Gerety Residence
HVAC Load Calculations
for
f Gerety
Lot 102 Venture III
Fort Pierce, Florida
i
I
MMVACHVAC LoADs
Prepared By:
Residential Energy Calc's
Sunday, December21, 2014
Rhvac is an ACCA approved Manual J and Manual D computer program. A^
16,3
f'�"' R COPYI
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manua
Rhvac m Residential & Light Commercial HVAC Loads Elite Software Development, Inc:
Residential Energy.Calc's„ Gerety Residence;
Port'saial.6,ce, FL 34983 Pa4e'2
Pro ect Report
Project Title:
Designed By:
Project Date:
Client Name:
Client Address:
Client City:
Company Name:
Gerety Residence
QEA Associate
Sunday, December 21, 2014
Gerety
Lot 102 Venture III
Fort Pierce, Florida
Residential Energy Calc's
Outdoor
Outdoor
Outdoor
Indoor
Indoor
Grains
Dry Bulb
Wet Bulb
Rel.Hum
Rel.Hum
Dry Bulb
Difference
Winter: 42
39.4
1 n/a
n/a
70
n/a
Summer: 90
78
, 59%
50%
75
61
� Check-Fi ores ;.. :,
, •,.
;.,_
Total Building Supply CFM: 1,235
CFM Per Square ft.: 0.893
Square ft. of Room Area: � 1,384
Square ft. Per Ton: 471
Volume (ft3) of Cond. Space: 11,545
Building Loads 7 '
f.
Total Heating Required Including Ventilation Air:
33,646
Btuh 33.646 MBH
Total Sensible Gain: i
27,729
Btuh 79 %
Total Latent Gain:
7,499
Btuh 21 %
Total Cooling Required Including Ventilation Air: I
35,228
Btuh 2.94 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary:
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
R.fivac Residential,&.Light Commercial,HVAC Loads_ _.. Elite.Software Development, Inc:
-
ResidenUal Energy Calds , _
.Gerety_Residence•
PortSaint Lucie, FL 34983
Miscellaneous Report
System 1 Rheem Or Equivalent Outdoor
Outdoor Outdoor,. . - Indoor,, -.indoor. Grains
Input Data "D Bulb.
Wet Bulb" Rel.Hum<, Rel.Hum Dry.Bulb ' Difference
Winter: 42
39.4 80% n/a 70 n/a
Summer: 90
78 59% 50% 75 61.09
Duct Sizin :,Inputs
Main Trunk
Runouts
Calculate: Yes
Yes
Use Schedule: Yes
Yes
Roughness Factor: 0.00300
0.01000
Pressure Drop: 0.1000 in.wg./l00 ft.
0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min
450 ft./min
Maximum Velocity: 900 ft./min
750 ft./min
Minimum Height: 0 in.
0 in.
Maximum Height: 0 in.
0 in.
Outside Air Data
Winter
Summer
Infiltration Specified: 0.450 AC/hr
0.230 AC/hr
87 CFM
44 CFM
Infiltration Actual: 0.412 AC/hr
0.141 AC/hr
Above Grade Volume:, X 11,547 Cu.ft.
X 11,547 Cu.ft.
4,753 Cu.ft./hr
1,626 Cu.ft./hr
X 0.0167
X 0.0167
Total Building Infiltration: 79 CFM
27 CFM
Total Building Ventilation: 35 CFM
35 CFM
--System 1--
Infiltration & Ventilation Sensible Gain Multiplier: 16.49
= (1.10 X 0.999 X 15.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 41.50
(0.68 X 0.999 X 61.09 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 30.77
= (1.10 X 0.999 X 28.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.450 AC/hr (871CFM), Construction: Average
Summer Infiltration Specified: 0.230 AC/hr (44ICFM), Construction: Average
'Duct Load Factor Scenarios for System '1
.'Attic
Duct Duct Surface From
No. Type DescriptionLocation Ceiling
Leakage. insulation Area [T]MDD'
1 Supply Attic 16B
0.12 6 374 No
1 Return Attic 16B
0.12 6 138 No
CUNI"RAC` OR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhwac Restdentralx8� Ught Commercial HVAC Loads ��{, z
Ehte,Software Development, lnc
Residential Energy Calc's t o- <
'r k fE` Gerety Residence
Port SamtsLucie, FL �34983 t, •: •: :. -; •. .' �, ,.,,, .,
,., .,
�� Pa e`4
Load Preview Report
Net
ft.2
Sen
Lat
Net
Sen
Sys
Fk
Htg
Sys
Clg
Sys
Act
Duct
Scope
Ton
/Ton
Area
Gain
Gain
Gain
Loss
CFM
CFM
CAM
Size
Building 2.94, 471: 1,384'
27,729
7,499
35,228
33646
4231 1,235'
1,235
System 1 2 94
471 1,384
--
27,729
• 7,499
_
. 36,228
, 33646
. - _
' 1
423mil
__.
1
- _235 ...
12x1 8
- -
Ventilation
577
- 1,453;
2,030
1,077
Duct Latent
1,322
1 322
Zone 1 -Clg.: 33/0, Htg:43/0
432
9377
1,436
10813
13,985
182
--
1-Den/Office
216:
6,0391
877
6916
6,929•
- W
275'
3
3-6-
--- - - --
2-Bath 1
64
706,
70 776
1,845
24®—
32.
