HomeMy WebLinkAboutTRUSS ENGINEERINGProject Information:
Name:
THYRRING RES
Address:
ROOF & FLOOR TRUSS SYSTEMS
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter., Computer Program Used:
FBC 2010-HVHZ RES VIEW by Alpine
Gravity: 55 psf Roof Total Load Gravity. 60 psf Floor Total Load
Wind., 170 mph from ASCE 7-10 code
This package includes a Truss, Index Sheet and 77 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with Chapter 61 G15-31.003 of the Florida Board of
Professional Regulations.
92
.:�
STq p
f"11/ 110
Note: Furthermore, the responsibility of the undersigned is solely limited to the
design of the truss components shown. The suitability and use of these
trusses fo,r any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
761 FT2 1 06/09/14
771 FT3 1 05/09/14
HomeBASE by Alpine Page 1 of 1
ROOF & FLOOD TRUSS SYSTEMS
4175 MARTIN H 1OHW Y
PALM O 1 TY. FL 34990
OFF: (7 72) 8 - 700
FAX: 772) -44
CUSTOMER NAME........ GM CONST.
JOB NAME ...................... THYRRING RES
JOB# ............................. KB0200
XOSEALED
PERMITTING O FIELD O APPROVAL ID PRELIMINARY
JOD:(KbULUU) / I HYKKIN(j Kt5 / Al
Top chord 2x4 SP 1650f-1.5E :T1 2x4 SP #2_l3A:
Bat chord 2x4 SP 1650f-1.5E
Webs 2x4 SP #3 13A :WS 2x4 SP_#2_13A:
:V1/9 2x4 SP 1650f-1.5E:
:Rt Bearing Leg 2x8 SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 92 plf at -2.00 to 92 plf at 7.00
TC- From 46 plf at 7.00 to 46 plf at 19.34
TC- From 46 plf at 19.34 to 46 plf at 31.08
BC- From 4 plf at -2.00 to 4 plf at 0.00
BC- From 20 plf at 0.00 to 20 plf at 7.03
BC- From 10 plf at 7.03 to 10 pit at 10.00
BC- From 10 plf at 10.00 to 10 plf at 21.69
BC- From 10 plf at 21.69 to 10 plf at 31.69
TC- 282.14 lb Conc. Load at 7.03
TC- 268.23 lb Conc. Load at 9.06,11.06,13.06,15.06
17.06,19.0 6, 21.06, 23.06, 25.06, 27.06, 29.06, 31.06
BC- 596.42 lb Conc. Load at 7.03
BC-128.41 lb Conc. Load at 9.06,11.06,13.06,15.06
17.06,19.06,21.06,23.06,25.06, 27.06,29.06,31.06
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT Ii, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'0"9
THIS UWG. PRtPAREU BY I HI- ALPINt JUB UtbIUNLK F'K(JUKAM YKUM I KUbb Mt-K'b LAYUU 1
2 Complete Trusses Required
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @ 8.50" o.c.
Bat Chord: 1 Row @12.00" o.c.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
Wind loads and reactions based on MWFRS.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
2829 2680 768E 266# 268# 268# 7666
7'0"s
1-- 7'
12
24"" -hI
31'8"4 -I
H ICI
596# 128tl 12a# ��� 1280 1� 1200 12d 1286 12J 126# 128t 12B6
R=3883# U=1241# W=511 R=4092# U=1153# W=5"8
(Rigid Surface) (Rigid Surface)
T
a
1
SEQ = 265884
PLT. TYP: WAVE DESIGNCRIT=FBCIOFMVRESRP42007FT1RT=2W.6(0%)110(0I QTY= 1 PLIES= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=0.1250
-WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
ft
o-K
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSUTPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC IL 15.Opsf
BC DL 10.Opsf
BC LL O.OPSf
TOT.LD. 55.Opsf
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE HI PM
IOD:(rtt3ULUU) I 1 MT MKINU Kt,-) / AL
Top chord 2x4 SP_#2 13A .T1 2x4 SP 1650f-1.5E:
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A :W9 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chard checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
THIS UWG. PHtPARLD BY I Ht ALPINt JUb UtbIUNtK YKLIUKAM FKUM I KU.S"b- MFK'b LAYUU 1
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C.
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
22'8"4
—6X8 =3X5 =5X7 =4X4 =5X7
01.SX4 T
12
5 T1
�4X6(A2)
=3X5 a3X5 =5X7 =3X5 =5X7
=H0310 III X
31'8"4
f 2 --�
R=1986# U=1037# RL=364/-109# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
R=1768# U=837# W=5"8
(Rigid Surface)
SEQ = 265732
PLT.TYP: WAVE DESIGN CRIT=FBC10HVHZRE5rtPI-207FT/RT=20%(0%)n0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
••WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING,, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
� p
REF
DATE 05-09-2014
ftt
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
m2
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 28&3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE HIPM
JOD:(I,CUZUU) / I NTKKINU KtJ / A3
Top chord 2x4 SP 1650f-1.5E :T2 2x4 SP #2_13A:
Bot chord 2x4 SP #2 13A :B1 2x4 SP 1650f-1.5E:
Webs 2x4 SP #3 13A :W7 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load rases on this truss have a 1.33 duration factor.
Gi
I HIS UWU. I'KtYAHLU UY I rt= ALYINM JU6 UM0IUI1MM rKUOKAM MUM I KU00 MrR 0 L 7 VU 1
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
31'8"4
20'8"4
R=19869 U=1018# RL=416/-124# W=5"8
—
R=1768# U=8450 W=5"8
(Rigid Surface)
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265737
PLT. TYP: WAVE
DESIGN CRIT=FBCIOHVNZRESfrPF2007FDRT-2014(0%)110(0) QTY= 1 TOTAL= 1
REV. 12.03.03.0225.14
SCALE=0.2500
**WARNING** TRUSSES RTREME CARE IN, HANDLING, SHIPPING, INSTALLING AND
REFER TO HIB-91 (HAN LINGUIRE INSTALLNG AND BRACING), NGPUBLISHED D BY TPI (TRUSS PLATE INSTITUTE, 5838RACING.
T. STILES
TC LL
30.Opsf
REF
DATE 05-09-2014
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
O
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
BC DL
10.0psf
DRWG
1
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27785
BC LL
TOT.LD,
O.Opsf
55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
DUR.FAC.
1.25
JOB #: KB0200
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
404 SW CAMDEN AVE
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
STUART, FL 34994
SPACING
24.0"
ITYPE HIPM
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrl?l 1-1995 SECTION 2.
)D;(KCULUU) / I HYKKIN(3 KES / A4
Top chord 2x4 SP #2_13A :Tt 2x4 SP 1650f-1.5E:
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chard checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
13'
R=1986# U=1008# RL=422/-150# W=5"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFK'S LAYOU 1
170 mph wind, 15.13 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T' brace. 80%length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC-.
Deflection meets U360 live and U240 total load. Creep increase factor far dead load is 1.50.
MWFRS loads based on trusses located at least 7.56 ft. from roof edge.
31'8"4
17'4"3 +1�1
.5X4
(V
R=1768# U=866# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265748
PLT. TYP: WAVE DESIGN CRrr=FBCIOHVHZRESRPI-2007FRRT=7D%(0%)/70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
••WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
O'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TIC DL 15.Opsf
BC DL 10.Opsf
DRWG
MXO
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE.
STUART, FL 34994 _
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE HIPS
JOD:kKt1UZUU) / I FIYKKIINU KtJ / AO
Top chord 2x4 SP 1650f-1.5E :T3, T5 2x4 SP_#2_13A:
:T4 2x6 SP_92 13A:
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50
MWFRS loads based on trusses located at least 15.55 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JUB UtSIGNtK PKUGKAM I-KUM I HUSS MI-K'S LAYUU 1
170 mph wind, 15.55 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on bath MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "'Ibrace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
14'6"5 - I - 2'—�'"-I- 11 4 3 + 3-4"1 —�
�1
1- - 31'8"4 -
R=1986# U=1013# RL=393/-177# W=5"8
R=1768# U=892# W=5"8
(Rigid Surface)
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265754
PLT. TYP: WAVE
DESIGN CRIT-FBCIOHVHZRES/rPI-2007FTIRT=7D%(D%)110(0) QTY= 1 TOTAL= 1
REV. 12.03.03.0225.14
SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL
30.0 sf
P
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
-TC DL
BC DL
15.Opsf
10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIITPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL
TOT.LD.
O.Opsf
55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 285-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
JOD:(KC000U) f I HYKKIN(3 RE6 / Ali
Top chord 2x4 SP #2_13A :T1 2x4 SP 1650f-1.5E:
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duraflon factor.
�_2
R=1986# U=1060# RL=440/-211# W=5"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFK'S LAYUU I
170 mph wind, 15.96 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11. EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1 x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.96 ft. from roof edge.
12'6'5 - 1 - 2' — i 4'5"11 74"3 1 5 4"1
31'8"4
R=1768# U=933# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265763
PLT. TYP: WAVE DESIGN CRR=F8C10MMZRESrrMW7Fr/RT=20%(0%)/70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC IL 15.0psf
BC DL 10.0psf
DRWG
MT
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIRPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE _
STUART, FL 3' 4
BC LL 0.0psf
TOT,LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DURFAC1.25
..
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
JOb:(Kt3UZUU) / I HYKKINL3 Kt5 / A/
Top chord 2x4 SP 1650f-1.5E :T4 2x4 SP 92_13A:
Bot chord 2x4 SP 165Df-1.5E :B2 2x4 SP_#2_13A:
:B3 2x4 SP M-31:
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 16.38 ft. from roof edge.
10'6"5
�2
R=1986# U=1071# RL=442/-242# W=5"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALNINL JUti UL61UNtK NKU(iKAM FKUM I KUSS Mt-K-S LAYUU 1
170 mph wind, 16.38 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and CBC.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 2x6 93 or better'T' brace. 80% length of web member. Attached
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
2' 615"11 3'4"3 7 4 1
31'8"4
R=1768# U=914# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265768
PLT. TYP: WAVE DESIGN CRIT-FBC10M/HZRESrrPI-2007FT1RT-D%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
..WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.0 sf
P
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TICDL 15.Opsf
BC DL 10.0psf
DRWG
01
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIfrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC ILL O.Opsf
TOT,LD. 55.0psf
ROOF 8r FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE SPEC
JOO:(KtiULUU) / I HYRRIN(3 Rt5 / Ad
Top chord 2x4 SP 1650f-1.5E :T2, T3 2x4 SP_#2_13A:
:T5 2x4 SP M-31:
Bot chord 2x4 SP #2 13A :Bt 2x4 SP 1650f-1.5E:
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 16.50 ft. from roof edge.
�_2'--d
R=1986# U=1078# RL=443/-252# W=5"8
(Rigid Surface)
THIS DWG. PREPARED BY I Ht ALI'INt JUB UtJIUNtK YKUUKAM I-KUM I KUAb Mrna LATUII I
170 mph wind, 16.50 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
8'6"5 2' 11'012 - I _ 2'2" 7'11 "3 -�
31
R=1768# U=893# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265776
PLT.TYP.-WAVE DESIGN CRIT=FBCI0M/HZRES/rPF2007FT/RT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0sf
P
REF
DATE 05-09-2014
O
O'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
M�'
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER. PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
_
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4176 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 2-
ITYPE SPEC
)D:(ICt1ULUU) / I HYKKIN(j KtZ5 / AU
Top chord 2x4 SP #2 13A :T1 2x4 SP 1650f-1.5E:
Bot chord 2x4 SP 1650f-1.5E :B3 2x4 SP_#2_13A:
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 16.08 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 16.08 ft. from roof edge.
I- 6'6"5----- 1 2' 11'012 67 5'11"3
31'8"4
�2
R=1986# U=1086# RL=4401-220# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
R=1768# U=905#
H=H1
SEQ = 265780
PLT. TYP: WAVE DESIGN CRIT=F8C10HVHZRESRP42007FTIRT-2D%(D%)1I0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI RUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.0psf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-2. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD, 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
11iVillVC4I\LC1C4; .W/GrtlJ
Top chord 2x4 SP #2_13A :T1 2x4 SP 1650f-1.5E:
Bot chord 2x4 SP 7650f--1.5E :B3 2x4 SP_92_13A:
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
4'6"5 1 T
�— 2 —"
R=1986# U=1092# RL=438/-189# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
11'0"12
THIS DWG. PREPARED BY THE ALPINt JUB Ut.SIGNtK PKOGRAM FKOM I KUSb MFK'8 LAYUU 1
170 mph wind, 15.67 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 R from roof edge, RISK CAT II, EXP C,
wind TIC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
(b) Continuous lateral bracing equally spaced on member. Or 2x4 #3 or better "T" brace. 80 % length of web member. Attached
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.67 ft. from roof edge.
31'8"4
10'2"
3-11"3
R=1768# U=907#
H=H1
SEQ = 265784
PLT. TYP.-WAVE DESIGN CRIT=FBC70HVHZRES/rP42007FT1RT-20%(0%)II0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
—WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON. W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z_ THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE SPEC
JOD:(KC000U) / I HYKKIN(3 Kt5 / Al l
Top chord 2x4 SP 1650f-1.5E :T1, T6 2x4 SP #2_13A:
Bot chord 2x4 SP 1650f-1.5E :B1 2x4 SP M41:
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
170 mph wind, 15.25 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
(H1) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
(a) Continuous lateral bracing equally spaced on member. Or 2x6 #3 or better "T' brace. 80% length of web member. Attached
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
�^ 2'6"5 --+- 2' -1 11'0"12
�-2 I
BY I Kt ALPINt JUt7 Ut=ZMUNtK YKUUKAM t-KUM I KUA0
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 92 plf at -2.00 to 92 plf at 2.53
TC- From 92 pit at 2.53 to 92 plf at 4.52
TC- From 92 pif at 4.52 to 92 plf at 15.59
TC- From 92 plf at 15.59 to 92 plf at 29.76
TC- From 92 pit at 29.76 to 92 plf at 31.69
BC- From 4 plf at -2.00 to 4 plf at 0.00
BC- From 20 plf at 0.00 to 20 pit at 31.69
BC- 464.88 lb Conc. Load at 1.94
Right end vertical not exposed to wind pressure.
(b) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
31'8"4
f 1'l t"4 j 29'9"
4650
R=2424# U=986# W=513
(Rigid Surface)
LEFT RAKE = 2'0"9
14'2"
I'll 1 "3 -�
R=1794# U=653#
H=H1
SEQ = 265809
PLT. TYP: WAVE DESIGNCRIT=FBC,OFMIZRESMP 2007FTIRT=2%(0%)H0(0I QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
M19tFUNCTIONS.
