HomeMy WebLinkAboutHVAC LOADSSCANNED By Wayne Thomas Residence HVAC Load Calculations for Wayne Thomas Lot 63 Nettles Island Blvd. Fort Pierce, Florida E Emijt J %1 Wie /FZZsiD9HTukL r C, - HVACLoADs Prepared By: Residential Energy Calds a Thursday, February 28, 2013 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. �Rhvac Residential'& Light Commercial HVAC Loads.. Eute 5otrware ueveiopmen�,,.i. Residential+Energy Calc's 1Nayne, s Thoma Residence ,Port,Saint,L6cie,,FL,34983,-�,�-,Pam 2 Project Report. Project Title: Designed By: Project Date: Client Name: Client Address: Client City: Company Name: Wayne Thomas Residence RFM Design Thursday, February 28, 2013 Wayne Thomas Lot 63 Nettles Island, Blvd. Fort Pierce, Florida Residential Energy Calc's Reference City: Fort Pierce, Florida Building Orientation: Front door faces West Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude Factor: 0.999 Elevation Sensible Adj. Factor: 1.000 Elevation Total Adj. Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 809% n/a 70 n/a Summer: 90 78 59% 50% 75 61 Cheek Figures Total Building Supply CFM. 906 CFM Per Square ft.: 0.695 Square ft. of Room Area: 1,303 Square ft. Per Ton: 555 Volume (W) of Cond. Space: 12,3111 Total Heating Required Including Ventilation Air: 26,130 Btuh 26.130 MBH Total Sensible Gain: 20,315 Btuh 72 % Total Latent Gain: 7,837 Btuh 28 % Total Cooling Required Including Ventilation Air: i 28,153 Btuh 2.35 Tons (Based On Sensible + Latent) Rhvac is an ACC_ A approved Manual J and Manual D computer program. , Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. L;:� ...xvvayne Thomas Residence.rh9 Thursday Fehruary 9R 9nl3 a•dn pen / Rhvac a Residential & Light Commercial HVAC Loads_.- „ Elite Software Development, inc. Residential Energy'Calc's Wayne Thomas Residence Por[,Samt�Lucie, FL 34983 •.. :, : -:... , , . Page Miscellaneous Report :, . System 1,Rheem Or Equivalent '' Outdoor'; Outdoor ; Outdoor,::_-, Indoor._ Indoor Grains, `Difference Input Data D Bulb VVet Bulb ' ReLHum°„ Rel.Hum D Bulb Winter: 1 42 39.4 80% n/a . 70 n/a Summer: 90 78 ' 59% 50% 75 61.09 Duct Siz166 inputs' Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01000 Pressure Drop: 0.1000 in.wg./100 ft. 0.1000. in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air: Data ° Winter Summer Infiltration Specified: 0.450 AC/hr 0.230 AC/hr 92 CFM 47 CFM Infiltration Actual: 0.433 AC/hr 0.195 AC/hr Above Grade Volume: X 12,311 Cu.ft. X 12,311 Cu.ft. 5,333 Cu.ft./hr 2,402 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 89 CFM 40 CFM Total Building Ventilation: 25 CFM 25 CFM ---System 1--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.450 AC/hr (92 CFM), Construction: Average Summer Infiltration Specified: 0.230 AC/hr (47 CFM), Construction: Average Duct Load �Factor, Scenarios for System 1 Attic ,: Duct Duct;; Surface from. N0. `. T pe . ..Description . Location Cpilin `" Leakage: Insulation Area [T]MDD' 1 Supply Open Crawl - 0.12 6 352 No 1 Return Cond. Space - 0.12 6 65 No t,: i ... xvvayne i nomas Kesiclence. rh9 Thursdav,Februarv28.2n1� A•anaen Rpvac -Residential &>Light Commercial HVAC Loads,Elite Software Development„ Inc. Residential Energy.Calc's Wayne Thomas Residence Port Saint Lucie, FL 34983' Pa e 4 Load Preview Report Net ft.z Sen Lat Net Sen Hts Sys Clg Sys Act Duct Scope Ton /Ton Area Gain Gain Gain Loss CFM CFM CFM Size Building 2.35 , 555! 1,303 20,315 7,837 28,1531 26,130_ 330 % 906, 906 - - - _ _ System . - - - -- - - - - 2.35 555, - -- - - 1,303 20,315 300 m . - - - 7837' 28,153 1;- ----- --.. 2613 - 6,J 330' 06 906 - I Ox0' _ Ventilation 4121 1,0383 1,450 i 769 Duct Latent 1040 1,040 _. _ ;.