Loading...
HomeMy WebLinkAbout96110399 BUILDING PLAN REVIEW 12-9-96ST. LUCIE COUNTY -FT PIERCE FIRE DISTRICT BUILDING PLAN REVIEW P. O. BOX 3030 Telephone: 561-462-2312 Ft. Pierce, FL 34949.3030 FAX: 561-462-2325 JURISDICTION: St Lucie County FPB #: 6606 PROJECT NAME: Circle H Maintenance BLDG DEPT #: 96110399 CONTRACTOR: Paul Jacquin _ PHONE #: 561-465-2475 ARCHITECT: J H White PHONE #: 561-489-3782 BUILDING OWNER: Circle H Citrus REVIEW DATE: 12-9-96 BUILDING LOCATION: 3500 Shinn Rd # OF STORIES: 1- OCCUPANCY TYPE: Storage AUTO SPKLS: Yes_ No X GROSS SQ FOOTAGE: 4740 sq ft NET SQ FT: OCCUPANT LOAD: BASED ON: sq ft per person ne CONSTRUCTION TYPE: NFPA #220 _II_(000) SBCCI (un) _ _IV _ NEW CONSTRUCTION _X_TENANT IMPROV _ RENOVATION_ ADDITION SHELL ONLY _ ALL REVISIONS LISTED MUST BE IN COMPLIANCE BEFORE THE FINAL INSPECTION. The Fire Marshal requires 24 hour notice on all inspections. The Building Department schedules all final inspections. ***k*******k*****k****k****k**k******k***k*k*k*****k*****k***kk***************k******kkk***k*****k*********k**#*1 1. Provide an additional exit sign as indicated in red. 2. Provide emergency lighting with a 90 minute battery back-up. 3. Because emergency lighting is required, the required exit signs shall be provided with 90 minute battery back-up. 4. The plans indicate electric service to gas pumps. Note that an emergency kill switch is required 100' from the dispenser. REVIEWED BY: DATE: / 2- 7— 97 >o Sheet / of /