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER. PER ANSIRPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 310804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE SPEC
' -, "Rnv0 KES /Al2
Top chord 2x4 SP #2 1 Bot cho3A :T1 2x4 SP 1650f 1.SE:
rd 2x4 SP #2 13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values Conform with those approved by ALSC on 1/5/2012 and those
Pproved by ALSC on 1/30/2013, Whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom Chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
R=1677# U=735# RLe3,#
PLT. TYP.-WAVE
TO
FAX:
117"1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.25 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.25 ft. from roof edge.
18'1"3
1 TOTAL= 1
'-LING AND BRA.CING). PUBLISHEDY TPI (TRUSS PLATE INSTITUTE, 583 INSTALLING AND BRACINQ
IN, ICATI-0W. FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
INDICATED, TOp CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
ALL HAVE A PROPERLY ATTACHED RIGID CEILING. --IMPORTANT— FURNISH A
'4 FROKJIOr CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
N FROM PHIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
LING $HIPPING INSTALLING AONA DE GN ECND BRACING OF TRUSSES. DESIGN CONFORMS
ECTOpE ONNECTORS ARE MADE OP 20GA A TM A653 GR40 GALV. HEAMER
STEELAN
DES
PER R$ TO EACH FACE OF TRUSS AND, UNLESS OTHERENTWISE LOCATED ON THIS
PUBLISH
RESpaN51B'GS 160 A-Z. THE SEAL ON THIS DRAWING IN
ACCEPTANCE
MP�NENT FpR NA pgRTICULAR BUIRLDINGHE TUS CIS MHE RESPONSISILITY OF THE HE
9995 cr..�.__. _
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
R=1663# U=806#
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.Opsf
BC DL
10.Opsf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 265792
SCALE=0.2500
REF
DATE 05-09-2014
DRWG
O/A LEN. 290804
JOB #: KB0200
TYPE SPEC
t—
)D:(KbULUU) / I HYRRIN(3 h(LS / A13
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A :B1 2x4 SP 1650f-1.5E:
Webs 2x4 SP #3 13A :W7 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use puffins to brace BC @ 24" OC
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
PI
97"1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg. not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better "T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
20'1"3
1 29'8"4 - 1
�2
R=1874# U=976# RL=378/-110# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
R=1655# U=7890
SEQ = 265819
PLT. TYP.-WAVE DESIGN CRIT-FBCIOWWREWPF2007FT/RT1M%(0%)IIIXO) QTY= 1 TOTAL= 1 REV. 12.03:03.0225.14 SCALE=0.2500
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
DZ
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD, 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 290804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX (772) 268-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE HIPM
JOD:(KCULUU) / I MYKKINU Kt5 / A14
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3 13A :W6 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
P1
29'8"4
�2
R=1874# U=995# RL=325/-95# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB UEbIUNER PRUGKAM FKOM T KUSS MFK'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 2x4 #3 or better "T" brace. 80 % length of web member. Attached
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
22'1"3
1
1
R=1655# U=780#
SEQ = 265822
PLT. TYP: WAVE DESIGN CRIT-FBC70HVHZRESrPI-2007FLRT"211%(0%)/I%0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. •'IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 290804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
7YpE HIPM
Jot)
/ Al
Top chord 2x4 SP_#2_13A :T1 2x4 SP 1650(1.5E:
Bot chord 2x4 SP 1650f-1.5E
Webs 2x4 SP #3 13A :W7 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
(a) Continuous lateral bracing equally spaced on member. Or 1x4 #3SRB SPF-S or better'T" brace. 80% length of web
member. Attached with 8d Box or Gun (0.113"x2.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
I 57"l
16'1"14
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(H1) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets L1360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
T11"5
2.32 v
1 29'8"4 I
2'--�
R=1854# U=1012# RL=381/-83# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
R=1627# U=80D#
H=H1
SEQ = 265829
PLT. TYP: WAVE DESIGN CRr-FBC10HVNZRESRP42D07FRRT-2D-90wv10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
U
MQ
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
-
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/rPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 290804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 266-3700
-4 FAX: (772) 286234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
JOD:(KbULUU) / I HYKKIN(i Ktb / A'Iti
Top chord 2x4 SP 1650f-1.5E :T4 2x4 SP #2_13A:
Bot chord 2x6 SP M-26
Webs 2x4 SP #3_13A :W2, W6 2x4 SP_#2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
(a) Continuous lateral bracing equally spaced on member. Or 2x6 #3 or better "T" brace. 80% length of web member. Attached
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
Calculated vertical deflection is 0.65" due to live load and 0.82" due to dead load at X=13-3-13.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
�— 37"1 10'0"4 -I 1211"5
29'8"4
�— 2' --I
R=1851# U=1041# RL=316/-76# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
__ 12
3-11.10 —�
T
1
R=1626# U=807#
H=H1
SEQ = 265841
PLT. TYP-WAVE DESIGN CRIT"FBC10WHZRESrrP42007FTIRT"20%(0%)J10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
—WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC IL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A663 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 290804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITypF SPEC
N(3 Kt5 / Al
Top chord 2x4 SP 92 13A
Bot chord 2x4 SP M-31 :B2 2x4 SP 1650f-1.5E:
:83 2x4 SP #2 13A:
Webs 2x4 SP #3 13A :W2 2x4 SP #2 13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
2 Complete Trusses Required
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @12.00" o.c.
Bot Chord: 1 Row @12.00" o.c.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
("') 2 plate(s) require special positioning. Refer to scaled plate plot details for special positioning requirements.
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
�► 1-7"1 +— 3.10.10 1 16'5"1 + 7'9"8
29'8"4
�-2
R=1846# U=1055# RL=269/-68# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
i
i
R=1626# U=762#
H=H1
SEQ = 265849
PLT. TYP.-WAVE DESIGN CRIT=FBC10HVRZRESRP42007FT1RT-21Pb(0%N10(0) QTY= 1 PLIES= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
wftzO
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPTAS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD, 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 290804
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DURYAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
/ I ttYKKINLJ Kt5 / Alt$
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUI
Top chord 2x4 SP #2_13A
x4 Bot chord 2SP 1650f-1.5E :B2 2x4 SP #2_13A:
Webs 2x4 SP #3 13A :W2 2x4 SP #2 13A:
2 Complete Trusses Required
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @12.00" o.c.
approved by ALSC on 113012013, whichever is less.
Bot Chord: 1 Row @ 6.75" o.c.
170 mph wind, 15.58 ft mean hgt, ASCE 7-10, CLOSED bidg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
Webs : 1 Raw @ 4" o.c.
Use equal spacing between rows and stagger nails
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
in each row to avoid splitting.
Wind loads and reactions based an MWFRS.
Special loads
End verticals not exposed to wind pressure.
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 91 pit at 0.00 to 91 pit at 10.17
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
TC- From 45 plf at 10.17 to 45 plf at 18.42
TC- From 91 pit at 18.42 to 91 pit at 20.68
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
BC- From 10 pit at 0.00 to 10 pit at 18.42
BC- From 20 pit at 18.42 to 20 pit at 20.68
All wind load cases on this truss have a 1.33 duration factor.
BC- 279.40 lb Conc. Load at 1.68
BC- 655.40 lb Conc. Load at 3.78
BC- 598.13 lb Conc. Load at 5.89
BC- 540.52 lb Conc. Load at 7.99
BC- 482.48 lb Conc. Load at 10.09
BC- 423.64 lb Conc. Load at 12.20
BC- 364.34 lb Conc. Load at 14.30
BC- 303.58 lb Conc. Load at 16.40
10,2" 1 BC- 243.30 lb Conc. Load at 1p q
2.32
�4X4
v
:3X5 =-3X5
3X7(R) Z3X7
T T
W2 -
N (V
1
=3X10 =-3X7 =H0310 =4X8 1113X7
B2
103 20'8"2 _ 1
�182 i 21-4;j 21.4 1 2'144,1 21"4 i 21"4 4J 2'1"4-----2'1"4 j 2'0"4- j 23.1�
2799 S96# 482# 364# 2430
R=3100# U=1027# W-6"5
(Rigid Sudam)
R=2519# U=792#
SEQ = 265857
PLT. TYP: WAVE DESIGN CRIT-FBC10lMORESrrPi-2007R1RT=20%(0%yf0(0) QTY= 1 PLIES= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
O
=�K
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. ••IMPORTANT^ FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OFTRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-2- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER. PER ANSUTPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 200802
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COMN
/ INYKKINUKtS/AlV
Top chord 2x4 SP 1650f-1.5E :T1 2x4 SP #2_13A:
•T4 2x4 SP M-31:
Bot chord 2x6 SP M-26
Webs 2x4 SP #3 13A
:W1, W4, W6, W8, W9 2x4 SP #2_13A::W2 2x4 SP 1650f-1.5E:
:Rt Wedge 2x4 SP #3_13A:
Lumber grades designated with "l3A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Special loads
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC- From 92 pit at 0.00 to 92 pff at 8.18
TC- From 92 pit at 8.18 to 92 pit at 11.89
TC- From 92 plf at 11.89 to 92 plf at 13.60
TC- From 92 plf at 13.60 to 92 plf at 23.89
BC- From 20 plf at 0.00 to 20 pit at 23.89
PLT- 278.70 lb Conc. Load at (15.62,15.82)
PLT- 98.09lb Conc. Load at (19.94,14.23)
PLT--11.23lb Conc. Load at (22.01,13.46)
PLB- 266.25 lb Conc. Load at (0.13,12.54). (5.89,12.54)
PLB- 1767.51 lb Conc. Load at (1.78,12.54), (3.78,12.54)
PLB-1793.90 lb Conc. Load at( 5.78,12.54)
PLB- 605.71 lb Conc. Load at (7.10,12.54), (9.10,12.54), (11.10,12.54)
PLB- 1662.96 lb Conc. Load at (7.78,12.54)
PLB- 1654.65I11 Conc. Load at (9.78,12.54), (11.78.12.54)
PLB- 599.74 lb Conc. Load at (13.10,12.54)
PLB- 1626.89 lb Conc. Load at (13.78,12.54), (15.78,12.54)
PLB- 1025.64 lb Conc. Load at (15.10,12.54)
PLB-133.21 lb Conc. Load at (15.62,12.54)
PLB-1625.74 lb Conc. Load at (17.78,12.54)
PLB- 2519.22 lb Conc. Load at (19.21,12.54)
PLB- 53.23 lb Conc. Load at (19.94,12.54)
PLB- 7.03 lb Conc. Load at (22.01,12.54)
Left end vertical not exposed to wind pressure.
Max JT VERT DEFL: LL: 0.36" DL: 0.45" recommended camber 3/4"
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
All wind load cases on this truss have a 1.33 duration factor.
PLT. TYP: WAVE
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX- (772)288-4234
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUI
3 Complete Trusses Required
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @12.00" o.c.
Bat Chord: 2 Rows @ 3.00" o.c. (Each Row)
Webs : 1 Row @ 4" o.c.
Repeat nailing as each layer is applied. Use equal spacing
between rows and stagger nails in each row to avoid splitting.
4" o.c. spacing of nails perpendicular and parallel to
grain required in area over bearings greater than 4"
(1) - plates so marked were sized using a Fabrication Tolerance of 0% and a Rotational Tolerance of 0 degrees.
170 mph wind, 15.17 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
Calculated horizontal deflection is 0.13" due to live load and 0.16" due to dead load.
(a) Continuous lateral bracing equally spaced on member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
2790 -IIS o
15'7"8 4.3"12 �a-f-YD"13_f`b,j
8'2"3 3'8"8 -
12
5
10'3"8
T1 Q 12
4.43 p
-8 8 5X7 =8 8
TI -1-- 1112X14(R)(I) OX10
T � 94X8
T4
W1 W2 W4 (a) a3X5
< IL,
W9
3(a) H03'10(C3)
T
1118XII(R)MOO IN 11IL2(R)
111 X 0 =H1010
23'10"11
2 T 2 ry ^ice T-E ^� n2
iesa 17680 1768R 1�606 6638 6556 606 fi55t l� fi27C 1� 16266 2519530
R=13242# U=4211# W=5"8
(Rigid Surface)
DESIGN GRIT.FaCIOWWRESITFF2007 FTIRT=M%(0%YI0(0) QTY= 1 PLIES= 3 TOTAL= 3
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
78#
R=11669# U=3957# W--4"8
(Rigid Surface)
REV. 12.03.03.0225.14
T. STILES
TC LL
30.Opsf
P E ET
TC DL
15.Opsf
BC DL
10.Opsf
PE# 49200
BC LL
O.Opsf
CA# 27788
TOT.LD.
55.Opsf
404 SW CAMDEN AVE
I DUR.FAC.
1.25
STUART, FL 34994
SPACING
24.0"
SEQ = 265874
SCALE=0.1875
REF
DATE 05-09-2014
DRWG
O/A LEN. 231011
JOB #: KB0200
TYPE COMN
)D:(NtSULUU) / IN Y NKINU Ktb / 1:11
Top chord 2x4 SP 92_13A
Bot chord 2x4 SP 1650f-1.5E
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
170 mph wind, 15.00 It mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 It from roof edge, RISK CAT If, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac=1.25)
TC- From 92 plf at -2.00 to 92 plf at 2.00
TC- From 46 pit at 2.00 to 46 pit at 10.87
TC- From 46 plf at 10.87 to 46 plf at 19.74
TC- From 92 plf at 19.74 to 92 plf at 23.74
BC- From 4 pit at -2.00 to 4 pit at 0.00
BC- From 10 plf at 0.00 to 10 pit at 21.74
BC- From 4 pit at 21.74 to 4 pit at 23.74
TC_
11.89 lb Conc. Load at 2.00,19.74
TC- 4.95 lb Conc. Load at 3.09, 5.09, 7.09, 9.09
10.87,12.65,14.65,16.65,18.65
BC- 23.14lb Conc. Load at 2.00,19.74
BC_
19.12lb Conc. Load at 3.09, 5.09. 7.09, 9.09
10.87,12.65,14.65,16.65,18.65
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
120 ^ �5Y} so so Ss S-Bt s-- e- ���� s�C{ 5M 59 _1220 -I
f 2. -+ 2,}_ - 2- � 2, -+ 1,9"6 t
T 1'9"6 �2 -+ - 2 T- 2 � T - 2 'I
10107 + 10'107
21'8"13
�_2�
�_ 2' --- d
230 I 19# 14 196 190+ 190 I 19s id 230
R=1035# U=818# W=5"8 R=1035# U=818# W=5"8
(Rigid Surface) (Rigid Surface)
LEFT RAKE = 2'0"9 RIGHT RAKE = 2'0"9
SEQ = 265897
PLT. TYP.-WAVE DESIGN CRIT=FBCI0hVHZRES1TP42007FTIRT4D%(0%YI0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
O
D'ONOFRIO DR., SUITE 200, MADISON, W1. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DATE 05-09-2014
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF 8 FLOOR TRUSS SYSTEMS
O/A LEN. 210813
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
.