1-4
3-Foyer
96:
2,114;_
—
401
- -i--_
2,515
3,335: 431
®--
96
1-6
--
4-Stairway
56,
518
� 88
606
1,875,
24
24
�
4
- -- - - .- _ ..-,
Zone 2 - Clg.: 67%, Htg : 57%
95_2_,
19,429
; 3,288
-
• 2_2,717
-
18,584
--i®--
242 �
884
.__.. -
10x17
-. .�
5-Master Bedroom
_
225
2,318
597
2,915r
3,487
45I.
105
1 6
6-Master Bath
5711
986
1,042 2 028
828
11
45
1-4
7_-Powder Room
39,
1971
27,
224
336
4®
9
1-4
_
8 Hall
56
1 002
645
1,647,
621
8 it®
9-Stairway
64
432
36.
468
1147
15
20
-
1-4
10-Living
238
6,635,
163
6,798
5,6_90
741
302 3-6
11 Kitchen
169
1360
668
2,028
1,343
17®62
1-512
Dining
104
6,499
i 1106,609
5,132;
67®296
3-6
._
_ -
Sum of room airflows may be greater than system airflow because
system has multiplezones.
"L"TOR COPY
CA ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac - ReWdential &-Light Commercial HVAC Loads Eli Software. Development,
"
a R6tiden tia I Energy I Z' lc's Gerety Residence'I I
Duct Size Preview
Room or
Source
Minimum
l
Maximum]
Rough. 1
Design
l SPI
Duct
Duct
Htg
I CIg I
Act.
Duct
Duct Name
Velocity
Velocity
Factor l
L/1�Loss_Velocity
Length
Flow
f!gw J_Flow
Size
System 1
Supply Runouts
Zone I
1-Den/Office
Built-in
450,
750.
0D1
0.1
4664,90
275
3-6
2-Bath 1
Built-in
450
750
0D11
0.1
367.9
24
32'
1-4
3-Foyer
Built-in
450
750
0.01
----------
0.1
489.9
43M
96'
1-6
4-Stairway Built-in
450
750
0.01
0.1
270.1
24
24
---1-4
Zone2
5-Master Bedroom
Built-in
450:
750,
0.01
0.1
537
45i
105
1-6
. - --I.- I.- ....... . .... .
6-Master Bath
....... . ...... ------- -
Built-in
- - .. ... . . ..... ... .. ..
450
------- ---- . . . ........
760
............... . .
0.01
. .....
0.1
-- ---
514.2:
----- --
11,
45
1-4
7-Powder Room
Built-in
450
750
0.01
0.1 -
102.8!
4,
9
1-4
............. -.1 -- ---- --- ----- ---------------
8-Hall
Built-in
.... . ........ ....... .. .... ... .
450
7501
...... __1 ----------------
0D1,
---- - --
0.1
---- ------- _ -
522.41
8'=
46'
1-4
9-Stairway
Built-in
450
750,
0.01,
01
225.31
151
20
1-4
1 0-LIVIng
Built-in
450
750
-
OP-
74 ;M1__
302
3-6
1 1-Kitchen
Bullt-In
4501
750.
ODI,
0.1,
___ ---f ------------
4,53,9,
17
1-5
12-Dining
Built In
----
450
. ...... .....
------
750
0.01
0.1
502
672
......
2961
3-6
Other Ducts in System I
Supply Main Trunk
Built-in
650
-
900 i
-- - ----- -
0.003,
- - - --- -- - ------
0.1
---- - ---- ----- ------ -
823.5
4231®1
1,235,
1208
Summary
System 1
Heating Flow: 423
Cooling Flow. 1235
W lk. 11
TRACTOR ACTOR COPY
CA ... \Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
R vac Residential 4 Lightommerc ial HVAC Loads
Cal
s C
Residential Energy c'
�`06&Sak
Elite Software Development, 'Inc.
Geretiy esidence, ;
r .;
Lucie, FL 34983
Pa a &
Total Buildin -Summa ,: Loads
Component h,'� H Area K�Sen �e Wr Sen Total
fi X° �.f Gainr�Gam
Description,.; -. Qua%i
,Loss. in
=Gain'
IA-rm-o: Glazing -Single -pane, operable window, 253
9,000 0
12,038
12,038
reflective, metal frame no break, u-value 1.27, SHGC
0.35
IA-rb-o: Glazing -Single pane, operable window, 75.4
2,280 0
2,107
2,107
reflective, metal frame with break, u-value 1.08,
SHGC 0.35
1A-rb-o: Glazing -Single pane, operable window, 12
194 0
194
194
reflective, metal frame with break, in partition wall, u-
value 1.08, SHGC 0.35 1
11 D: Door -Wood - Solid Core 84
704 0
672
672
13A-5ocs: Wall -Block, board insulation only, R-5 board 1303.3
4,562 0
2,492
2,492
insulation, open core, siding finish
12B-6sw: Part -Frame, R-11 insulation in 2 x 4 stud cavity, 358.8
523 0
523
523
no board insulation, siding finish, wood studs
1213-0sw: Wall -Frame, R-11 insulation in 2 x 4 stud 51
139 0
119
119
cavity, no board insulation, siding finish, wood studs
16F-30: Roof/Ceiling-Under Attic with Insulation on Attic 1383.6
1,239 0
665
665
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, White
Tile, Slate or Concrete, White Metal or White
Membrane, R-30 insulation
22A-ph: Floor -Slab on grade, No edge insulation, no 112
4,259 0
0
0
insulation below floor, any floor cover, passive, heavy
moist soil
20P-30: Floor -Over open crawl space or garage, Passive, 888
871 0
311
311
_ _R_30 blanket insulation, any cover
Subtotals for structure:
23,771 0
19,121
19,121
People: 6
1,200
1,380
2,580
Equipment:
2,400
1,200
3,600
Lighting: 0
0
0
Ductwork: 1
6,360 1,322
5,004
6,326
Infiltration: Winter CFM: 79, Summer CFM: 27 I
2,438 1,124
447
1,571
Ventilation: Winter CFM: 35, Summer CFM: 35
1,077 1,453
577
2,030
Total Building Load Totals:
33,646 7,499
27,729
35,228
Cheek.Fi ures r r
Total Building Supply CFM: 1,235 CFM Per Square ft.:
0.893
Square ft. of Room Area: 1;384 Square ft.