- ----- ---- Zone 1 1 303 : 19,903 5,760 663 25 360 330 � 91-Foyer/StairwayI_25 1-Foyer/Stairway 74 437 ' 34471 r 1707 22 ®I_ _20 -1-0" --..L _... _ . _ _ 2-Dining .___-` _.,. �----_ 169 , ; 2,276 - , 812 ; 3,088 1,704 2_2 ; - 104 -1-0' - --- ... --- --- ---° Mtchen --- 112, 2,854� 1,228 1 4,082._.3,053 130 1-0' 4-Bath 1 100, 932 +. 254 ; 1,1861 3,380 44. 42 1-0' 5-Great Roam 247' 4,008! 401 , 4,409: 7,659 100 182 2-0' 6-Stairway 98: 772' 65: 837; 755 M - 35 - - 1-0' - _._..._.. -. ..__ . .. - .. ..__._. ...._ ._ _ .- _ ---- 7-Bath2_ . _. ._ 617' r -. 347f; <. . - 445rt 28 1-0« - 8-Master Bedroom _ r�.., -- 182 4,217 933 5150 9�_;�. 4000 52i 192 -.. 2-0' _._. ._._, ._.._.._. _:...__ 9-Walk In Closet .__..70 50 378 108 486 807 -6® 10117 1-0' 10-Master Bath 92. 1,663, 779 2,442 843 1'I M 76 1-0' 11 Den ------------- 109 1,750 799 s 2,549 1,006 13 80 1-0' CA ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential & Light` Commercial HV_ AC Loads Elite Software Development, Inc. Residential Energy Calds 111"Port.SEiint .. Wayne Thomas Residence LFL 34983 � - Pae5'ucie, Duct Size Preview Room or Source Minimum Maximum Rough. Design SP Duct Duct Htg Clg Act. Duct Duct Name Velocity Velocity Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 Supply Runouts Zone 1 1-Foyer/Stairway Built -In 450 750, 0, 0.1 0, 22 20 1-0 2-Dining Built -In 450 750' 0. 0.1 ` - 0 - - - 22 ® 104 1-0 3-Kitchen Built-in_ 450 750 01 J 0.1 - 0, - 40 ® 130 1-0 4-Bath 1 Built -In 450 750 0 0.1 0 44 42 1-0 5-GreatRoom Built -In 450 750 0 0.1 0 100' 182' 2-0 6-Stairway Built-in 450 750 0 0.10 1035 i 1-0 - - -- - 7-Bath2 Built-in _ ---- 450 - . 750 8-Master 8M s Built -In 450 750 Oi _ 0.1 . 0.1 0` ._ 52 ® 192' 2-0 9-Walk In Closet Built -In 450 750' 0 0.1 0 10 17, 1-0 10-Master Bath -- 'Built-in 450 750 0 0.1 0 - --- - 11 ® 76 1-0 _. .._ _ ....._. _...., 11-Den ...... ,.,.._. Built -In ._ 450 ..... 750 _0 0.1 , 0 13 ® 80' _ ..._ 1-0 Other Ducts in System 1 Supply Main Trunk Built -In 650' 900 0. 0.1 0. 330 906; Ox0 Summary System 1 Heating Flow 330 Cooling Flow: 906 CA ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhv1C 7 Residential & Light Commercial KVAc LOWS =uir oulmdua uCvtkupulcny Residential Energy_Cald' Wayrie Thomas Residence Port Saint Lucie EL 34963 Page 9 Total Building SummaryL Loads 1A-cb-o: Glazing=Single pane, operable window, clear, 44 1,331 0 3,802 3,802 metal frame with break, u-value 1.08, SHGC 0:75 1A-cm-o: Glazing -Single pane, operable window, clear, 84 2,988 0 3,012 3,012 metal frame no break, u-value 1.27, SHGC 0.75 11 D: Door -Wood - Solid Core 21 229 0 213 213 13A-5ocs: Wall -Block, board insulation only, R-5 board 1392.6 4,875 0 2,664 2,664 insulation, open core, siding finish 12E-Obw: Part -Frame, R-19 insulation in 2 x 6 stud 132 135 0 135 135 cavity, no board insulation, brick finish, wood studs 16C-19: Roof/Ceiling-Under Attic with Insulation on Attic 847.7 1,163 0 1,662 1,662 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 138 5,248 0 0 0 insulation below floor, any floor cover, passive, heavy soil ---moist Subtotals for structure: - 15,969 0 11,488 11,488 People: 10 2,000 2,300 4,300 Equipment: 2,100 3,000 5,100 Lighting: 0 0 0 Ductwork: 6,656 1,040 2,454 3,494 Infiltration: Winter CFM: 89, Summer CFM: 40 2,735 1,660 661 2,321 Ventilation: Winter CFM: 25, Summer CFM: 25 769 _ _1,038 412 1,450 ---------------------------------------- -- -- Total Building Load Totals: 26,130 7,837 20,315 28,153 Total Building Supply CFM: 906 CFM Per Square ft.: 0.695 Square ft. of Room Area: 1,303 Square ft. Per Ton: 555 Volume (ft3) of Cond. Space: 12,311 Buildin Loads Total Heating Required Including Ventilation Air: 26,130 Btuh 26.130 MBH Total Sensible Gain: 20,315 Btuh 72 % Total Latent Gain: 7,837 Btuh 28 % Total Cooling Required Including Ventilation Air: 28;153 Btuh 2.35 Tons (Based On Sensible + Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:1... 1Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential_& Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's Wayne Thomas Residence 'e Port Saint Lucie, FL 34983 Pa 12. S stem 1,, Rh:eeM 'Or EgWvalent :Sumrna ;Loads, ; Sen r Lat : Sen .. Total` [qomponen,ti."Area Desch tion":; h. ,Quan :; Loss f ,Gain; Gain ; Gain, _. _,_ 1A-cb-o: Glazing -Single pane, operable window, clear, 44 1,331 0 3,802 3,802' metal frame with break, u-value 1.08, SHGC 0.75 1A-cm-o: Glazing -Single pane, operable window,, clear, 84 2,988 0 3,012 3,012 metal frame no break, u-value 1.27, SHGC 0.75 11 D: Door -Wood - Solid Core 21 229 0 213 213 13A-5ocs: Wall -Block, board insulation'only, R-5 board 1392.6 4,875 0 2,664 2,664 insulation, open core, siding finish 12E-ObIw: Part -Frame, R-19 insulation in 2 x 6 stud 132 135 0 135 135 cavity, no board insulation, brick,finish, wood studs 16C-19: Roof/Ceiling-Under. Attic with Insulation on Attic 847.7 1,163 0 1,662 1,662 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 138 5,248 0 0 0 insulation below floor, any floor cover, passive, heavy soil _ _moist Subtotals for structure: 15,969 0 11,488 11,488 People: 10 <, 2,000 2,300 4,300 Equipment: .2,100 3,000 5,100 Lighting: 0 0 0 Ductwork: 6,656 1,040 21-454 3,494 Infiltration: -Winter CFM: 89, Summer CFM: 40 2,735 1,660 661 2;321 Ventilation: Winter CFM: 25, Summer CFM: 25 769 1,038 412 1,450' _ System 1 Rheem Or Equivalent Load Totals 26,130 7,837 20,315 28,153 Check Fi uses Supply CFM: 906 CFM Per Square ft.` 0.695 Square ft. of Room Area: 1,303 Square ft. Per Ton: 555 Volume (ft) of Cond. Space: 12,3'11 S` stem "Loads Total Heating Required Including Ventilation Air: 26,130 Btuh 26.130 MBH Total Sensible Gain: 20,315, Btuh 72• % Total Latent Gain: 7,837 Btuh 28 % Total Cooling Required Including Ventilation Air: 28,153 Btuh 2.35 Tons (Based On Sensible + Latent) Notes r r Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit.that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Re$ Light Commercial HVAC Loads ; Development, IncElite Sftwa `sidential C Energy alp' WayneTiora6 ResidenceResdentaI 'Page „Port'Saint` Lucie -FL 34983 , 1? Systom 1, Zone 1 Summary,Loads '(Average Load Procedure for Rooms) Cornponent Area Sen; , -C ; Lat ;; Sen :' �< Quan Loss_ ; Gain r 'Gam Total Gain Descnption ` . . 1A-cb-o: Glazing -Single pane, operable window, clear, 44 1,331 0 3,802 3,802 metal frame with break, u-value 1.08, SHGC 0.7, 5 1A-cm-o: Glazing -Single pane, operable window, clear, 84 2,988 0 3,012 3,012 metal frame no break, u-value 1.27, SHGC 0.75 11 D: Door -Wood - Solid Core 21 229 0 213 213 13A-5ocs: Wall -Block, board insulation only, R-5 board 1392.6 4,875 0 2,664 2,664 insulation, open core, siding finish 12E-Obw: Part -Frame, R-19 insulation in 2 x 6 stud 132 135 0 135 135 cavity, no board insulation, brick finish, wood studs 16C-19: Roof/Ceiling-Under Attic with Insulation on Attic 847.7 1,163 0 1,662 1,662 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake; Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 138 5,248 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil_ _ Subtotals for structure: 15,969 0 11,488 11,488 People: 10 2,000 2,300 4,300 Equipment: 2,100 3,000 5,100 Lighting: 0 0 0 Ductwork: 6,656 0 2,454 2,454 Infiltration: Winter CFM: 89, Summer CFM: 40 2,735 1,660 661 2,321 System 1, Zone 1 Load Totals: 25,360 5,760 19,903 25,663 Check Fi ures` r Supply CFM: 906. CFM