.E.C.
13. MINIMUM WIRE SIZE SHALL BE #12 A.W.G. EXCLUDING CONTROL WIRING. REFER TO
SPECIFICATION SECTION 16050 FOR CONDUIT AND WIRE REQUIREMENTS.
14. ALL UNDERGROUND CONDUIT NOT INSTALLED UNDER THE ASPHALT SHALL BE HAND DUG
INSTALLED 24" MINIMUM BELOW GRADE.
15. CONTRACTOR SHALL VERIFY TYPE AND LOCATION OF EXISTING UNDERGROUND UTILITIES,
INCLUDING IRRIGATION, GAS, TELEPHONE, DOMESTIC WATER & SEWER, ELECTRIC, ETC., PRIOR TO
BEGINNING WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING THESE UTILITIES.
UTILITY DAMAGE BY THE CONTRACTOR SHALL BE REPAIRED BY THE CONTRACTOR AT THE
CONTRACTORS EXPENSE.
16. PROVIDE YELLOW WARNING/LOCATOR TAPE 12" ABOVE ALL UNDERGROUND CONDUIT LOCATIONS.
LOCATOR TAPE SHALL BE "TERRA TAPE" SENTRY LINE 1350 OR EQUAL.
CONFORMED SET
10620 GRIFFIN ROAD, SUITE
COOPER CITY, FLORIDA 333
PHONE: (954) 448-793C
C.O.A. NO. 6783
Stephen E. Bailey, P.E.
Florida P.E. No. 42461
In
CD
cf)
m
CD
N
LIJ
a.a,
o
<n
0
LIJuj
LD
w
Z
x
LLJ
Y
U
i
H
Q
uvi
0
0
U
MEN
Z
J
a
w®
F., Z
a
—1 W
Q J
V 0
w Z
F' Q
V
W
".J
uj
Z
w o
LLI
0®
Z c)
Q Z
wa
��ai1111(1ll/�/ � 0 m
CE
F•,�
N
p ATEOF
.:w 1 SHEET
14-169B
TRANSFORMER
METER ROOM
EXISTING SINGLE LINE DIAGRAM
1� EXISTI NOTES: XICONDUIT TO BE ABANDONED.
EXISTING WIRE TO BE DISCONNECTED AND
REMOVED.
2� EXISTING ELECTRICAL EQUIPMENT TO BE
DISCONNECTED AND REMOVED.
�3 EXISTING ELECTRICAL EQUIPMENT TO BE
REFED. SEE SHEET E-03.
® CONTRACTOR SHALL BE RESPONSIBLE FOR
FOR PROVIDING STANDBY GENERATOR POWER
DURING CONSTRUCTION.
CONFORMED SET
10620 GRIFFIN ROAD, SUITE 2
COOPER CITY, FLORIDA 33328
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E.
Florida P.E. No. 42461 4
N E.egi�
IF
r,
d
W
N
2
Q
>
Lu
W
W
W
2
Q
W
U
0
0
0
N
w
U
w
W
. N
UZ
Zw
w
w
Z
W "
z
W
Q
Z
U�
Oo
U) w
Z
Q w
0 o
a
Z
Q U
U�
U N
Z
0
LL o
N
Q
O
Z
Z
TF
II
w
J
F5
0
z
x
W
0
N
r7 M
Q O C
E1°�a
w cr r,
�0�r,
LLLL r
r
rn QUw.
m O <
0 a L
W
z
t!J O
w H
uj
O�
� d
z0
az
wo
U J
05
co
SHEET
O i
L
14-169B
4-500KCMIL-4"
FPL METER NO.1
7
FPL TRANSFORM =R
IN VAULT
4-500KCMIL-4"
FPL METER NO.2
0
3-350KCMIL, 1-350KCMIL N & 1 #2 GND-4"
�1
NOTES:
ATS-1
CONTROL
MODULE
(GEN
START).
!�2
ATS-2
CONTROL
MODULE
(GEN
START).
3
TO ATS-2 CONTROL MODULE.
®
MAGNETIC ONLY BREAKER 65,000 AIC. NEMA
3R SS.
0
GENERATOR NEUTRAL SHALL BE BONDED TO
SERVICE ENTRANCE GROUND IN SERVICE
ENTRANCE MAIN BREAKER.
©
APT SPDEE SPD
GENERATOR IS A SEPARATELY DERIVED
SYSTEM.
®
RELOCATION WORK TO BE PERFORMED BY
OTHERS. ELECTRICAL CONNECTION BY
CONTRACTOR.
O NEMA
M � NEMA 1
200A,3P
65,000 AIC
6 6 I
4-500KCMIL-4"
NEMA 1 WIREWAY WITH
POLARIS TAPS
4#3/0-2 1/2"
4-250KCMIL-3"
MB1
NEMA 1
250A,3P
BARE COPPER
GROUND GRID
3#3/0, 1#3/0 N & 1#2 GND-2 1/2"
3-250KCMIL, 1-250KCMIL
N & 1#2 GND-3"
SERVICE NO, 1 1
LB
FURNISHED BY OTHERS. RELOCATED SERVICE
INSTALLED BY CONTRACTOR ENTRANCE RATED FIRE
PLIMP
�CONTROLLER
ATS2 350A,3P FIRE PUMP DISCONNECTING
MEANS. MAIN BREAKER SET TO CARRY
LOCKED ROTOR CURRENT INDEFINITELY
MB2
350A,3P
- #1/0 BARE
COPPER TO
GROUND
GRID
350A,4P I
I
SINGLE LINE DIAGRAM
FIRE PUMP
POWER MONITOR
3-350KCMIL & 1/0 GND-3 1/2"
1 M
FIRE PUMP
(5)3-350KCMIL, 1-350KCMIL N
& 1#2 GND-4"
® 350A,3P
BREAKER
GEN BREAKER
NO.1
260A,4P
L1
LC
1 #2 GND 1-250KCMIL N
& 1#2
& GND-3"
3#2, 1#2 N & 1#6GND-1 1/2"
3-350KCMIL, 1-350KCMIL N & 1#2 GND-3 1/2"�5
6#14-3/4"
GENERATOR CONTROL PANEL
300A,3P
GEN BREAKER
NO.2
200 KW, 120/208V,30,4W
GENERATOR
CONFORMED SET
10620 GRIFFIN ROAD, SUITE 20
COOPER CITY, FLORIDA 33328
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E.
Florida P.E. No. 42461
n
❑
CZ7
w
Z
❑
Y
U
=
W
o
Q
cUn
❑
❑
U
N
N O
O O
N M M O
O Qo°0
Z ❑ r
Z W O
F: 0
OR
um) :I xn N
C�
F 0) Q W x
0 0O
CL
L w
o >
LL
w
U
0
W
Z
J
Z
W
O
IL
w
n.
SHEET
OF
14-169B
PANEL "LB" TO REMAIN.
PROVIDE
LABEL ON
FRONT TO
READ "PANEL LB"
EXISTING
A S TO BE
DISCONNECTED AND REMOVED
3,
!---
EXISTING PANEL "LC"
3,.
