July 31, 2014
St. Lucie County Building and Code Regulation Division
Plan Review Comments
2300 Virginia Ave.
Ft. pierce, FL 34982
RE: Plan Review Comments, Permit # 1406-0259
/116omment 1: Helical Pile Tech. Data
GC to provide
Comment 2: Crawl Space Vent Requirements to Comply with FBC 2010 R322.2.2
Floor Area =1600 SF. Vent Area=1600 SI =11.11 SF. (3) I '-8 " x 3 '-4 " Openings
= 16.67 SF, Therefore Adequate. Vent Area Complies, Note Added to Sheet S-2
Comment 3: Wood I -Joists are not P.T., Beams are not P.T.
Floor System has been Changed to Pre -Engineered P.T. Wood Trusses, Parallam
Beams Called out are Pressure Treated, see S-2, FF raised 3/ "to allow non P. T.
plywood floor I
t�Comment 4: Under Floor Batt Insul. Improper
Batt Insulation has been Changed to Icynene Foam
t/ Comment 5: Below Floor Plumbing to Resist Floodwater Forces
Note added to plan, see sheet S-2
Comment 6: Wall Panel Shop Drawings
GC to provide i
Comment 7: Roof Truss Shop Drawings
GC to provide I
&--c"'omment 8: Correct/Sheet/Detail Numbers
All Section Callouts are now correct. "S" number shown on section cut on plan
sheets reference sheet number section is drawn on, "S" number on Section references
the plan sheet the section first appears on. See "Section Key" on Sheet A-1
�omment 9: Ventilation to Comply with FBC 2010 R408.1
Complies, Note Added to Sheet S-2
pleomment 10: Show Compliance with Table 301.2(1), Climatic Design Criteria
Termite Risk "Very High", Design Complies
comment 11: Correct Page & Detail Numbers
Page & Detail Callouts are correct, see Comment 8
mment 12: Show Compliance with FBC 2010 R315 Carbon Monoxide Alarms
Smoke Alarms to Comply. See Note on Sheet A-2 & Electrical Plan Legend Sheet E-1
Comment 13: ' Show Wind Design Pressures
Design Pressures are on Sheet A-1 in the General Notes, See "Design Pressures " in "
Design Live Load" Section
Respect l yPbmilled,
T. tiles Pe.E.
P:\2014\14-041 THYRRING RESIDENCE\COR\071114-PRI.doc
fMf&NEEFSN GRWOS,.
PROFESSIONAL
404 SW
Voice: (772):
August 13, 2014
'URAL CONSULTANTS
Ave., FL 34994
Fax:(772)223-9502
St. Lucie County Building and Code Reguli tion Division
Attn: Ed Roseberry
Plan Review Comments
2300 Virginia Ave.
Ft. pierce, FL 34982
RE: Plan Review Comments, Permit # 1
Comment 1: Vented Crawlspace Opening Compliance
The vented crawlspace net area openings comply with CH 322.2.2
Comment 2: All wood material below flood elev. Must be moisture resistant per code
All materials are moisture resistant. The floor joists are P.T., The dropped beams are 51/4""X14"
ME PARALLAM PLUS PSL SL1. This beam is wolmanized (P.T.), for product specifications go to...
Comment 3: Provide Wall Panel Shop Drawings
Wall panel shop drawings are for erector only. They are not generated until just
prior to fabrication. GC will provide approved set when received from fabricator just
prior to erection.
Comment 4: Vented Crawlspace
See comment 1
Comment 5: Show complete Wind Pressures
See Wind Load Schedule Sheet A-1
Comment 6: Sign & Seal all correspondence
OK
Comment 7: Approved Roof Truss Shop Drawing Layout
�C�fRP'�*4ol i
� gTILES p�ii��
I�pec
.� F
�, i
692 ,
:. tales @6€ �.E. \;
ORION • &0 N�
�ONAL ENG\\\���
lilllII10
P:\2014\14-041 THYRRING RESIDENCE\COR\071114-PR2.doc