Per Ton:
471
Volume (ft3) of Cond. Space: 11,545
Builciin Loads s- r ., ;_ 4
`
Total Heating Required Including Ventilation Air: 33,646 Btuh
33.646 MBH
Total Sensible Gain: 27,729 Btuh
79
Total Latent Gain: 7,499 Btuh
21 %
Total Cooling Required Including Ventilation Air: 35,228 Stuh
2.94 Tons (Based On
Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according
to the manufacturer's performance data at
your design conditions.
CONTRACTOR
COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac Residential & Light Commercial; HVAC Loads, _
, Elite.Softwa1re Development, Inc.
Residential Energy Calc's .,
Gerety Residence
Port Saint Lucie, FL, 34983
Pa e'8
Detailed Room .Loads -Room 1 - Den/Office . (Peak Fenestration
Gain Procedure
i
Room is in zone 1, which peaks at 11
am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length:
18.0 ft.
System Number:
1
Room Width:
12.0 ft. i
Zone Number:
1
Area:
216.0 sq.ft.
Supply Air:
275 CFM
Ceiling Height:
8.0 ft. ,
Supply Air Changes:
9.5 AC/hr
Volume:
1,728.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
3
Actual Winter Vent.:
7 CFM
Runout Air:
92 CFM
Percent of Supply.:
3 %
Runout Duct Size:
6 in.
Actual Summer Vent.:
7 CFM
Runout Air Velocity:
466 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
466 ft./min.
Actual Winter Infil.:
12 CFM
Actual Loss:
0.140 in.wg./100 ft.
Actual Summer Infil.:
4 CFM
Ul' � Nwai
��at ` s Sen
oss
M G"�HT
E -Wall-13A-5ocs 12 X 8
33 0.125
3.5 116
1.9 0 63
S -Wall-13A-5ocs 18 X 8
130 0.125
3.5 455
1.9 0 249
N -Part-15°/15°-12B-Osw 12 X 8
96 0.097
1.5 140
1.5 0 140
E -GIs-1A-rm-o shgc-0.35 0%S (3)
63 1.270
35.6 2,241
57.0 0 3,591
S -GIs-1A-rm-o shgc-0.35 100%S
5 1.270
35.6 178
23.6 0 118
S -GIs-IA-rb-o shgc-0.35 100%S
9 1.080
30.2 272
21.7 0 195
UP-Ceil-16F-30 18 X 12
216 0.032
0.9 194
0.5 0 104
Floor-22A-ph 42 ft..Per.
42 1.358
38.0 1,597
0.0 0 0
Subtotals for Structure:
5,193
0 4,460
Infil.: Win.: 12.5, Sum.: 4.3
336
1.140 383
0.208 177 70
Ductwork:
1,353
1,049
People: 200 lat/per, 230 sen/per:
2
400 460
Equipment:. ------ — --
--
-- - --— 300 _ 0
Room Totals:
I
I
6,929.
877 6,039
NAC"IR COPY
C:\ ...1Gerety Residence.rh9 Sunday, December21, 2014, 7:13 PM
Rhvac Residential,8 Light Commercial HVAC Loads
Eiite,Softwa'e Development, Inc.
ResidenUat Energy Calc's , .
Gerety Residence -
'e
Port Saint Lucie, FL' 34983
Pa 9
Detailed Room, Loads - Room 2 - Bath 1 (Peak. Fenestration Gain Procedure)
,x
General s.},.�:,RAW��"
Room is in zone 1, which peaks at 11 am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length: 10.6 ft.
System Number:
1
Room Width: 6.0 ft.
Zone Number:
1
Area: 63.6 sq.ft,.
Supply Air:
32 CFM
Ceiling Height: 8.0 ft. 1
Supply Air Changes:
3.8 AC/hr
Volume: 508.8 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers: 1
Actual Winter Vent.:
2 CFM
Runout Air: 32 CFM
Percent of Supply.:
6 %
Runout Duct Size: 4 in.
Actual Summer Vent.:
1 CFM
Runout Air Velocity: 368 Urnin:
Percent of Supply:
3 %
Runout Air Velocity: 368 ft./min.
Actual Winter Infil.:
5 CFM
Actual Loss: 0.155 in.wg./100 ft.