TO REMAIN PROVIDE
a
LABEL ON FRONT TO
READ "PANEL LC"
PICTURE DETAIL N0.1
EXISTING ENCLOSURES
TO BE REMOVED
EXISTING WIREWAY
TO BE REMOVED
EXISTING POOL
PUMP STARTER TO
BE RELOCATED
EXISTING AC TO BE
DISCONNECTED,
RELOCATED AND
RECONNECTED BY
OWNER.
PICTURE DETAIL NO.3
EXISTING GENERATOR, MUFFLER
AND EXHAUST PIPING TO BE
DISCONNECTED AND REMOVED
EXISTING AC TO BE
DISCONNECTED,
RELOCATED AND
RECONNECTED BY
OWNER. SEE PICTURt.
DETAIL NO.3
EXISTING
LIGHTING IN THIS
AREA TO
DISCONNECTED
AND REMOVED
GARAGE DOOR OPENER
TO BE RELOCATED
EXISTING DOORS
AND WALLS TO
BE REMOVED
EXISTING FUEL
TANK TO BE
DECOMMISSIONED
AND REMOVED
EXISTING POOL
PUMP TIMER TO
BE RELOCATED
EXISTING POOL
PUMP STARTER TO
BE RELOCATED.
EXTEND WIRING AS
REQUIRED SPLICE
O NEW WIRING AND
EXISTING WIRING IN
J—BOX1. SEE
DRAWING E-05
1 FOR LOCATION
EXISTING PANEL —J
"LC" TO BE REFED
EXISTING ATS TO BE
DISCONNECTED AND REMOVED
EXISTING PANEL "LA" TO BE
DISCONNECTED REMOVED AND
REPLACED
EXISTING PANEL "LB" TO BE REFED
ELECTRICAL DEMOLITION PLAN
SCALE: 3/8"=V-0"
12" 0 1 2 4'
(�1
NOTES.
PICTURE
DETAIL
NO.1
SEE
�2
SEE
PICTURE
DETAIL
NO.2
TANKLESS WATER HEATER
CONFORMED SET
N�EN 1E 18A/�����
��F'••��CENSF'• F`
N .42
�'• E F
10620 GRIFFIN ROAD, SUITE 202 � F, E 14�
COOPER CITY, FLORIDA 33328 c
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E. 0 0
Florida P.E. No. 42461
z
0
w
Of
r`
0
a
�
❑
w
cn
oN
LIJ
�
w
Z
�
Y
U
2
H
00
Q
U)
❑
❑
U
Us
z
L
. L
W
f— L_
Q4F
U6
O
U)
Q�
0
z_ e
U
F
LL
I H
N O
OD
m
d w o o
0
�_r-
K LL � N
o = = C
= F U LLJ
w 0
m
o 0 a w
L
w
U i
LL
Lu
w
IU
J
0
2
Lu
Q
ci
w
F—
L)
Lu
J
LJJ
z
V) 0
w �.
0
F Q
z0
a Z
wa
0.1
0S
m
E-04
OF
14-169B
GEN ESTOP GCP
2#14-3/4"
GEN SPACE
HEATER I
GEN JACKET —
WATER HEATER
GEN BATTERY
CHARGER
EXHAUST FAN
EF-1
0
M
X
Cu
m
z STORAGE ROOM
= 6'-0" X 10'-0"
T
EF-1
L1-14
2#14-3/4"L)
m
N
w
I
a..00u�Off
j
U)
a
M
PANEL L1 =�
0
z
ATS-2
LD
3:
U
wui
Q
U
TVz
W
2
_
❑
fn
❑
❑
U
GEN BKRS
L1-9
L1-17 L1-37,39,41
fPANEL "LC' f
GEN CP J
L1-13
— GENERATOR
JBOX1 NEMA 3R SS ENCLOSURE
r'-�' I F- PANEL 'LB" LB—
FPL METER —
---------- NO. 1
-::T - - -
1 0 BARE
5/8" X 20 COPPER GROUND
COPPER GROUND (TYP) 0
ROD (TYP,2)
GROUND TEST
WELL
— MB3
MB3 M81
0
d
a
a
d
1 1/2" EMPTY
CONDUIT
ja
MB2 '
FPL METER NO. 2-
RELOCATED FIRE PUMP
L1-2
MB1
ZR-M
(RELOCATED POOL
PUMP TIMER
RELOCATED POOL
PUMP STARTER
1 FANKLESS WATER
HEATER
RELOCATED FIRE
PUMP CONTROL
PANEL
BY OTHERS UNDER
SEPARATE CONTRACT
ATS-2 v
HYDRO -
TANK
L1-8,10,12-� I TANK L1 -15
I o
L1 I o
I I
.o e
I I
I ® I
° I I STORAGE ROOM
I �
149
r
L1-2
F� I
I
1.5 I L1-2
I
JOCKEY PUMP
IL
FIRE ALARM PANEL. FURNISHED
BY OTHERS INSTALLED BY
CONTRACTOR
L1-2
�1 JOCKEY PUMP CONTROL PANEL AND JOCKEY
PUMP FURNISHED BY OTHER UNDER
SEPARATE CONTRACT AND INSTALLED BY
CONTRACTOR.
LOCATED BELOW MAIN BREAKERS.
SEE SHEET E-01 FOR CONTINUATION.
® EXISTING PANEL LB LOADS TO SPLICED AT
THIS POINT.
Us
Zc
U
IW—
Q
U's
Q
:
In
U`-
LL. i
� N
N O
o rn
M m
z-0'0
0 LU
i~OOrti
LL ry
0 m: C�
03
U W x
' Q LUco O
i W r 0 a LL
w
U
LL
Cr
w
H
V
w
J
w
11- u I z 4 —
E 0 5
10620 GRIFFIN ROAD, SUITE 202 2G� IB � iry OF
COOPER CITY, FLORIDA 33328
PHONE: (8-7930
C.O.A. . N 60. 783
Stephen E. Bailey, P.E. p q
CONFORMED SET Florida P.E. No. 42461 a
HSV � T P� 14-169B
TYPE "Al" LTG -
FIXTURE (TYP,S)
m
a
i
Q
1
R
PANEL L1
ATS-2
L1-7
TORK 2101
PHOTOCELL
E
HYDRO- L_ —
CUMULATOR
TANK
WP
L1-7 L1-2
L1-2
TYPE "B" FIXTURE
(TYP,3)
L1-
L1-2
TYPE "A" FIXTURE (TYP,4)
a �co 0 w
w `�
❑ N }
�= Z Z Y W Lu
LU
❑ ❑ U
10620 GRIFFIN ROAD, SUITE 202
COOPER CITY, FLORIDA 33328
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E.
