HomeMy WebLinkAboutENERGY EFFICIENCY CODEFORM 405-10
- FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Gerety Residence
Builder Name:
Street: Lot 102 Venture III
Permit Office: St. Lucie County
City, State, Zip: Fort Pierce , FL ,
Permit Number:
Owner:
Jurisdiction:
Design Location: FL, Fort Pierce
1. New construction or existing
New (From Plans)
9. Wall Types (2280.0 sqft.)
Insulation Area
2. Single family or multiple family
Single-family
a. Concrete Block - Int Insul, Exterior
R=5.0 2040.00 ft2
b. Frame - Wood, Exterior
R=11.0 240.00 ft2
3. Number of units, if multiple family
1 ,
c. N/A.
R= ft2
4. Number of Bedrooms
1
d. N/A
R= ft2
10. Ceiling Types (1384.0 sqft.)
Insulation Area
5. Is this a worst case?
No
a. Under Attic (Vented)
R=30.0 1384.00 ft2
6. Conditioned floor area above grade (ft2)
1384
b. N/A
R= ft2
Conditioned floor area below grade (ft2)
0
c. N/A
R= ft2
11. Ducts
R ft2
7. Windows(464.6 sqft.) Description
Area
a. Sup: Attic, Ret: Attic, AH: RoomslnBlock1 6 276.8
a. U-Factor: Sgl, U=0.29
464.60 ft2
SHGC: SHGC=0.30
b. U-Factor: N/A
ft2
12. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
35.0 SEER:16.00
c. U-Factor: N/A
ft2
SHGC:
13. Heating systems
kBtu/hr Efficiency
d. U-Factor. N/A
ft2
a. Electric Heat Pump
35.0 HSPF:9.50
SHGC:
Area Weighted Average Overhang Depth: 1.000 ft.
Area Weighted Average SHGC:
0.300
14. Hot water systems
a. Electric Tankless
Cap: 1 gallons
8. Floor Types (1384.0 sqft.)
Insulation Area
EF: 0.990
a. Raised Floor
R=30.0 888.00 ft2
b. Conservation features
b. Slab -On -Grade Edge Insulation
R=0.0 496.00 ft2
None
c. N/A
R= ft2
15. Credits
CF. Pstat
Glass/Floor Area: 0.336
Total Proposed Modified Loads: 28.40
PASS
Total Standard Reference Loads: 36.80
I hereby certify that the plans and sp
icatio s cov d by
Review of the plans and
4�KE ST.gp
this calculation are in compliance with
the Florida ergy
specifications covered by this
Code.
calculation indicates compliance
with the Florida Energy Code.
//
PREPARED BY: �CF.��LZ��_
_L�tt�� ��c `s
Before construction is completed
DATE: i5/ZZ7/i�
this building will be inspected for
compliance with Section 553.908
I hereby certify that this buil g, as design , is in compliance
Florida Statutes.
COD
with the Florida Energy C9
WE't��
OWNER/AGENT: `�'u
BUILDING OFFICIAL:
DATE: -
DATE:
- Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist
12/22/2014 8:50 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 5
_ ENERGY
PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 77
The lower the EnergyPerformance Index, the more efficient the home.
Lot 102 Venture III, Fort Pierce, FL,
1. New construction or existing _
New (From Plans) 9. Wall Types Insulation
Area
2. Single family or multiple family
Single-family a. Concrete Block - Int Insul, Exterior R=5.0
2040.00 ft2
b. Frame - Wood, Exterior R=11.0
240.00 ft
3. Number of units, if multiple family
1 c. N/A R=
ft2
4. Number of Bedrooms
1 d. N/A R=
ft2
10. Ceiling Types Insulation
Area
5. Is this a worst case?
No a. Under Attic (Vented) R=30.0
1384.00 ft2
6. Conditioned floor area (ft2)
1384 b. N/A R=
ft2
7. Windows- Description
Area c. N/A R=
ft z
a. U-Factor: Sgl, U=0.29
464.60 ft2 11. Ducts
a. Sup: Attic, Ret: Attic, AH: RoomslnBlockl
R ft
6 276.8
SHGC: SHG0=0.30
b. U-Factor: N/A
ft2
SHGC:
12. Cooling systems kBtu/hr
Efficiency
c. U-Factor: N/A
ft2 a. Central Unit 35.0 SEER:16.00
SHGC:
d. U-Factor: N/A
ft2 13. Heating systems kBtu/hr
Efficiency
SHGC:
a. Electric Heat Pump 35.0
HSPF:9.50
Area Weighted Average Overhang Depth:
1.000 ft.
Area Weighted Average SHGC:
0.300
8. Floor Types Insulation Area 14. Hot water systems
Cap:
1 gallons
a. Raised Floor R=30.0 888.00 ft2 a. Electric
EF: 0.91
b. Slab -On -Grade Edge Insulation R=0.0 496.00 ft2
c. N/A R=
ft2 b. Conservation features
None
15. Credits
CF, Pstat
I certify that this home, has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code co liant feat es.