Actual Summer Infil.:
2 CFM
Items] fiSArea gar fU �'` F a�;, . w,,.
x Late` �k Seen
Desen lion. ..arm ,. Quanti ' .,Vsalue
, , , _, ,H�TM� ; toss rc,:
FIl'M ,::..Gain Gain.,
S -Wall-13A-5ocs 6 X 8 20.1 0.125
3.5 70
1.9 0 38
W -Part-15°/15'-12B-Osw 10..6 X 8 84.8 ! 0.097
1.5 123
1.5 0 123
S -Door-11 D 3 X 7 21 ! 0.390
10.9 229
10.1 0 213
S -GIs-1A-rb-o shgc-0.35 100%S 6.9 1.080
30.2 209
21.7 0 150
UP-Ceil-16F-30 10.6 X 6 63.6 0.032
0.9 57
0.5 0 31
Floor-22A-ph 17 ft..Per. 17 1.358
38.0 646
0.0 0 0
Subtotals for Structure:
1,334
0 555
Infil.: Win.: 4.9, Sum.: 1.7 133
1.137 151
0.211, 70 28
Ductwork:
360.
123
_ _
Room Totals: i
I
I
I
_
1,845
,
70 706
�RKUTOR DOPY
Q\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac - Re§Idential"& Light Commercial HVAC Loads
Elite Software Development, Inc.
Residential Energy Calc's -
-
Gerety. Residence
Port Saint Lucie, FL 34983 "
Page 1'0�
Detailed Room Loads,--; Room 3 = Fo er (Peak Fenestration Gain Procedure)
Room is in zone 1, which peaks at 11 am
Calculation Mode: Htg. & clg. ,
Occurrences:
1
Room Length:
12.0 ft.
System Number:
1
Room Width:
8.0 ft.
Zone Number:
1
Area:
96.0 sq.ft.
Supply Air:
96 CFM
Ceiling Height:
8.0 ft. I
Supply Air. Changes:
7.5 AC/hr
Volume:
768.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
1 I
Actual Winter Vent.:
4 CFM
Runout Air:
96 CFM
Percent of Supply.:
4 %
Runout Duct Size:
6 in.
Actual Summer Vent.:
3 CFM
Runout Air Velocity:
490 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
490 ft./min.
Actual Winter Infil.:
7 CFM
Actual Loss:
0.154 in.wg./100 ft.
Actual Summer Infil.:
2 CFM
r . ,:. �r ,. k b
W
"ArOHtg5Clg,Quanta
IF tqTTl
Value`
HTIUIx€�� , ;:Lo
1-1TMGain Gain,
N -Wall-13A-5ocs 8 X 8
21.8 0.125
3.5 76
1.9 0 42
W -Part-15°/15°-12B-Osw 4 X 8
32 0.097
1.5 47
1.5 0 47
E -Part-150/150-126-0sw 12 X 8
63 0.097
1.5 92
1.5 0 92
N-Door-11 D 3 X 7
21 0.390
10.9 229
10.1 0 213
E-Door-11 D 3 X 7
21 0.390
5.9 123
5.9 0 123
N -GIs-1A-rm-o shgc-0.35 0%S
12 1.270
35.6 427
23.6 0 283
N -GIs-1A-rb-o shgc-0.35 0%S
9.2 1.080
30.2 278
21.7 0 200
E -GIs-IA-rb-o in partition
12 1.080
16.2 194
55.1 0 661
UP-Ceil-16F-3012 X 8
96 0.032
0.9 86
0.5 0 46
Floor-22A-ph 24-ft..Per.
24 1.358
38.0 913
0.0 0 0
Subtotals for Structure:
2,465
0 1,707
Infil.: Win.: 7.1, Sum.: 2.4
192
1.141 219
0.208 101 40
Ductwork:
651
367
Equipment:
300 0
Room Totals:
i
I
I
3,335
401 2,114
C0 TRA(W% I COPY
CA ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac - Residential & Light Commercial HVAC Loads
Elite Software Development, Inc.
Residential Energy Calc's ,:
Gerety Residence
Port Saint Lucie, FL 34983
Page 11
Detailed Room Loads - Room 4 - Stairway
(Peak Fenestration Gain Procedure
Room is in zone 1, which peaks at 11 am
Calculation Mode:
Htg. & clg.
Occurrences:
1
Room Length:
8.0 ft.
System Number:
1
Room Width:
7.0 ft.
Zone Number:
1
Area:
56.0 sq.ft:
Supply Air:
24 CFM
Ceiling Height:
8.0 ft.
Supply Air Changes:
3.2 AC/hr
Volume:
448.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
1
Actual Winter Vent.:
2 CFM
Runout Air:
24 CFM
Percent of Supply.:
9 %
Runout Duct Size:
4 in.
Actual Summer Vent.:
1 CFM
Runout Air Velocity:
270 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
270 ft./min.
Actual Winter Infil.:
6 CFM
Actual Loss:
0.084 in.wg./l00 ft.
Actual Summer Infil.:
2 'CFM
Item ' S Area , _ j U Htg Sen
r
Clg
Lat " >Sen
NGain
Desch tion -:2 r.._3 r ,.Quantit�
sxValue
"_ : HTM - L_oss
FiTM�
;
N -Wall-13A-5ocs 8 X 8
64 0.125
3.5 224
1.9
0 122
W -Part-15*/15°-1213-0sw 7 X 8
35 0.097
1.5 51,
1.5
0 51
S -Part-150/150-12B-Osw 6 X 8
48 0.097
1.5 70
1.5
0 70
W-Door-11 D 3 X 7
21 0.390
5.9 123
5.9
0 123
UP-Ceil-16F-30 8 X 7
56 0.032
0.9 50
0.5
0 27
Floor-22A-ph 21 ft..Per.