CONFORMED SET
Florida P.E. No. 42461
y
w
U
Lu
w
in
UZ
Z a
w
W x
Z �
W
Q z
O 2 `n
Q W C
06
Z J c
u
Q U F
U
N Z u
C O F
G j u
1, J
0
Q
z
Z
Z
O
to
13,
N M
M
COOF ❑Lo
- 0
LU W w t
0 r'- C>
In h ^
F- (=j `ur,
0)w xx
m 0
Boa``
w
z
a
J
a
0
z
J
f1moy
SHEET
E-06
OF
I ElIW:�L
^^LIMI 11T ^I ALAM
�"2"
STAINLESS STEEL CHANNEL
1 CONDUIT PIPE
E-08
GROUND WIRE BOND
BIND CIRCUIT CONDUCTOR
IN EACH CONDUIT WITH
NYLON STRIPS. °
COPE TYPE 'C' CABLE C
RACK AND ARM
#6 BARE TO STEEL
CONDUITS AND STEEL
COVER BOND WIRES.
9
5/8" X 20' GROUND ROD
TRAPEZE ASSEMBLY
P MOUNTIN
N.T.S.
CLASS H2O TRAFFIC RATED COVER AND FRAME.
WALKWAY AND
WALL MOUNTED
D ETAI
J '
n
2' X 2' X 4' OLDCASTLE PRECAST
CONCRETE PULLBOX
PVC END BELL FITTING SUITABLE
FOR USE WITH SCHEDULE 80, AND
SCHEDULE 60. MANUFACTURED BY
CARLON ELECTRICAL PRODUCTS OR
EQUAL. (TYPICAL)
OPEN SUMP
PULL —IN EYE OPPOSITE
DUCT ENTRANCE
GRAVEL
QIKLUG TYPE
"QDA" —�
E
LIGHTING FIXTURE SCHEDULE
MANUFACTURER
TYPE
WATT
DESCRIPTION
INFORMATION
4'-0" LONG LED FIXTURE WITH DIE —CUT CLOSED CELL NEOPRENE GASKET SEALS/HOUSING.
KENALL NOVA 1 N548
50 WATT 5000 K LED WITH DIMMINS CONSTANT LED DRIVER WITH PHILLIPS BODINE BSL310
SERIES
Al
50
EMERGENCY BATTERY BACK—UP. U.L. LISTED SUITABLE FOR WET LOCATIONS.
(7100)—LED OR EQUAL
SAME AS TYPE 'Al', EXCEPT WITHOUT EMERGENCY BATTERY PACK.
KENALL NOVA 1 N548
A
50
SERIES
(7100)—LED OR EQUAL
FULL CUT—OFF WALLPACK. DECORATIVE, DIE—CAST ALUMINUM HOUSING AND DOOR. TYPE III
LITHONIA DSXW2 LED
B
log
OPTICAL PRECISION LENS. 120V INTEGRAL BALLAST WITH 30 LED PLATFORM. 5000 K COLOR
SERIES OR EQUAL
TEMPERATURE
EXIT SIGN W/CAST ALUMINUM HOUSING & ALUMINUM STENCIL FACE, BLACK BAKED ENAMEL
BEGHELLI OR
®
5
FINISH, SEALED NICKEL CADMIUM BATTERY, SELF CONTAINED AUTO —CHARGING, WALL OR
APPROVED EQUAL
CEILING MOUNTED AS REQUIRED. 120V—AC, 12V—DC.
CD
U)
w
CD
`"
a
W
>
>
0
LU
Z
0
LLJ
Y
=
FW
o
Q
cVn
0
o
v
RECESSED HOLD
14-5/8" -I
DOWN (TYPICAL)
PRE -CAST
CONCRETE
o
£
MECHANICAL
CONNECTION
I:
`
e
N
�
U
LIFTING HOLE
°
z i
COURSE SAND OR
CAST IRON COVER
PEA GRAVELLLJ
(OPEN BOTTOM)
Q j
U I
3" HIGH LETTERS
GROUND WIRE
O
CAST IN IRON COVER
U '
05 '
COMPACTED
Z
GRAVEL BASE
Q1
5/8" X 20'
v
COPPERCLAD
5
SECTION
GROUND ROD
GROUND TEST
WELL
FINISHED GRADE
a
Q
d a
d d Q00
d O
O
d O
MOTOR
NOTES: RIGID CONDUIT
1� ALL WIRES IN PULL BOX TO BE LABELED INDICATING CIRCUIT
NUMBERS. SEE SPECIFICATIONS. O
MOTOR FOUNDATION
Q DO NOT SPLICE CABLES IN PULL BOXES UNLESS OTHERWISE NOTED.
3� PATCH CONDUIT ENTRY WINDOW WITH CONCRETE. 1 FINISHED SLAB
#2 GROUNDING CABLE
TO GROUND LOOP OR
3
PULL BOX D ETAI L SIMILAR SYSTEM GRID
t 7--A
—08 N.T.S.
NOTE:
THIS GROUND IS IN ADDITION TO THE GROUND
FROM THE MAIN ELECTRICAL SERVICE.
�\ MOTOR GROUNDING DETAIL
NTS
N.T.S.
CONCRETE SLAB
3000 P.S.I
°
d
O
O
a
°
d
Q
d
a
°
Q
a
CONCRETE SLAB DETAIL
N.T.S.
9 °
CONCRETE SLAB NOTES:
iv
O GENERATOR PAD SHALL BE 12" THICK AND
'-
REINFORCED W/S 12' O.C. EA. WAY TOP AND
° IL
BOTTOM. GC TO VERIFY ALL PAD SIZES AND T/PAD
ELEVATIONS WITH THE VENDOR DRAWINGS AND
MEP/CIVIL DRAWINGS. PADS SHALL BE A MINIMUM
OF 4' ABOVE FINISH GRADE AND CONSTRUCTED ON
COMPACTED SUBGRADE.
(Z STRUCTURAL CALCS SHALL BE SUBMITTED WITH
GENERATOR SHOP DRAWINGS. G.0 SHALL PROVIDE
CALCS SIGNED AND SEALED BY A STRUCTURAL
ENGINEER REGISTERED IN THE STATE OF FLORIDA.
CONFORMED SET
��: •'�,�CENSF
N .424
�0 5 F
r ....
.
r � .
I 3`/ r 1
10620 GRIFFIN ROAD, SUITE 203` d•
COOPER CITY, FLORIDA 33328
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E. O
Florida P.E. No. 42461 0. AAA
N
rno
;o
M m
Z
.-
W p1LL
0� 0 o
J
>
U) W ti ry
O
x x r
�x
I—ULij
a Z
C Q
W
xx
O Q
0
0- W
; <
-0
W
U
>
K
? U
I
J
F_
W
p
J
U
w
U
Lu
Z
cn 0
W ~
p
0p
�a
Z
a Z
Wp
0
�t
SHEET
E-08
OF
14-169B
SYMBOLS
NOTES
O THERMOSTAT
1. WORK SHALL BE COORDINATED WITH BUILDING CONDITIONS
® SMOKE DETECTOR
AND THE WORK OF OTHER TRADES PRIOR TO STARTING AN!
WORK.