SPACING 240"
TYPE SPEC
)D:(I,t)UZUU) / I I -IT KKINU Ktb / t)Z
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP 1650f-1.5E
Webs 2x4 SP #3_13A
Lumber grades designated with "l3A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 92 plf at -2.00 to 92 plf at 10.87
TC- From 92 plf at 10.87 to 92 pit at 23.74
BC- From 4 plf at -2.00 to 4 plf at 0.00
BC- From 20 plf at 0.00 to 20 plf at 7.15
BC- From 80 plf at 7.15 to 80 plf at 14.59
BC- From 20 plf at 14.59 to 20 plf at 21.74
BC- From 4 plf at 21.74 to 4 plf at 23.74
Wind loads and reactions based on both MWFRS and C&C.
10'10"7
THIS DWG. PREPARED BY THE ALPINE JUB DESIGNER PROGRAM FROM TRUSS MFR'S LAYUU 1
170 mph wind, 15.00 It mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
(a) Continuous lateral bracing equally spaced on member.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
10'107
I 21'B"13 - I
�_2--�
R=1634# U=786# RL=241/-241# W=5"8
(Rigid Surface)
�2
R=1634# U=786# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9 RIGHT RAKE = 2'0"9
SEQ = 265444
PLT. TYP.-WAVE DESIGN CRIT=FBCI0HVHZRESrrPI-2007 FTIRT-2D%(0%y10(0) QTY= 3 TOTAL= 3 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA.# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.0psf
BC DL 10.0psf
BC LL 0.0psf
TOT.LD. 55.Opsf
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 210813
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COMN
JOD:(IKCUZUU) / 1 NYKKINU KtJ / LA
Top chord 2x4 SP 1650f-1.5E :T2 2x4 SP #2_13A:
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
�— 2 0.11
R=1242# U=1068# RL=171/-1839 W=11"14
(Rigid Surface)
LEFT RAKE = 2'1"4
9'3"2
=4x4
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TIC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on bath MWFRS and CBC.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
9'2'
R=1024# U=820# W=5.1
(Rigid Surface)
SEQ = 265545
PLT. TYP: WAVE DESIGN CRIT=FSC1QHVHWES/fPF2007FT1RT=2D%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0r1sf
Y
REF
DATE 05-09-2014
i�K
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
-
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSIIrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF 8 FLOOR TRUSS SYSTEMS
O/A LEN. 180502
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
JOD:(KbU2UU) / I NYKKIN(3 RE6 / L:2
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_92 13A
Webs 2x4 SP #3 13A
:Rt Stub Wedge 2x6 SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live.and U240 total load. Creep increase factor for dead load is 1.50.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
9'3"4 8'2"5 it
=4X4
o3X5 1.5X4
12
4.93 p
v
If6X8(G1)
3X5(A1)
m
-5x7
17'5"9
�— 2'0"9
R=1196# U=10360 RL=173/-175# W=5"5
(Rigid Surface)
R=961# U=783# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1"2
SEQ = 265526
PLT. TYP: WAVE MIGNCRIT-FBC10HVHZRESfTPF2007FTIRT-20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI RUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
MKO
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 170509
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
)D:(KtSULUU) / I HYKKIN(i KEb / G3
Top chord 2x4 SP #2_13A :T2 2x4 SP 1650f--1.5E:
Bot chord 2x4 SP #2_13A
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
1 9'3"4
�__20"9---]
R=1141# U#93# RL=1761-166# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1"2
16'5"11
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and CBC.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
7'2'7
R=904# U=447# W=5"5
(Rigid Surface)
SEQ = 265516
PLT. TYP: WAVE DESIGN CRIT=FBCI0HVKWEsrrar-2007FrmT 20%(0x)n0(0l QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
—WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
MKO
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TIC DL 15.Opsf
BC DL 10.0psf
DATE 05-09-2014
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIITPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD, 55.Opsf
ROOF $ FLOOR TRUSS SYSTEMS
O/A LEN. 160511
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX'. (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
JOD:(KbtULUU) / 1 HYKKINCi Kt5 / G4
Top chord 2x4 SP #2 13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
2 0"9 --d
R=1086# U=674# RL=179/-157# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1 "2
9'3"4
15'5"13
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
6'2"9
R=848# U=437# W=5"5
(Rigid Surface)
SEQ = 265511
PLT.TYP.-WAVE DESIGN CRIT-FBCIOHVWAESaPI-2W7FT/RT=70%(0%y70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
—WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING,, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
Wnu,u
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 150513
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COMN
JOD:kKbULUU) / I NYKKIN(i KtJ / L:5
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
9'3"4
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent five load.
All wind load cases on this truss have a 1.33 duration factor.
4X4
5'2"11
14'S"15
R=1031# U=654# RL=200/-149# W=5"5 R=791# U=429# W=5"5
(Rigid Surface) (Rigid Surface)
LEFT RAKE = 2T'2
SEQ = 265506
PLT. TYP: WAVE DESIGN CRn"FBCIOHNRRES/rP1-E107FTIRT-M%(0%)r10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
—WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
UK
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
p E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
BSUITABILITY AND UILDING DESIGNER, OF THIS
SCO COMPONENTFOR
ON 2. PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 140515
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 266-3700
FAX. (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
-APE COMN
)D:(KbU000) / I t1YKKIN(3 Kt5 / L:b
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
(1-11) = (J) Hanger not calculated (2)2x4 SP 1650f-1.5E
supporting member.
Bottom chard checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
9'3"4
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
All plates are 3X5(A1) except as noted.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
m4X4
3'10"4
1 6.4" - 1 2'9"7 + 4 0"1 _�
�--2'0"5 T 13'1"8 —1
R=7110 U=526# RL=235/-136# W=3" R=248pif U=139plf W=2'9'7 R=279# U=145#
(Rigid Surface) (Rigid Surface) H = H1
LEFT RAKE = 2'0"14
SEQ = 265501
PLT. TYP.-WAVE DESIGN CRIT4BC10KVKZRESlrPI-2007FnRT=20%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
ft
m2—K
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING,SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T. STILES
P E ET
TIC LL 30.0 sf
p
TIC DL 15.Opsf
BC DL 10.0psf
REF
DATE 05-09-2014
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIITPI I-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 130108
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 281-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
JOD:kKt1ULU1J) / I t1YKKINLj KtJ / Lam/
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
VON
R=902# U=596# RL=263/-128# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1 "2
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(Ht) = (J) Hanger not calculated (2)2x4 SP 1650f-1.5E
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
9'3"4 2'10"6 —�
12'1"1D
=4X4
R=655# U=413#
H=H1
SEQ = 265469
PLT. TYP: WAVE DESIGN CRR=FBC10HVWAESRPI-M07FRRT=2D%(O%YIO(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING,, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING). PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, W1. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER .PER ANSUTPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 120110
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE COMN
1D:ktKt5UZUU) / I t1YKKINU KtJ / L;b
Top chord 2x4 SP #2 13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'1"2
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C.
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP 1650f-1.5E
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
9'3"4 1 1-10"8 -�
4X4
1 11'1"12 1
2 0"9 —�
R=8489 U=564# RL=304/-120# W=5"5
(Rigid Surface)
R=598# U=391#
H=H1
SEQ = 265473
PLT. TYP: WAVE DESIGN CRIT-F8C70FNHZRESrrP42007FTIRT=ID%(0%yI0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
O
D'ONOFRIO DR., SUITE 200, MADISON, W1. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA# 2775$
404 SW CAMDEN AVE
STUARTFL 34994
,
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE 05-09-2014
DRWG
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 110112
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX (772) 28&4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 240"
.
TYPE COM N
)D:(KbUZUU) / 1 HYRRING RES / C9
Top chord 2x4 SP_#2_13A
Bot chord 2x4 SP #2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC
Bottom chard checked for 10.00 psf non -concurrent live load.
All wind load rases on this truss have a 1.33 duration factor.
f 2'0"9
R=794# U=530# RL=347/-111# W=5"5
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP 16501--1.5E
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
9'3"4 - 1 - 10.10 -d
10'1"14
o4X4(R1)
R=541# U=370#
H=H1
LEFT RAKE = 2'1"2
SEQ = 265480
PLT.TYP.-WAVE DESIGN CRR=FBC10HVHWESn?42WFTIRT=2D%(G%U10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
—WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 503
T. STILES
TC LL 30.0 Sf
p
REF
DATE 05-09-2014
MKO
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSUTPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC ILL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 100114
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
JOD:(tICUZUU) / IN Y KKINIJ KtJ / LA
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
2-0-9
R=741# U=497# RL=382/-103# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1"2
9-2-
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM 1 RUSS MFK'S LAYUU 1
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP 1650E-1.5E
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
111.5X4
R=482# U=356#
H=H1
SEQ = 265486
PLT.TYP. WAVE DESIGN CRIr=FBC10KH7RESRPF2007FTIRT=20%(0%u10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
O
K-
D'ONOFRIO DR., SURE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A663 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 90200
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 206-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COMN
)D:(ICt1UZUU) / I r1T KKINU Ktb / l:T 1
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSO on 1/30/2013, whichever is less.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
2 0"9
R=688# U=489# RL=359/-96# W=5"5
(Rigid Sudam)
LEFT RAKE = 2'1"2
8'2"2
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP_#2_13A
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
M WFRS loads based on trusses located at least 15.00 ft. from roof edge.
nisxs
R=424# U=333#
H=H1
SEQ = 265490
PLT. TYP: WAVE DESIGN CRIT=FSC10Mtl¢RESRP42007FLRT=2D%(0%)7(xO) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
AaKO
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE 05-09-2014
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 80202
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COM N
)D:kt\tSUZUU) / I HYKKINI.i Kt5 / G12
Top chord 2x4 SP_#2 13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
nkrLl
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 It mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP_#2_13A
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
2'0"9
_II 72"4
R=637# U=482# RL=335/-90# W=5"5 R=364# U=309#
(Rigid Surface) H = H1
LEFT RAKE = 2'1"2
SEQ = 265492
PLT. TYP. WAVE DESIGN CRIT=FBCIOFNHZRESIrM2D07FTIRT"7D%(0%)HO(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDUNG INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
IDL 15.Opsf
a
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
P E ET
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27785
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD. 55.Opsf
DRWG
ROOF & FLOOR TRUSS SYSTEMS
4176 MARTIN HIGHWAY
O/A LEN. 70zD4
DUR.FAC. 1.25
JOB #: K60200
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 240"
COMN
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
.
TYPE
JOD:(Kt3ULUU) / I HYKKIN(3 KLS / G13
Top chord 2x4 SP #2 13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
T
Q,
i
6'2"6
I� 2'0"9
R=586# U=477# RL=3101-83# W=5"5
(Rigid Surface)
LEFT RAKE = 2'1 "2
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP_#2_13A
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
It3X5
R=304# U=2839
H=H1
SEQ = 265494
PLT. TYP: WAVE DESIGN CRIT=F8C10HVHZRESITPI4007FTIRT•20%(0%p0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.7500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.0 sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. "IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TIC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-7-
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 60206
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: K60200
SPACING 24.0"
TYpE COM N
)b:(KB0200) / THYRRING RES / G14
Tap chord 2x4 SP #2_13A
Bot chord 2x4 SP #2_13A
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
In lieu of rigid ceiling use puffins to brace BC Q 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
T
Pj1
1
2'0"9
R=540# U=473# RL=286/-76# W=5"5
(Rigid Surface)
5'2"15
THIS DWG. PREPARED 6Y I HE ALPINL JUt7 Ut50.iNtR rRUUKAM rRUM I MU.Sa IVIM b LAY UU I
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bidg, Located anywhere in roof, RISK CAT If. EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (2)2x4 SP 92_13A
supporting member.
Deflection meets L/350 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
1113X5
R=243# U=249#
H=H1
LEFT RAKE = 2'1 "2
SEQ = 265496
PLT.TYP.-WAVE DESIGN CRIT-FBC1011MMESITPI-2007FTIRT=20%(OX)110(0) QTY=1 TOTAL=1 REV. 12.03.03.0225.14 SCALE=0.7500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
P E ET
10.0psf
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPTAS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
THIS DRAWING INDICATES ACCEPTANCE
PE# 49200
CA# 27788
BC LL O.Opsf
TOTID. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 50215
4175 MARTIN HIGHWAY
1.25
JOB #: KB0200
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z- THE SEAL ON
404 SW CAMDEN AVE_
DUR.FAC.
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
USE THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
COMN
FAX: (772) 288-4234
SUITABILITY AND OF
BUILDING DESIGNER, PER ANSIIrPI 1-1995 SECTION 2. _ _
SPACING 24.0"
TYPE
JOD:(Kt$ULUU) / I HYKKINL5 Kt5 / U1
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3 13A :W5 2x4 SP #2 13A:
:Lt Bearing Leg 06 SP #2_13A::Rt Bearing Leg 2x8 SP_#2_13A:
I HIS UW(i. YKtF'AKtU UY I r1t ALYIINC JUb ULOJUNCK YKUUKAM MUM I KUAA MI'm a 1 Y1 VU I
Special loads
-(Lumber Dur.Fac. 1.25 / Plate Dur.Fac. 1.25)
TC- From 92 plf at -2.06 to 92 pit at 6.60
TC- From 46 plf at 6.60 to 46 plf at 11.60
BC- From 4 pit at -2.06 to 4 plf at 0.00
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those BC- From 20 plf at 0.00 to 20 plf at 6.64
approved by ALSC On 1/30/2013, whichever is less. BC- From 10 plf at 6.64 to 10 plf at 11.01
PLT- 388.70 Ib Conc. Load at ( 6.64,15.77)
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C, PLT- 288.28 lb Conc. Load at ( 8.67,15.77). (10.67,15.77)
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18 PLB- 521.30lb Conc. Load at (6.64, 9.04)
PLB-193.31 lb Conc. Load at (8.67, 9.04), (10.67,9.04)
Wind loads and reactions based on MWFRS. 3a9# 2Ba#
6'7"10 f - TO, - In�jeu of ri riling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concur en f live load. l
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.3f duration factor. 7'0"12 T 4'11"15
�-- 2'0"12
R=1311# U=465# W=3"4
(Rigid Surface)
LEFT RAKE = 27'5
12'0"11
11'5'7 I 1'
5210 1938 193#
R=1817# U=478# W=5"8
(Rigid Surface)
SEQ = 265889
PLT.TYP.-WAVE DESIGN CRIT-FBC101M/ZRES1TPI2MD7FTIRT"2D%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
D'ONOFRIO DR., SUITE 200, MADISON, WL 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
P E ET
TC DL 15.Opsf
DRWG
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.0psf
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27788
BC LL O.Opsf
TOT.LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 120011
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
404 SW CAMDEN AVE
DUR.FAC. 1.25
JOB #: KB0200
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
ITYPE SPEC
FAX: (772) 288-4234
SUITABILITY
BUILDING DESIGNER. PER ANSIRPI 1-1995 SECTION 2.