21 1.358
38.0 799
0.0
0 0
Subtotals for Structure:
1,317
0 393
Infil.: Win.: 6.2, Sum.: 2.1
168
1.143 192
0.208
88 35
Ductwork:
366
90
Room Totals:
i
i
i
i
I
1,875
_
_ _
88 518
WNTRACTOR COP
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac =Residential & Light.Commerclal HVAC Loads:
Elite Software Development, Inc:
Residential Energy Calcis , .;
Gerety Residence
,rt Saint Lucie, FL 3496
Po
Pa a 12"
'Detailed Room Loads-.Room,5'- Master Bedroom (Peak fenestration Gain
:Procedure)
Gener i ti .
Room is in zone 2, which peaks at 11 am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length: 15.0 ft.
System Number:
1
Room Width: 15.0 ft.
Zone Number:
2
Area: 225.0 sq.ft. ,
Supply Air:
105 CFM
Ceiling Height: 8.5 ft.
Supply Air Changes:
3.3 AC/hr
Volume: 1,912.5 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers: 1
'Actual Winter Vent.:
4 CFM
Runout Air: 105 CFM
'Percent of Supply.:
4 %
Runout Duct Size: 6 in.
Actual Summer Vent.:
3 CFM
Runout Air Velocity: 537 ft./min.
Percent of Supply:
3 %
Runout Air Velocity: 537 ft./min.
Actual Winter Infil.:
14 CFM
Actual Loss: 0.185 in.i' J100 ft. Actual Summer Infil.:
5 CFM
Item
w v�
Descn
N -Wall-13A-5ocs 15 X 8.5 118.3
0.125 3.5 414
1.9 0 226
S -Wall-13A-5ocs 15 X 8.5 127.5
0.125 3.5 446
1.9 0 244
W -Wall-13A-5ocs 14 X 8.5 104
0.125 3.5 364
1.9 0 199
N -GIs-1A-rb-o shgc-0.35 0%S 9.2
1.080 30.2 278
21.7 0 200
W -GIs-IA-rb-o shgc-0.35 0%S 15
1.080 30.2 454
21.4 0 321
UP-Ceil-16F-30 15 X 15 225
0.032 0.9 202
0.5 0 108
Floor-20P-30 15 X 15 225
0.035 1.0 221
0.4 0 79
Subtotals for Structure:
2,379
0 1,377
Infil.: Win.: 13.9, Sum.: 4.7 374
1.142 427
0.209 197 78
Ductwork:
681
403
People: 200 lat/per, 230 sen/per: 2
400 460
Room Totals:
i
3,487
597 2,318
COFACTOR COPY
C:1... 1Gerety Residence.rh9 Sunday, December21, 2014, 7:13 PM
Rhvac Residential,& Light Commercial HVAC Loads
Elite Software Development, Inc.
Residential Energy Calds
GeretyResidence
Port Saint.Lucie, FL 34983
Pa a 13
Detailed Room Loads. - Room 6 - Master Bath (Peak Fenestration, Gain Procedure)
Room is in zone 2, which peaks at 11 am
Calculation Mode:
Htg. & clg.
Occurrences:
1
Room Length:
9.5 ft.
System Number:
1 .
Room Width:
6.0 ft.
Zone Number:
2
Area:
57.0 sq.ft.
Supply Air:
45 CFM
Ceiling Height:
8.5 ft. I
Supply Air Changes:
5.6 AC/hr
Volume:
484.5 cu.ft. '
Req. Vent. Clg:
0 CFM
Number of Registers:
1
Actual Winter Vent.:
1 CFM
Runout Air:
45 CFM
Percent of Supply.:
2 %
Runout Duct Size:
4 in.
Actual Summer Vent.:
1 CFM
Runout Air Velocity:
514 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
514 ft./min.
Actual Winter Infil.:
3 CFM
Actual Loss:
0.299 in.wg./100 ft.
Actual Summer Infil.:
1 CFM
Gltem; i :
Area e .. U - Htg :Sen
Cig Lat� Sen
Descn tion,
Quantlt ,Value
Htl'M Loss
HTM Gain
S -Wall-13A-5ocs 9.5 X 8.5
73.8 0.125
3.5 258
1.9 0 141
S -GIs-1A-rb-o shgc-0.35 100%S
6.9 1.080
30.2 209
21.7 0 150
UP-Ceil-16F-30 9.5 X 6
57 0.032
0.9 51
0.5 0 27
Floor-20P-30 6 X 9.5
57 0.035
1.0 56
0.4 0 20
Subtotals for Structure:
574
0 338
Infil.: Win.: 3.0, Sum.: 1.0
81
1.139 92
0.211 42 17
Ductwork:
162
171
People: 200 lat/per, 230 sen/per:
2
400 460
Equipment:
600 0
Room Totals:
828
1,042 986
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac - Residential & Light Commercial HVAC Loads:
Elite Software Development, Inc.
Residential Energy Calds
Gerety Re _ sidence
_.
Port'Saint Lucie, FL 34983
Page 14
Detailed Room Loads - Room 7 - Powder Room (Peak Fenestration Gain
Procedure)
cl .
