HVAC LOADS
SCANNkU By S IP.tOP►h1101 Gerety Residence HVAC Load Calculations for f Gerety Lot 102 Venture III Fort Pierce, Florida i I MMVACHVAC LoADs Prepared By: Residential Energy Calc's Sunday, December21, 2014 Rhvac is an ACCA approved Manual J and Manual D computer program. A^ 16,3 f'�"' R COPYI Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manua Rhvac m Residential & Light Commercial HVAC Loads Elite Software Development, Inc: Residential Energy.Calc's„ Gerety Residence; Port'saial.6,ce, FL 34983 Pa4e'2 Pro ect Report Project Title: Designed By: Project Date: Client Name: Client Address: Client City: Company Name: Gerety Residence QEA Associate Sunday, December 21, 2014 Gerety Lot 102 Venture III Fort Pierce, Florida Residential Energy Calc's Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 1 n/a n/a 70 n/a Summer: 90 78 , 59% 50% 75 61 � Check-Fi ores ;.. :, , •,. ;.,_ Total Building Supply CFM: 1,235 CFM Per Square ft.: 0.893 Square ft. of Room Area: � 1,384 Square ft. Per Ton: 471 Volume (ft3) of Cond. Space: 11,545 Building Loads 7 ' f. Total Heating Required Including Ventilation Air: 33,646 Btuh 33.646 MBH Total Sensible Gain: i 27,729 Btuh 79 % Total Latent Gain: 7,499 Btuh 21 % Total Cooling Required Including Ventilation Air: I 35,228 Btuh 2.94 Tons (Based On Sensible + Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary: Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM R.fivac Residential,&.Light Commercial,HVAC Loads_ _.. Elite.Software Development, Inc: - ResidenUal Energy Calds , _ .Gerety_Residence• PortSaint Lucie, FL 34983 Miscellaneous Report System 1 Rheem Or Equivalent Outdoor Outdoor Outdoor,. . - Indoor,, -.indoor. Grains Input Data "D Bulb. Wet Bulb" Rel.Hum<, Rel.Hum Dry.Bulb ' Difference Winter: 42 39.4 80% n/a 70 n/a Summer: 90 78 59% 50% 75 61.09 Duct Sizin :,Inputs Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01000 Pressure Drop: 0.1000 in.wg./l00 ft. 0.1000 in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air Data Winter Summer Infiltration Specified: 0.450 AC/hr 0.230 AC/hr 87 CFM 44 CFM Infiltration Actual: 0.412 AC/hr 0.141 AC/hr Above Grade Volume:, X 11,547 Cu.ft. X 11,547 Cu.ft. 4,753 Cu.ft./hr 1,626 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 79 CFM 27 CFM Total Building Ventilation: 35 CFM 35 CFM --System 1-- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.450 AC/hr (871CFM), Construction: Average Summer Infiltration Specified: 0.230 AC/hr (44ICFM), Construction: Average 'Duct Load Factor Scenarios for System '1 .'Attic Duct Duct Surface From No. Type DescriptionLocation Ceiling Leakage. insulation Area [T]MDD' 1 Supply Attic 16B 0.12 6 374 No 1 Return Attic 16B 0.12 6 138 No CUNI"RAC` OR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhwac Restdentralx8� Ught Commercial HVAC Loads ��{, z Ehte,Software Development, lnc Residential Energy Calc's t o- < 'r k fE` Gerety Residence Port SamtsLucie, FL �34983 t, •: •: :. -; •. .' �, ,.,,, ., ,., ., �� Pa e`4 Load Preview Report Net ft.2 Sen Lat Net Sen Sys Fk Htg Sys Clg Sys Act Duct Scope Ton /Ton Area Gain Gain Gain Loss CFM CFM CAM Size Building 2.94, 471: 1,384' 27,729 7,499 35,228 33646 4231 1,235' 1,235 System 1 2 94 471 1,384 -- 27,729 • 7,499 _ . 36,228 , 33646 . - _ ' 1 423mil __. 1 - _235 ... 12x1 8 - - Ventilation 577 - 1,453; 2,030 1,077 Duct Latent 1,322 1 322 Zone 1 -Clg.: 33/0, Htg:43/0 432 9377 1,436 10813 13,985 182 -- 1-Den/Office 216: 6,0391 877 6916 6,929• - W 275' 3 3-6- --- - - -- 2-Bath 1 64 706, 70 776 1,845 24®— 32. 