SPACING 24.0"
)D:(KbUZUU) / I tiYKKINLi Kt5 / UZ
Top chord 2x4 SP 1650f-1.5E :T2 2x4 SP #2_13A:
Bot chord 2x4 SP #2_13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x6 SP #2_13A::Rt Bearing Leg 2xB SP_#2_13A:
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Lumber grades designated with "13A" indicate design values conform with those approved by ALSO on 1/5/2012 and those In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50. Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
MWFRS loads based on trusses located at least 7.50 ft, from roof edge.
9'0"12 2.11.15
goO
- T
1
12'0"11
R=665# U=318# RL=285/F5# W=3"4 R=679# U=477# W=5"8
(Rigid Surface) (Rigid Surface)
LEFT RAKE = 5"15
SEQ = 265556
PLT. TYP: WAVE DESIGN CRIT=FBC10HVWRESrrP4A07Fr/RT-2D5g0%V10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FA'RICATING, HANDLING,SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
MKO .
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
_
BC DL 10.0psf
BC LL O.Opsf
TOT.LD. 55.Opsf
DATE 05-09-2014
DRWG
ROOF & FLOORTRUSs SYSTEMS
O/A LEN. 120011
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 2845-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 240"
.
TYPE SPEC
)D:(ICt)UYUU) / I HYKKING RE6 / U3
Top chord 2x4 SP 1650f-1.5E :T2 2x4 SP #2_13A:
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x6 SP #2_13A::Rt Bearing Leg 2xB SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
04.
T6
11'0"12
1 12'0"11
[El
R=666# U=290# RL=341/-79# W=3"4
(Rigid Surface)
LEFT RAKE = 5"15
10'11"15
R=646# U=422# W=5"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
{-h 1 plate(s) require special positioning. Refer to scaled plate plot details for special positioning requirements.
170 mph wind, 15.17 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.58 ft. from roof edge.
SEQ = 265553
PLT.TYP: WAVE DESIGN CRIT-F0CIOMMZRESrrP42007FT1RT=20%(0%)H010) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
'*WARNING— TRUSSES REQUIRE TREME CARE IN FABRICATING, , SHIPPING, INSTALLING AND
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED YDLINGTPI (TRUSS PLATE INSTITUTE, 683 BRACING.
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
0
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-7 THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIIrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
FL 34994
STUART,(772)
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 120011
4175 MARTIN HIGHWAY
PALM.CITY, FL 34990
OFF: (772) 286-3700
FAX: 288-4234
DURYAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP #2 13A-
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x6 SP #2_13A::Rt Bearing Leg 2x8 SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MW=RS (Gads based on trusses located at least 15.00 ft. from roof edge.
12'0"11 1
2'0"12 _1 _ - 11'5'7
R=879# U=522# RL=458/-129# W=3"4 R=660# U=437# W=5"8
(Rigid Surface) (Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JUB UEbIGNEK I'KUGKAM FKUM I KUZSb MrK-o LPITUU I
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MW=RS and C&C.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 27"5 RIGHT RAKE = 7"14
SEQ = 265549
PLT. TYP: WAVE DESIGN CRIT=F8C10HVWAESrTPi-2007FTIRT=2D%(0%y10(0) QTY= 4 TOTAL= 4 REV. 12.03.03.0225.14 SCALE=0.2500
—WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
D'ONOFRIO DR., SURE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.Opsf
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
P E ET
10.Opsf
b�K
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL
DRWG
mz
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PE# 49200
BC LL O.Opsf
ROOF & FLOOR TRUSS SYSTEMS
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
CA# 27788
404 SW CAMDEN AVE
TOT.LD. 55.Opsf
O/A LEN. 120011
4176 MARTIN HIGHWAY
PALM CITY, FL 34990
DUR.FAC. 1.25
JOB #: KB0200
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPEC
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY
RI III nlNr; nFRIr mFR PFR ANSI/TPI 1-1995 SECTION 2
SPACING 24.0"
TYPE
JOD:(ICtlULUU) / I HYKKINU K1=5 / HI
Top chord 2x4 SP #2 13A
Bot chord 2x4 SP #2 13A
Webs 2x4 SP #2 13A
Filler 2x4 SP #2 13A
Lumber grades designated with 13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 16.55 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS. 779
a
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 dUrlWn_fad - _ 2-11-6
=3X5
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
All plates are 1.5X4 except as noted.
Special loads
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC- From 92 plf at -2.00 to 92 plf at 2.95
TC- From 92 pit at 2.95 to 92 plf at 7.96
BC- From 4 plf at -2.00 to 4 plf at 0.00
BC- From 20 plf at 0.00 to 20 plf at 2.95
BC- From 20 plf at 2.95 to 20 plf at 5.89
BC- From 4 pit at 5.89 to 4 plf at 7.96
TC- 76.98 lb Conc. Load at 2.95
BC- 44.33 lb Conc. Load at 2.95
Laterally brace BC at 24" OC in lieu of rigid ceiling. Laterally brace BC above filler at 24" OC.
211"6 -----� Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
aaa
R=587# U=262# W=1"8 R=586# U=262# W=1"B
(Rigid Surface) (Rigid Surface)
LEFT RAKE = 2'1 "6 RIGHT RAKE = 21 "6
SEQ = 265664
PLT.TYP: WAVE DESIGN CRR"FBC70FM2RESrrMD07FTIRT-2D%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON. WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. ••IMPORTANT' FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI(rPI 1-1995 SECTION 2. __ _ __ _ ___
PE# 49200
CA# 2775$
404 SW CAMDEN AVE
STUART, FL 34994
_
BC LL 0.0psf
TOT.LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 60004
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (T72) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
_
TYpE COMN
JOD:(KbULUU) / I HYKKIN(i Kt=b / H"L
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #2 13A
Filler 2x4 SP #2 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013. whichever is less.
Bottom chord checked for 10.00 pat non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
1 2'11"6 1 2'11"6 --�
=3X5
R=526# U=534# RL=117/-117# W=1"8 R=526# U=534# W=1"8
(Rigid Surface) (Rigid Surface)
THIS DWG. PREPARED 8Y l HE ALPINE JUH UESIGNER PRUGRAM FROM I HUSS MFIi'J LAYUU I
All plates are 1.5X4 except as noted.
170 mph wind, 16.55 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 pat, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Laterally brace BC at 24" OC in lieu of rigid ceiling. Laterally brace BC above filler at 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
LEFT RAKE = 2'1"6 RIGHT RAKE = 2'1"6
SEQ = 265638
PLT. TYP -WAVE DESIGNCRIT-FBC10HVHZRES/TPM07FTIRT=29%(0%)110(0) QTY= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
0
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
Tor. LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 60004
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 268-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE COMN
)b:(KbUZUU) / I HYRRING RES / H3
Top chord 2x4 SP 42_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #2 13A
Filler 2x4 SP #2 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
1 2'11"6 1 2'11"6
12 =3X5
T
m3X5(At',
T�
R=332# U=289# RL=461-46# W=1"8
(Rigid Surface)
tn
R=332# U=289# W=1"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
All plates are 1.5X4 except as noted.
170 mph wind, 16.98 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TIC DL=5.0
psf, wind BC DL=5.0 pat. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Laterally brace BC at 24" OC in lieu of rigid ceiling. Laterally brace BC above filler at 24' OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 8.49 ft. from roof edge.
SEQ = 265626
PLT. TYP: WAVE DESIGN CRIT=FBC70lMRREarM2007FRRT-2D%(0%v70(0) QTY= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC ILL 30.0 sf
P
REF
DATE 05-09-2014
Wrft
D'ONOFRIO DR., SUITE 200, MADISON, N. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
,
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOORTRUSS SYSTEMS
O/A LEN. 51012
4175 MARTIN HIGHWAY
PALM CITY, FL 34NO
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPF COMN
lob:(KB0200) / THYRRING RES / EJ7A
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
I� 2' 1 7'
R=621# U=473# RL=3331-91# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THt ALHINt JUH UtJIUNLK PKL)UKAM FKUM I KUbS MI'K 2A LATUU 1
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TIC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
R=268# U=307# NAILED
v
0
-v
R=128# NAILED
SEQ = 265376
PLT. TYP: WAVE DESIGN CRIT"F8C1OWMESUPF2007FTIRT-2D%(0%YI0(0) QTY= 13 TOTAL= 13 REV. 12.03.03.0225.14 SCALE=0.7500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
D'ONOFRIO DR., SURE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
T� °` 15.Opsf
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
P E ET
A�K
COPY OFTHIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.Opsf
DRWG
MWITH
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
PE# 49200
CA# 27788
404 SW CAMDEN AVE
BC LL O.Opsf
TOT.LD. 55.0psf
ROOF &FLOOR TRUSS SYSTEMS
O/A LEN. 7
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
DUR.FAC. 1.25
JOB #: KB0200
OFF: (772) 288-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
STUART, FL 34994
SPACING 24.0"
TYPE EJACK
FAX: (772) 288-4234
SUITABILITY AND USE OFTHIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
RIIII ❑INr7 nFSIGNFR PER ANSIrrPI 1-1995 SECTION 2.
IOb:(KBUZUU) I 1 HYKKING RE6 I EJ71:3
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP #2_13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 06 SP #2_13A:
Lumber grades designated With "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
Truss passed check for 20 psf additional bottom chord live load in areas with 42"-high x 24"-wide clearance.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
—2' -1 -7'1"8
R=739# U=498# RL=336/-92# W=5"8
(Rigid Surface)
LEFT RAKE = 2'811
R=288# U=329# NAILED
R=1930 NAILED
THIS DWG. PKtPAKEU BY I Ht ALPINt JUtl UtSIGNtK PKUGKAM MUM 1 KUJJ MI•rca L TVU 1
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wnd loads and reactions based on both MWFRS and C&C.
Calculated horizontal deflection is 0.28" due to live load and 0.23" due to dead load.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265380
PLT. TYP: WAVE DESIGN CRR=FBCIOfMRRFSRPF2M7FTIRT=2D%(0%)11%0) QTY= 3 TOTAL= 3 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING- TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0Sf
p
REF
DATE 05-09-2014
D'ONOFRIO DR., SURE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
P E ET
TC DL 15.Opsf
DRWG
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.0psf
ma
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27788
BC ILL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 70108
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 16D A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
404 SW CAMDEN AVE
DUR.FAC. 1.25
JOB #: KB0200
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
USE THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPEC
FAX: (772) 288-4234
SUITABILITY AND OF
BUILDING _DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
SPACING 24.0"
TYPE
BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP 92_13A
Webs 2x4 SP #2 13A
Filler 2x4 SP #2 13A
Lumber grades designated with "'I 3A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
I
R=435# U=480# RL=229/-62# W=1"8
(Rigid Surface)
LEFT RAKE = 2'1"6
R=77# U=133# NAILED
T_ 7
1
R=44# Rv--49# U=11# NAILED
All plates are 1.5X4 except as noted.
170 mph wind, 16.55 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Laterally brace BC at 24" OC in lieu of rigid ceiling. Laterally brace BC above filler at ZV OC.
Deflection meets U360 live and L/240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 16.55 ft. from roof edge.
SEQ = 265654
PLT.TYP: WAVE DESIGN CRIT-FBC10HVHZRES/rPF1007FTIRT-20%(0%)M0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI RUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
whzu
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIlrPI 1-1995 SECTION 2.
PE# 49200
CA# 27758
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 3
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TypE EJACK
JOD:(KbULUU) / I HYRRIN(i RtS / EJ2A
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
T
2' + 2'
R=423# U=879# RL=319155# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC Q 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=5# Rw=98# U=50# NAILED
1
R=19/-15# Rw=-103# U=22# NAILED
SEQ = 265378
PLT. TYP.-WAVE DESIGN CRIT=FBCI0lM4RESrrPF2007FTIRTe2D%(0%y10(D) QTY= 9 TOTAL= 9 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING' TRU(SES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
b
9-
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EP
EXCT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSirrPI 1-1995 SECTION 2.
-
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
-
TOT.LD. 55.Opsf
DATE 05-09-2014
DRWG
-1
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 2
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DLI W AC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE EJACK
Top chord 2x4 SP #2_13A
Bot chord 2x6 SP_#2_13A
Webs 2x4 SP #3 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
(1-11) = (J) Hanger not calculated (1)2x4 SP M-31
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50
r
i
11
- 1110"8+ 713
�-- -7-13 --�
7"1 1'3"7
16778 18
R=1523# U=448# W=5"8 R=465# U=250#
(Rigid Surface) H = H1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 92 pit at 0.00 to 92 pit at 2.53
BC- From 20 plf at 0.00 to 20 plf at 1.87
BC- From 24 plf at 1.87 to 24 plf at 2.53
PLT- 6.57 lb Conc. Load at ( 1.87,13.57)
PL8-1677.08 lb Conc. Load at ( 0.59,12.81)
PLB-17.82 lb Conc. Load at ( 1.87,12.54)
Wind loads and reactions based on MWFRS.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265798
PLT. TYP.-WAVE DESIGN CRIT=FBCI0M/HZREB/rPF2007FT1RT-Mj0%)H0i0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=1.0000
—WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
maKO
D'ONOFRIO DR., SUITE 200, MADISON, VVI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
_
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIITPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 20605
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX: (772) 288-4234
DUR.FAC. _ 1.25
JOB #: KB0200
SPACING 24.0"
TYPE HI PM
/J1
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1130/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
T
Pl
LEFT RAKE = 2'0"9
THIS DWG. PREPAKLU BY I Ht ALI INt JUtl LILZAUNtK PKUUKAM rKUM I KUAO mrm O L T vV I
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and L/240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
R=279# U=313# NAILED
2' 7'2"13 — -
R=633# U=474# RL=3391-93# W=5"8
(Rigid Surface)
R=133# NAILED
SEQ = 265454
PLT. TYP: WAVE DESIGN CRIT-FBC70MMZRESfrM007FTIRT-2D%(0%u70(0) QTY= 1 TOTAL= 1 -REV. 12.03.03.0225.14 SCALE=0.7500
—WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
E ET
TC DL 15.Opsf
DRWG
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P
BC DL 10.0psf
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
INDICATES
PE# 49200
CA# 27785
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 70213
4175 MARTIN HIGHWAY
1.25
KB0200
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING ACCEPTANCE
404 SW CAMDEN AVE
DUR.FAC.
JOB #:
OFF: (772) 286-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
THIS FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
JACK
FAX: (772) 288-4234
_
SUITABILITY AND USE OF COMPONENT
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2.
