HomeMy WebLinkAboutNOTICE PRODUCT CERTIFICATIONNOTICE OF PRODUCT CERTIFICATION
SGANWED
By CERTIFICATION NO: NI011489
(IdArAW& DATE: 03/06/2013
CERTIFICATION PROGRAM: Structural
COMPANY: JELD-WEN
CODE: 822-1
To verify that the "Notice of Product Certification" is valid, please visit www.NAMICei-tification.com to assure that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied. A NAMI approved certification label must be applied to the product to claim
certification status. Please review and advise NAMI if any corrections are required to this document.
COMPANY NAME AND ADDRESS
PRODUCT DESCRIPTION
JELD-WEN
Series -"Contours Premium Steel Wood
3737 Lakeport Boulevard
Edge with Half Vent Lite (ODL 799)"
Klamath Falls, OR 97601
Steel Glazed Side Hinged Door
Configuration: X
Glazing: Insulating Glass (Tempered)
Frame: W-953mm(37.50") H-2052mm(80.75")
Panel: W-909mm(35.75") H-2013mm(79.25")
DLO: W-499mm(19.63") H-397mm(15.63")
SPECIFICATION
PRODUCT RATING
TAS 202-94
Design Pressure: 2634 Pa (55 psi)
Negativg Design Pressure: 2634 Pa (55 psi)
Water Penetration Resistance Test Pressure: 396 Pa (8.25 pso
Product Tested By: National Certified Testing Laboratories
Report No: NCTL-210-3857-1/A009078
Expiration Date: January 31, 2017
Administrator's Signature:
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial Highway
Hayes, VA 23072
Tel: (804) 684-5124'
Fax: (804) 684-5122
BUILDING DROPS
Q
A Perfect Solution in Every Drop
Certificate of Authorization: 29578
Manufacturer: JELD-WEN, Inc.
Product Category: Exterior Door Assembly
Product Sub -Category: Swinging Exterior Door Assemblies
FL#:
Date: 02/25/2013
Report No: 2333
Compliance Method: State Product Approval Rule 9N-3.005 (1)(a)
Product Name: Contours Premium Steel Wood Edge Half Lite Non -Impact Outswing Door
(Non -Impact)
3'-0" x 6'-8"
Scope: This is a Product Evaluation Report issued by Hermes F. Norero, P.E. (FL # 73778) for JELD-WEN inc.
based on Rule Chapter No. 9N-3.005, Method 1a of the State of Florida Product Approval,
Department of Community Affairs - Florida Building Cpmmission.
Limits of Use:
Hermes F. Norero, P.E. does not have nor will acquire financial interest in the company
manufacturing or distributing the product or in any other entity involved in the approval process of
the product named herein.
This product has been evaluated for use in locations adhering to the 2010 Florida Building Code.
See Installation Instructions A009078, signed and sealed by Hermes F. Norero, P.E. (FL # 73778) for
specific use parameters.
1. This product has been evaluated and is in compliance with the 2010 Florida Building Code,
including the "High Velocity Hurricane Zone" (HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Section 1609.1.2 of the 2010 Florida Building Code and does require an impact resistant
covering.
4. Site conditions that deviate from the details of drawing A009078 require further engineering
analysis by a licensed engineer or registered architect.
5. See Installation Instructions A009078 for size and design pressure limitations.
Hermes F. Norero, P.E.
Florida No. 73778
Page 2 of 6
BUILDING DROPS FL#:
Date: 02/25/2013
i P A Perfect Solution in Every Drop Report No: 2333
Certificate of Authorization: 29578
Equivalence of Test Standards:
Various test standards have been evaluated for differences in test methodology, if any, between tested
editions of the test standards listed below and those editions referenced in the 2010 Florida Building Code.
Jeld-Wen, Inc. has tested their products to the following test standard edition(s):
1) ASTM D635-03
2) ASTM D1929-96
3) ASTM E84-08
4) ASTM G26-95
Chapter 35 of the 2010 Florida Building Code references the following editions of the above mentioned test
standards:
1) ASTM D635-06
2) ASTM D1929-96(00)e01
3) ASTM E84-07
4) ASTM G155-05a
After review of the above mentioned referenced standards and editions, it has been found that no significant
technical changes have been made to the test standards that would affect the results. All referenced
standards have been found to be equivalent. All materials test results meet minimum requirements of the
2010 FBC including HVHZ provisions.
Hermes F. Norero, P.E.