Builder Signature: Gv Date: I I -A
Address of New Home: � City/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software
C 0 N T R ATOR COPY
PROJECT
Title:
Gerety Residence
Bedrooms: 1
Address Type: Street Address
- Building Type:
FLProp2010
Conditioned Area: 1384
Lot #
Owner:
Total Stories: 2
Block/SubDivision:
# of Units:
1
Worst Case: No
PlatBook:
- Builder Name:
Rotate Angle: 0
Street: Lot 102 Venture III
Permit Office:
St. Lucie County
Cross Ventilation:
County: St. Lucie
Jurisdiction:
Whole House Fan:
City, State, Zip: Fort Pierce,
Family Type:
Single-family
FL,
New/Existing:
New (From Plans)
Comment:
CLIMATE
IECC Design Temp
Int Design Temp Heating Design Daily Temp
/
V Design Location
TMY Site Zone 97.5 % 2.5 %
Winter
Summer Degree Days Moisture Range
FL,
Fort Pierce FL ST LUCIE_CO INTL 2 39 90
70
75 722 62 Low
BLOCKS
Number
Name
Area Volume
1
Blockl
1384 11072
SPACES
Number
Name
Areal Volume Kitchen Occupants
Bedrooms
InfilID Finished Cooled Heated
1
RoomslnBlock1
1384: 11072 Yes 1
1
1 Yes Yes Yes
FLOORS
#
Floor Type
Space Perimeter Perimeter R-Value
Area
Joist R-Value Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio RoomslnBlockl 112 ft 0
496 ft2
-- 0 0 1
2 Raised Floor
RoomslnBlockl ____ _--_
888 ft2
30 0 0 1
ROOF
Roof Gable Roof
Solar
Absor.
SA Emitt Emitt Deck Pitch
Tested Tested Insul. (deg)
#
Type
Materials Area' Area Color
1
Hip
Metal 1499 ft2 0 ft2 Medium
0.96
No 0.9 No 0 22.6
ATTIC
V #
Type
Ventilation Vent Ratio (1 in)
Area
RBS IRCC
1
Full attic
Vented 300
1384 ft2
N N
CEILING
#
Ceiling Type
Space R-Value Area
Framing Frac Truss Type
1
Under Attic (Vented)
RoomslnBlock1 30 1384 ft2
0.11 Wood
C01"NT R., AC T C P
12/22/2014 8:50 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 5
WALLS
Adjacent
Cavity Width
Height
Sheathing Framing Solar
Below
mt
TO
Wall
Type Space
R-Value Ft
In
Ft In Area
R-Value
Fraction Absor
Grad °
1 N
Exterior
Concrete Block - Int lnsi loomSInBloc
5 45
16 720 ft2
0 0.75
0
2 S
Exterior
Concrete Block - Int InsBloomslnBloc
5 45
16 720 ft2
0 0.75
0
3 E
Exterior
Concrete Block - Int lnsEloomsInBloc
5 30
16 480 ft2
0 0.75
0
4 W
Exterior
Concrete Block - Int InsOloomslnBloc
5 15
8 120 ft2
0 0.75
0
5 W
Exterior
Frame - Wood RoomslnBloc
11 30
8 240 ft2
0.23 0.75
0
DOORS
#
Ornt
Door Type Space
Storms U-Value
Width
Height
Area
Ft
In
Ft In
1
N
Wood RoomslnBloc
None
0.460000 3
7
21 ft2
2
W
Wood RoomslnBloc
None
0.460000 3
7
21 ft2
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall
Overhang
# Ornt ID
Frame
Panes NFRC U-Factor SHGC
Storms Area Depth
Separation
Int Shade
Screening
1
N 1
Metal
Single (Tinted) Yes
0.29 0.3
N
56 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
2
N 1
Metal
Single (Tinted) Yes
0.29 0.3
N
9.199999 1 It 0 in
0 ft 0 in
HERS 2006
None
3
N 1
Metal
Single (Tinted)' Yes
0.29 0.3
N
36 ft2 1 ft 0 in
0 It 0 in
HERS 2006
None
4
N ' 1
Metal
Single (Tinted) Yes
0.29 0.3
N
15 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
5
S 2
Metal
Single (Tinted) Yes
0.29 0.3
N
15 ft2 1 It 0 in
0 It 0 in
HERS 2006
None
6
S 2
Metal
Single (Tinted) Yes
0.29 0.3
N
6.899999 1 ft 0 in
0 ft 0 in
HERS 2006
None
7
S 2
Metal
Single (Tinted) Yes
0.29 0.3
N
5 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
8
S 2
Metal
Single (Tinted) Yes
0.29 0.3
N
15 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
9
S 2
Metal
Single (Tinted) Yes
0.29 0.3
N
5 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
10
W 4
Metal
Single (Tinted) Yes
0.29 0.3
N
22.5 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
11
E 3
Metal
Single (Tinted) Yes
0.29 0.3
N
27 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
12
E 3
Metal
Single (Tinted) Yes
0.29 0.3
N
252 ft2 1 ft 0 in
0 ft 0 in
HERS 2006
None
GARAGE
#
Floor Area
Ceiling Area Exposed Wall Perimeter
Avg. Wall Height
Exposed Wall Insulation
1
382.8 ft2
382.8 ft2
64 ft
8 It
1
INFILTRATION
# Scope
Method
SLA CFM 50 ELA
EgLA ACH
ACH 50
1 BySpaces
Proposed SLA 0.000360 1306.8 71.746
134.93 0.3235
7.0821
v
12/22/2014 8:50 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 6
HEATING SYSTEM
# System Type
Subtype
Efficiency
Capacity