�+1 VD VOLUME DAMPER
2. WORK IN THIS CONTRACT INVOLVES NEW BUILDINGS AND
EQUIPMENT. ADJUSTMENTS TO DESIGN LAYOUTS REQUIRED I'Y
FIELD CONDITIONS SHALL BE MADE AT NO ADDITIONAL COS"
—® FD FIRE DAMPER
TO THE OWNER.
rev ER EXHAUST REGISTER
3. THE HVAC SYSTEMS IN THIS PROJECT ARE PROCESS COOLI JG
SYSTEMS, WHICH ARE EXEMPT FROM THE REQUIREMENTS 0 -
THE FLORIDA BUILDING CODE, CHAPTER 13 FLORIDA ENERG f
RG RETURN GRILLE
EFFICIENCY FOR BUILDING CONSTRUCTION. SEE SECTION
101.5.7 OF THE REFERENCED ENERGY CODE.
�xy SR SUPPLY REGISTER
WALL MOUNTED EXHAUST FAN
�\ ROUND FLEXIBLE INSULATED DUCT
SHEET METAL DUCT
ELECTRIC UNIT HEATER
ABBREVIATIONS
A AIR
GS GALVANIZED STEEL
ACCU AIR COOLED CONDENSING UNIT
GPM GALLONS PER MINUTE
AHU AIR HANDLING UNIT
HP HORSEPOWER
ALUM ALUMINUM
HW HOT WATER
AFF ABOVE FINISHED FLOOR
KW KILOWATT
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING
LD LINEAR DIFFUSER
AND AIR—CONDITIONING ENGINEERS
NTS NOT 70 SCALE
BDD BACKDRAFT DAMPER
OA OUTSIDE AIR
BS BIRDSCREEN
PCD PERFORATED CEILING DIFFUSER
BTU BRITISH THERMAL UNITS
PAC PACKAGED AIR CONDITIONING UNIT
CFM CUBIC FEET PER MINUTE
PSI POUNDS PER SQUARE INCH
CD CEILING DIFFUSER
PVC POLYVINYL CHLORIDE
COND CONDENSATE
RA RETURN AIR
DB DRY BULB
RG RETURN GRILLE
DG DOOR GRILLE
REF REFRIGERANT
DN DOWN
SEER SEASONAL ENERGY EFFICIENCY RATIO
DS DISCONNECT SWITCH
SP STATIC PRESSURE
DIA DIAMETER
SS STAINLESS STEEL
EA EACH
SR SUPPLY REGISTER
EAG EXHAUST AIR GRILLE
SMACNA SHEET METAL AND AIR CONDITIONING
EDH ELECTRIC DUCT HEATER
CONTRACTORS NATIONAL ASSOCIATION
EUH ELECTRIC UNIT HEATER
TG TRANSFER GRILLE
EER ENERGY EFFICIENCY RATIO
TYP TYPICAL
EF EXHAUST FAN
UH UNIT HEATER
ER EXHAUST REGISTER
UL UNDERWRITERS LABORATORY
FD FIRE DAMPER
WB WET BULB
FRP FIBERGLASS REINFORCED PLASTIC
WG WATER GAUGE
FT FEET
EXHAUST FAN SCHEDULE
ITEM
NO.
N0.
IREQ�D
AREA SERVED
[SHEET
N0.
CFM
S.P.
TYPE
H.P.
VOLT
FAN
RPM
SONS
VALUE
GREENHECK
MODEL N0.
REMARKS
CONTROL
SET
WHEEL
DRNE
PHASE
EF-1
1
GENERATOR ROOM
H-2
707
0.25"
WALL
PROP.
DIRECT
1/12
1115
1550
5.6
SE1-10-440—D-1
EC,D,WH,T
THERMOSTAT
T = LINE VOLTAGE THERMOSTAT
HONEYWELL T631 OR EQUAL
EC = HI —PRO POLYESTER COATING
r-
ON FAN &ALL ACCESSORIES
m
CD N
UJ
TE = TEFC MOTOR
a
1n
D = INTERNAL NEMA 3R DISCONNECT
SWITCH, MOUNTED AND WIRED.
o
WH = EC COATED WALL HOUSING WITH
Z
0
Z
Y
W
a
J
WALL ANGLES & MOTOR GUARD.
o
iL
MALL HOUSING FOR FAN
,LL THREAD ROD, EXTEND
UCTURE ABOVE. SECURE
S FASTENERS. TYPICAL
SS U—CHANNEL SUPPORT. TYPICAL.
EXHAUST FAN MOUNTING DETAIL
N.T.S.
t1111 I1t
QNEN E Ba
No. 61
= Tyr
10620 GRIFFIN ROAD, SUITE 202
COOPER CITY, FLORIDA 33328
PHONE: (954) 448-7930
C.O.A. NO. 6783
Stephen E. Bailey, P.E.
CONFORMED SET Florida P.E. No. 42461
�4
w
w
U
D:
W
U�
Z of
w
w
_z
W zw
z
f— w
Z
UW
Oz
z
in 02
fn >
Qz
w
06 z
z
a
Z�
Q U
U�
U z
z
� o
LL o
V)
j w
z
z
z
T
0
to
rn
N
(0M
W 0 0 0
O
c~n LL
2 2 � rc—N
rn U W x
m O
O d W
W
SHEET
H-01
OF
14-169B
INTAKE LOUVERED -
DOUBLE DOORS WITH
24 SQUARE FEET OF
LOUVERED AREA
6'W X 5'H
EXHAUST
LOUVER
I
GARAGE :�E
0
DOOR �:D
MOTOR o�
m
z
T
EF-1
m
SH
GEN BKRS
JLrB
GEN CP
n_
GENERATOR
EF-1
700 CFM
-1 SEE DETAIL
FPL METER
—_— NO. 1 —
;E ROOM
X 10'-0"
JBOX1 lil
F- PANEL "LB"
2'X4' INTAX
LOUVER
u m.
FPL METER NO. 2
RELOCATED FIRE PUMP
m
a
PANEL L1
MB1
MB3
RELOCATED POOL
PUMP TIMER
RELOCATED POOL
PUMP STARTER
1 TANKLESS WATER
HEATER.
IATS-2
v
IN
RELOCATED FIRE
PUMP CONTROL
PANEL
1
I
BY OTHERS UNDER
SEPARATE CONTRACT
I
HYDRO-
CUMULATOR
TANK
I
I
I
STORAGE ROOM
J *HVAC WORK IN THIS
AREA TO BE PROVIDED BY
t� OWNER
JOCKEY PUMP
FIRE ALARM PANEL
WP
U!
z i
SHEET
H-0A9
OF
14-169B
PLUMBING SYMBOLS
SYMBOLS
DESCRIPTION
L
BOOSTER PUMP SYSTEM SPECIFICATION
TWO PUMP VFD IRONHEART REMOTE TANK
Water Pressure Booster System
Furnish and install a prefabricated variable speed IronHeart water pressure booster system
as manufactured by SyncroFlo, Inc., Norcross, GA. The system shall be capable of
providing a controlled system pressure of 97 psig with flow rates from 0 to 220 GPM
when suction pressure is 50 psig minimum, and 70 psig maximum, using 208 Volt, 3
phase, 60 hertz power.