Per Square ft.: 0.695 Square ft. of Room Area: 1,303 Square ft. Per Ton: 609 Volume (f?) of Cond. Space: 12,311 ;Zone Loads: - Total Heating Required: 25,360 Btuh ' 25.360 MBH Total Sensible Gain: 19,903 Btuh 78 % Total Latent Gain' 5,760 Btuh 22 % Total Cooling Required: 25,663 Btuh 2.14 Tons (Based On Sensible + Latent) .Notes r Rhvac is an ACCA approved Manual J and Manual,D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Reside1 1,ntial & LI ht Commercial, HVAC Loads °. - f Elite Software Development, ncr "Wayne [=n-;,tialEnergy CaVs `: Thomas Residence Port Saint Lucie, FL 34983 ;... , . „ . s Page 20 Detailed, Room. Loads..- Room ,1 - Fo er/Stairway (Average.'Load Procedure - General _ Calculation Mode: Htg. & clg. Occurrence's: 1 Room Length: 18.4 ft. System Number: 1 Room Width: 4.0 ft. Zone Number: 1 . Area: 74.0 sq.ft- Supply Air: 20 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 2.0 AC/hr Volume: 589.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 20 CFM Percent of Supply.: 8 % Runout Duct Size: 0 in. Actual Summer Vent.: 1 ' CFM Runout Air Velocity: 0 ft./min. - Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual. Winter Infil.: 2 CFM Actual Loss: 0.000 in.WgJ100 ft. Actual Summer Infil.: 1 CFM Item ,; n_ ,�� AreaY U �, ., Htg s Sye/n �� Clg; �y' Lat;,Sen. r ... Description ,' ; , Quanti# ;;Value,„, :; HTM r 7 >, LossGain' ,'.. W -Wall-13A-5ocs 4 X 8 11 0.125 3.5 39 1.9 0 21 S -Part-150/150-12E=0bw 16.5 X 8 132 0.068 1.0 135 1.0 0 135 W-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 Floor-22A-ph 21 ft.. Per. 21' 1.358 38.0 799 0.0 0 0 Subtotals for Structure: ^ 1,202 0 369 Infil.: Win.: 1.8, Sum.: 0.8 32, 1.781 57 0:438 34 14 Ductwork: 448 54 Room Totals: 1,707 34 437 UA ... Mayne Thomas Residence.rh9 I Thursday, February 28, 2013, 9:40 PM Ijhv_ac Residential & Light Commercial HVAC Loads ,, Residential Energy Cal c's . Port 5610t1 cie, FL 34983 °.'-Page Software h glopme Inc:' Elite S ev Residence Wayne T omas Resid 21 Detailed Room Loads-- Room .2 -Dining (Average Load Procedure). `General r Calculation Mode: Htg. &,clg. Occurrences: 1 Room Length: Room Width: 13.0 ft. 13.0 ft. System Number: Zone Number: 1 1 Area: 169.0 sq.ft. Supply Air: 104 CFM Ceiling Height: Volume: 8.0 ft. 1,352.0 cu.ft. Supply Air Changes: Req. Vent. Clg: 4.6 AC/hr 0 CFM Number of Registers: Runout Air: 1 104 CFM Actual Winter Vent.: Percent of Supply.: 2 CFM 2 % Runout Duct Size: 0 in. Actual Summer Vent.: 3 CFM Runout Air Velocity: Runout Air Velocity: Actual Loss: 0 ft./min. 0 ft./min. 0.000 in.wg./100 ft. Percent of Supply: Actual Winter Infil.: Actual Summer Infil.: 3 % 6 CFM 3 CFM Item, Area r U j Htg <� Sen Clg Lat ; Description' Quantit'` Value HTM Lossr "" HTM Gain °: Sen G_ ain , E -Wall-I3A-5ocs 13 X 8 96 0.125 3.5 336 1.9 0 184 E -GIs-1A-cb-o shgc-0.75 0%S (2) Floor-22A-ph 13 ft..Per. 8 1.080 13 1.358 30.2 242 38.0 494 88.3 0.0 0 0 706 0 Subtotals for Structure: 1,072 0 890 Infil.: Win.: 6.0, Sum.: 2.7 104 1.779 185 0.433 112 45 Ductwork: 447 281 People: 200 lat/per, 230 sen/per: Equipment: 2 400 300 460 600 Room Totals: 1,704 812 2,276 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Residential ✓I< Light Commercial HVAC Loads Elite Software Development, Inc.' 1,,,Rbvae gy �., t , Wayne Thomas Residence, Port Saint Lucie, FL 34983 Page 22'' _Detailed Room Loads - Room 3 - Kitchen (Average Loaal:,Procedure) Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number. 1 Room Width: 8.0 ft. Zone,Number: 1 Area: 112.0 sq.ft. Supply Air: 130 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 8.7 AC/hr Volume: 896.0 cu.ft. Req. Vent. 'Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 3 CFM Runout Air: 130 CFM Percent of Supply.: 2 % Runout Duct Size: 0 in. Actual Summer Vent.: 4 CFM Runout Air Velocity: 0 ft./min. Percent of. Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 12 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 6 CFM Htg r y 4 n x C�9 Lat Sen Gain: Description,;, . Quantity. HTM.._'_ Loss ` ,_:M HTM Gam W -Wall-13A-5ocs 14 X 8 108 0.125 3.5 378 1.9 0 207 N -Wall-13A-5ocs 8 X 8 64 0.125 3.5 224 1.9 0 122 S -Wall-13A-5ocs 4.5 X 8 36 0.125 3.5 126 1.9 0 69 W -GIs-IA-cb-o shgc-0.75 0%S 4 1.080 30.2 121 88.3 0 353 Floor-22A_ph 27 ft.. Per. _ _ _ _ _ _27 1.358 _ _ 38.0_ 1,027 _ 0.0 0 0 Subtotals for Structure: 1,876 0- 751 Infil.: Win.: 12.2, Sum.: 5.5 212 1.774 376 0.429 228 91 Ductwork: 801 352 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment: 600 1,200 Room Totals: 3,053 1,228 2,854 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential $ Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calcs _ Wayne Thomas Residence ' Port`SainfLuci' 'FL. 34983 Pa a 23 Detailed Room Loads - Room 4= -.Bath 1 (Average Load Procedure) :. General 'r "¢ � r Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 12.5 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 1 Area: 100.0 sq.ft. Supply Air: 42 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 3.2 AC/hr Volume: 800.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 3 CFM Runout Air: 42 CFM Percent of Supply.: 8 % Runout Duct Size: 0 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 14 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 6 CFM Item h Area USen Clg Lat ,; , Sen, Gain Descn tiort:' Quantity .Value, ', „ _ HTM Loss . Hl'All , Gain - ° ` E -Wall-13A-5ocs 12.5 X 8 100 0.125 3:5 350 1.9 0 191 NW -Wall- 1 3A-5ocs 11 X 8 84 0.125 3.5 294 1.9 0 161 W -Wall-13A-5ocs 6 X 8 48 0.125 3.5 168 1.9 0 92 NW-GIs-lA-cb-o shgc-0.75 0%S 4 1.080 30.2 121 68.0 0 272 Floor-22A-ph 30 ft..Per. 30 1.358 38.0 1,141 0.0 0 0 Subtotals for Structure: 2,074 0 716 Infil.: Win.: 13.6, Sum.: 6.1 236 1.775 419 0.428 254 101 Ductwork: 887 115 Room Totals: 3,380 254 932 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac - Residential & Light Commercial HVAC Loads Software Development, Inc. Residential Enegy Calds Wayne Thomas Residence • _Eliteli PortSaint Lucie, FL 349a3 Pa a 24 Detailed Room Loads - Room 5 -'Great Room (Average Load Procedure) General. Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 21.5 ft. System Number: 1 Room Width: 11.5 ft. Zone Number: 1 Area: 247.0 sq.ft. Supply Air: 182 CFM Ceiling Height: 11.0 ft. Supply Air Changes: 4.0 AC/hr Volume: 2,720.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.: 8 CFM Runout Air: 91 CFM Percent of Supply.: 4 % Runout Duct Size: 0 in. Actual Summer Vent.: 5 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 21 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 10 CFM Item Area,,. U- . Htg „ Sen. Clg ' Lat ;: Sen Descri tion Quantity . Value °,; HTM Loss HTM Gain Gain S -Wall-13A-5ocs 21.5 X 8 130 0.125 3.5 455 1.9 0 249 E -Wall-13A-5ocs 13.5 X 8 100 0.125 3.5 350 1.9 0 191 W -Wall-13A-5ocs 11.5 X 8 92 0.125 3.5 322 1.9 0 176 E -GIs-1A-cb-o shgc-0.75 0%S (2) 8 1.080 30.2 242 88.3 0 706 S -GIs-1A-cm-o shgc-0.75 0%S (2) 42 1.270 35.6 1,494 36.9 0 1,548 U P-Ceil-1 6C-1 9 21.5 X 11.5 247.2 0.049 1.4 339 2.0 0 485 Floor-22A-ph 47 ft..Per. 47 1.358 38.0 1,787 0.0 0 0 Subtotals for Structure: 4,989 0 3,355 Infil.: Win.: 21.4, Sum.: 9.7 372 1.774 660 0.427 401 159 Ductwork: 2,010 _ 494 _ Room Totals: _ i _ 7,659 401 4,008 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM IRhvac Residential & Light Commercial HVAC Loads Ejite sonware oevelopmenti inc. Residentiaftnergy Calc's Wayne Thomas Residence p6ftsaint Lucie FL 34983 Page 25 -De'tailed Room Loads = Room 6 Stairway (Average Load Procedure) Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.0 ft. System Number: 1 Room Width: 7.5 ft. Zone Number: 1 Area: 98.0 sq.ft. Supply Air: 35 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 2.7 AC/hr Volume: 780.