1-4 3-Foyer 96: 2,114;_ — 401 - -i--_ 2,515 3,335: 431 ®-- 96 1-6 -- 4-Stairway 56, 518 � 88 606 1,875, 24 24 � 4 - -- - - .- _ ..-, Zone 2 - Clg.: 67%, Htg : 57% 95_2_, 19,429 ; 3,288 - • 2_2,717 - 18,584 --i®-- 242 � 884 .__.. - 10x17 -. .� 5-Master Bedroom _ 225 2,318 597 2,915r 3,487 45I. 105 1 6 6-Master Bath 5711 986 1,042 2 028 828 11 45 1-4 7_-Powder Room 39, 1971 27, 224 336 4® 9 1-4 _ 8 Hall 56 1 002 645 1,647, 621 8 it® 9-Stairway 64 432 36. 468 1147 15 20 - 1-4 10-Living 238 6,635, 163 6,798 5,6_90 741 302 3-6 11 Kitchen 169 1360 668 2,028 1,343 17®62 1-512 Dining 104 6,499 i 1106,609 5,132; 67®296 3-6 ._ _ - Sum of room airflows may be greater than system airflow because system has multiplezones. "L"TOR COPY CA ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac - ReWdential &-Light Commercial HVAC Loads Eli Software. Development, " a R6tiden tia I Energy I Z' lc's Gerety Residence'I I Duct Size Preview Room or Source Minimum l Maximum] Rough. 1 Design l SPI Duct Duct Htg I CIg I Act. Duct Duct Name Velocity Velocity Factor l L/1�Loss_Velocity Length Flow f!gw J_Flow Size System 1 Supply Runouts Zone I 1-Den/Office Built-in 450, 750. 0D1 0.1 4664,90 275 3-6 2-Bath 1 Built-in 450 750 0D11 0.1 367.9 24 32' 1-4 3-Foyer Built-in 450 750 0.01 ---------- 0.1 489.9 43M 96' 1-6 4-Stairway Built-in 450 750 0.01 0.1 270.1 24 24 ---1-4 Zone2 5-Master Bedroom Built-in 450: 750, 0.01 0.1 537 45i 105 1-6 . - --I.- I.- ....... . .... . 6-Master Bath ....... . ...... ------- - Built-in - - .. ... . . ..... ... .. .. 450 ------- ---- . . . ........ 760 ............... . . 0.01 . ..... 0.1 -- --- 514.2: ----- -- 11, 45 1-4 7-Powder Room Built-in 450 750 0.01 0.1 - 102.8! 4, 9 1-4 ............. -.1 -- ---- --- ----- --------------- 8-Hall Built-in .... . ........ ....... .. .... ... . 450 7501 ...... __1 ---------------- 0D1, ---- - -- 0.1 ---- ------- _ - 522.41 8'= 46' 1-4 9-Stairway Built-in 450 750, 0.01, 01 225.31 151 20 1-4 1 0-LIVIng Built-in 450 750 - OP- 74 ;M1__ 302 3-6 1 1-Kitchen Bullt-In 4501 750. ODI, 0.1, ___ ---f ------------ 4,53,9, 17 1-5 12-Dining Built In ---- 450 . ...... ..... ------ 750 0.01 0.1 502 672 ...... 2961 3-6 Other Ducts in System I Supply Main Trunk Built-in 650 - 900 i -- - ----- - 0.003, - - - --- -- - ------ 0.1 ---- - ---- ----- ------ - 823.5 4231®1 1,235, 1208 Summary System 1 Heating Flow: 423 Cooling Flow. 1235 W lk. 11 TRACTOR ACTOR COPY CA ... \Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM R vac Residential 4 Lightommerc ial HVAC Loads Cal s C Residential Energy c' �`06&Sak Elite Software Development, 'Inc. Geretiy esidence, ; r .; Lucie, FL 34983 Pa a & Total Buildin -Summa ,: Loads Component h,'� H Area K�Sen �e Wr Sen Total fi X° �.f Gainr�Gam Description,.; -. Qua%i ,Loss. in =Gain' IA-rm-o: Glazing -Single -pane, operable window, 253 9,000 0 12,038 12,038 reflective, metal frame no break, u-value 1.27, SHGC 0.35 IA-rb-o: Glazing -Single pane, operable window, 75.4 2,280 0 2,107 2,107 reflective, metal frame with break, u-value 1.08, SHGC 0.35 1A-rb-o: Glazing -Single pane, operable window, 12 194 0 194 194 reflective, metal frame with break, in partition wall, u- value 1.08, SHGC 0.35 1 11 D: Door -Wood - Solid Core 84 704 0 672 672 13A-5ocs: Wall -Block, board insulation only, R-5 board 1303.3 4,562 0 2,492 2,492 insulation, open core, siding finish 12B-6sw: Part -Frame, R-11 insulation in 2 x 4 stud cavity, 358.8 523 0 523 523 no board insulation, siding finish, wood studs 1213-0sw: Wall -Frame, R-11 insulation in 2 x 4 stud 51 139 0 119 119 cavity, no board insulation, siding finish, wood studs 16F-30: Roof/Ceiling-Under Attic with Insulation on Attic 1383.6 1,239 0 665 665 Floor (also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, White Tile, Slate or Concrete, White Metal or White Membrane, R-30 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 112 4,259 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil 20P-30: Floor -Over open crawl space or garage, Passive, 888 871 0 311 311 _ _R_30 blanket insulation, any cover Subtotals for structure: 23,771 0 19,121 19,121 People: 6 1,200 1,380 2,580 Equipment: 2,400 1,200 3,600 Lighting: 0 0 0 Ductwork: 1 6,360 1,322 5,004 6,326 Infiltration: Winter CFM: 79, Summer CFM: 27 I 2,438 1,124 447 1,571 Ventilation: Winter CFM: 35, Summer CFM: 35 1,077 1,453 577 2,030 Total Building Load Totals: 33,646 7,499 27,729 35,228 Cheek.Fi ures r r Total Building Supply CFM: 1,235 CFM Per Square ft.: 0.893 Square ft. of Room Area: 1;384 Square ft. Per Ton: 471 Volume (ft3) of Cond. Space: 11,545 Builciin Loads s- r ., ;_ 4 ` Total Heating Required Including Ventilation Air: 33,646 Btuh 33.646 MBH Total Sensible Gain: 27,729 Btuh 79 Total Latent Gain: 7,499 Btuh 21 % Total Cooling Required Including Ventilation Air: 35,228 Stuh 2.94 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac Residential & Light Commercial; HVAC Loads, _ , Elite.Softwa1re Development, Inc. Residential Energy Calc's ., Gerety Residence Port Saint Lucie, FL, 34983 Pa e'8 Detailed Room .Loads -Room 1 - Den/Office . (Peak Fenestration Gain Procedure i Room is in zone 1, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 18.0 ft. System Number: 1 Room Width: 12.0 ft. i Zone Number: 1 Area: 216.0 sq.ft. Supply Air: 275 CFM Ceiling Height: 8.0 ft. , Supply Air Changes: 9.5 AC/hr Volume: 1,728.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 7 CFM Runout Air: 92 CFM Percent of Supply.: 3 % Runout Duct Size: 6 in. Actual Summer Vent.: 7 CFM Runout Air Velocity: 466 ft./min. Percent of Supply: 3 % Runout Air Velocity: 466 ft./min. Actual Winter Infil.: 12 CFM Actual Loss: 0.140 in.wg./100 ft. Actual Summer Infil.: 4 CFM Ul' � Nwai ��at ` s Sen oss M G"�HT E -Wall-13A-5ocs 12 X 8 33 0.125 3.5 116 1.9 0 63 S -Wall-13A-5ocs 18 X 8 130 0.125 3.5 455 1.9 0 249 N -Part-15°/15°-12B-Osw 12 X 8 96 0.097 1.5 140 1.5 0 140 E -GIs-1A-rm-o shgc-0.35 0%S (3) 63 1.270 35.6 2,241 57.0 0 3,591 S -GIs-1A-rm-o shgc-0.35 100%S 5 1.270 35.6 178 23.6 0 118 S -GIs-IA-rb-o shgc-0.35 100%S 9 1.080 30.2 272 21.7 0 195 UP-Ceil-16F-30 18 X 12 216 0.032 0.9 194 0.5 0 104 Floor-22A-ph 42 ft..Per. 42 1.358 38.0 1,597 0.0 0 0 Subtotals for Structure: 5,193 0 4,460 Infil.: Win.: 12.5, Sum.: 4.3 336 1.140 383 0.208 177 70 Ductwork: 1,353 1,049 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment:. ------ — -- -- -- - --— 300 _ 0 Room Totals: I I 6,929. 877 6,039 NAC"IR COPY C:\ ...1Gerety Residence.rh9 Sunday, December21, 2014, 7:13 PM Rhvac Residential,8 Light Commercial HVAC Loads Eiite,Softwa'e Development, Inc. ResidenUat Energy Calc's , . Gerety Residence - 'e Port Saint Lucie, FL' 34983 Pa 9 Detailed Room, Loads - Room 2 - Bath 1 (Peak. Fenestration Gain Procedure) ,x General s.},.