Each Pump shall deliver 143 GPM at 120 FT TDH (52 PSID) with 10 HP motor. (65%
/ 65% split)
CODE COMPLIANCE
All packaged equipment shall be independently Third Party labeled as a system suitable
for the intended use by a Nationally Recognized Testing Laboratory in accordance with
OSHA Federal Regulations, and NFPA Pamphlet 70, National Electric Code Article 90-7
MANUFACTURERS QUALIFICATIONS
Pump system manufacturer must have no less than 20 years experience as a designer
and manufacturer of domestic water pumping systems for commercial buildings.
Manufacturer must have designed, built, and supported not less than 10,000 pump
systems and been under continuous management for not less than twenty
years. Manufacturer's testing instrumentation must be traceable to NIST standards. Include
current certifications with substitution request. Manufacturer must be ISO 9000 certified.
PUMPS AND MOTORS
Pumps shall be single stage end -suction design with cast iron bronze -fitted or stainless
steel construction, equipped with sleeve -mounted mechanical shaft seals and close coupled
to a high efficiency motor with class F insulation. Pump designs that do not have shaft
sleeves shall not be acceptable. Pump shall be fitted with single inside mechanical seal
with carbon vs. ceramic faces, stainless steel spring and hardware and Buno-N
elastomers. Pumps shall be selected closest to the best efficiency point. Motors shall be
non -overloading at duty point.
To protect the pump against overheating, provide a mechanical over -temperature protection
device on the pump discharge that will divert flow to drain when water temperature
exceeds 140 F.
ISOLATING VALVES
Provide isolation valves on the suction and discharge of each pump. Valves shall be lug
style butterfly valves with hand lever operator rated for a minimum 200psig W.P. Valves
shall be certified to NSF 61 drinking water standards. Gate valves shall not be
acceptable.
CHECK VALVES
Provide a wafer style check valve to prevent back flow of water on each pump discharge.
Check valve shall be manufactured from gray iron and shall be rated for a minimum of
200psig W.P. All contact surfaces shall be suitable for potable water service.
PUMP SEQUENCING
The controller shall optimize power consumption based on flow, VFD speed, and power
consumption. As a backup, a factory set pressure switch shall sequence pumps when
system pressure falls below the setpoint. Automatic sequencing shall include the following
features:
I. Flow sequencing, if a flow sensor is specified.
2. Power sequencing, programmable in horsepower not Watts
3. Pressure sequencing .
4. End -of -curve protection, based on pump differential, with 2% accuracy
5. VFD speed sequencing
6. Lead pump shutdown feature that can be enabled or disabled by the operator
7. Low -flow test feature testing pressure, power, VFD speed, and flow (if equipped
with flow sensor), to reduce pump short -cycling, pressure swings, power surges, and
motor wear.
8. Tank pressurization sequence to increase the energy stored in the tank prior to
shutdown
9. Time clock to disable lead -pump shutdown during building occupancy.
10. Sequence shifting that adjusts the pump sequence when any pump is disabled
11. Successive and 24 hour alternation of equal capacity pumps
12. Pump overlap during 24-hour alternation
13. Lag pump exerciser function
14. Special sequencing to reduce surges during power restoration
15. Sequential sequencing of lag pumps
16. Minimum run and stop delay timer for each pump
17. Field adjustable time delay for lag pump pressure start signals
18. Field adjustable low suction pressure alarm
19. Field adjustable selection to enable / disable limited auto reset of low suction and
high system pressure alarms
*i1111:IerA&IIIILI(IRTIEVA; N' I III
Provide a factory pre -charged, ASME code and NB stamped, HydroCumulator tank. Tank
shall include a replaceable FDA approved Butyl rubber flexible membrane to separate air
and water. No water shall come in contact with the walls of the tank. The
HydroCumulator tank shall be shipped pre -charged to the proper design conditions. The
tank shall be located near the top of the building, as indicated on the plans. Contractor
shall install the tank and provide floor drain as required by the manufacturer for adequate
serviceability.
POWER AND CONTROL PANEL
Furnish a power and control panel in NEMA I (minimur d enclosure complete with
programmable controller, epoxy -coated backpan, operate r interface, individual pump
through -the -door disconnects, and 120V control circuit transformer. The complete
assembly shall have the UL listing mark for industrial ontrol panels. Provide
circuit -breaker protection, not fuses that require replacement. The primary control power
circuit breaker shall comply with UL file code 489 one the secondary circuit breaker with
UL file code 1077. All components must conform to It.- IPIO finger safe design to
protect against accidental contact. All internal power wl ing must be 90 C rated per
UL508A. Size power wire in accordance with UL508A Table 28.1. Control panel must
meet 65,000 SCCR Rating.
5.7"COLOR TOUCHSCREEN INTERFACE
The touchscreen interface shall be flush mounted in the door of the control panel.
The following data shall be accessible through the operator interface:
I. System status including flow rate (GPM), current , ystem pressure and setpoint, pump
run status, the current speed of the pumps (in % , and the method of speed
control.
2. Usage history shall record the maximum instanton= ous flow, along with the date and
time. Overall and current day totalized flow, puml starts, and pump run hours are
also recorded. Usage history may be reset.
3. A Set Points Menu system for adjusting setpoints Display and adjust flow, pressure,
differential pressure, VFD speed, power, minimum speed, lead pump shutdown mode,
and tank pressurizer set points and time delays. I'estore to either factory defaults
or the last saved field defaults. Protect adjustab a settings with a password.
4. Alarm History of the past 200 alarms. Each log shall include individual pump run
status, system pressure and run setpoint, alarm t) )e and the date and time.
5. Alarm List of all possible alarms and their currer status.
6. Startup instructions and checklist.
The HMI shall include a method for transferring data
I. Alarms shall automatically copy to an installed ca ipact flash drive.
2. Include fault codes from the PLC and the VFD.
3. Copy usage data to the drive daily.
4. Data shall be stored in a text file, readable by m n-proprietary software.
5. HMI Software shall allow for program changes to the HMI and PLC to be
transferred via the compact flash drive.
PROGRAMMABLE LOGIC CONTROLLER
The PLC manufacturer shall be clearly marked on the I ontroller, and non-proprietary. The
PLC shall be installed on the control panel backpan, ni t the door, to protect it from
damage. The PLC shall continue to function even if thi touchscreen is broken, damaged,
or removed.
VARIABLE FREQUENCY DRIVES
Each pump shall have its own variable frequency drive tith the following features:
I. Voltage source, GTR or IBGT power transistor ba ed inverter - PWM Type
2. Use a high carrier frequency to reduce drive and notor noise
3. Shall be capable of operating in an ambient temp :rature between 15 degrees F and
100 degrees F and a line voltage variation of les! than 10 percent.
4. Self protection features shall include: under voltag I and over voltage protection,
current overload protection, short circuit protection power failure protection, ground
fault protection, and over -temperature protection.
5. Include a four -digit LED readout to indicate the f plowing: drive enabled, output
frequency, and all VFD fault conditions.
6. The drive shall automatically restart after any of Ile following: overload over -voltage,
converter over -current, inverter over -current, or power failure.
7. The following drive parameters shall be user adju: 'able: acceleration speed (I to
300 seconds), deceleration speed (I to 300 sect ids), minimum speed, and
maximum speed.