Room is in zone 2, which peaks at 11 am
Calculation Mode:
Htg. & clg.
Occurrences:
1
Room Length:
6.5
ft.
System Number:
1
Room Width:
6.0
ft.
Zone Number:
2
Area:
39.0
sq.ft.
Supply Air:
9 CFM
Ceiling Height:
8.5
ft.
Supply Air Changes:
1.6 AC/hr
Volume:
331.5
cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
1
1Actual
Winter Vent.:
0 CFM
Runout Air:
9
CFM
Percent of Supply.:
4 %
Runout Duct Size:
4
in. ,
Actual Summer Vent.:
0 CFM
Runout Air Velocity:
103
ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
103
ft./min.
Actual Winter Infil.:
2 CFM
Actual Loss:
0.013
in.wg./l00 ft.
Actual Summer Infil.:
1 CFM
Item; ¢
Area' k 1M1=
Fltg ` San
Clg L"at P ,"Sen
M��
Descn_fion� N * , ,;.
Quanta ,.,;, . ,\/value H�T�M doss
HTM Gana
N -Wall-1213-0sw 6 X 8.5
51 0.097
2.7 139
2.3 0 119
UP-Ceil-16F-30 6.5 X 6
39 0.032
0.9 35
0.5 0 19
Floor-20P-30 6 X 6.5
39 0.035
1.0 38
0.4 0 14
Subtotals for Structure:
212
0 152
Infil.: Win.: 1.9, Sum.: 0.6
51
1.137 58
0.216 27 11
Ductwork:
66
34
Room Totals:
I
336
27 197
C )ACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
F hvac - Residential & Light Commefcoal HVAC Loads
EliteSoftware Development, Inc.:
Residential Energy Calc's .
Gerety Residence
[Port Saint Lucie, FL 34983
Pa a 15
Detailed Room Loads - -Room 8 - Hall (Peak -Fenestration Gain Procedure)
General r m f, x`. ' °",k .. ',� ..;. z:Y �<
Room is in zone 2, which peaks at 11 am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length: 14.0 ft.
System Number:
1
Room Width: 4.0 ft.
Zone Number:
2
Area: 56.0 sq.ft.
Supply Air:
46 CFM
Ceiling Height: 8.5 ft. '
Supply Air Changes:
5.7 AC/hr
Volume: 476.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers: 1 .
Actual Winter Vent.:
1 CFM
Runout Air: 46 CFM
Percent of Supply.:
1 %
Runout Duct Size: 4 in.
Actual Summer Vent.:
1' CFM
Runout Air Velocity: 522 ft./min.
Percent of Supply:
3 %
Runout Air Velocity: 522 ft./min.
Actual Winter Infil.:
3 CFM
Actual Loss: 0.308 in.wg./100 ft.
Actual Summer Infil.:
1 CFM
Item
Qescnption�
N -Wall-13A-5ocs 10 X 8.5 85, 0.125
3.5 298
1.9 0 163
UP-Ceil-16F-30 14 X 4 56 ' 0.032
0.9 50
0.5 0 27
Floor-20P-30 4 X 14 56 : 0.035
1.0 55
0.4 0 20
Subtotals for Structure:
403
0 210
Infil.: Win': 3.1, Sum.: 1.1 85
1.141 97
0.212 45 18
Ductwork:
121
174
Equipment:
600 600
Room Totals:
I
621
645 1,002
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 I Sunday, December 21, 2014, 7:13 PM
Rhvac Residential & Light Commercial HVAC Loads
Elite Software Development, Inc.
Residential Energy Calc's .
Gerety Residence
Poit Saint Lucie, FL 34983
Pa a 16'
We -tailed Room Loads - Room 9 - Stairway
(Peak Fenestration Gain Procedure)
General ..;,`.��` ....��P''L.��� �3^t���q+'1. � l�'_Si,'v�.'-01. .,... A'N�,� r i'..f..fiFY' �.`''.�, h�S1 yMRg4��
�h,.'fi i'` �i•4id
Room is in zone 2, which peaks at
11 am
Calculation Mode:
Htg. & clg.
Occurrences:
1
Room Length:
8.0 ft.
System Number:
1
Room Width:
8.0 ft.
Zone Number:
2
Area:
64.0 sq.ft.
Supply Air:
20 CFM
Ceiling Height:
8.5 ft.
Supply Air Changes:
2.2 AC/hr
Volume:
544.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
1
Actual Winter Vent.:
1 CFM
Runout Air:
20 CFM
Percent of Supply.:
6 %
Runout Duct Size:
4 in.
Actual Summer Vent.:
1 CFM
Runout Air Velocity:
225 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
225 ft./min.
Actual Winter Infil.:
3 CFM
Actual Loss:
0.059 in.wg./100 ft.
Actual Summer Infil.:
1 CFM
ItemF'g' s t
..
Area' y U Ht "Sen
g
Clg Lat ,�Sen
Desert .tion:'
. , .. Quantitw r..�, Valued<yw4++H�
,. Loss , .. ..HTM
Ga%�a Gain
N -Wall-1 3A-5ocs 8 X 8.5
58.8 0.125
3.5 206
1.9 0 112
N-GIs-lA-rb-o shgc-0.35 0%S
9.2` 1.080
30.2 278
21.7 0 200
UP-Ceil-16F-30 8 X 8
64 0.032
0.9 57
0.5 0 31
Floor-22A-ph 8 ft.. Per.
8 1.358
38.0 304_
0.0 0_ 0
_
_
Subtotals for Structure:
845
0 343
Infil.: Win.: 2.5, Sum.: 0.9
68
1.147 78
0.206 36 14
Ductwork:
224
75
Room Totals:
1,147
36 432
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
RhvAc - Residential & Light Commercial HVAC Loads
Elite Software, Development, Inc.
Residential Energy Calc's ,.
Gerety Residence
Port Saint,Lucie, FL 34983
Pa a V
Detailed Room Loads - Room 10 - Lvin (Peak Fenestration Gain Procedure)
.. ,. r. .,,.. yre
Generals � -r a.. <,1,_ � . ���..
.0 !
��. 4�: .� � � 3 ��.
� _ ..+_
t ,.
wK a, y z..
`� �� �.,:._ �� 4� x :
Room is in zone 2, which peaks at 11 am
Calculation Mode:
Htg. & clg.
Occurrences:
1
Room Length:
17.0 ft.
System Number:
1
Room Width:
14.0 ft.
Zone Number:
2
Area:
238.0 sq.ft.
Supply Air:
302 CFM
Ceiling Height:
8.5 ft.
Supply Air Changes:
9.0 AC/hr
Volume:
2,023.0 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers:
3
Actual Winter Vent.:
6 CFM
Runout Air:
101 CFM
Percent of Supply.:
2 %
Runout Duct Size:
6 in.
Actual Summer Vent.:
8 CFM
Runout Air Velocity:
512 ft./min.
Percent of Supply:
3 %
Runout Air Velocity:
512 ft./min.
Actual Winter Infil.:
11 CFM
Actual Loss:
0.168 in.wg./100 ft.
Actual Summer Infil.:
4 CFM
eaWUIN
Arty
Fitg " Sen
Clg Late
Stan.ie,;
HTM. Loss
HTM Gain.:.
Gain
N -Wall-13A-5ocs 17 X 10
170 0.125
3.5 595
1.9 0
325
E -Wall-13A-5ocs 14 X 10
56 0.125
3.5 196
1.9 0
107
E -GIs-1A-rm-o shgc-0.35 O%S
(3) 84 1.270
35.6 2,988
57.0 0
4,788
UP-Ceil-16F-30 17 X 14
238 0.032
0.9 213
0.5 0
114
Floor-20P-30 14 X 17
238 0.0_3_5
1.0 233
0.4 0
83
_
Subtotals for Structure:
4,225
0
5,417
Infil.: Win.: 11.5, Sum.: 3.9
310
1.142 354
0.210 163
65
Ductwork:
1,111
1,153
Room Totals:
I
5,690
163
6,635
COriTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac Residential & Light Commercial HVAC Loads, w
Elite.Sottware Development, Inc.
Residential Energy,Calds
Gerety Residence_
Port Saint Lucie, FL, 34983
Pa a 18
Detailed Room Loads - Room 11 '- )Kitchen
(Peak Fenestration Gain Procedure)
Room is in zone 2, which peaks at 11 am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length: 13.0 ft.
System Number:
1
Room Width: 13.0 ft. i
Zone Number:
2
Area: 169.0 sq.ft.
Supply Air:
62 CFM
Ceiling Height:. 8.5 ft.
Supply Air Changes:
2.6 AC/hr
Volume: 1,436.5 cu.ft.
Req. Vent. Clg:
0 CFM
Number of Registers: 1
Actual Winter Vent.:
1 CFM
Runout Air: 62 CFM
Percent of Supply.:
2 %
Runout Duct Size: 5 in.
Actual Summer Vent.:
2 CFM
Runout Air Velocity: 454 ft./min.
Percent of Supply:
3 %
Runout Air Velocity: 454 ft./min.
Actual Winter Infil.:
5 CFM
Actual Loss: 0.171 in.wg./100 ft.
Actual Summer Infil.:
2 CFM
Itemti t "k, I� . AreaU `"
Htg1Sen'
CIg ` Laten nw. kd
,sueN,ot
, r..._ zr. _Quantity ,.F,,:aValue :,
„HTM1160s-
HTM Game Gam:
S -Wall-13A-5ocs 13 X 10 125 0.125
3.5 438
1.9 0 239
S -GIs-1A-rm-o shgc-0:35 100%S 5 1.270
35.6 178
23.6 0 118
UP-Ceil-16F-30 13 X 13 169 0.032
0.9 151
0.5 0 81
Floor-20P-30 13 X 13 169 0.035
1.0 166
0:4 0 59
Subtotals for Structure:
933
0 497
Infil.: Win.: 4.8, Sum.: 1.6 130
1.138 148
0.208 68 27
Ductwork:
262
236
Equipment:
600 600
Room Totals:
I
1,343
668 1,360
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac Residential & Light Commercial HVAC Loads
Elite Software Development, Inc.
Residential ;Energy Calc's . `
Gerety Residence;
Poit Saint Lucie, FL 34983,
0,a a 19
.Detailed Room Loads : Room 1.2 ,- Dining (Peak Fenestration Gain Procedure)
"Al
Room is in zone 2; which peaks at 11 am
Calculation Mode: Htg. & clg.
Occurrences:
1
Room Length: 13.0 ft.
System Number:
1
Room Width: 8.0 ft.