�:,RAW��" Room is in zone 1, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 10.6 ft. System Number: 1 Room Width: 6.0 ft. Zone Number: 1 Area: 63.6 sq.ft,. Supply Air: 32 CFM Ceiling Height: 8.0 ft. 1 Supply Air Changes: 3.8 AC/hr Volume: 508.8 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 32 CFM Percent of Supply.: 6 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 368 Urnin: Percent of Supply: 3 % Runout Air Velocity: 368 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.155 in.wg./100 ft. Actual Summer Infil.: 2 CFM Items] fiSArea gar fU �'` F a�;, . w,,. x Late` �k Seen Desen lion. ..arm ,. Quanti ' .,Vsalue , , , _, ,H�TM� ; toss rc,: FIl'M ,::..Gain Gain., S -Wall-13A-5ocs 6 X 8 20.1 0.125 3.5 70 1.9 0 38 W -Part-15°/15'-12B-Osw 10..6 X 8 84.8 ! 0.097 1.5 123 1.5 0 123 S -Door-11 D 3 X 7 21 ! 0.390 10.9 229 10.1 0 213 S -GIs-1A-rb-o shgc-0.35 100%S 6.9 1.080 30.2 209 21.7 0 150 UP-Ceil-16F-30 10.6 X 6 63.6 0.032 0.9 57 0.5 0 31 Floor-22A-ph 17 ft..Per. 17 1.358 38.0 646 0.0 0 0 Subtotals for Structure: 1,334 0 555 Infil.: Win.: 4.9, Sum.: 1.7 133 1.137 151 0.211, 70 28 Ductwork: 360. 123 _ _ Room Totals: i I I I _ 1,845 , 70 706 �RKUTOR DOPY Q\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac - Re§Idential"& Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's - - Gerety. Residence Port Saint Lucie, FL 34983 " Page 1'0� Detailed Room Loads,--; Room 3 = Fo er (Peak Fenestration Gain Procedure) Room is in zone 1, which peaks at 11 am Calculation Mode: Htg. & clg. , Occurrences: 1 Room Length: 12.0 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 1 Area: 96.0 sq.ft. Supply Air: 96 CFM Ceiling Height: 8.0 ft. I Supply Air. Changes: 7.5 AC/hr Volume: 768.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 I Actual Winter Vent.: 4 CFM Runout Air: 96 CFM Percent of Supply.: 4 % Runout Duct Size: 6 in. Actual Summer Vent.: 3 CFM Runout Air Velocity: 490 ft./min. Percent of Supply: 3 % Runout Air Velocity: 490 ft./min. Actual Winter Infil.: 7 CFM Actual Loss: 0.154 in.wg./100 ft. Actual Summer Infil.: 2 CFM r . ,:. �r ,. k b W "ArOHtg5Clg,Quanta IF tqTTl Value` HTIUIx€�� , ;:Lo 1-1TMGain Gain, N -Wall-13A-5ocs 8 X 8 21.8 0.125 3.5 76 1.9 0 42 W -Part-15°/15°-12B-Osw 4 X 8 32 0.097 1.5 47 1.5 0 47 E -Part-150/150-126-0sw 12 X 8 63 0.097 1.5 92 1.5 0 92 N-Door-11 D 3 X 7 21 0.390 10.9 229 10.1 0 213 E-Door-11 D 3 X 7 21 0.390 5.9 123 5.9 0 123 N -GIs-1A-rm-o shgc-0.35 0%S 12 1.270 35.6 427 23.6 0 283 N -GIs-1A-rb-o shgc-0.35 0%S 9.2 1.080 30.2 278 21.7 0 200 E -GIs-IA-rb-o in partition 12 1.080 16.2 194 55.1 0 661 UP-Ceil-16F-3012 X 8 96 0.032 0.9 86 0.5 0 46 Floor-22A-ph 24-ft..Per. 24 1.358 38.0 913 0.0 0 0 Subtotals for Structure: 2,465 0 1,707 Infil.: Win.: 7.1, Sum.: 2.4 192 1.141 219 0.208 101 40 Ductwork: 651 367 Equipment: 300 0 Room Totals: i I I 3,335 401 2,114 C0 TRA(W% I COPY CA ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's ,: Gerety Residence Port Saint Lucie, FL 34983 Page 11 Detailed Room Loads - Room 4 - Stairway (Peak Fenestration Gain Procedure Room is in zone 1, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 8.0 ft. System Number: 1 Room Width: 7.0 ft. Zone Number: 1 Area: 56.0 sq.ft: Supply Air: 24 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 3.2 AC/hr Volume: 448.