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 35 CFM Percent of Supply.: 2. % Runout Duct Size: 0 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 2 CFM E -GIs-1A-cb-o shgc-0.75 0%S 4 1.080 30.2 121 88.3 0 353 UP-Ceil-16C-19 13 X 7.5 97.5 0.049 1.4 134 2.0 0 191 Subtotals for Structure: 451 0 651 Infil.: Win.: 3.5, Sum.: 1.6 60 1.767 106 0.433 65 26 Ductwork: 198 95 Room Totals: 755 65 772 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac - Residential � Light Commercial HVAC Loads 9 re EI'te S v r_EliteSoftware Development, Inc., Y Resitlential8'nergyCalcs ��', �_ n _ �: - WayneTho mas Residence Port Saint`Lucie, FL 34983 __Rage 26 -Detailed Ro6m Loads>=`: Room _7 T. Bath2 (A. vera e Load Procedure) Calculation Mode: Htg. & clg. Occurrences.` 1 Room Length: 13.0 ft. System Number: 1 Room Width: . 5.4 ft.; Zone Number: 1 Area: 70.0 sq.ft. ,; Supply Air: 28 CFM Ceiling Height: 8.0 ft., Supply Air Changes: 3.0 AC/hr Volume: 562.0 cu,ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 1 ' Actual Winter Vent.: .0 CFM Runout Air: 28 CFM Percent of Supply.: 2 % Runout Duct Size: 0 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min.: Actual Winter Infil.: 3 CFM Actual Loss: 0.000 in! wg./100 ft. Actual Summer Infil.: 1 CFM Item< �_ r Area m U Ht Sen Sen; ` Game. Descnption ' , ,.. <:Quantity 'Value„ HTM' :Loss HTM Gain E -Wall:13A-5ocs 5.5 X 8 44: 0.125 3.5 154 1.9 0 84 UP-Ceil-1 6C-1 9 13 X 5.4 70.2 0.049 1.4 96 2.0 0 138 Subtotals for Structure: 250 0 222 Infil.: Win.: 2.5, Sum.: 1.1 44' 1.773 78 0.432 47 19 Ductwork: 117 76 Equipment: 300 300 Room Totals: 445, 347 617 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential & Light'Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc s " _. Wayrie Thomas Residence Port Saint Lucie, FL. 34983 Page 27. :Detailed .Room, Loads- Room, 8 - Master Bedroom (Average Load.Procedure) 4Gerieral , j Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 13.0 ft. Zone Number: 1 Area: 182.0 sq.ft. Supply Air: 192 CFM Ceiling Height: 11.0 ft. Supply Air Changes: 5.7 AC/hr Volume: 2,002.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.: 4 CFM Runout Air: , 96 CFM Percent of Supply.: 2 % Runout Duct Size: 0 in. Actual Summer Vent.: 5 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 12 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 6 CFM Item: E a Area U ' , , z Htg Sen Cl g Lat ,; Descri tion::'. Quantity Value °. ' .hITM Loss .HTM Gain' I Sen Gain` E -Wall-13A-5ocs 14 X 8 104 0.125 3.5 364 1.9 . 0 199 N -Wall-13A-5ocs 13 X 8 62 0.125 3.5 217 1.9 0 119 E -GIs-1A-cb-o shgc-0.75 0%S (2) 8 1.080 30.2 242 88.3 0 706 N -GIs-1A-cm-o shgc-0.75 100%S 42 1.270 35.6 1,494 34.9 0 1,464 (2) UP-Ceil-16C-19 14 X 13 182 0.049 1.4 250 2.0 0 357 Subtotals for Structure: 2,567 0 2,845 Infil.: Win.: 12.5, Sum.: 5.6 216' 1.773 383 0.426 233 92 Ductwork: 1,050 520, People: 200 lat/per, 230 sen/per: 2 400 460 Equipment_ _ _ _ _ _ 300 300 Room Totals: 4,000 933 4,217 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM - Residential & Light Commercial HVAC Loads ftwa elopment, Inc Elite So re DevRhvac Residential Energy Calcs Wayne Thomas Residence' Fi6rt(Saint Lucie, FL 34983 ..`' "' ' Pa e.28 Detailed Room:`Load.§'.- Room 9.