HomeMy WebLinkAboutREVIEW COMMENTS FOR CONTRACTORSr I
Planning 8 Development 9en►le s
Building 8, Code_ Regulation Division
2300 Virginia Avenue
Fort Ple'rce, FL: 34982
Phone:(772)462-2172 Fax:(i72)462�6443
July 08, 2013
26556
SHERLOCK HOMES OF THE TREASURE COAST
LLC
JOHN MCQUAID
1958 SE BOLTON AVE
PORT ST LUCIE, FL 34952
REVIEW COMMENTS FOR CONTRACTOR
Page 1 of 2
RE: Building Permit Number 1305-0348
As of today's date the owner listed on your application is bing notified along with yourself that the referenced buiding permit
has some issues listed in the comments below.
Please address these issues as quickly as possible so that v e are able to continue to process this permit in a timely manner. If
you have any questions regarding the comments below, please call our office.
PROPERTY INFORMATION
501 NETTLES BLVD
JENSEN BEACH, FL 34957
APPLICATION INFORMATION
Permit Number: 1305-0348
Permit Type: Building Residential Renovation
REVIEWS AND COMMENTS
OWNER INFORMATION
Jack A Rood
501 Nettles Blvd
Jensen Beach, FL 34957-3334
Stories: 1
Review Type
Status
Reviewed By
Front Counter Review
Complete
Deanna Givens
Comment:
To be reviewed by Plans
Complete
Examiner
Comment:
Plans Examiner Review
Incomplete
Dave Johnson
6/12/2013 10:32:51 AM
Comment:
PROVIDE ENERGY CALC'S
FBC"**7/8/13 ENERGY CAI
6/12/2013 10:32:52 AM
Comment:
PROVIDE AC LAYOUT IN D
BALANCED AIR M1602.4
6/12/2013 10:32:52 AM
Comment:
PROVIDE ELECTRICAL PU
ART. 210.70 NEC ****7/8/13
216.70 NEC
Date Started Date Completed Date Released
5/23/2013 5/23/2013
6/10/2013 5/23/2013
) MANUAL J CALC'S FOR THIS PROJECT. 101.4.3 ENERGY
REQUIRED .TO HAVE ORIGINAL SIGNATURE
CATE. 107.2.1 FBC— 7/8113 NEW OFFICE MUST PROVIDE FOR
DUPLICATE TO INCLUDE REQUIRED LIGHTING FOR NEW ROOMS.
:D EXTERIOR DOOR IN BEDROOM REQUIRES EGRESS LIGHTING.
Monday, -July 08, 2013 3:5,7 PM
i
Planning & Development Services
REVIEW COMMENTS FOR CONTRACTOR
Building & Code Regulation. Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)4t2.6443
Page 2 of 2
7/8/2013 3:49:28 PM Comment:
AS NOTEDf BY ZONING TECH FLOOD ELEVATION CERT WILL BE REQUIRED PRIOR TO PERMIT
BEING ISSUI ED
Zoning Review Incomplete
Lydia Galbraith 6/12/2013 6/12/2013
6/12/2013 11:56:42 AM Comment:
PLEASE PRPVIDE A SIGNED AND SEALED FLOOD CERT FROM A SURVEYOR INDICATING THE
FINISHED FLOOR ELEVATION OF THE PROPOSED ENCLOSING OF THE TWO SCREEN ROOMS.
THE PROPOSED AREAS.ARE REQUIRED TO MEET THE MINIMUM FLOOD ELEVATION OF 6' NAVD.
6/12/2013 1:44:35 PM Comment:
I
6/12/13 SENT COMMENTS BY EMAIL
Documents Missing Incomplete
7/8/2013 3:57:15 PM Comment:
ENERGY CA C'S & EPL CARD MUST BE SIGNED.OWNERIAGENT. THIS CAN BE DONE AT TIME OF
PICK UP
Monday, July 08,� 2013 3:57 PM