Zone Number:
2
Area: 104.0 sq.ft;
Supply Air:
296 CFM
Ceiling Height: 8.5 ft.
Supply Air Changes:
20.1 AC/hr
Volume: 884.0 cu.fti
Req. Vent. Clg:
0 CFM
Number of Registers: 3
Actual Winter Vent.:
6 CFM
Runout Air: 99 CFM
Percent of Supply.:
2 %.
Runout Duct Size: 6 in.
Actual Summer Vent.:
8 CFM
Runout Air Velocity: 502 ft./min.
Percent of Supply:
3 %
Runout Air Velocity: 502 ft./min.
Actual Winter Infil.:
8 CFM
Actual Loss: 0.162 in.wg./100 ft. Actual Summer, Infil.:
3 CFM
Item r �', ;, �Y�'Area UKHtg xz ; `x Sen =
ACIgtu°Sen
Desch tion�?""g.�Quanti
Loss..,
HTIIII
.KgvalueHTM
_., .,...t ..
.,„ ,GarnGain
E -Wall-13A-5ocs 13 X 10 46
0.125 3.5 161
1.9 0 88
S -Wall-I3A-5ocs 8 X 10 70
0.125 3.5 245
1.9 0 134
E -GIs-IA-rm-o shgc-0.35 0%S (3) 84
1.270 35.6 2,988
57.0 0 4,788
S -GIs-IA-rb-o shgc-0.35 78%S 10
1.080 30.2 302
23.0 0 230
UP-Ceil-16F-30 13 X 8 104
0.032 0.9 93
0.5 0 50
Floor-20P-30 8 X 13 104
0.035 1.0 102
0.4 0 36
Subtotals for Structure:
3,891
0 5,326
Infil.: Win.: 7.8, Sum.: 2.7 210
1.138 239
0.210 110 44
Ductwork:
1,002
1,129
Room Totals:
5,132
110 6,499
CO.NT ACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM
Rhvac Residential & Light Commercial HVA_C Load_ s_
Elite.Software Development, Inc.
.Residential Energy Calc's , .
Gerety Residence
Port Saint Lucie; FL 34983 ' , .
Pa a 20
System 1 Room "Load Summary
l f3 - iY fi fl Ml
z °Htg ' Mln Rerun Run�Gylg�x"Clg �Mrn ;Act
# bl 4S 3'rc. '%e f1� q.. _ 4 t "4$' A S. fit!.ctµ M i 9 "'.3:.A1'4
)6 z r t t
Roorn � ,5g w }x� Aif a Sense fiq Ducts; Duct t.. °Seros Lat CigSys
`.�
uh�:Btuh'``CFIVI':.GFIUI`
---Zone 1---
1 Den/Office 216 6,929 90 3-6
466 6,039 877 275 275
2 Bath 1 64 1,845 24 1-4
368 706 70 32 32
3 Foyer 96 3,335 43 1-6
490 2,114 401 96 96
4 Stairway 56 1,875 24 1-4
270 518 88 24 24
Zone 1 subtotal 432 13,985 182
9,377 1,436 427 427
---Zone 2---
5 Master Bedroom 225 3,487 45 1-6
537 2,318 597 105 105
6 Master Bath 57 828 11 1-4
514 986 1,042 45 45
7 Powder Room 39 336 4 1-4
103 197 27 9 9
8 Hall 56 621 8 1-4
522 1,002 645 46 46
9 Stairway 0 64 1,147 15 1-4
225 432 36 20 20
10 Living 238 5,690 74 3-6
512 6,635 163 302 302
11 Kitchen 169 1,343 17 1-5
454 1,360 668 62 62
12 Dining 104 5,132 67 3-6
502 6,499 110 296 296
Zone 2 subtotal 952 18,584
19,429 3,288 884 884
_ _2_42
TVentilation 1,077
577 1,453
Duct Latent
1,322
_ _ _ _
System 1 total 1,384 33,646 423
_
27,729 7,499 1,235 1,235
System 1 Main Trunk Size: 12x18 in.
Velocity: 824 ft./min
Loss per 100 ft.: 0.095 in.wg
Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains
at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended
to equal the totals at the system level. Room and zone sensible gains
and cooling CFM values are for the hour in which
the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load
Procedure + Excursion" method.
Coolin ;S siernSiimma .�. ;.�� .,,�'.'.n �,;: ,_,�.: �T:�` �_`: ��.; ,,..._. .,.�-�"•
n f x Yr� LtotCoo6n ensibe/anSensible r al
r
Net Required: 2.94 79% / 21 %
27,729 7,499 35,228
Actual: 2.95 78% / 22%
27,775 7,625 35,400
E pigment Data
Heating System
Cooling System
Type: Two Speed Heat Pump
Standard Air Conditioner
Model: RXBH24A10J
RPRL036JEC
Indoor Model:
RHPLHM3621JC
Brand: PRESTIGE
PRESTIGE SERIES
Description: HEAT PUMP HSPF 9.5
SPLIT SYTEM 16 SEER
Efficiency: Hi: 9.5 / Lo: 0 HSPF
16 SEER
Sound: 0
0
Capacity: 35,400 Btuh
35,400 Btuh
Sensible Capacity: n/a
27,775 Btuh
Latent Capacity: n/a
7,625 Btuh
CONTRACTOR COPY
C:\ ...\Gerety Residence.rh9 Sunday, December 21, 2014, 7:13 PM