- Walk In„Closet (Average Load Procedure) `General' Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 9.0 ft. System Number: 1 Room Width: 5.5 ft. Zone Number: 1 Area: 50.0 sq.ft. Supply Air: 17 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 2.6 AC/hr Volume: 396.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 17 CFM Percent of Supply.: 5 % Runout Duct Size: 0 in. Actual Summer Vent.: 0 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 6 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 3 CFM Item;ri 1-e,sc Area U Htg� } Sen ,„CI Lat ; ' Sen. Gain ion pt'', Quantit Value; .. .NTM w L"o'ss HTM .. ., . ,` Gain'. NW-Wall-13A-5ocs 10 X 8 80 0.125 3.5 280 1.9 0 153 W -Wall-13A-5ocs 2.5 X 8 20 0.125 3.5 70 1.9 0 38 UP-Ceil-I6C-19 9 X 5.5 49.5 0.049 1.4 68 2.0 0 97 Subtotals for Structure: 418 0 288 Infil.: Win.: 5.8, Sum.: 2.6 100 1.770 177 0.430 108 43 Ductwork: 212 47 Room Totals: 807 108 378 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential & Cight Commercial HVAC Loads, Elite Software Development, Inc. Residential Energy Calds ' Wayne Thomas Residence. _ PortSaint Lucie, FL' 34983 Pa a 29 Detailed Room Loads - Room '10,- Master Bath (Average load Procedure) - Calculation Mode: Htg. & clg. nces: Occurrences: 1 Room Length: 10.0 ft. System Number: 1 Room Width: 9.2 ft. Zone Number: 1 Area: 92.0 sq.ft. Supply Air: 76 CFM Ceiling Height: 11.0 ft. Supply Air Changes: 4.5 AC/hr Volume: 1,012.0 cu.ft. Req. Vent. Clg: 0 CFM . Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 76 CFM Percent of Supply.: 1 % Runout Duct Size:' 0 in. Actual Summer Vent.: 2 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 4 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 2 CFM ttern F s �4r3 Area U Ht9 y;;iY Sent/;Clga w Lat U,HTM HTM Sen: 7�QuanvL. •., ;Gain: _ .Game W -Wall-13A-5ocs 9.2 X 8 69.6 0.125 3.5 244 1.9 0 133 W -GIs-1A-cb-o shgc-0.75 0%S 4 1.080 30.2 121 88.3 0 353 UP-Ceil-1 6C-1 9 10 X 9.2 92 0.049 1.4 126 2.0 0 180 Subtotals for Structure: 491 0 666 Infil.: Win.: 4.2, Sum.: 1.9 74 1.780 131 0.435 79 32 Ductwork: 221 205 People: 200 lat/per, 230 sen/per: 2 400 460 .Equipment:. 300 300 Room Totals: 843 779 1,663 C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential & Light Commercial HVAC Loads Elite S elopme Residential Energy Calc's Wayne Thomas RePsa en O Port Saint Lucie, FL 34963 . -Detailed Room.,Loads.= R0'om;1 f , Den (Average Load Procedure) Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 11.5 ft. System Number: 1 Room Width: 9.5 ft. Zone Number: 1 Area: 109.0 sq.ft. Supply Air: 80 CFM Ceiling Height: 11.0 ft: Supply Air Changes: 4.0 AC/hr Volume: 1,202.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 80 CFM Percent of Supply.; 1 % Runout Duct Size: 0 in. Actual Summer Vent.: 2 CFM Runout Air Velocity: 0 ft./min. Percent of Supply: 3 % Runout Air Velocity: 0 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.000 in.wg./100 ft. Actual Summer Infil.: 2 CFM ItemsHt91" xSen> A t 4 �' ,, [ cis 4 t ! Description:. k h-:Quantif ;HTM F.', zLoss 4 . ,HTM ? . Y..: Gain;,:;: Gain W -Wall-13A-5ocs 11.5 X 8 „ r . .:Value, 88 0.125 3.5 308 1.9 0 168 W -GIs-1A-cb-o shgc-0.75 0%S 4 1.080 30.2 121 88.3 0 353 UP-Ceil-1 6C-1 9 11.5 X 9.5 109.2 0.049 1.4 150 2.0 0 214 Subtotals for Structure: 579 0 735 Infil.: Win.: 5.3, Sum.: 2.4 92 1.772 163 0.424 99 39 Ductwork: 264 216 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment: 300 300 Room Totals: 1,006 799 1,750 C:1... 1Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM Rhvac Residential & Light Commercial HVAC Loadsune a bonware.uevewpmen�, Residential Energy,cal Wayne Thomas Residence Port Saint Lucie FL 34983" Page 35 System 1 Room Load Summary 1. Foyer/Stairway 74 1,707 22 1-0 0 437 34 20 20 2, -:Dining . 