8. The drive shall have a front mounted "HAND-OFF -AUTO" selector switch and a
potentiometer for adjusting drive speed in the "HA JD" position.
9. Minimum 1000,000 SCCR
10. The VFD shall use the following energy saving tel hniques
a. Slows down the motor
b. Reduce current
c. Reduces voltage
d. Evaluates 6 motor characteristics to further increc re efficiency
II. The VFD shall communicate with the PLC with a AGITAL connection, with the
following capabilities:
a. Able to modify 300 different VFD parameters thr Hugh the PLC and HMI
b. Read all VFD data and communicate it to the PL :, HMI, and write to the compact
flash drive.
c. BACNei Conn still available
Install variable frequency drives smaller than 40 HP im de a NEMA I control panel, or
provide dust protection to an externally -mounted drive. I" installing inside an
enclosure, provide thermostat -controlled ventilation, size( according to manufacturer's
instructions.
PRESSURE TRANSMITTERS
Digital pressure transmitters shall be connected to the suction and system headers. The
transmitter shall have 1.0% accuracy, stainless steel wetted parts and a waterproof
enclosure. Transmitter shall be IP67 rated, and capable of withstanding over
pressurization of double its range. The transmitter shall use a digital 1-6 kHz pulse
output that can be directly sent to a programmable logic controller (PLC) without requiring
an additional analog module for measuring current. The transmitter zero set point must be
capable of field calibration.
INSTRUMENTATION
Each system shall have pressure gauges for indicating suction and system discharge
pressure, and control power light. All pump or header -mounted pressure gauges shall
be 4Yz"glycerin filled gauges. All panel mounted gauges shall be 2 1/2"glycerin filled
gauges. Gauges shall have a stainless steel case and crimp ring, copper alloy movement
with the case connection sealed with EPDM 'O"-ring. Gauges shall be according to ASME
B40.100, Grade A and shall have an accuracy of 1% of span.
EMERGENCY CONTROLS AND ALARMS
Furnish temperature relief valves at each pump, low suction, low system and high system
pressure alarms, indication of first activated alarm, pulsing alarm horn with silence
function, and individual alarm auxiliary contacts, time delays, and indicating lights. Provide
backup sequencing and controls to provide temporary operation when the touchscreen or
PLC is inoperable or removed.
FACTORY PREFABRICATION
The system shall be factory prefabricated. Furnish flanged schedule 40 suction and
discharge headers, which can be reversed in the field. All branch and header wetted parts
shall be minimum 304 stainless steel. The only field connections required will be to
system headers, tank, over -temperature drain tube, and one incoming power connection at
the control panel.
All skid members must be properly designed structural steel members to adequately
support the weight of the entire system and resist bending during transportation.
To minimize leak points, all branch and header connections shall be flanged or welded
with the only threads located at the pump discharge.
FACTORY TEST AND CERTIFICATION
The booster system and its component parts shall undergo a complete operational flow
test from zero to 100% design flow rate under the specified suction and net system
pressure conditions. This flow test shall be performed by supplying the control panel with
the specified incoming voltage. Each pump's performance shall be tested over its full
range of flow. All adjustments shall be set and all functions verified. Components shall
be tested for hydraulic shock, vibration, or excessive noise. Any parts found to be
defective must be replaced prior to shipment. Full documentation shall be maintained by
the manufacturer showing flow rates, pressures, and amp draws for future service and
troubleshooting. In the Operation and Maintenance Manuals, include an X-Y graph of
system pressure -flow performance, when required.
FIELD PIPING
The contractor shall install the system adjacent to a floor drain sized in accordance with
local code. This drain is to prevent building damage in the event of seal failure and to
receive over -temperature protection discharge. The contractor shall pipe the temperature
relief valve discharge line to the drain. To reduce the possibility of damaging vibration,
the contractor shall install the pump system on a flat housekeeping pad, bolted and
grouted in place. The pump system shall be piped with a bypass and isolation valves,
and with flexible connectors at the header connections.
SYSTEM WARRANTY
The complete pumping system shall be guaranteed in writing by the manufacturer for a
period of one year from date of startup or eighteen months from shipment, whichever
comes first, against defects in materials and workmanship. Warranties and guarantees by
the suppliers of various components in lieu of single -source responsibility by the
manufacturer will not be accepted. The PLC, Touchscreen HMI, and VFD's shall also be
warranted for 5 years by a single third -party.
OPTIONAL EQUIPMENT
The IronHeart system is available with several optional equipment that will enhance the
performance of the system and customize it to your specific application. Please select
one or more of the available options that is required for your application:
• TEFC motors
• NEMA 12 enclosure
• NEMA 4 enclosure
• Energy savings mode light (during high suction or tank operation)
• Low level alarm in lieu of low suction (controls by others)
• Electric purge valves
• Split skid
• Pressure transmitter on suction
• Vertical configuration
• Left hand connections
• Electrical by-pass for ATL operation with relief valve
M
CD -
- X
8
-SD-
P
VTR
WC
UR
HL
L-(No)
HB
SS
OF
EWC
EWH
GWH
SH
HS
FD
RD
E)
C.O.?
-C.O.
--0-- C.O.
�I
773�7-
�A.B,C,D
COLD WATER (CW)
HOT WATER (HW)
SEWER (S)
VENT LINE (V)
RECIR. HOT WATER
CONDENSATE DRAIN
EXISTING PIPE
CONNECT TO EXISTING
STORM DRAIN (SD)
PUMP
VENT THRU ROOF
WATER CLOSET
URINAL
HAND LAVATORY
LAVATORY
HOSE BIBB
SERVICE SINK
DRINKING FOUNTIAN
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
GAS WATER HEATER
SHOWER
HAND SINK
FLOOR DRAIN
ROOF DRAIN
GATE VALVE
GLOBE VALVE
CHECK VALVE
BACK FLOW PREVENTER
VALVE IN YARD BOX
(TYPE AS NOTED)
PRESURE RELEIF VALVE (RV)
WATER METER
ELBOW - UP
RISE OR DROP
CONCENTRIC REDUCER
DIRECTION OF FLOW
CLEAN OUT (RISER)
CLEAN OUT
WALL CLEAN OUT
PLUGGED PIPE
SHOWER HEAD
PUMP W/FLOW DIRECTION
FLOW SWITCH
PRESSURE SWITCH
WATER HAMMER ARRESTER
WITH P.D.I. SIZE
I. PLUMBING CONTRACTOR IS TO FURNISH AND INSTALL ALL
PLUMBING FIXTURES COMPLETE AS LISTED IN "PLUMBING FIXTURE
SCHEDULE".
2. PLUMBING CONTRACTOR MAY USE SCHEDULE 40 OR 80 TYPE I,
GRADE I, POLYVINYL CHLORIDE PIPE FOR ALL SOIL, WASTE AND
VENT PIPING WHERE PERMITTED BY LOCAL CODES. WHERE PVC
PIPING IS NOT PERMITTED BY LOCAL CODES, USE STANDARD
WEIGHT CAST IRON PIPING. ALL PIPING ABOVE GRADE MAY HAVE
HUBLESS FITTINGS. PLASTIC PIPING SHALL NOT BE USED IN A
RETURN AIR PLENUM. COORDINATE THIS REQUIREMENT WITH
H.V.A.C. CONTRACTOR.