SPACING 24.0"
TYPE
1OD:(KbUZUU) / I HYKKINLi Ktb / JZ I HIS UWG. PREPARED BY I Ht ALPINE JUH UtbIUNtK PKUliKAM t-KUM I KUAJ WK A LAYUU I
Top chord 2x4 SP #2_13A 170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
Bot chord 2x4 SP_#2_13A psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those Wind loads and reactions based on both MWFRS and C&C.
approved by ALSC on 1 /30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
T
P1
1 2.
LEFT RAKE = 2'0"9
PLT. TYP.-WAVE
rml IK;O� T
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 288-3700
FAX: (772) 288-4234
R=604# U=471# RL=3251-89# W=5"8
(Rigid Surface)
DESIGN CRIT=FSCI0FNITZRESfTM007
R=253# U=297# NAILED
0
io
6'8"2 1
R=123# U=1# NAILED
QTY= 1 TOTAL= 1
:R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
OFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
MONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
.LS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
(OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
IONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
:PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
ROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
4BILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
vr,ir_ ncelr_uoo oce �IJCl/TDI �_100C CClTln�l O
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART. FL 34994
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.Opsf
BC DL
10.Opsf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 265452
SCALE=0.7500
REF
DATE 05-09-2014
DRWG
O/A LEN. 60802
JOB #: KB0200
TYPE JACK
)D:(KbUZUU) / I HYRRING RES / J3
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "l3A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
T
Pj1
1
�— 2' 57"9
R=552# U=466# RL=2981A1# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft, from roof edge.
R=206# U=265# NAILED
R=101# U=1# NAILED
SEQ = 265451
PLT.TYP.-WAVE DESIGN CRIT=FBC70HVHZRESrrPI-2007FHRT=2D%(0%u10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE =0.7500
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.Opsf
REF
O
M—K
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TIC DL 15.Opsf
BC DL 10.Opsf
DATE 05-09-2014
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A663 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-7- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI(rPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 3_4
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 50709
4176 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 281-3700
FAX: (772) 26&4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 240"
.
TYPE JACK
Job:(KB0200) If THYRRING RES / J4
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP #2 13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
z' 1 47
R=502# U=462# RL=269/-74# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=157# U=221# NAILED
R=79# NAILED
SEQ = 265450
PLT.TYP-WAVE DESIGN CRIT-FBCIOHVHZRES/rPP2007FTIRT-2D%(C%N70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=1.0000
'•WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC ILL. 30.0 Sf
P
REF
DATE 05-09-2014
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
TC DL 15.0PSf
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
P E ET
i�K
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.OPSf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
PE# 49200
CA# 27788
404 SW CAMDEN AVE
BC LL O.OPSf
TOT.LD. 55.OPSf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 40700
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
DUR.FAC. 1.25
JOB #: KB0200
OFF: (772) 28IS-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
STUART, FL 34994
SPACING 24.0"
TYPE JACK
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
]ID:(KtiUZUU) / I HYKKING KEb / J5
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
R=989 U=156# NAILED
(- 2 _I_ 3 5. 1
R=453# UT=465# RL=236/-65# W=5"8 R=53# U=5# NAILED
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265455
PLT.TYP.-WAVE DESIGN CRn-F8C1@MRRESrrPF2007FT1RT-2D%(0%y10(0) QTY=1 TOTAL=1 REV. 12.03.03.0225.14 SCALE=1.0000
..WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (rRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
=KO
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. —IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET -
TC IL 15.Opsf
BC DL 10.Opsf
DRWG
.
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPTAS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT. LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 30500
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
-4 FAX: (772) 288234
_
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
)D:kMtSULUU) / I I ITKKINU Kt,) / Jb
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All Wind load cases on this truss have a 1.33 duration factor.
T
L
I- 2'
LEFT RAKE = 2'0"9
I rII, UVVU. Fn(CF'AKt:U tlT I MM ALr II%M JU6 umoi Nmm t'KUUr mm Alum I muoo warm O L 1 w—
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
R=36# Rw=107# U=61# NAILED
1'7" —�
R=433# U=550# RL=183/-52# W=5"8
(Rigid Surface)
R=7/31# Rw=78# U=32# NAILED
SEQ = 265456
PLT. TYP: WAVE DESIGN GRIT"FBC10nVHZRESfrPF2007FT1RT-20%I0%y10(0) QW= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
ft
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
o—K
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER. PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 10700
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
)D:(Kt1UGUU) / I HYRRIN(3 RES / J7 THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Top chord 2x4 SP 1650f-1.5E 170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
Bot chord 2x4 SP_#2_13A psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those Wind loads and reactions based on both MWFRS and C&C.
approved by ALSC on 1/3012013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load. In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
All wind load cases on this truss have a 1.33 duration factor. Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=99# Rw=313# U=104# NAILED
1 2"3
R=467# U=1077# RL=278/-49# W=5"8
(Rigid Surface)
R=47# Rw=157# U=45# NAILED
LEFT RAKE = 2'0"9
SEQ = 265448
PLT.'TYP: WAVE DESIGN CRr=FBC10HJHZRES1TPF2007FT/RT=2D%(0%)/10(0) QTY= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.Opsf
REF
D'ONOFRIO DR., SURE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TIC DL 15.Opsf
DATE 05-09-2014
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. •'IMPORTANT" FURNISH A
P E ET
DRWG
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.Opsf
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27788
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
O/A LEN. 10203
DUR.FAC. 1.25
JOB #: KB0200
PALM CITY, FL 34990
OFF: (772) 286-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 24.0"
JACK
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
TYPE
Rtb / L:JbA
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A' indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load
All wind load cases on this truss have a 1.33 duration factor.
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 R mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MW RS and C&C.
In lieu of rigid ceiling use pudins to brace BC Q 24" OC.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=177# U=241# NAILED
I _ 2' T
_ _I_ 5, 1
R=521# U=464# RL=281/470 W=5"8 R=88# U=1# NAILED
(Rigid Surface)
LEFT RAKE = 2'0"9
SEQ = 265374
PLT. TYP.-WAVE DESIGN CRIT-FBCIONVHZRESrrPI-2007FTIRT"2D%(0%)t10(0) QTY= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SURE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD, 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 5
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
)D:(t\t1UZUU) / I NYKKINC9 K1=5 / GJbb
Top chord 2x4 SP_#2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x6 SP_#2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50
MWFRS loads based on trusses located at least 15.00 ft, from roof edge.
R=168# U=246# NAILED
I� 2' 1 5'
R=527# U=495# RL=281/-77# W=5"8 R=87# NAILED
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind (Gads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'8"11
SEQ = 265382
PLT. TYP: WAVE DESIGN CRR=FBCIOHVHZRE5/TP42007FTIRT-2D%(0%)70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIS-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
D'ONOFRIO DR., SURE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
TC DL 15.0psf
DATE 05-09-2014
b
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
P E ET
DRWG
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
BC DL 10.0psf
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PE# 49200
CA# 27788
BC LL O.Opsf
Tor.LD. 55.Opsf
ROOF & FLOORTRUSS SYSTEMS
4175 MARTIN HIGHWAY
O/A LEN. 5
DUR.FAC. 1.25
JOB #: KB0200
PALM CITY, FL 34990
OFF: (772) 281-3700
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
404 SW CAMDEN AVE
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
STUART, FL 34994
SPACING 240"
SPEC
BUILDING DESIGNER PER ANSIITPI 1-1995 SECTION 2.
.
TYPE
IOD:(KCULUU) / I HYKKINU Ktb / L;JbL;
Top chord 2X4 SP #2_13A
Bot chord 2X4 SP_#2 13A
Webs 2X4 SP #3 13A
:Lt Bearing Leg 06 SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets 1-/360 live and U240 total load. Creep increase factor for dead load is 1.50. ,
2'0"12 —
R=526# U=481# RL=282/-77# W=3"4
(Rigid Surface)
LEFT RAKE = 27'5
R=179# U=256# NAILED
4'11 "4 M I
R=89# NAILED
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 4.50 It from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265394
PLT. TYP: WAVE DESIGN CRIT=FBCIOHVHZRES/rPI-N7/FT/RT-20%(0%)H0(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
=-1
ft
D'ONOFRIO OR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
_TC IL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 3, 994
BC LL O.Opsf
TOT,LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 41104
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
F-4 FAX: (772) 288234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
J0D:(ICtfU000) / I HYRRING RES / CJ3A
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=75# U=129# NAILED
2, 1 3, 1
R=439# U=471# RL=224/E2# W=5"8
(Rigid Surface)
R=44# Rw=49# U=10# NAILED
SEQ = 265372
PLT. TYP: WAVE DESIGN CRr=FBC1@M4RESrfP42007FDRTrA%(0%)11a0) QTY= 2 TOTAL= 2 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 Sf
p
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SURE 200, MADISON. WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. "'IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
IDL 15.0psf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-7- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 3
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
REb / GJ313
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x6 SP #2_13A:
Lumber grades designated with "13A" indicate design values confomt with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
R=54# Rw=60# U=123# NAILED
in
v I
�--2'012- -I 2'11"4 -i
R=446# U=494# RL=224/b3# W=3"4
(Rigid Surface)
R=49# NAILED
LEFT RAKE = 27'5
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265392
PLT. TYP: WAVE DESIGN CRR-FBc10WHzaesrmi-aro7FT1RT=mvlozlnam QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
'"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
0
M <-,
O'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
_
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-7- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSUfPI 1-1995 SECTION 2.
PE# 49200
CA# 27786
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 21104
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYpE SPEC
JOD:(IKt$ULUU) / 1 t1YKKINLi KtJ / L;JJL;
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP_#3_13A
:Lt Bearing Leg 2x6 SP_#2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC an 1/30/2013, whichever is less.
Deflection meets U360 live and L/240 total load. Creep increase factor for dead Iliad is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
R=36# Rw-83# U=106# NAILED
�2 + 3
R=4549 U=518# RL=2241-62# W=5"8
(Rigid Surface)
R=47# NAILED
LEFT RAKE = 2'8"11
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265384
PLT. TYP: WAVE DESIGN CRR-FBC10HVHZRES/TPI-2007FDRT=2D%(D'%)110(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
wKft
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.0psf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIIrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 3
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (T72) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE SPEC
JOb:(KBUZUU) / 1HYRRING RES / CJ1A
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Top chord 2x4 SP 1650f-1.5E
Negative reaction(s) of -199# MAX. (See below) from a non -wind load case requires uplift connection.
Bot chord 2x4 SP_#2_13A
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
approved by ALSC on 1/30/2013, whichever is less.
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
R=200# Re --592# U=198# NAILED
2' 11"--}. I
R=500# U=1181# RL=268/48# W=5"8
(Rigid Sudare)
LEFT RAKE = 2'0"9 RIGHT RAKE = 1 "1
SEQ = 265399
PLT. TYP: WAVE DESIGN CRR=FBC10HVHZRESlrPF2007FTIRT=20'b(0'%)/10(0) QTY= 10 TOTAL= 10 REV. 12.03.03.0225.14 SCALE=1.0000
—WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING,. SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
O
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC' DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/rPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 1
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE JACK
JOD:(I\tSULUU) / I NY KKINU KtJ / L;JI b
Top chord 2x4 SP 1650f-1.5E
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
11"4
R=-1779 Rw=572# U=1870 NAILED
2'0"12 1 10"4 --1^1
R=468# U=1174# RL=273/-48# W=1"8
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Negative reaction(s) of -177# MAX. (See below) from a non -wind load case requires uplift connection.
170 mph wind, 16.13 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'1 "6 RIGHT RAKE = 1 "1
SEQ = 265617
PLT. TYP: WAVE DESIGN CRIT=FBC10M/F2RESrrPF2(107FTIRT-2%(0%)110(0) QTY= 4 TOTAL= 4 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
D%Kft
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
.
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A.Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 1
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
)D:(IItSUZUU) / I r1TKKINIi KtJ / HJ(A
Top chord 2x4 SP M-31
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3 13A
:Lt Bearing Leg 2x8 SP #2_13A:
Lumber grades designated with "l3A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013. whichever is less.
170 mph wind, 15.00 ft mean hgt. ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load.
Top chord overhangs have been checked only for loads as indicated. Overhangs not checked for man loads or long -tens
deflection.
-1770 _ 3479
�m�-- 2'9"15 ---+- 2-9.15 - 2-11.5
R=100# U=22# NAILED
T
1
�_ 2-t V 1 911112 1
�- 3-6.10
sss
R=455# U=507# W=3"14
(Rigid Surface)
LEFT RAKE = 37'
175:
R=328# U=139# NAILED
PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 0 plf at-2.92 to 91 plf at 0.00
TC- From 2 plf at 0.00 to 2 plf at 9.32
BC- From 0 plf at -2.92 to 4 plf at 0.00
BC- From 2 plf at 0.00 to 2 plf at 9.32
TC--127.23 lb Conc. Load at 0.72
TC- 89.79 lb Conc. Load at 3.55
TC- 347.07 lb Conc. Load at 6.38
BC- 95.39lb Conc. Load at 3.55
BC- 175.41 lb Conc. Load at 6.38
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265430
PLT. TYP. WAVE DESIGN CRR"FBC10Ha1ZAESrrPF2D07FTIRT-2D%(0%N10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.2500
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI RUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
m2��K
i
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED, APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY, AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUARTFL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 91102
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 2a8-4234
DURFAC1.25
..
JOB #: KB0200
SPACING 24.0"
TYpE SPEC
IOD:(RC3000U) / 1171TKKINU KtJ / NJ/C
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSO on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
170 mph wind, 15.00It mean hgt, ASCE 7-10. CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
LEFT RAKE = 2'10"6
THIS DWG. PREPARED BY 1 Fit- ALPINt JOB Ut51GNLK PROGRAM FROM TRUSS MFF
Special loads
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC- From 0 pit at -2.83 to 91 pit at -0.00
TC- From 2 pit at -0.00 to 2 pit at 9.84
BC- From 0 pit at -2.83 to 4 pit at -0.00
BC- From 2 pit at -0.00 to 2 pit at 9.84
TC--127.23 lb Conc. Load at 1.37
TC-149.63 lb Conc. Load at 4.20
TC- 353.45 lb Conc. Load at 7.03
BC- 87.34lb Conc. Load at 4.20
BC- 175.49 lb Conc. Load at 7.03
In lieu of rigid Ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
-1270 160 353#
�-- 1'4"7 T 2'9"15 2'9"15 2'9"12 +I
2'9"15 +I
R=14/5# Rw=43# NAILED
M
N
G
�f
2'9"15 9110"1 I
R=470# U=538# W=7"
(Rigid Surface)
4'2"6 1 I
87# 175p
R=4689 U=266# NAILED
SEQ = 265723
PLT. TYP: WAVE DESIGN CRIT=FBC10hVKRE5rrPI-2W7FTIRT=20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 563
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
wirFUNCTIONS.
w
D'ONOFRIO DR., SURE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z_ THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIRPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART , FL 34994OB
BC LL O.Opsf
TOT.LD. 55.0pSf
ROOF 8 FLOOR TRUSS SYSTEMS
O/A LEN. 91001
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
J #: KB0200
SPACING 24.0"
TypE HIP JACK
)D:kl\bULUU) / I f1YKKINU Kt5 / tiJSA
Top chord 2x4 SP#213A
Bot chord 2x4 SP_ #2__13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets L/360 live and U240 total load. Creep increase factor for dead load is 1.50.