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 2 CFM Runout Air: 24 CFM Percent of Supply.: 9 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 270 ft./min. Percent of Supply: 3 % Runout Air Velocity: 270 ft./min. Actual Winter Infil.: 6 CFM Actual Loss: 0.084 in.wg./l00 ft. Actual Summer Infil.: 2 'CFM Item ' S Area , _ j U Htg Sen r Clg Lat " >Sen NGain Desch tion -:2 r.._3 r ,.Quantit� sxValue "_ : HTM - L_oss FiTM� ; N -Wall-13A-5ocs 8 X 8 64 0.125 3.5 224 1.9 0 122 W -Part-15*/15°-1213-0sw 7 X 8 35 0.097 1.5 51, 1.5 0 51 S -Part-150/150-12B-Osw 6 X 8 48 0.097 1.5 70 1.5 0 70 W-Door-11 D 3 X 7 21 0.390 5.9 123 5.9 0 123 UP-Ceil-16F-30 8 X 7 56 0.032 0.9 50 0.5 0 27 Floor-22A-ph 21 ft..Per. 21 1.358 38.0 799 0.0 0 0 Subtotals for Structure: 1,317 0 393 Infil.: Win.: 6.2, Sum.: 2.1 168 1.143 192 0.208 88 35 Ductwork: 366 90 Room Totals: i i i i I 1,875 _ _ _ 88 518 WNTRACTOR COP C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac =Residential & Light.Commerclal HVAC Loads: Elite Software Development, Inc: Residential Energy Calcis , .; Gerety Residence ,rt Saint Lucie, FL 3496 Po Pa a 12" 'Detailed Room Loads-.Room,5'- Master Bedroom (Peak fenestration Gain :Procedure) Gener i ti . Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 15.0 ft. System Number: 1 Room Width: 15.0 ft. Zone Number: 2 Area: 225.0 sq.ft. , Supply Air: 105 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 3.3 AC/hr Volume: 1,912.5 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 'Actual Winter Vent.: 4 CFM Runout Air: 105 CFM 'Percent of Supply.: 4 % Runout Duct Size: 6 in. Actual Summer Vent.: 3 CFM Runout Air Velocity: 537 ft./min. Percent of Supply: 3 % Runout Air Velocity: 537 ft./min. Actual Winter Infil.: 14 CFM Actual Loss: 0.185 in.i' J100 ft. Actual Summer Infil.: 5 CFM Item w v� Descn N -Wall-13A-5ocs 15 X 8.5 118.3 0.125 3.5 414 1.9 0 226 S -Wall-13A-5ocs 15 X 8.5 127.5 0.125 3.5 446 1.9 0 244 W -Wall-13A-5ocs 14 X 8.5 104 0.125 3.5 364 1.9 0 199 N -GIs-1A-rb-o shgc-0.35 0%S 9.2 1.080 30.2 278 21.7 0 200 W -GIs-IA-rb-o shgc-0.35 0%S 15 1.080 30.2 454 21.4 0 321 UP-Ceil-16F-30 15 X 15 225 0.032 0.9 202 0.5 0 108 Floor-20P-30 15 X 15 225 0.035 1.0 221 0.4 0 79 Subtotals for Structure: 2,379 0 1,377 Infil.: Win.: 13.9, Sum.: 4.7 374 1.142 427 0.209 197 78 Ductwork: 681 403 People: 200 lat/per, 230 sen/per: 2 400 460 Room Totals: i 3,487 597 2,318 COFACTOR COPY C:1... 1Gerety Residence.rh9 Sunday, December21, 2014, 7:13 PM Rhvac Residential,& Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calds GeretyResidence Port Saint.Lucie, FL 34983 Pa a 13 Detailed Room Loads. - Room 6 - Master Bath (Peak Fenestration, Gain Procedure) Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 9.5 ft. System Number: 1 . Room Width: 6.0 ft. Zone Number: 2 Area: 57.0 sq.ft. Supply Air: 45 CFM Ceiling Height: 8.5 ft. I Supply Air Changes: 5.6 AC/hr Volume: 484.5 cu.ft. ' Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 45 CFM Percent of Supply.: 2 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 514 ft./min. Percent of Supply: 3 % Runout Air Velocity: 514 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.299 in.wg./100 ft. Actual Summer Infil.: 1 CFM Gltem; i : Area e .. U - Htg :Sen Cig Lat� Sen Descn tion, Quantlt ,Value Htl'M Loss HTM Gain S -Wall-13A-5ocs 9.5 X 8.5 73.8 0.125 3.5 258 1.9 0 141 S -GIs-1A-rb-o shgc-0.35 100%S 6.9 1.080 30.2 209 21.7 0 150 UP-Ceil-16F-30 9.5 X 6 57 0.032 0.9 51 0.5 0 27 Floor-20P-30 6 X 9.5 57 0.035 1.0 56 0.4 0 20 Subtotals for Structure: 574 0 338 Infil.: Win.: 3.0, Sum.: 1.0 81 1.139 92 0.211 42 17 Ductwork: 162 171 People: 200 lat/per, 230 sen/per: 2 400 460 Equipment: 600 0 Room Totals: 828 1,042 986 CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac - Residential & Light Commercial HVAC Loads: Elite Software Development, Inc. Residential Energy Calds Gerety Re _ sidence _. Port'Saint Lucie, FL 34983 Page 14 Detailed Room Loads - Room 7 - Powder Room (Peak Fenestration Gain Procedure) cl . Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 6.5 ft. System Number: 1 Room Width: 6.0 ft. Zone Number: 2 Area: 39.0 sq.ft. Supply Air: 9 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 1.6 AC/hr Volume: 331.5 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 1Actual Winter Vent.: 0 CFM Runout Air: 9 CFM Percent of Supply.: 4 % Runout Duct Size: 4 in. , Actual Summer Vent.: 0 CFM Runout Air Velocity: 103 ft./min. Percent of Supply: 3 % Runout Air Velocity: 103 ft./min. Actual Winter Infil.: 2 CFM Actual Loss: 0.013 in.wg./l00 ft. Actual Summer Infil.: 1 CFM Item; ¢ Area' k 1M1= Fltg ` San Clg L"at P ,"Sen M�� Descn_fion� N * , ,;. Quanta ,.,;, . ,\/value H�T�M doss HTM Gana N -Wall-1213-0sw 6 X 8.5 51 0.097 2.7 139 2.3 0 119 UP-Ceil-16F-30 6.5 X 6 39 0.032 0.9 35 0.5 0 19 Floor-20P-30 6 X 6.5 39 0.035 1.0 38 0.4 0 14 Subtotals for Structure: 212 0 152 Infil.: Win.: 1.9, Sum.: 0.6 51 1.137 58 0.216 27 11 Ductwork: 66 34 Room Totals: I 336 27 197 C )ACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM F hvac - Residential & Light Commefcoal HVAC Loads EliteSoftware Development, Inc.: Residential Energy Calc's . Gerety Residence [Port Saint Lucie, FL 34983 Pa a 15 Detailed Room Loads - -Room 8 - Hall (Peak -Fenestration Gain Procedure) General r m f, x`. ' °",k .. ',� ..;. z:Y �< Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 4.0 ft. Zone Number: 2 Area: 56.0 sq.ft. Supply Air: 46 CFM Ceiling Height: 8.5 ft. ' Supply Air Changes: 5.7 AC/hr Volume: 476.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 . Actual Winter Vent.: 1 CFM Runout Air: 46 CFM Percent of Supply.: 1 % Runout Duct Size: 4 in. Actual Summer Vent.: 1' CFM Runout Air Velocity: 522 ft./min. Percent of Supply: 3 % Runout Air Velocity: 522 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.308 in.wg./100 ft. Actual Summer Infil.: 1 CFM Item Qescnption� N -Wall-13A-5ocs 10 X 8.5 85, 0.125 3.5 298 1.9 0 163 UP-Ceil-16F-30 14 X 4 56 ' 0.032 0.9 50 0.5 0 27 Floor-20P-30 4 X 14 56 : 0.035 1.0 55 0.4 0 20 Subtotals for Structure: 403 0 210 Infil.: Win': 3.1, Sum.: 1.1 85 1.141 97 0.212 45 18 Ductwork: 121 174 Equipment: 600 600 Room Totals: I 621 645 1,002 CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 I Sunday, December 21, 2014, 7:13 PM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Residential Energy Calc's . Gerety Residence Poit Saint Lucie, FL 34983 Pa a 16' We -tailed Room Loads - Room 9 - Stairway (Peak Fenestration Gain Procedure) General ..;,`.��` ....��P''L.��� �3^t���q+'1. � l�'_Si,'v�.'-01. .,... A'N�,� r i'..f..fiFY' �.`''.�, h�S1 yMRg4�� �h,.'fi i'` �i•4id Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 8.0 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 2 Area: 64.0 sq.ft. Supply Air: 20 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 2.2 AC/hr Volume: 544.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 20 CFM Percent of Supply.: 6 % Runout Duct Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air Velocity: 225 ft./min. Percent of Supply: 3 % Runout Air Velocity: 225 ft./min. Actual Winter Infil.: 3 CFM Actual Loss: 0.059 in.wg./100 ft. Actual Summer Infil.: 1 CFM ItemF'g' s t .. Area' y U Ht "Sen g Clg Lat ,�Sen Desert .tion:' . , .. Quantitw r..