3. PROVIDE SHUT-OFF GATE VALVES ON ALL EQUIPMENT a HOSE
BIBBS, 8 STOP COCKS IN HOT AND COLD WATER PIPING TO ALL
PLUMBING FIXTURES.
4. ALL WATER PIPING BELOW GRADE SHALL BE TYPE "L" SOFT
TEMPERED COPPER AND ALL WATER PIPING ABOVE GRADE SHALL
BE TYPE "L" HARD TEMPERED COPPER.
5. INSTALL I" FOAM RUBBER INSULATION ON ALL HOT WATER
PIPING ABOVE 8 BELOW GRADE. ALL JOINTS IN INSULATION ARE
TO BE TAPED.
6. ELEVATION OF ALL FLOOR DRAINS SHALL BE HELD 1/2" BELOW
FINISH FLOOR TILE.
7. ALL MATERIAL AND INSTALLATIONS SHALL BE IN ACCORDANCE
WITH ALL LOCAL AND STATE PLUMBING AND MECHANICAL CODES,
INCLUDING THE STANDARD BUILDING, PLUMBING AND MECHANICAL
CODES, NFPA, ASME, ASHRAE, ASA AND AGA.
8. THE SANITARY SYSTEM INCLUDES CONNECTION TO FIXTURES,
RUNNING OF SOIL AND WASTE LINE AND SOIL AND VENT
SANITARY SEWER SYSTEM AND/OR SEPTIC TANKS AND DRAIN
FIELDS AND ALL ITEMS AS SHOWN ON DRAWINGS. VENT STACKS
SHALL EXTEND THROUGH ROOF WITH LEAD FLASHING.
9. THE DOMESTIC WATER SYSTEM INCLUDES CONNECTIONS TO THE
DESIGNED SYSTEM, CONTROL VALVES AND PIPING TO PLUMBING
FIXTURES, INCLUDING CONNECTIONS TO EQUIPMENT FURNISHED BY
OTHERS.
10. PIPE INSTALLATIONS AND MATERIALS SHALL BE AS REQUIRED TO
MAINTAIN FIRE RATINGS WHERE REQUIRED BETWEEN FLOORS
AND/OR BETWEEN UNITS.
II. ARRESTERS SHALL BE INSTALLED WHERE NECESSARY TO
PREVENT WATER HAMMER.
12. COPPER PIPING WHERE USED SHALL NOT CONTACT DISSIMILAR
METALS OR MASONRY. PROVIDE ISOLATING BUSHINGS WHEN
CONNECTING TO ANY DISSIMILAR METALS.
13. PLUMBING CONTRACTOR SHALL COORDINATE WITH ARCHITECT FOR
DETAILED DIMENSIONS AND LOCATIONS OF ALL FIXTURES AND
EQUIPMENT AND FOR ANY CHANGES IN LAYOUT.
14. PLUMBING CONTRACTOR SHALL MAKE ALL TEST AND ADJUST-
MENTS AS REQUIRED, UPON COMPLETION OF WORK AND PRIOR TO
FINA_ ACCEPTANCE BY OWNER.
15. AFTER COMPLETION OF THIS WORK, THE CONTRACTOR SHALL
OBTAIN A CERTIFICATE OF FINAL INSPECTION AND APPROVAL
FROM ALL AUTHORITY'S HAVING JURISDICTION.
16. ALL WORKMANSHIP, MATERIALS AND APPARATUS UNDER THIS
CONTRACT SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR
FROM DATE OF FINAL ACCEPTANCE BY THE OWNER.
PLUMBING DRAWING INDEX
SHEET DESCRIPTION
P-1 I PLUMBING Lt GEND, NOTES, a SPECIFICATIONS
P-2 PLUMBING Pi AN
ISSUED
YES
YES
�a C
Fort Pierce
Engineering, Inc.
Dependable Mechanical, Electrical
& Plumbing Design
C.A. No. 28173
315 South 7th Street
Fort Pierce, FL. 34950
Phone: 772 672-4636
Fax: 772 672-4637
>0)
0 m
� o v
te
a�// a u-
24 U
W of
E x a
v� w
O m
O 11 z oN w
w 0
w �
z
W_J O rnUJ
Q
W
47
Q >�
0 a
w W z
Ix z ro
0 w
V F_0 a:Q O U =
U
w
[� 0 3o j W
� z F- I__
IAJ Q U n Z
W o w U to
U 0Z
LU
0- O ° 0 rn
ENGINEER SEAL
3. SVO
00
.-"!o E �v5
(�o } '982
cc
c As
,toP�pP:���.
fr��roA `O''N� A4ilto
Eric J. Svoboda, PE
P.E. No. 60982
UK ""CIKIRS, P `Ill" TK CO PM MID M "ES1=
PRESEIRID HSh]N ME WEII OEr FM THE SPEf,61C
PURPLE MO OMT T FOR PIERCE IMMERMG, MG M
NRCN UY VERE PREPPFED, REUSE M IMWD'FR RSuPPSE OI
TITRE OINEIITS VITIWT VRI NJIIQtI]ATIOi MID
AOii"im! "r Fan PIERCE EIEOEX ERM., MC SHALL T
V)ilpJl LIARILITr TR THE S R CO'YK=VM 6, FOR
PORT£ OIGDEFRMG, MC ALL RRHIS RESERVE0.
SHEET TITLE
PLUMBING
LEGEND, NOTES,
SCHEDULES
& DETAILS
ISSUE DATE: 07-11-2017
DRAWN: EJS
APPROVED: EJS
If DRAWING NUMBER I
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
SHEET I OF 2
16039-01
U) a
W a
U) Y
W
U) ¢
W
Model 132 HydroCumulator Tank
Features and Benefits
1. The vessel is ASME code
(Section 8. Div. 1, UG 90 C-2) and
NB stamped for 125 PSIG*.
Maximum temperature is 240' F
(consult the factory for higher
temperatures). Nominal volume
is 132 gallons.
2. The tanks shell is made of Steel.
The bladder is FDA approved
Heavy Duty Butyl.
3. The 100% draw down design of
the tank prevents the bladder from
rupturing at any storage volume
or pressure within its ratings. This
provides maximum water storage
at all conditions.
4. The vertical design and bottom
water connection eliminate water
stagnation in the tank, making it
ideal for drinking water use.
5. The specially designed distribution
tube allows the tank to be fully
pre -charged with air at the factory.
6. Water is kept inside the bladder
while air is between the bladder and
the tank shell. This keeps water rust
free and protects the tank from corrosion.
7. Tank dry weight: 330 Lbs.
AIR PRESSURE: -
GAUGE 0-300 LB.
SYSTEM
CONNECTION
1 1/2"NPT
13 1/2"
LIFTING
RING
STANDBY
GENERATOR
I Li 18" OVERHANG
d �
WV
WV
I
I I
ASPHALT PARKING LOT
B
E
F
H
I
J
1
I
I
I
I PUMP
a0•
TNSK M / L
PACKAGE 4' HEADER CONNECTIONS.