-710
�157
T
W14
i
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUI
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 92 plf at -2.30 to 92 plf at 5.24
BC- From 4 plf at -2.30 to 4 pff at 0.00
BC- From 20 plf at 0.00 to 20 plf at 5.24
TC--71.22 Ib Conc. Load at 1.45
BC--9.73 lb Conc. Load at 1.45
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
3'9'7
R=166# U=133# NAILED
— 2'3"10 1 5'2"14 _I
R=511# U=474# W=67
(Rigid Sudam)
LEFT RAKE = 2'41
f
-100
R=90# U=18# NAILED
SEQ = 265712
PLT. TYP: WAVE DESIGN CRR=F8C10MMZRESrrMDD7FrIRT=2D%(0%)I10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.7500
—WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
P
REF
DATE 05-09-2014
M2KO
D'ONOFRIO DR., SURE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
.
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSIRPI 1-1995 SECTION 2. _ _ _ _
PE# 49200
CA# 27788
404 SW CAMDEN AVE,
STUART, FL 34994
BC LL O.Opsf
TOT,LD. 55.0psf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 50214
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
-4 FAX: (772) 288234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE JACK
iOD:kMt3ULUU) / I t1YKKINCi KtZ5 / NJSti
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP_#2 13A
Filler 2x4 SP #2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 16.52 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Laterally brace BC at 24" OC in lieu of rigid ceiling. Laterally brace BC above filler at 24" OC
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50,
LEFT RAKE = 2'1011
PLT. TYP.-WAVE
O
ROOF & FLOOR TRUSS SYSTEMS
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 2a8-4234
_ssa
�— V411 2 8 5 —�
R=43/-33# U=61# NAILED
T
1
R=286# U=341# W=2"2
(Rigid Surface)
DESIGN CRIT48C10HVHZRESrrPi-2007
R=62/-26# U=33# NAILED
PREPARED BY THE ALPINE
All plates are 1.5X4 except as noted.
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 0 plf at -2.83 to 91 p1f at 0.00
TC- From 2 pit at 0.00 to 2 pit at 4.08
BC- From 0 pit at-2.83 to 4 pit at 0.00
BC- From 2 plf at 0.00 to 2 plf at 4.08
TC--95.69 lb Conc. Load at 1.39
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load.
All Wind load cases on this truss have a 1.33 duration factor.
QTY= 2 TOTAL= 2
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. ••IMPORTANT^ FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z_ THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
PROGRAM FROM
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.0psf
BC DL
10.0psf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 265646
SCALE=0.5000
REF
DATE 05-09-2014
DRWG
O/A LEN. 40104
JOB #: KB0200
TYPE HIP JACK
JOD:(KtSULUU) / I HYKKIN(i KES / HJ3A
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 15.00 ft mean hgt. ASCE 7-10, CLOSED bldg. Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From
0 plf at -2.83 to 91 pif at 0.00
TC- From
2 pif at 0.00 to 2 pif at 2.59
BC- From
0 pit at -2.83 to 4 pit at 0.00
BC- From
2 pif at 0.00 to 2 pif at 2.59
TC- -127.23lb
Conc. Load at 1.41
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
-127#
R-7l- 79 U=129# NAILED
V14 3X5(A1)
3.54 p
T
a _
2'9"15 27"1 1
R=259# U=288# W=7' R=18144# U=40# NAILED
(Rigid Surface)
LEFT RAKE = 2'10"6
SEQ = 265786
PLT.TYP: WAVE DESIGN CRrT=FBC70KHnESrrPF2W7FTIRTep%(0%y10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
wkrFUNCTIONS.
w
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL 0.0psf
TOT.LD. 55.0psf
ROOF 8 FLOOR TRUSS SYSTEMS
O/A LEN. 20701
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 285-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
_
TYPE HIP JACK
JOD:(tIbSUZUU) / I f1YKKINU Kt_S / HJZA
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph vrind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bidg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360live and U240 total load. Creep increase factor for dead load is 1.50.
T
LEFT RAKE = 210"6
PLT. TYP: WAVE DESIGN
M&K
ROOF & FLOOR' SYSTEMS
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 281-3700
FAX (772)289-4234
=-3x5(A7)
12
3.54 p
5
-1270
I 1'4"7
2'9"3
R=261# U=306# W=7"
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB UESIUNtK PKUGKAM
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac=1.25)
TC- From 0 plf at -2.83 to 91 plf at 0.00
TC- From 2 pit at 0.00 to 2 pit at 2.77
BC- From 0 plf at -2.83 to 4 plf at 0.00
BC- From 2 pit at 0.00 to 2 plf at 2.77
TC- -127.23lb Conc. Load at 1.37
Wind loads and reactions based on MWFRS.
Bottom chord checked for 10.00 psf non -concurrent live load
Al wind load cases on this truss have a 1.33 duration factor.
QTY= 2 TOTAL= 2
1'4"12
R=12/ 8# U=109# NAILED
=R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
IOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
:TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
=LS AND BOTTOM CHORD SHALL HAVE PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
Y OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
'ONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
t TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
i APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
=PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
ABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
Illl.11- hCCll^_1 . ... AI.Ie .. I_1... cCt`T—K. �
R=23/42# U=41# NAILED
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.0psf
BC DL
10.0psf
BC LL
0.0psf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
MFK'b LAYUU I
SEQ = 265446
SCALE=1.0000
REF
DATE 05-09-2014
DRWG
O/A LEN. 20903
JOB #: KB0200
TYPE HIP_JI
)D_(Kt9UZUU) / I HYRRING RES / M1
Top chord 2x4 SP #2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/3012013, whichever is less.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
�1
�2-+I
R=848# U=508# RL=436/-121# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
11'3"1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(H1) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 15.00 ft. from roof edge.
R=606# U=404#
H=H1
SEQ = 265690
PLT. TYP.-WAVE DESIGN CRIT=FBC10MMZRESRPF2007Fr1RT=iD%(0%U70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.0 sf
P
REF
DATE 05-09-2014
Md_1
k
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TIC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
0/A LEN. 110301
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 2843-3700
FAX: (T72) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
TYPE MONO
)D:kr,bULUU) / IN Y KKIN(j Kt5 / ML
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Top chord 2x4 SP #2_13A
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT 11, EXP C,
Bot chord 2x4 SP_#2_13A
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Webs 2x4 SP #3_13A
Wind loads and reactions based on both MWFRS and C&C.
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Right end vertical not exposed to wind pressure.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Bottom chord checked for 10.00 psf non -concurrent live load.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load rases on this truss have a 1.33 duration factor.
M WFRS loads based on trusses locate at least 7.50 ft. from roof edge.
10'3"4
- - 11"12 -'
�2'-�
R=848# U=521# RL=4101-114# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
PLT. TYP. WAVE
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 266-3700
FAX: (772) 288-4234
DESIGN CRIT=FBC70HVHZRESrrP42007
QTY= 1 TOTAL= 1
:R TOHIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
OFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
:TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
.LS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. --IMPORTANT-" FURNISH A
(OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
�ONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 200A ASTM A653 GR40 GALV. STEEL
:PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
ROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
4BILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
vMr nrSirhirp GGC eMQITPl 1-10OR QPrTInM 9
D 1.5X4
:3X5
R=606# U=415#
H=H1
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.Opsf
BC DL
10.0psf
BC LL
O.Opsf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
SEQ = 265699
SCALE=0.5000
REF
DATE 05-09-2014
DRWG
O/A LEN. 110301
JOB #: KB0200
TYPE MONO
JOD:(KCULUU) / I HYKKINU Kt5 / M3
Tap chord 2x4 SP_#2_13A
Bot chord 2x4 SP_#2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 113012013, whichever is less.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
�-2
R=848# U=552# RL=3551-100# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYUU 1
170 mph wind, 15.00 It mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 R from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft. from roof edge.
8'3"4 2'11"l2
11'3"1
R=606# U=4319
H=H1
SEQ = 265703
PLT. TYP. WAVE DESIGN CRIT-F8C10HVHZRESTTPF2007FT1RT"2D%(0%)10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 30.0 sf
P
REF
DATE 05-09-2014
WA-
U
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
_
P E ET
TIC DL 15.0psf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z- THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONS1131LITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 110301
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 2845-3700
FAX: (772) 28& 4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE COMN
IDD:(Kb000U) / I HYRRING RES / M4
Top chord 2x4 SP #2_13A
Sot chord 2x4 SP #2_13A
Webs 2x4 SP #3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Bottom chord checked for 10.00 psf non -concurrent live load.
All wind load cases on this truss have a 1.33 duration factor.
2
R=847# U=541# RL=3951-98# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
7'10"8
11'3"1
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
(`7 1 plate(s) require special positioning. Refer to scaled plate plot details for special positioning requirements.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
Right end vertical not exposed to wind pressure.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
MWFRS loads based on trusses located at least 7.50 ft, from roof edge.
2'7"9 1 815 +
2.32 0
R=600# U=388#
H=H1
SEQ = 265710
PLT. TYP: WAVE DESIGN CRIT=FBCI0MIIiZRESrrP4M07FT1RT-WA(0%Y70(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING NSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.Opsf
REF
DATE 05-09-2014
WKKU
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
_
P E ET
TC DL 15.Opsf
BC DL 10.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BULDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT,LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 110301
4175 MARTIN HIGHWAY
34990
PALM CITY, FL OFF: (772) 288-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: K60200
SPACING 24.0"
TYPE COMN
)D:(I\CUGUU) / 1 r1TKKINU Kt:b / M5
Top chord 2x4 SP #2_13A :T2 2x4 SP M-31:
Bot chord 2x4 SP 1650f--1.5E
Webs 2x4 SP_#3_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 ft from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
(111) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
THIS DWG. PREPARED BY THE ALPINE JOB UESIGNEK
Special loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac=1.25)
TC- From 92 pit at -2.00 to 92 pit at 4.57
TC- From 45 pit at 4.57 to 45 plf at 11.25
BC- From 4 pit at -2.00 to 4 pif at 0.00
BC- From 20 pit at 0.00 to 20 pit at 4.57
BC- From 10 pif at 4.57 to 10 pif at 11.25
TC- 323.39 lb Conc. Load at 4.57
TC- 205.69 lb Conc. Load at 6.91
TC- 252.66 lb Conc. Load at 9.17
BC-168.57 Ib Conc. Load at 4.57
BC-100.95 lb Conc. Load at 6.91
BC-122.64 lb Conc. Load at 9.17
323# msl Right end vertical not exposed to wind pressure.
(a) Continuous lateral bracing equally spaced on member. Or 2x4 #3 or better "T' brace. 80% length of eb membe[ ,ached 7e� �,�"1 J
with 16d Box or Gun (0.135"x3.5",min.)nails @ 6" OC. n lieu of rj " ding use p runs to br a BC @ 24 `IOC.
Deflection meets U360live and U240 total load. Preep increase factorforAW load is 1.50. Bottom ct ff4checked for 10.00 sf non-concurre t ii live load.
Al[ wind load cases on this truss have a 1.33 duration factor.
R=1220# U=523# W=5"8
(Rigid Surface)
LEFT RAKE = 2'0"9
111 12 1113X5 _
11'3"1
1690 Io1>f 1230
PLT. TYP: WAVE DESIGN CRIT=FBCIOMMZRESrrPF2(p7FTIRT=2D%(0%)110(0) QTY= 1 TOTAL= 1
REFER TO HIS-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 563
D'ONOFRIO DR., SURE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
O
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
ROOF & FLOOR TRUSS SYSTEMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
4175 MARTIN HIGHWAY
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
PALM CITY, FL 34990
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OFF: (772) 288-3700
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
FAX: (772) 288-4234
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
RI III nwr nFCIr NPR PPP ANCVTPI 1-1 PQS CPr:TInM 2
R=1026# U=415#
H=H1
T. STILES
PEET -
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
REV. 12.03.03.0225.14
TC LL
30.Opsf
TC DL
15.0psf
BC DL
10.0psf
BC LL
0.0psf
TOT.LD.
55.Opsf
DUR.FAC.
1.25
SPACING
24.0"
FlVNl3L
SEQ = 265714
SCALE=0.5000
REF
DATE 05-09-2014
DRWG
0/A LEN. 110301
JOB #: KB0200
TYPE COMN
)1):(KLJU000) / I HYRRING RES / V4A
Top chard 2x4 SP #2_13A
Bot chord 2x4 SP #2_13A
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Bottom chord checked for 10.00 psf non -concurrent live load.
See DWG VAL180100212 for valley details.
MWFRS loads based on trusses located at least 7.50 ft, from roof edge.
2'3"6 ZTE
12 =3X5
T
I
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT 11, EXP C, wind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on both MWFRS and C&C.
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
All wind load cases on this truss have a 1.33 duration factor.
R=112pif U=100plf RL=5/-5plf W=4'612
(Rigid Surface)
SEQ = 265685
PLT. TYP. WAVE DESIGN CRR-FBC10rM2REBRP42707FTIRT-2D%(0%)/10(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=1.0000
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
S
D'ONOFRIO DR., SUITE 200, MADISON, WI.53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC IL 15.0psf
BC DL 10.0psf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIRPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994.
BC LL O.Opsf
TOT.LD. 55.Opsf
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 40612
4175 MARTIN HIGHWAY
PALM CITY, FL 34"0
OFF: (772) 286-3700
FAX: (772) 288-4234
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0°
ITYPE VAL
KES/F11
Top chord 2x6 SP #2_13A
Bol chord 2x6 SP #2_13A
Webs 2x4 SP #3_13A :W1, W9 2x6 SP_#2_13A:
:W2, WS 2x4 SP_#2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
Special loads
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC- From 4 pit at 0.00 to 4 pit at 21.74
BC- From 20 pit at 0.00 to 20 plf at 21.74
TC- 455.09 lb Conc. Load at 0.11
TC- 500.38 lb Conc. Load at 1.09
TC- 446.46 Ib Conc. Load at 3.09
TC- 525.931b Conc. Load at 5.09
TC-1320.54 lb Conc. Load at 7.19
TC- 665.33 lb Conc. Load at 9.19,11.19
TC- 878.74 lb Conc. Load at 13.19,15.19,17.19,19.19
TC-1007.43 lb Conc. Load at 21.34
170 mph wind, 15.00 ft mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 It from roof edge, RISK CAT 11, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
End verticals not exposed to wind pressure.