169 1,704 22 1-0 0 2,276 812 104 104v 3'. Kitchen 112 3,053 40 1-0 0 2,854 1,228 130 130v 4 Bath 1 100 3,380 44 1-0 0 932 254 42. 42V 5 Great Room 247 7,659 100 2-0 0 4,008 401 182 182N 6 Stairway 98 755 10 1-0 0 772 65 35 35v 7 Bath2 70 445 6 1-0 0 617 347 28 28v 8 Master Bedroom 182 4,000 52 2-0 0 4,217 933 192 192v 9 Walk In Closet 50 807 10 1-0 0 378 108 17 17 • 10 Master Bath 92 843 11 1-0 0 1,663 779 76 76., 11 Den 109 1,006 13 1-0 0 1,750 799 80 80ti Ventilation 769 412 1,038 Duct Latent 1,040 _ System 1-total 1,303 26,130 330 20,315 7,837 906 906 System 1 Main Trunk Size: OxO in. Velocity: 0 ft./min Loss per 100 ft.: 0.000 in.wg Cooling S stem.Summary; Net.Required: 2.35 72% / 28% 20,315 7,837 28,153 Actual 2.50 73% / 27% 21,900 8,100 30,000 Eauinment Data Type: Model: Indoor Model: Brand: Description: Efficiency: . Comment: Sound: Capacity: Sensible Capacity: Latent Capacity: Two Speed Heat Pump RXBH17A07J PRESTIGE SERIES HEAT PUMP HSPF 9.0 0 0 30000 n/a n/a Standard Air Conditioner RPQL030JEZ RHLLHM3617JA PRESTIGE SERIES CENTRAL AIR 15.5 SEER 0 0 0 30000 21,900 Btuh 8,100 Btuh C:\ ...\Wayne Thomas Residence.rh9 Thursday, February 28, 2013, 9:40 PM K 1 FORM 405-10 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING, CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Wayne Thomas Residence Builder Name: Street: 63 LotRfNettles Island Blvd. Permit Office: St. Lucie County City, State, Zip: .Fort Pierce, FL, Permit Number: Owner: Wayne Thomas Jurisdiction: Design Location: FL, Fort Pierce 1. New construction or existing New (From Plans) 9. Wall Types (1592.0 sgft.) Insulation Area a. Concrete Block - Int Insul, Exterior R=5.0 1460.00 ft2 2. Single family or multiple family Single-family b. Frame - Wood, Exterior R=13.0 132.00 ft2 ,3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d. N/A R= ft2 10. Ceiling Types (849.0 sgft.) Insulation Area 5. Is this a worst case? No a. Under Attic (Vented) R=19.0 849.00 ft2 6. Conditioned floor area above grade (ft?) 1304 b. N/A R= ft2 c. N/A R= ft2 Conditioned floor area below grade (ft2) 0 11. Ducts R ft2 7. Windows(128.0 sgft.) Description Area a. Sup: RoomslnBlock1, Ret: RoomslnBlock1, AH: 6 169.8 a. U-Factor: Sgl, U=0.29 128.00 ft2 SHGC: SHGC=0.22 12. Cooling systems kBtu/hr Efficiency b. U-Factor: N/A ,ft2 a. Central Unit 30.0 SEER:15.00 SHGC: c. U-Factor: N/A ft2 SHGC: 13. Heating systems ' kBtu/hr Efficiency d. U-Factor_: N/A ft2 a. Electric'Heat Pump 38.7 HSPF:9.00 SHGC: Area Weighted Average Overhang Depth: 0.000 ft. Area Weighted Average SHGC: 0.220 14. Hot water systems a. Electric Tankless Cap: 1 gallons 8. Floor Types (849.0 sgft.) Insulation Area EF: 0.990. . a. Slab -On -Grade Edge Insulation R=0.0 849.00 ft2 b. Conservation features b. NIA R= ft2 None . c. NIA R= ft2 15. Credits CF, Pstat Glass/Floor Area: 0.098 Total Proposed Modified Loads: 16.66 PASS Total Standard Reference Loads: 21.62 I hereby, certify that the plans and specifics ion vered by Review of the plans and ST.g?A this calculation are in compliance with the Flori a Energy specifications covered by this ��'tE _ 1+ O Code. calculation indicates compliance y'�ii,'' _=,�,.���A0, with the Florida Energy Code. rmri��•-.;-•=;��,�ti O PREPARED BY: eP&D � /-11WI& s Before construction is completed DATE: Z%i ja //I this building will be inspected for compliance with Section 553.908 * ° I hereby certify that this build' g, as designed, is in compliance Florida Statutes. COD with the Florida Energy Co . WE OWNER/AGENT:--v �� BUILDING OFFICIAL: DATE: DATE: - Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist 2/28/2013 10:44 PM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 5