Florida No. 73778
Page 4 of 6
. BUILDING DROPS FLO:
A Perfect Solution in Every Drop Date: 02/25/2013
Certificate of Authorization:29578 Report No: 2333
Installation: 1. Approved anchor types and substrates areas follows:
�Thcough_Frame-Instal lation:
A. For 2x wood buck subs `rate, use #10 Wood Screw type installation anchors of sufficient
length to achieve a. minimum embedment of 1.50" into the wood substrate.
B. For concrete or masonry substrate where one by (1X), non-structural, wood bucking is
employed, use 3/16" diameter ITW Tapcon type concrete screw anchors of sufficient
length to achieve minimum embedment of 1.25" into concrete or masonry.
C. For concrete or masonry substrate where wood bucking is NOT employed, use 3/16"
diameter ITW Tapcon type concrete screw anchors of sufficient length to achieve
minimum embedment of 1.25" into concrete or masonry.
Refer to Installation Instructions (A009078) for anchot spacing and more details of the installation
requirements.
Design Pressure:
Design Pressure
Positive
-----_____55_P_SL
�Negative'""""
7 ,r ',1�05,5 PSF
Hermes F. Norero, P.E.
Florida No. 73778
Page 5 of 6
BUILDING DROPS FL#:
F.i Date: 02/25/2013
A Perfect Solution in Every Drop
Certificate of Authorization:29578 Report No: 2333
Certification Agency: The manufacturer has demonstrated compliance of door products in Accordance
with the Florida Building Code and Rule 9N-3.005 (3) for manufacturing under a
quality assurance program audited by an approved quality assurance entity through
National Accreditation & Management Institute, Inc. (FBC Organization #QUA1789)
Performance Standards: The product described herein has been tested per:
• TAS 202-94
Referenced Data:
Reports to qualify use of 25 Ga. Steel bottom rail:
1. Product Testing performed by National Certified Testing Laboratory, Inc.
(FBC Organization # TST1589)
Report #: NCTL-210-3857-1, Report Date: 01/08/2013
Reports to qualify use of 1.688" x 1" wood bottom rail:
3. Product Testing performed by Certified Testing Laboratories, Inc.
(FBC Organization # TST1577)
Report #: CTLA718W, Report Date: 11/18/2001
The use of either the 25 Ga. Steel or wood bottom rail is permitted for use with steel door at the design pressures
listed herein.
4. Certification Agency
National Accreditation & Management Institute, Inc.
(FBC Organization #QUA1789)
5. Component Material Testing of Dylite Expandable Polystyrene by
Intertek Testing Services NA, Inc.
ASTM E84-08
Report#: 3113726SAT-001 R1Report Date: 03/13/2009
6. Component Material Testing of ODL HP Polypropylene (Spartech PP5330-C13
& BASF HP -Pro) by Testing Evaluation Laboratories, Inc.
ASTM D 1929-96, ASTM D 2843-99. ASTM 635-03. ASTM G26-95
& ASTM D 638-03
Report #: TEL 013110297-A,B,C,&D Report Date: 12/01/2010
Report #: TEL 013110299-A,B,C,&D Report Date: 12/01/2010
Hermes F. Norero, P.E.
Florida No. 73778
Page 3 of 6
BUILDING DROPS
A Perfect Solution in Every Drop
Certificate of Authorization: 29578
Of
JELD-WEN, inc.
Contours Premium Steel Wood Edge
Half Lite Outswing Door
for
Florida Product Approval
Ad, .9 J 1 / O, 9J
Repo 1 No. 2333
Florida Building Code 2010
Per Rule 9N-3
Method:
Category:
Sub — Category:
Product:
Material:
Product Dimensions:
398 East Dania Beach Blvd.
Suite 338
Dania Beach, FL 33004
954.399.8478 PH
55-4.74-4.4738 FX
contact@buildingdrops.com
1— A (Certification)
Exterior Do6r Assembly
Swinging Exterior Door Assemblies
Contours Premium Steel Wood Edge
Half Lite Non -Impact Outswing Door
Wood/24 Ga. Steel
3'-0" x V-8"
Prepared For:
.Jl<ILD-Wl,N, inc.
3737 Lakeport Blvd.
Klamath Falls, OR. 97601
Prepared by:
l ieirnies F. N oreiro,
Florida Professional Engineer # 73778
Date: 02/25/2013
Contents.
Evaluation Report Pages 1— 5
Installation Details Page 6
Digitally signed by Hermes F Norero, P.E. -'-*i�
Reason: I am approving this document Herml6gy Aro, P.E.
Date: 2013.02.28 1'8:49:10-05'00' Florida No. 73778