Max JT VERT DEFL: LL: 0.14" DL: 0.19" recommended camber 3/8"
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
The TC of this truss shall be braced with attached spans at 24" OC in lieu of structural sheathing.
PLT. TYP: WAVE DESIGN
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S
2 Complete Trusses Required
Nail Schedule:0.120"x3", min. nails
Top Chord: 1 Row @ 3.25" o.c.
Bot Chord: 1 Row @12.00" o.c.
Webs : 1 Row @ V o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
4" o.c. spacing of nails perpendicular and parallel to
grain required in area over bearings greater than 4"
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Truss must be installed as shown with top chord up.
All wind load cases on this truss have a 1.33 duration factor.
455# 446# 1321# 666# 8790 979E
2 2 21 "3 +- 2 !1 -- 2� 2 e�- 2 �-+- 2 9 2 21"1'807 0l
Te -8 0 m4X4- 8
W9
T�2 _ =3 0 2
1113 10 =5X7 1113 10
21'8"13 _1
R=4482# U=1575# W=5"8 R=5142# U=1369# W=5"8
(Rigid Surface) (Rigid Surface)
QTY= 1 PLIES= 2 TOTAL= 2
=R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 563
IOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
::TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
=L5 AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
Y OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
�ONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
i TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
i APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
.PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
ABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
REV. 12.03.03.0225.14
T. STILES
TC LL
30.Opsf
PEST
TIC DL
15.Opsf
BC DL
10.Opsf
PE# 49200
BC LL
O.Opsf
CA# 27788
TOT.LO.
55.Opsf
404 SW CAMDEN AVE DUR.FAC. 1.25
STUART, FL 34994
SPACING 24.0"
SEQ = 265683
SCALE=0.1875
REF
DATE 05-09-2014
DRWG
O/A LEN. 210813
JOB #: KB0200
TYPE FLAT
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Top chord 2x6 SP_#2_13A
Bot chord 2x4 SP_#2 13A
Webs 2x4 SP #3_13A :Wt, W5 2x6 SP #2_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 113012013, whichever is less.
170 mph wind, 16.00 It mean hgt, ASCE 7-10, CLOSED bldg, not located within 9.00 It from roof edge, RISK CAT II, EXP C,
wind TC DL=5.0 psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
Wind loads and reactions based on MWFRS.
(1-11) = (J) Hanger not calculated (3)2x6 SP M-26
supporting member.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
The TC of this truss shall be braced with attached spans at 24" OC in lieu of structural sheathing.
All plates are 3X7(R) except as noted.
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac=1.25)
TC- From 90 plf at 0.00 to 90 pit at 2.88
TC- From 4 plf at 2.88 to 4 plf at 11.07
BC- From 20 plf at 0.00 to 20 plf at 11.07
TC- 586.50 Ib Conc. Load at 2.88
TC- 525.84111 Conc. Load at 4.88, 5.48
TC- 331.56111 Conc. Load at 7.48, 9.48
End verticals not exposed to wind pressure.
In lieu of rigid ceiling use purlins to brace BC @ 24" OC.
Bottom chord checked for 10.00 psf non -concurrent live load
Truss must be installed as shown with top chord up.
All wind load cases on this truss have a 1.33 duration factor.
srfsn
1 2'10"8 2' 7"44 2' — 2' 1,7"
PLT. TYP.-WAVE DESIGN
rffi"1101"�—Iomsllmffin
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
R=438pif U=155pif W=5'9"12 R=266# U=35#
(Rigid Surface) H = H1
2 TOTAL= 2
:R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
OFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
:TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
.LS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
(OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
IONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
:PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
ROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
4BILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
REV. 12.03.03.0225.14
SEQ = 265675
SCALE=0.5000
TC LL
TC DL
BC DL
BC LL
TOT.LD.
30.Opsf
15.Opsf
10.Opsf
O.Opsf
55.Opsf
REF
DATE 05-09-2014
DRWG
O/A LEN. 110013
DUR.FAC.
1.25
JOB #: KB0200
SPACING
24.0"
TYPE FLAT
Ait
)D:(A[1UZUU) / I HYKKINh Kt,-) / I- 13
Top chord 2x4 SP M-31
Bot chord 2x4 SP_#2_13A
Webs 2x6 SP #2_13A :W2 2x4 SP #3_13A:
Lumber grades designated with "13A" indicate design values conform with those approved by ALSC on 1/5/2012 and those
approved by ALSC on 1/30/2013, whichever is less.
170 mph wind, 16.00 It mean hgt, ASCE 7-10, CLOSED bldg, Located anywhere in roof, RISK CAT II, EXP C, vrind TC DL=5.0
psf, wind BC DL=5.0 psf. GCpi(+/-)=0.18
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Deflection meets U360 live and U240 total load. Creep increase factor for dead load is 1.50.
The TC of this truss shall be braced with attached spans at 24" OC in lieu of structural sheathing.
10"5 1'11"1 � t'11"1 11"9 --4
I9Gx1NR1 maxR
VQ
5 10 12 III MrR1
ax7
R=1007# U=664# W=4"12
(Rigid Surface)
R=1018# U=676# W=4"12
(Rigid Surface)
THIS DWG. PREPARED BY I Ht ALPINL JUb UtblLiNtK I'KUliKAM t KUM I KUbb Mr-K'b LATUU I
Special loads
—(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC- From 4 plf at 0.00 to 4 pit at 5.89
BC- From 10 plf at 0.00 to 10 plf at 5.89
TC- 285.66 lb Conc. Load at 0.17, 5.83
TC- 468.11 lb Conc. Load at 1.03, 4.87
TC- 435.13 lb Conc. Load at 2.95
Wind loads and reactions based on MWFRS.
End verticals not exposed to wind pressure.
Bottom chord checked for 10.00 psf non -concurrent live load.
Truss must be installed as shown with top chord up.
All wind load cases on this truss have a 1.33 duration factor.
SEQ = 265668
PLT. TYP.-WAVE DESIGNCRR=FBC10KVHZRESrrP42007FrIRT=2D%(D%)HO(0) QTY= 1 TOTAL= 1 REV. 12.03.03.0225.14 SCALE=0.5000
"WARNING' TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIS-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 30.0 sf
p
REF
DATE 05-09-2014
WAZU
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/rPI 1-1995 SECTION 2.
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC DL 15.Opsf
BC DL 10.Opsf
BC LL O.Opsf
TOT.LD, 55.Opsf
DRWG
ROOF & FLOOR TRUSS SYSTEMS
O/A LEN. 51012
4175 MARTIN HIGHWAY
PALM CITY, FL 34990
OFF: (772) 286-3700
FAX: (772) 288-4234
_
DUR.FAC. 1.25
JOB #: KB0200
SPACING 24.0"
ITYPE FLAT
-,.w�us..�.w.-s.es:Hx:x^cnzas..�e�a-xes.:•wr.x _.e,..
—Project Information:
Name:
THYRRING RES
Address:
City, State, Zip:
GENERAL TRUSS ENGINEERING CRITERIA & DESIGN LOADS:
Building Code & Chapter. Computer Program Used:
VIEW by Alpine
Custom
Gravity: Gravity:
55 psf Roof Total Load 60 psf Floor Total Load
Wind.
170 mph from ASCE 7-10 code
This package includes a Truss Index Sheet and 14 individual truss design drawings, together with the attached index of the Truss System
design drawings. I hereby certify that this serves as a cover sheet in accordance with -Chapter 61G15-31.003 of the -Florida Board of
Professional Regulations.
..�Illllfl/._
* 49200
O
TF pF ;
,-�.r_\���
MAN Rltil
Note: Furthermore, the responsibility of the undersigned is solely limited to the'
design of the truss components shown. The suitability and use of these
trusses for any building is the responsibility of the building designer.
Delegated Engineer: T. Stiles Peet, P.E.
Stiles Engineering Group, Inc.
FL Reg Nos: PE# 49200 CA# 27788
404 SW Camden Ave. Stuart, FL 34994
TEL: 772-223-9883 FAX:772-223-9502
No I
Truss ID
Date
11
FT12
07/31/14
12
FT13
07/31/14
13
FT14
07/31/14
14
FT15
07/31/14
HomeBASEbyAlpine Page 1 of 1
JOD:(KbL!gUUt-) / I MYKKINU KtJ / I- 11
Top chord 2x4 SP_#2_BORATE_TRTD_13B :T2 2x4 SP #1_BORATE_TRTD_13B:
Bot chord 2x4 SP_#2_BORATE_TRTD_13B
Webs 2x4 SP_#2_BORATE_TRTD_13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Truss must be installed as shown with top chord up.
L!,
R=517# W=6"8
(Rigid Surface)
31'7"12
R=1582# W=5"4
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
See detail STRBRIBRO211 for bracing and bridging recommendations.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
R=538# W=6"8
(Rigid Surface)
SEQ = 274371
PLT. TYP: WAVE DESIGN CRIT=CUST0M/rP1-2007 FT/RT=20%(0%y10(0) QTY= 17 TOTAL= 17 REV. 13.01.05.0725.00 SCALE=0.2500
..WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 40.Opsf
REF
DATE 07-30-2014
7 T '
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT** FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 5.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2. _
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT. LD. 60.Opsf
ROOF &FLOORTRUSS 5Y3TU0
O/A LEN. 310712
41 M MARTIN HIGHWAY
PALM CITY, FL 's4"o
OFF- (772) 2&&3700
FAX? (772) 28"234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
JOD:(KB WUUF) / I HYKKING RES / FT3
Top chord 2x4 SP_#2_BORATE TRTD_13B :T2 2x4 SP_#1_BORATE_TRTD_13B:
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by Al -SC
Truss must be installed as shown with top chord up.
15'6"8
R=518# W=6"8
(Rigid Surface)
R=1467# W=5"4
(Rigid Surface)
37'6"10
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRU85 MFR'S LAYUU I
See detail STRBRIBRO211 for bracing and bridging recommendations.
In lieu of rigid ceiling use pudins to brace BC @ 24" CC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
15'10"12 i 6'1"6—�
R=11219 W=5"4
(Rigid Surface)
R=200/-141# W=6"8
(Rigid Surface)
SEQ = 274375
PLT. TYP: WAVE DESIGN GRIT=CUSTOM/TPI-2007 FT/RT=20%(0%y10(0) QTY= 4 TOTAL= 4 REV. 13.01.05.0725.00 SCALE=0.1875
- -
ti
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, W. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
T . STILES
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 40.Opsf
TC DL 15.Opsf
BC DL 5.0pSf
BC LL O.Opsf
TOT. LD. 60.Opsf
REF
DATE 07-30-2014
DRWG
RIFF &FLOORTRUSS SYST1 115
O/A LEN. 370610
4175 MARTIN HIGHWAY
PAW OtN, F4 '34". 0
OFF: Z) 26&2700
FAQ �Z,94
_
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
ob:(K130200F) / THYRRING RES / FT4
Top chord 2x4 SP #2_BORATE TRTD_13B
:T2, T3 2x4 SP #1_BORATE _TRTD 13B:
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Truss must be installed as shown with top chord up.
r43'1"3
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
See detail STRBRIBRO211 for bracing and bridging recommendations.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and L/360 total load. Creep increase factor for dead load is 1.50.
15'6"8 15'10"12
R=525# W=6"8 R=1469# W=5"4
(Rigid Surface) (Rigid Surface)
117'15 —I
R=1272# W=5"4 R=401# W=6"8
(Rigid Surface) (Rigid Surface)
SEQ = 274379
PLT. TYP: WAVE DESIGN CRIT=CUSTOMITPI-2007FT/RT=20%(0%u10(0) QTY= 2 TOTAL= 2 REV. 13.01.05.0725.00 SCALE=0.1875
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TIC LL 40.Opsf
REF
DATE 07-30-2014
• •'`...
fi b
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
III f KIM r1PCl!_MPR PPR GMCl/TPI 1_1QQ5 CPrTIn KI �
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TIC DL 15.Opsf
BC DL 5.Opsf
BC LL O.Opsf
TOT. LD. 60.Opsf
DRWG
ROOF&FLOOR-MUSS SYSTEMS
O/A LEN. 430103
4176 WRTAN 141"WAY
PAW 04TY, FL 34"13
OFF- (772)28&37DD
FAX (^j p2) 234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.011
FLATRI
TYPE
IOb:(KBQ200F) / THYRRING RES / FT5
Top chord 2x4 SP_#2_BORATE _TRTD 13B :T1 2x4 SP_#1_BORATE_TRTD_13B:
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/3012013 by ALSC
Truss must be installed as shown with top chord up.
T
I
13'6"8
R=460# W=6"8
(Rigid Surface)
PLT. TYP: WAVE
Rm oF�FLOOR7R1l.SS7E IS a.°1Y$
4175 VARTAN (HIGHWAY
OFF: (772) 2G&27,00
FAX (772) 288-4234
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S
See detail STRBRIBRO211 for bracing and bridging recommendations.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
41'1"3
- - 15'10"12 r 11715 —1
R=1364# W=5"4 R=1276# W=5"4 R=396# W=6"8
(Rigid Surface) (Rigid Surface) (Rigid Surface)
DESIGN CRIT=CUSTOMM-2007 FT/RT-20%(0%y10(0)
QTY= 7 TOTAL= 7
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
RI III Illl.l!_ niFCi _,.IF{] PFP ANCNTPI 1-1QQF CFf:TInm 9
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
REV. 13.01.05.0725.00
SEQ = 274388
SCALE=0.1875
TIC LL
TC DL
BC DL
BC LL
TOT.LD.
40.Opsf
15.0psf
5.Opsf
0.0psf
60.Opsf
REF
DATE 07-30-2014
DRWG
O/A LEN. 410103
DUR.FAC.
1.00
JOB #: KB020OF
SPACING
16.0"
TYPE FLAT
JOD: KbUGUUl / THYRRING KES / I- 16
-Top chord 2x4 SP_#2 BORATE _TRTD 13B :T1 2x4 SP #1_BORATE_TRTD_13B:
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "1313" use design values approved 1/30/2013 by ALSC
Truss must be installed as shown with top chord up.
'T
I
13'6"8
R=456# W=6"8
(Rigid Surface)
R=13659 W=5"4
(Rigid Surface)
39'4"3
15'10"12
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFF
See detail STRBRIBRO211 for bracing and bridging recommendations.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
910 15
R=1206# W=5"4 R=333# W=11"2
(Rigid Surface) (Rigid Surface)
SEQ = 274394
PLT. TYP.-WAVE DESIGN CRIT=CUST0M/TPI-2007 FT RT=2G%(e%y10O) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.1875
ti
L/'A,111V fjtt
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HII B-91 (HANDLING NSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
T. . STILE S
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 40.Opsf
TC DL 15.Opsf
BC DL 5.0p Sf
BC LL O.Opsf
TOT.LD. 60.Opsf
REF
DATE 07-30-2014
DRWG
ROOF&FLOORTRIJSS SYSTEMS
O/A LEN. 390403
41 7S MAIRTlIN NIGHWAY
PALM C4TY, FL 34"a
OFF- 72> 2 0-2700
FAX 28&4234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
Job:(KB0,200F) / THYRRING RES / FT7
Top chord 2x4 SP_#2_BORATE TRTD_13B
Bot chard 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
R=35/-304# W=6"9
(Rigid Surface)
R=1144# W=5"4
(Rigid Surface)
2T0"8
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYO
See detail STRBRIBRO211 for bracing and bridging recommendations.