�, Valued<yw4++H� ,. Loss , .. ..HTM Ga%�a Gain N -Wall-1 3A-5ocs 8 X 8.5 58.8 0.125 3.5 206 1.9 0 112 N-GIs-lA-rb-o shgc-0.35 0%S 9.2` 1.080 30.2 278 21.7 0 200 UP-Ceil-16F-30 8 X 8 64 0.032 0.9 57 0.5 0 31 Floor-22A-ph 8 ft.. Per. 8 1.358 38.0 304_ 0.0 0_ 0 _ _ Subtotals for Structure: 845 0 343 Infil.: Win.: 2.5, Sum.: 0.9 68 1.147 78 0.206 36 14 Ductwork: 224 75 Room Totals: 1,147 36 432 CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM RhvAc - Residential & Light Commercial HVAC Loads Elite Software, Development, Inc. Residential Energy Calc's ,. Gerety Residence Port Saint,Lucie, FL 34983 Pa a V Detailed Room Loads - Room 10 - Lvin (Peak Fenestration Gain Procedure) .. ,. r. .,,.. yre Generals � -r a.. <,1,_ � . ���.. .0 ! ��. 4�: .� � � 3 ��. � _ ..+_ t ,. wK a, y z.. `� �� �.,:._ �� 4� x : Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 17.0 ft. System Number: 1 Room Width: 14.0 ft. Zone Number: 2 Area: 238.0 sq.ft. Supply Air: 302 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 9.0 AC/hr Volume: 2,023.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 6 CFM Runout Air: 101 CFM Percent of Supply.: 2 % Runout Duct Size: 6 in. Actual Summer Vent.: 8 CFM Runout Air Velocity: 512 ft./min. Percent of Supply: 3 % Runout Air Velocity: 512 ft./min. Actual Winter Infil.: 11 CFM Actual Loss: 0.168 in.wg./100 ft. Actual Summer Infil.: 4 CFM eaWUIN Arty Fitg " Sen Clg Late Stan.ie,; HTM. Loss HTM Gain.:. Gain N -Wall-13A-5ocs 17 X 10 170 0.125 3.5 595 1.9 0 325 E -Wall-13A-5ocs 14 X 10 56 0.125 3.5 196 1.9 0 107 E -GIs-1A-rm-o shgc-0.35 O%S (3) 84 1.270 35.6 2,988 57.0 0 4,788 UP-Ceil-16F-30 17 X 14 238 0.032 0.9 213 0.5 0 114 Floor-20P-30 14 X 17 238 0.0_3_5 1.0 233 0.4 0 83 _ Subtotals for Structure: 4,225 0 5,417 Infil.: Win.: 11.5, Sum.: 3.9 310 1.142 354 0.210 163 65 Ductwork: 1,111 1,153 Room Totals: I 5,690 163 6,635 COriTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac Residential & Light Commercial HVAC Loads, w Elite.Sottware Development, Inc. Residential Energy,Calds Gerety Residence_ Port Saint Lucie, FL, 34983 Pa a 18 Detailed Room Loads - Room 11 '- )Kitchen (Peak Fenestration Gain Procedure) Room is in zone 2, which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.0 ft. System Number: 1 Room Width: 13.0 ft. i Zone Number: 2 Area: 169.0 sq.ft. Supply Air: 62 CFM Ceiling Height:. 8.5 ft. Supply Air Changes: 2.6 AC/hr Volume: 1,436.5 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air: 62 CFM Percent of Supply.: 2 % Runout Duct Size: 5 in. Actual Summer Vent.: 2 CFM Runout Air Velocity: 454 ft./min. Percent of Supply: 3 % Runout Air Velocity: 454 ft./min. Actual Winter Infil.: 5 CFM Actual Loss: 0.171 in.wg./100 ft. Actual Summer Infil.: 2 CFM Itemti t "k, I� . AreaU `" Htg1Sen' CIg ` Laten nw. kd ,sueN,ot , r..._ zr. _Quantity ,.F,,:aValue :, „HTM1160s- HTM Game Gam: S -Wall-13A-5ocs 13 X 10 125 0.125 3.5 438 1.9 0 239 S -GIs-1A-rm-o shgc-0:35 100%S 5 1.270 35.6 178 23.6 0 118 UP-Ceil-16F-30 13 X 13 169 0.032 0.9 151 0.5 0 81 Floor-20P-30 13 X 13 169 0.035 1.0 166 0:4 0 59 Subtotals for Structure: 933 0 497 Infil.: Win.: 4.8, Sum.: 1.6 130 1.138 148 0.208 68 27 Ductwork: 262 236 Equipment: 600 600 Room Totals: I 1,343 668 1,360 CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Residential ;Energy Calc's . ` Gerety Residence; Poit Saint Lucie, FL 