Block
Ducts
1 Electric Heat Pump
None
HSPF: 9.5
35 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type
Subtype
Efficiency
Capacity Air Flow
SHR
Block
Ducts
1 Central Unit
None
SEER: 16
35 kBtu/hr 1050 cfm
0.75
1
sys#1
HOT WATER SYSTEM
# System Type SubTpe
Location
EF Cap
Use SetPnt
Conservation
1 Electric Tankless
Garage
0.9108 1 gal 40 gal 120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector Storage
Cert # Company Name
System Model # Collector Model # Area
Volume
FEF
None None
ftz
DUCTS
— Supply —
V
— Return —
Air
Percent
HVAC #
# Location R-Value Area
Location
Area Leakage Type
Handler CFM 25
Leakage QN
RLF
Heat Cool
1 Attic 6 276.8 ft Attic
69.2 ftz DSE=0.88
RoomslnBl 0.0 cfm
0.00 % 0.00
0.60
1 1
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
May Jun x I
Se
ct
ov
Dec
Venting JXXJ
Jan �XjFeb IX
X� Mar
Apr
Rj May rxi IXj
r� � Sep
r
lX
Jun Jul
Aug Xug
lx� Oct
X� Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type 1
2 3
4 5 6
7 8
9
10
11
12
Cooling (WD) AM 78
78 78
78 78 78
78 78
80
80
80
80
PM 80
80 78
78 78 78
78 78
78
78
78
78
Cooling (WEH) AM 78
78 78
78 78 78
78 78
78
78
78
78
PM 78
78 78
78 78 78
78 78
78
78
78
78
Heating (WD) AM 66
66 66
66 66 68
68 68
68
68
68
68
PM 68
68 68
68 68 68
68 68
68
68
66
66
Heating (WEH) AM 66
66 66
66 66 68
68 68
68
68
68
68
PM 68
68 68
68 68 68
68 68
68
68
66
66
12/22/2014 8:50 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 5
FORM 405-10
Florida Code Compliance Checklist
Florida Department of Business and Professional Regulations
Residential Whole Building Performance Method
ADDRESS: Lot 102 Venture III PERMIT #:
Fort Pierce, FL,
MANDATORY REQUIREMENTS SUMMARY - See individual code sections for full details.
COMPONENT
SECTION
SUMMARY OF REQUIREMENT(S)
CHECK
Air leakage
402.4
To be caulked, gasketed, weatherstripped or otherwise sealed.
Recessed lighting IC -rated as meeting ASTM E 283. Windows and
doors = 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces:
gasketed doors & outdoor combustion air. Must complete envelope
leakage report or visually verify Table 402.4.2.
Thermostat &
403.1
At least one thermostat shall be provided for each separate heating and
controls
cooling system. Where forced -air furnace is primary system,
programmable thermostat is required. Heat pumps with supplemental
electric heat must prevent supplemental heat when compressor can
meet the load.
Ducts
403.2.2
All ducts, air handlers, filter boxes and building cavities which form the
primary air containment passageways for air distribution systems shall
be considered ducts or plenum chambers, shall be constructed and
sealed in accordance with Section 503.2.7.2 of this code.
403.3.3
Building framing cavities shall not be used as supply ducts.
Water heaters
403.4
Heat trap required for vertical pipe risers. Comply with efficiencies in
Table 403.4.3.2. Provide switch or clearly marked circuit breaker
(electric) or shutoff (gas). Circulating system pipes insulated to = R-2
+ accessible manual OFF switch.
Mechanical
403.5
Homes designed to operate at positive pressure or with mechanical
ventilation
ventilation systems shall not exceed the minimum ASHRAE 62 level.
No make-up air from attics, crawispaces, garages or outdoors adjacent
to pools or spas.
Swimming Pools
403.9
Pool pumps and pool pump motors with a total horsepower (HP) of = 1
& Spas
HP shall have the capability of operating at two or more speeds. Spas
and heated pools must have vapor -retardant covers or a liquid cover or
other means proven to reduce heat loss except if 70% of heat from
site -recovered energy. Off/timer switch required. Gas heaters minimum
thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters
minimum COP= 4.0.
Cooling/heating
403.6
Sizing calculation performed & attached. Minimum efficiencies per
Tables 503.2.3. Equipment efficiency verification required. Special
equipment
occasion cooling or heating capacity requires separate system or
variable capacity system. Electric heat >10kW must be divided into two
or more stages.
Ceilings/knee walls
405.2.1
R-19 space permitting.
CONTRACTOR COPY