Negative reaction(s) of -303# MAX. (See below) from a non -wind load case requires uplift connection.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Truss must be installed as shown with top chord up.
R=1138# W=5"4
(Rigid Surface)
R=212/-80# W=11"2
(Rigid Surface)
SEQ = 274403
PLT. TYP: WAVE DESIGN CRIT=CUSTOMrrPI-2007FT/RT-20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.2500
.rsw
—WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT* FURNISH APEET COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T. STILES
TC LL 40.0 sf
p
TC DL 15.Opsf
BC DL 5.Opsf
REF
DATE 07-30-2014
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WRH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 60.Opsf
ROOF A FLOOR7RIM SYSTEMS
O/A LEN. 270008
41n VAR*nN H*HWAY
PALM VrY, FL 34"0
OFF: (772)28&3700
FAX-(7j2) 288-4234
_ _ _
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
Job:(KB0200F) / THYRRING RES / FT8
Top chord 2x4 SP_#2_BORATE_TRTD_13B
Bot chard 2x4 SP #2_BORATE_TRTD_13B
Webs 2X4SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
I
R=-4149 W=6"9
(Rigid Surface)
R=1208# W=5"4
(Rigid Surface)
23'9"10
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
See detail STRBRIBRO211 for bracing and bridging recommendations.
Negative reaction(s) of -414# MAX. (See below) from a non -wind load case requires uplift connection.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Truss must be installed as shown with top chord up.
R=1156# W=5"4
(Rigid Surface)
R=77/-240# W=11"2
(Rigid Surface)
SEQ = 274410
PLT. TYP: WAVE DESIGN CRIT=CUSTOM/TPI-2007FrMT=20W0%)I10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.2500
{ Y
—WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T. STILES
PEE T
TC LL 40.0tr'11sf
N
TC DL 15.Opsf
BC DL 5.Opsf
REF
DATE 07-30-2014
DRWG
' Vti `
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV, STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT. LD. 60.Opsf
ROOF & FWCOR 3 a.+YS7EM8
O/A LEN. 230910
417E MARTIN WOHWAY
PALM K+`1M FI. '3M"D
OFF- (772}28g"8700
8•r1
FAX (772) 28234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE - FLAT
)b:(KB0200F) / THYRRING RES / FT9
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYO
Tap chord 2x4 SP_#2_BORATE TRTD_13B
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
20'6"11
See detail STRBRIBRO211 for bracing and bridging recommendations.
Negative reaction(s) of -668# MAX. (See below) from a non -wind load case requires uplift connection
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Truss must be installed as shown with top chord up.
R=-618# W=6"9 R=14289 W=5"4
(Rigid Surface) (Rigid Surface)
R=1380# W=5"4 R=-668# W=11"2
(Rigid Surface) (Rigid Surface)
SEQ = 274421
PLT. TYP.-WAVE DESIGN GRIT=CUST0MrrPI-2007IFTIRT=20-90%y10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.3750
.i
�yPANELS
VA,4 0
..WARNING— TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200. MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT**FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSVTPI 1-1995 SECTION 2.
T. STILES
P E ET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TIC LL 40.Opsf
TIC DL 15.Opsf
BC DL 5.Opsf
BC LL O.Opsf
TOT. LD. 50.0psf
REF
DATE 07-30-2014
DRWG
ROOF SFLOORTRIM SyZT MS
O/A LEN. 200611
4175 MARVN HIGHWAY
PALM CITY, FL 34"0
OFF- (772)286.370G
FA; (m) 28"2334
_
DURYAC. 1.00
JOB #: KB0200F
SPACING 11
ITYPF FLAT
Job:(KB0200F) / THYRRING RES / FT10
i op chord 2x4 SP_#1_BORATE TRTD_13B :T2 2x4 SP #2_BORATE_TRTD_13B:
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
1 17'3"13
R=1187# W=6"9
(Rigid Surface)
R=1999# W=5"4
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
See detail STRBRIBRO211 for bracing and bridging recommendations.
Negative reaction(s) of -1187# MAX. (See below) from a non -wind load case requires uplift connection.
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Truss must be installed as shown with top chord up.
R=526# W=11"2
(Rigid Surface)
SEQ = 274430
PLT. TYP -WAVE DESIGN CRIT=CUSTOM/TPI-2007"1RT=20%(0%p10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.3750
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT— FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSI/TPI 1-1995 SECTION 2.
T. STILES
PEE T
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TIC LL 40.Opsf
TC DL 15.Opsf
BC DL 5.Opsf
BC LL O.Opsf
TOT.LD. 60.Opsf
REF
DATE 07-30-2014
DRWG
ROOF $ FLOOR ZUSS SYSTEMS
O/A LEN. 170313
4175 MARTIN H101AWAY
PALM OtTY, F4 34"a
OFF: (772)288.2700
FAX'�) 234
DURTAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
)b:(KB0200F) / THYRRING RES / FT11
Top chord 2x4 SP_#2_BORATE _TRTD_13B
Bot chord 2x4 SP #2 BORATE_TRTD_13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
Truss must be installed as shown with top chord up.
1 14'0"14
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
Negative reac8on(s) of -1620# MAX. (See below) from a non -wind load case requires uplift connection
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
R=-1621# W=6"g R=441# W=11"2
(Rigid Surface) (Rigid Surface)
R=2278# W=5"4
(Rigid Surface)
SEQ = 274437
PLT. TYP.-WAVE DESIGN CRIT=CUSTOWTPI-2007FT/RT=2(1%(0%y10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=0.5000
Lf1�/
�I T -�
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING. SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER, PER ANSI/TPI 1-1995 SECTION 2. _
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 40.0 sf
p
TC DL 15.Opsf
BC DIL 5.Opsf
BC LL O.Opsf
TOT. LD. 60.Opsf
REF
DATE 07-30-2014
DRWG
ROOF do FLOORTRM SYSTEMS
O/A LEN. 140014
417E VARVN HIGH WAY
PALM Cit7Y, FL 34"a
CWF- (772)2 &370D
FAX1(772) 28"234
_
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
Job:(K80200F) / THYRRING RES / FT12
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S
Top chord 2x4 SP #2 BORATE TRTD 13B
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
=3X7
T
lull
m 1.5X4
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50
Truss must be installed as shown with top chord up.
=3X5
=3X7
R=433# W=6"9 R=433# W=11"2
(Rigid Surface) (Rigid Surface)
PLT. TYP.-WAVE
.r
IV
ROOF3FLOOR7RUSSSYSTEMS
41 n MARTIN HIGHWAY
PALM CITY. FL 34"0
OFF: (772)2a&270o
FAX (772) 28"234
DESIGN CRIT=CUST0M/TPI-20G7 FT/RT=20%(0%N10(0)
QTY= 1 TOTAL= 1
:R TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
OFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
:TIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
=LS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. "IMPORTANT" FURNISH A
V OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
'ONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
I TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
I APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
-PT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
GN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
ROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
ABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
flll11 npF 11 19I 0— C 1C 0I 1-1005 CP T1/1M �
T. STILES
PEET
PE# 49200
CA# 27788
404 SW CAMDEN AVE
STUART. FL 34994
REV. 13.01.05.0725.00
SEQ = 274440
SCALE=0.7500
TIC LL
TC DL
BC DL
BC LL
TOT.LD.
40.Opsf
15.Opsf
5.Opsf
O.Opsf
60.Opsf
REF
DATE 07-30-2014
DRWG
O/A LEN. 101000
DUR.FAC.
1.00
JOB #: KB020OF
SPACING
16.0"
TYPE FLAT
)b:(KB0200F) / THYRRING RES / FT13
Top chord 2x4 SP_#2_BORATE TRTD_13B
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4SP #2 BORATE TRTD 13B
Lumber grades designated with 13B" use design values approved 1/30/2013 by ALSC
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
In lieu of rigid ceiling use pudins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
Truss must be installed as shown with top chord up.
=3X5 III1.5X4 =3X5
SEQ = 274442
PLT. TYP.-WAVE DESIGN CRIT=CUSTOMITPI-2007FT/RT=20%(0%y10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=1.0000
I
"WARNING" TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. —IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
T. STILES
PEET
TC LL 40.Opsf
TIC DL 15.Opsf
BC DL 5.Opsf
REF
DATE 07-30-2014
DRWG
4.
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NDS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GA ASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 60.Opsf
ROOF&FLQORYRIAS SYSTEMS
O/A LEN. 70701
41 M MARTIN NIf>t WAY
PALM CITY, FL 34"0
OFF: (772)=!;- 700
FAX(772) 2884234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
Job:(KBO200F) / THYRRING RES / FT14
Top chord 2x4 SP #2_BORATE_TRTD 13B
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "1313" use design values approved 1/30/2013 by ALSC
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
In lieu of rigid ceiling use puriins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
Truss must be installed as shown with top chord up.
=3X5
SEQ = 274444
PLT.TYP.-WAVE DESIGN CRIT=CUSTOMrrP1-2007FT/RT-M96(0%y10(0) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=1.0000
**WARNING** TRUSSES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING.
REFER TO HIB-91 (HANDLING INSTALLING AND BRACING), PUBLISHED BY TPI (TRUSS PLATE INSTITUTE, 583
T. STILES
TC LL 40.Opsf
REF
DATE 07-30-2014
/
D'ONOFRIO DR., SUITE 200. MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL -
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. -IMPORTANT" FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
P E ET
TC DL 15.Opsf
BC DL 5.Opsf
DRWG
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
BUILDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
PE# 49200
CA# 2775$
404 SW CAMDEN AVE
STUART, FL 34994
BC LL O.Opsf
TOT.LD. 60.Opsf
ROOF & FLOORTRUSS SYSTEMS
O/A LEN. 40403
41176 WRTIN IHnHWAY
PAW G1TY, FL 34"0
OFF: (772)26S.2700
FAX (n2) 28 4234
DUR.FAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
Job: KB0200F / THYRRING RES / FT15
'Top chord 2x4 SP_#2_BORATE_TRTD_13B
Bot chord 2x4 SP #2 BORATE TRTD 13B
Webs 2x4 SP #2 BORATE TRTD 13B
Lumber grades designated with "13B" use design values approved 1/30/2013 by ALSC
=3X5
R=44# W=6"9
(Rigid Surface)
THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
In lieu of rigid ceiling use puffins to brace BC @ 24" OC.
Trusses to be spaced at 16.0" OC maximum.
Deflection meets U480 live and U360 total load. Creep increase factor for dead load is 1.50.
Truss must be installed as shown with top chord up.
SEQ = 274446
PLT. TYP: WAVE DESIGN CRIT=CUSTOM TPI-2007FT/RT-20%(0%y1010) QTY= 1 TOTAL= 1 REV. 13.01.05.0725.00 SCALE=1.0000
L
(HAND I GUIRE EXTREME CARE IN FABRICATING, IN TAL NG AND BRAG NG) PUBLISHED BYDTPI (TRUSS PLATE ALLING NLING, SHIPPING. T TITU E,`583ND BRACING.
R FER TO HWARNING*IB-91TRUSSES
D'ONOFRIO DR., SUITE 200, MADISON, WI. 53719) FOR SAFETY PRACTICES PRIOR TO PERFORMING THESE
FUNCTIONS. UNLESS OTHERWISE INDICATED, TOP CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL
PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEILING. **IMPORTANT- FURNISH A
COPY OF THIS DESIGN TO THE INSTALLATION CONTRACTOR. ALPINE ENGINEERED PRODUCTS, INC. SHALL NOT BE
RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN; ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE
WITH TPI; OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS
WITH APPLICABLE PROVISIONS OF NOS (NATIONAL DESIGN SPECIFICATION PUBLISHED BY THE AMERICAN FOREST
AND PAPER ASSOCIATION) AND TPI. ALPINE CONNECTORS ARE MADE OF 20GAASTM A653 GR40 GALV. STEEL
EXCEPT AS NOTED. APPLY CONNECTORS TO EACH FACE OF TRUSS AND, UNLESS OTHERWISE LOCATED ON THIS
DESIGN, POSITION CONNECTORS PER DRAWINGS 160 A-Z. THE SEAL ON THIS DRAWING INDICATES ACCEPTANCE
OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHOWN. THE
SUITABILITY AND USE OF THIS COMPONENT FOR ANY PARTICULAR BUILDING IS THE RESPONSIBILITY OF THE
I
BULDING DESIGNER PER ANSIrrPI 1-1995 SECTION 2.
T. STILES
P E ET
PE# 49200
CA# 27785
404 SW CAMDEN AVE
STUART, FL 34994
TC LL 40.Opsf
TC DL 15.Opsf
BC DL 5.Opsf
BC LL O.Opsf
TOT.LD. 60.Opsf
REF
DATE 07-30-2014
DRWG
ROOF&,n00R7RW3 8:STIMS
O/A LEN. 10105
4175MAR77N HIGHWAY
PALM GIM FL 34"13
OFF: (772)24&3700
FAX (772) 28&4234
DURYAC. 1.00
JOB #: KB020OF
SPACING 16.0"
TYPE FLAT
DESIGN CRITERIA
rT�fo�m�i�]41q
29'7"13 11'0"12 17T6
TRUSSES HELD IN 1-1 2" FROM ALL EDGES
-BEARING SCHEDULE
9 0.F.F
j � 12 6'A.F.F
# - A.G.F.
AT
A.F.F
0.F.F
r A.F.F
A.F.F
_ �A.F.F
in
ROOF END DETAIL
12" DEEP FLOORS / 16" OC
2' �r
FLOOR END DETAIL
F—
HANGEERSCHEDULE
---ion. -
9
in n
MAW
1100
MPO IRTANT 1—K
c AFPROVAL�P
❑ APPROVED
❑APPROVED AS NO ED
❑REVIS AND RESUBMIT
TRUSS DELIVERY
FL.REG.ENGINEER
T. STILES PEET
PEb49200 - CAy27788
w. alma] uNt�94
i. fL
O
0
ROOF & FLOOR TRUSS SYSTEMS
mw: Ii[-�-ifio F.�c Iil-i9&+a11
JOB INFORMATION
1 1 5'1'4 12'4'7 16'8'7
a.o� rxm mnn