BYPASS CONNECTION WITH
CHECK VALVE.
EDGE OF PAVEMENT
f�
f�
C= PLUMBING PLAN
D
m
u)
Cn
-
0
—44
ch
00
SCALE: 1/4" = 1'-0"
18" OVEi
r1 NU,
I UESUKIF I1UN
Inventory #
QTY,
1
DUPLEX IRUNHEART SKID
09-200-4428
1
2
110 HP PUMP/MOTOR
12-511-4010
2
3
2,5' x 4,5' 150-150#
S770-025-0045
2
4
REDUCER SPOOL 2,5' x 15' 150-150#
S771-025-0015
2
5
CHECK VALVE WAFER STYLE 2-1/2'
43-022-1024
2
6
2,5' x 7' 150-150#
S770-025-0070
2
7
2,5' LUG ISOLATION BUTTERFLY VALVE NSF_42-447-3024
4
8
DUPLEX HEADER 4' x 2,5'
S772-040-0024
2
9
DUPLEX PANEL STAND 42' X 36'
779-200-4236
1
t0
SYSTEM POWER AND CONTROL PANEL
SF952-0100-208S
1
PLEASE ENSURE THE USE OF PROVIDED
PIPE SUPPORT DURING SYSTEM INSTALLATION
HYDRO TANK DRAWING BOOSTER SYSTEM DRAWING
SCALE: 2:I SCALE 2:1
NOTES,
1. ALL DIMENSIONS SUBJECT TO CHANGE VnIWr HMCE
2 PURGE VALVE AMAIN LOW TO BE PIPED TO FLOOR DRAIN IN PROOOTY
OF BLUSTER SYSTEM GY OTHERS)
3 SEE DATA SHEET FOR UH OR RAH (FADERS ENTRY/EKIT CONNECTION
SYNCNIFLO PACKAGED PUMPING SYSTEMS COMPLY YRH OSHA
REGULATIONS AND FEDERAL REGULATION 29 CAR 1910399, THE ENTIRE
PACKAGED SYSTEM IS TIDRD PARTY CERTIFD34
PROPRIETARY DRAWING
TIDE K IOLIIEIIr B HIE PiBFRIT 6
SyncroFlo
�pF ppeLopv�ueop G[eeeu
pl �0 p NIY VAY �cL 1il TE CDPMII'
DUPLEX IRONHEART
I 10 HP
SlyncroRo
6)tl kst AFN Dtl -s,aas G 3♦ll - OAO MMRI - is UN Niel
4 1�22D110XXX-4H-XX-SWF55-3
(GENERAL NOTES:
I. INSTALL NEW BOOSTER PUMP IN EQUIPMENT ROOM AS INDICATED.
2. FIELD COORDINATE EXACT SYSTEM CONFIGURATION a LOCATION TO ALLOW
FOR PROPER PLACEMENT WITH NECESSARY SERVICE CLEARANCE / ACCESS
IN ROOM & COORDINATE WITH FIRE PUMP INSTALLATION.
3. CONNECT PACKAGE HEADER PIPING TO BUILDING WATER SERVICE AND
WATER SUPPLY THROUGH EQUIPMENT ROOM WALL.
4. INSPECT AND MONITOR EXISTING BUILDING PIPING UPON PUMP START UP
FOR LEAKS DO TO INCREASED PRESSURE. PRESSURE REDUCING VALVES
MAY BE REQUIRED ON LOWER BUILDING FLOORS TO KEEP PRESSURE BELOW
80PSI. CONTRACTOR IS RESPONSIBLE TO ENSURE INTEGRITY OF BUILDING
WATER SYSTEM PIPING IS MAINTAINED WHEN PUMP IS ACTIVATED.
ESPECIALLY AT INTERFACES/CONNECTIONS BETWEEN COPPER OR CAST IRON
PIPE AND PVC PIPE.
5. SEE CIVIL PLANS FOR FURTHER DETAIL ON INCOMING / OUTGOING WATER
CONNECTIONS.
6. SEE ELECTRICAL PLANS FOR ELECTRICAL CONNECTIONS.
KEYNOTES:
lO INCOMING 6' WATER - SEE CIVIL PLANS,
0 OUTGOING 6' WATER TO BUILDING SUPPLIES - SEE CIVIL PLANS.
BOOSTER PUMP CALCULATIONS
Building Elevation = 100 9
Pressure required at top = 50 PSI
Type of structure is an apartment
Total Fixture Units = 2368
Total Peak Load = 220 GPM
Building static head = 43 PSI
Building piping friction loss = 4 PSI
Required system pressure = 97PSIG
Minimum suction pressure = 50 PSI
Maximum measured suction pressure = 70 PSI
(65 PSI average street pressure)
Differential (boost) pressure = 47 PSID
E1'STEM
DATA
System Information
Nominal
Pump Information
Model: 22Dnoxxx-4H-xxsWFls1
Pump#:
1&2
Design Flow rate: 286
Gpm
Pump Type:
CCES
System Pressure: 97
Psig
Construction:
SS
Min. Suction Pressure: 50
Psig
Pump Model:
A3U-40-160
Max. Suction Pressure: 70
Psig
Design Split:
65
% Each
Boost Pressure: 47
Psig
Design Flow:
143
Gpm
Control Valve: 2.5
In
Pump Head:
120
Ft
Pump Shutoff:
82
Psig
Seal Type:
Mechanical
Motor Size:
10
Hp
Headers: 4" SS
Motor Speed:
3500
Rpm
Configuration: Horizontal
Motor Enclosure:
ODP
Connection: Flange
Motor S.F.
1.15
Power Data
Sliecial
Comments
Incoming Power Requirement:
Tank Model: 132
Voltage: 30/60-/ 208
V
Connection FLA: 68.7
A
Wire Size: 4
G
Control panel: NEMA 12
Panel SCCR: 10,000
PRESSURE SET POINTS
Low System set at: Sys Pr - 5
Sig
Low Suction set at. 5
)Sig
Horsepower set at: 10
rc
Shutoff Boost: 10
is d
Fort Pierce
Engineering, Inc.
Dependable Mechanical, Electrical
& Plumbing Design
C.A. No. 28173
315 South 7th Street
Fort Pierce, FL. 34950
Phone: 772 672-4636
Fax: 772 672-4637
w I`
�0)
�
o v
M
Z
Q J
tea/
W
LLJ
U
W
o=
E
V]
=a
w
�
m
0
U) z
w
w
w
O z
a/
J
U
CF ILI
0)
W
E�
U
E-'
Q
>
U)
�v
x
M
W
W
z
Z
M
U
o
w
~ w
O
moLd
Z
w
wooU=U)
ZL_4w
IL
CC
o
0) Lu
ENGCILNEER SEAL
"E OF
Eric J. Svoboda, PE
P.E. No. 60982
SHEET TITLE
PLUMBING
FLOOR PLAN
"""" --"` 07-11-2017
DRAWN: I
APPROVED: EJS
DRAWING NUMBER
P 2
SHEET 2 OF 2
16039-01