34983, 0,a a 19 .Detailed Room Loads : Room 1.2 ,- Dining (Peak Fenestration Gain Procedure) "Al Room is in zone 2; which peaks at 11 am Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.0 ft. System Number: 1 Room Width: 8.0 ft. Zone Number: 2 Area: 104.0 sq.ft; Supply Air: 296 CFM Ceiling Height: 8.5 ft. Supply Air Changes: 20.1 AC/hr Volume: 884.0 cu.fti Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 6 CFM Runout Air: 99 CFM Percent of Supply.: 2 %. Runout Duct Size: 6 in. Actual Summer Vent.: 8 CFM Runout Air Velocity: 502 ft./min. Percent of Supply: 3 % Runout Air Velocity: 502 ft./min. Actual Winter Infil.: 8 CFM Actual Loss: 0.162 in.wg./100 ft. Actual Summer, Infil.: 3 CFM Item r �', ;, �Y�'Area UKHtg xz ; `x Sen = ACIgtu°Sen Desch tion�?""g.�Quanti Loss.., HTIIII .KgvalueHTM _., .,...t .. .,„ ,GarnGain E -Wall-13A-5ocs 13 X 10 46 0.125 3.5 161 1.9 0 88 S -Wall-I3A-5ocs 8 X 10 70 0.125 3.5 245 1.9 0 134 E -GIs-IA-rm-o shgc-0.35 0%S (3) 84 1.270 35.6 2,988 57.0 0 4,788 S -GIs-IA-rb-o shgc-0.35 78%S 10 1.080 30.2 302 23.0 0 230 UP-Ceil-16F-30 13 X 8 104 0.032 0.9 93 0.5 0 50 Floor-20P-30 8 X 13 104 0.035 1.0 102 0.4 0 36 Subtotals for Structure: 3,891 0 5,326 Infil.: Win.: 7.8, Sum.: 2.7 210 1.138 239 0.210 110 44 Ductwork: 1,002 1,129 Room Totals: 5,132 110 6,499 CO.NT ACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM Rhvac Residential & Light Commercial HVA_C Load_ s_ Elite.Software Development, Inc. .Residential Energy Calc's , . Gerety Residence Port Saint Lucie; FL 34983 ' , . Pa a 20 System 1 Room "Load Summary l f3 - iY fi fl Ml z °Htg ' Mln Rerun Run�Gylg�x"Clg �Mrn ;Act # bl 4S 3'rc. '%e f1� q.. _ 4 t "4$' A S. fit!.ctµ M i 9 "'.3:.A1'4 )6 z r t t Roorn � ,5g w }x� Aif a Sense fiq Ducts; Duct t.. °Seros Lat CigSys `.� uh�:Btuh'``CFIVI':.GFIUI` ---Zone 1--- 1 Den/Office 216 6,929 90 3-6 466 6,039 877 275 275 2 Bath 1 64 1,845 24 1-4 368 706 70 32 32 3 Foyer 96 3,335 43 1-6 490 2,114 401 96 96 4 Stairway 56 1,875 24 1-4 270 518 88 24 24 Zone 1 subtotal 432 13,985 182 9,377 1,436 427 427 ---Zone 2--- 5 Master Bedroom 225 3,487 45 1-6 537 2,318 597 105 105 6 Master Bath 57 828 11 1-4 514 986 1,042 45 45 7 Powder Room 39 336 4 1-4 103 197 27 9 9 8 Hall 56 621 8 1-4 522 1,002 645 46 46 9 Stairway 0 64 1,147 15 1-4 225 432 36 20 20 10 Living 238 5,690 74 3-6 512 6,635 163 302 302 11 Kitchen 169 1,343 17 1-5 454 1,360 668 62 62 12 Dining 104 5,132 67 3-6 502 6,499 110 296 296 Zone 2 subtotal 952 18,584 19,429 3,288 884 884 _ _2_42 TVentilation 1,077 577 1,453 Duct Latent 1,322 _ _ _ _ System 1 total 1,384 33,646 423 _ 27,729 7,499 1,235 1,235 System 1 Main Trunk Size: 12x18 in. Velocity: 824 ft./min Loss per 100 ft.: 0.095 in.wg Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure + Excursion" method. Coolin ;S siernSiimma .�. ;.�� .,,�'.'.n �,;: ,_,�.: �T:�` �_`: ��.; ,,..._. .,.�-�"• n f x Yr� LtotCoo6n ensibe/anSensible r al r Net Required: 2.94 79% / 21 % 27,729 7,499 35,228 Actual: 2.95 78% / 22% 27,775 7,625 35,400 E pigment Data Heating System Cooling System Type: Two Speed Heat Pump Standard Air Conditioner Model: RXBH24A10J RPRL036JEC Indoor Model: RHPLHM3621JC Brand: PRESTIGE PRESTIGE SERIES Description: HEAT PUMP HSPF 9.5 SPLIT SYTEM 16 SEER Efficiency: Hi: 9.5 / Lo: 0 HSPF 16 SEER Sound: 0 0 Capacity: 35,400 Btuh 35,400 Btuh Sensible Capacity: n/a 27,775 Btuh Latent Capacity: n/a 7,625 Btuh CONTRACTOR COPY C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM