INCLUDES:
• True Power'' Electrical Technology
• Two Line LCD Multilingual Digital
Evolution'11 Controller (English/Spanish/
French/Portuguese)
• Two Transfer Switch Options Available:
100 Amp, 16 Circuit Switch or
200 Amp Service Rated Smart Switch.
See Page 4 for Details.
• Electronic Governor
• System Status & Maintenance Interval LED
Indicators
Is Sound Attenuated Enclosure
• Flexible Fuel Line Connector
• Direct -To -Dirt Composite Mounting Pad
• Natural Gas or LP Gas Operation
• 5 Year Limited Warranty
• Capability to be installed within 18" (457 mm)
of a building*
0
GENERAC®
scm9p;U _m"Alm I
GUARDIAN° SERIES
qltudoftrb Residential Standby Generators
Air -Cooled Gas Engine
Standby Power Rating
Models G007036-0, G007037-0 (Aluminum - Bisque) -16 kW 60 Hz
Model G007035-0 (Aluminum - Bisque) - 16 kW 60 Hz
Moclels 0007039-0, 0007038-0 (Aluminum - Bisque) - 20 kW 60 Hz
Models G007043-1, G007042-1 (Aluminum - Bisque) - 22 kW 60 Hz
cvus QUI
LISTED
limited circuit switch s. ation only
nitapplies
packaged with unbundled
he Smart and
arunits e ULce tlwith
ied In
the USA only.
*Only if located away from doors, windows and fresh air Intakes,
and unless otherwise directed by local codes.
FEATURES
0 INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING are at the heart of Generac's 0
success in providing the most reliable generators possible, Generac's G-Force engine
lineup offers added peace of mind and reliabillty for when you need it the most. The
G-Force series engines are purpose built and designed to handle the rigors of
extended run times in high temperatures and extreme operating conditions.
0 TRUE 1101YER" ELECTRICAL YE13NMOLOGY: Superior harmonics and sine wave 0
form produce less than 5%Total Harmonic Distortion for utility quality power. This allows
confident operation of sensitive electronic equipment and micro -chip based appliances,
such as variable speed HVAC systems.
SDLID uT:�=E, FREQUc„CY C013NSt?Teu �rOt ,E f;E:GU{ t#TIOi'b:
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque -matching the surge loads to the engine. Digital
voltage regulation at ±1%.
SINGLE SOU110E SERVICE RESPONSE from Generac's extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
O TEST CRITERIA: 0 GENERAC TRANSFER 31,1VITCHES: Long life and reliability are
J PROTOTYPE TESTED ✓ NEMA MM-22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
SYSTEM TORSIONAL TESTED V MOTOR STARTING ABILITY confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
w GENERAC at7.3s
PROMISE
.8.411. Uu USA UI/np 90 0,it, MO W,,pp party,
GENERAC"
16/20/22 kW
features and benefits
1=.aging
• Generac G-force design
Maximizes engine "breathing" for Increased fuel efficiency. Plateau honed cyllnderwalls and plasma moly rings helps the engine
run cooler, reducing oil consumption resulting in longer
• "Spiny-lok" cast iron cylinder walls
engine life.
Rigid construction and added durability provide long engine life.
• Electronic Ignition/spark advance
These features combine to assure smooth, quick starting every time.
• Full pressure lubrication system
Pressurized lubrication to all vital bearings means better performance, less maintenance and longer engine life. Now featur-
ing up to a 2 year/200 hour oil change interval.
• Low oil pressure shutdown system
Shutdown protection prevents catastrophic engine damage due to low oil.
• High temperature shutdown
Prevents damage due to overheating.
�tCTrG?6'c3tw�r'
.
• Revolving field
• Skewed stator
Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Produces a smooth output waveform for compatibility with electronic equipment.
• Displaced phase excitation
Maximizes motor starting capability.
• Automatic voltage regulation
Regulates the output voltage to ±1 % prevents damaging voltage spikes.
• UL 2200 listed
For your safety.
Transfer %witch (hf appticabBe)
• Fully automatic Transfers your vital electrical loads to the energized source of power.
• NEMA 3R Can be installed inside or outside for maximum flexibility.
• Remote mounting Mounts near your existing distribution panel for simple, low-cost installation.
Ivvastrwifon"' Canjvoijc
• Auto/Manual/Off illuminated buttons Selects the operating mode and provides easy, at -a -glance status indication in any condition.
• Two-line LCD multilingual display Provides homeowners easily visible logs of history, maintenance and events up to 50 occurrences.
• Sealed, raised buttons Smooth, weather -resistant user interface for programming and operations.
• Utility voltage sensing Constantly monitors utility voltage, setpoints 65% dropout, 80% pick-up, of standard voltage.
• Generator voltage sensing Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
• Utility interrupt delay Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default setting of 5 seconds by a
qualified dealer.
• Engine warm-up Ensures engine is ready to assume the load, setpoint approximately 5 seconds.
• Engine cool -down Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
• Programmable exercise Operates engine to prevent oil seal drying and damage between power outages by running the generator for 5 minutes every
other week. Also offers a selectable setting for weekly or monthly operation providing flexibility and potentially lower fuel
costs to the owner.
• Smart battery charger Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Compatible with lead acid and AGM -style batteries.
• Main line circuit breaker Protects generator from overload.
• Electronic governor Maintains constant 60 Hz frequency.
Unit
• SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding winds up to 150
mph. Hinged key locking roof panel for security. Lift -out front for easy access to all routine maintenance items. Electrostat-
ically applied textured epoxy paint for added durability.
• Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
• Small, compact, attractive Makes for an easy, eye appealing installation, as close as 18" away from a building.
IRCI IN'Iflon s1/^.3t n6
• 1 ft (305 mm) flexible fuel line connector Absorbs any generator vibration when connected to rigid pipe.
• Direct -to -dirt composite mounting pad Complex lattice design prevents settling or sinking of the generator system.
• Integral sediment trap Prevents particles and moisture from entering the fuel regulator and engine, prolonging engine life.
GENERAL°
16/20/22 kw
specifications
>:s0o a�f'cai;�p
Madel
Rated Maximum Continuous Power Capacity (LP)
0007035.0,0007036.0.
G007037-0 (16 kW)
G007038-0,0007039.0
(20 NW)
G00704G007043-1
{22 (22 kW)
Rated Maximum Continuous Power Capacity (NG)
16,000 Walls'
20,000 Walls'
22,000
Rated Voltage
16,000 Watts'
18,000 Wafts`
19,500
Rated Maximum Continuous Load Current-240 Volts (LP/NG)
240
240
240
Total Harmonic Distortion
66.6/66.6
83.3/75
91-6/81.3
Main Line Circuit Breaker
Less than 5%
Less than 5%
Less than 5%
Phase
70 Amp
100 Amp
100 Amp
Number of Rotor Pales
1
1
1
Rated AC Frequency
2
2
2
Power Factor
60 Hz
60 Hz
Battery Requirement (not included)
1.0
1.0
.60Hz
1.0
Unit Weight (Ib/kg)
12 Volts, Group 26R 540 CCA Minimum or Group 35AGM 650 CCA Minimum
Dimensions (L x W x H) iit/mm`
406/186
448/203
466/211
Sound output In dB(A) at 231t (7 m) with generator operating at normal load"
481i 25 x 29/1218 x 638 x 732
Sound output In dB(A) at 23 it (7 m) with generator in Quiet -Test- low -speed exercise mode**
56
58
66
67
Exercise duration
58
58
�r7c9ruc
5 min
5 min
1 5 min__
Type of Engine
Number of Cylinders
GENERAL G-Farce 1000 Series
Displacement
2,
2
2
Cylinder Block
999 cc
999 cc
999 cc
Valve Arrangement
Aluminum w/ Cast Iron Sleeve
Ignition System
Overhead Valve
Overhead Valve
Overhead Valve
Governor System
Solid-state w/ Magneto
Solid-state w/ Magneto
Solid-state w/Magneto
Compression Ratio
Electronic
Electronic
Electronic
Starter
9.5:1
9.5:1
9.5:1
Oil Capacity Including Filter
12 Vdc
12 Vdc
12 Vdc
Operating rpm
Approx 1.9 gl/1.8 L
Approx.1.9 gV1.8 L
Approx.1.9 gV1.8 L
Fuel Consumpllon
3,600
3,600
3,600
Natural Gas, it3/ry (mJhr): '
1/2 Load
Ltquid Propane ft3Wi (gal/hr). [Vhr]-
1/2 Goad
Full Load
Note: Fuel pipe must be sized for full load. Required fuel pre.sst
for LP gas.For Btu content, multiply it /hr x 2500 (LP) or 113/hr x 1
218 (6.17)
309. (8:75)
91,6.(2.52) [9,53j
106.8.(2.94) (11.11],
to generator fuel Inlet at all load ranges - 3.5-71, water column (7-13 mm
0 (NG). For Mega)oule content multiply m3/hr x 9315 (LP) 0 31h
204 '(5.78).
`301
228. (k4'6)
(8.52)..
;.327 (%26) .
8642.37) [8.99]
92;(2,53) 0:571-
129,6 (4;56) [13,481'
142{3.90)
ury) far natural gas,10-12° water column (19-22 mm mercury)
cm1a11rols - — -
rm rx3r co (NG)
2-Line Plain Text Multilingual LCD Display
Mode aullons:Aulo
Simple user interface for ease of operation.
Manual
Automatic Start on Utility failure. 7 day exerciser.
on
Start with starter control, unit slays on. II utility jails, transfer to load takes place.
Re
Ready to Run/Mafntenance Messages
Stops unit. Power is removed. Control and charger still operate.
Engine Run Hours Indication
Standard
Programmable start delay between 2-1500 seconds
Standard
Utility Voltage Loss/Return to Utility Adjustable (Brownout Setting)
Standard (programmable by dealer only)
Future Set Capable Exerciser/Exercise Set Error Warning
From 140-171 V/190-216 V
Rurt/Alarm/Maintenance Lags
Standard
Engine Start Sequence
50 Events Each
Starter Lock -out
Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Smart Battery Charger
Starter cannot re-engage until 5 sec after engine has slopped,
Charger Faull/Missing AC Warning
Standard
Low Battery/Battery Problem Protection and Battery Condition Indication
Standard
Autorratio.Voltage Regulation with Over and Under voltage Protection
Standard
Under-Frequency/Overload/Stepper Overcurrent Protection
Standard
Safety Fused/Fuse Problem Protection
Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown
Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown
Standard
High Engine Temperature Shutdown
Standard
Internal FaultAncgrrectWiring Protection
Standard
Common External Fault Capability
Standard
Field Upgradable Firmware
Standard
"Sound levels are Men from the front oflhegenerator. Sound levels taken from other sides Ofthe generatorparameers,RalStandard
of the utility power outage. No overload capability is available for this rating. (All ratings in accorance with BS5514, IS03046 and depending anfor supplying emergency
content,
subject rBlu/megalofor the
kilovvagampsiand current arYons e
o and funillicable
uch Nctors as fuel
ambient temperature, altitude, engine power and condition, etc. Madmum power decreases about 3,5 percent for each 1.000last (3o4.o meters) above sea level; and alsowilt decrease ols
1
about percent forach a T (10 "F) above 16 `C (60-�.
GENERACA
16/20/22 W switch options
•- -
U111 OU bir colas 6ttrfitell FBatL9YGs
• 16 space, 24 circuit, breakers not included.
• Electrically operated, mechanically -held contacts for fast, positive
connections
• Rated for all classes of load,100% equipment rated, both inductive and
resistive.
• 2-pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil design.
• Rated for both copper and aluminum conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking,
• NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
• Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexible and cast effec-
tive install.
Dimensions
MA175.4
W2
Depth
In3,5
6.91
3.0
175.4
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
1/0-#14 210-#14 2/0-#14
Model
G007036.0 (16kW)
No. of Poles
2
Current Rating (Amps)
100
Voltage.Rating.(VAG)
.120/240,10
Utility Voltage Monitor (Fixed)*
Pick-up
80%
-Dropout
65%
Return to Utility"
approx.15 sec
Exercises bi-weekly for 5 minuies't
Standard
UL Listed
Standard
Total Circuits Available
24
Tandem Breaker Capabilities
8 tandems
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current O 250 Volts
10,000
*Function of Evolution Controller
Exercise can be set to weekly or monthly
w,
142
HI
DEPTH
I_
M
Service plated smut e;0t.'e ich r-a'92 res
kW)/
•
Includes Digital Power Management Technology standard (DPM).
Model 0007037.0 (16 kW)/6007039.0 (20�m0
0007043.0 (22 kW)
•
Intelligently manages up to four air conditioner leads with no additional
No. of Poles
2
hardware.
Current Rating (Amps)
200
•
Up to four more large (240 VAC) loads can be managed when used in
Voltage Rating (VAC)
120/240,10
conjunction with Smart Management Modules (SMMs).
UtilityVollage Monitor (Fixed)'
-Pick-up
80%
•
Electrically operated, mechanically -held contacts for fast, clean connections.
-Dropout
65%
•
Rated for all classes of load,100% equipment rated, both inductive and resis-
Return to utility'
apptox 13 sec
tive.
Exercises bi-weekly for 5 minutes*
Standard
•
2-pole, 250 VAC contactors,
uL Listed
Standard.
•
Service equipment rated, dual coil design,
Enclosure Type
NEMA/UL 3R
•
Rated for both aluminum and copper conductors.
Circuit Breaker Protected
22,000
•
Main contacts are silver plated or silver alloy to resist welding and sticking.
Lug Range
250 MCM - #6
•
NEMA/UL 3R aluminum outdoor enclosure allows for Indoor or outdoor mount-
*Function of Evolution Controller
ing flexibility.
Exercise can be set to weekly or monthly
Dimensions
200 Amps 120/240,1e
Open Transition Service Rated
Height
H1 H2
Width
W1 W2
Depth
In
26.75
30.1
10.5
13.5
6.91
mm
679.4
764.3
266.7
343.0
175.4
w,
H2
HI
DEPTH
_.... —_
I
GENERAC
7 6/20/22 kW available accessories
Modeh,'# Product DescnptrRif
The WI-Fi enabled LP fuel level monitor provides constant monitoring of the connected LP fuel tank, Mon-
G007005-0 Wi-Fi LP Fuel Level Monitor storing the LP tank's fuel level is an Important step in making sure your generator Is ready to run during an
unexpected powerfailure. Status alerts are available through a free application to notify when your LP tank
is in need of a refill.
G006463 4 Mobile Link"
Generays Mobile Link allows you to check the status of your generator from anywhere that you have ac-
cess to an Internet connection from a PC or with
any smart device. You will even be notified via a -mall or
-text message when a change in the generators status occurs. Available In the U.S. only.
G005819.o 26R Wet Cell Battery
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet
cell battery for use with all air-cooled standby
product (excluding PowerPact@).
G007101-0 'Battery Pad Warmer
The pad warmer rests underthe battery. Recommended for use if the temperature regularly falls below 0°F.
(Not necessary for use with AGM -style batteries).
G007102-0 till Warmer
O 0117
Fwarmer slips directly over the oil fitter. Recommended for use If the temperature regularly falls below
G005621-0 Auxiliary Transfer Switch
Contact Kit
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load
you may not need. Not compatible with 50 amp pre -wired switches.
G007027.0 - Bisque Fascia Base Wrap Kit
(Standard on 22 kW)
The fascia base wrap snaps together around the bottom of the new air cooled generators. This offers a
sleek, contoured appearance as well as offering
protection from rodents and Insects by covering the lifting
holes located in the base.
G005703-0 - Bisque Paint Kit
If the generator enclosure Is scratched or damaged, it is Important to touch-up the paint to protect from
future corrosion. The paint kit Includes the necessa
enclosure. ry paint to properly maintain or touch-up a generator
6006485-0 Scheduled Maintenance Kit
Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine
maintenance on a Generac automatic standby
G006873-0
generator.
Smart Management Modulo
Smart Management Modules are used in conjunction unction with the Automatic Transfer Switch to increase Its
(60 Amps)
power management capabilities. It provides additional power management flexibility not found in any other
power management system.
I-ti ar
LEFT SIDE VIEW
dimensions & PCs
Dimensions shown are approximate. Refer to installation manual for exact dimensions. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
FRONT VIEW
GENERAC" Generac Power •
Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189
Y
• generac.com
@2017 Generac Power Systems, Inc. All rights reserved. All SWIlicatlons are subject to change without notice. Part NO. 100000001 94-F 513/17
v'na�g Management
Modules
0
GENERACMMMO
DESCRIPTION r
Gerwrao's Smart power Management system is designed to optimize the performance of a
Smart Management Modules (sMM). Unlike other load aware standby gene, t
GENEWO ACCE2,90RjE,9
Model Goo6878.0
COUB
uffe
and operate autonomously, management systems that depend on another control devise the tem an modules Of UP actually Bali 5�tfl
Frequency Is the true measure of Generator engine 9 performance and does not need to fasts, in Increased am6lerri temperatures,
generator fuel type, the modules monitor the ngin frequency (Hz) of the powerno
threshold, the module will automatically follow a power management algorithm to ensure that the generator Is not overloaded elevation changes or
being produced by Generao's standby generators and It It falls below a certain
The modules can be set to a load priority between 1-8 or be set In a lock out only mode for loads that just stm I
reducing the necessary size of the generator for a more cost effective solution.
p y do not need to run in an outage, therefore
SMM SPECIFICATIONS
rowar Supply source....
Supported Voltages.......................... ........ ........... ................................ »..... .......... .................................
contaotor Coll
CoilVA Inrush., itage...................................................................»,..........................................,...............,..........,................».............................. 240 VAC (krom Line Input)
CoilVA Sealed................................».»»...»...................................»..._...............................»...................................................„....,................,.....................11....._.......240 VAC
Poles... ..................................................................1,...................»»............................................................................240 VAC
ReslsUaAm s..........................................................................................................»...............................................................................................»..........»..........._.........,so
p ............I... ...........
8.5
F/LlnduativaAmps......................................................................................................................................................»....... ..2
LookedRoMrAmps....................................................»................................................».................. ...........,..................................... ....................50
E11150 ......»......................................................................................................................................................................................»..40
nclosure Racing ............................._..............»..............................
..............., ........
;...,......................I......................,.,............,............. 240@2 0V
., _:....... ..... .............................................. NEMASR
GENERAL;°
Smart
Model
Height awrom) H7
H2
WfdUt (it►hrun] 1 W2
r We"M RINGS)
UPC Code
®ENERAC
modules VIEW Dfm®nylons and UP
C
00097H
6.17/166.8
2.36/80
7.081179A
L72112D
V194
2A8/0.94
244/1.11
693471003733
-7
D1
o 0
Wish!Contr®ls €100a1®d behind the cover of the module)
B
1
LED 0 a LOAD OONtD;OTSD
PRIORITY
LOOKOur
LIMPLAMIS-LOADSRED
6
3 7
LOAD ON
GENERATOR
LED FLASH SS a So 1N LOQKODP
LEDFLASUSSa GENLOADL00KODT
I
®
M
O LED OFF _NOINODREPOIdtEA
0LOCKOtJi
°
TEST
DItiAEIEB
Prlorhy Dtal (A) — Sets TrOdule priority.
Lockout Switch (8) — Plaverds load From operating when system is opereting under generator power,
Test Button (C) — Disables oentaclOr output for a epectlted time.
LED (D) — Provides module almus »1th easy viewing through the wdemal viewing window
located in the upper fight comer of the module,
�������„ Generac Power Systems, Inc. 845 W29290 HWY. 59, Waukesha, W153189 � generac.cam M @2016t3enerao PowerSysteme, Ins, All dehts reserved. AU speoiilcaUone are subject m ssenge velhout notice. Bu11eUn OL19oa�C 03/ta/t8
Site cere..��-- -- • —
a&Won 3: Site Selecfion and PmParation
site Selection
r` 6 ft (1,62 m)
r
O '
j3 r 3 fE �
(0.91 m) A �.- 3 �
(0.81 rn)
d
s ft (0.91 m)
®o
Mli'll" � ILA
t
esortpttoctnerator
dand clearance
ranmand openings
B Eklating waft
F Removable fence
Overhead clearance
Figure 3.9. Instaffad'M Clearances
Comments
• ••, • . �l+ai auur 1
Minimum clear distances cannot include shnrba, bushes, or try
18 Jn (4g.7 —� mfnIM,, o clearance er NFPA t
dictate otherwise. cs6rrg, labeling, and jismg, unless state or local Codes
he operable windows, doors, or openings in the wall are permifted within 6 it (1.62 M) from any Point of
the generator.
One -hour fire rated wails allow closer placement of tha generator sat. Con Irm before IngWation.
Removable fence panels for senticfng cannot be placed less than 3 ft (0.91 m) In front of the generator,
5 ff (1.52 m) minlmum distance from any structure, overhang, or projections from the wall.
DO NOT install under wooden decks or structures unless this distance is maintained.
lnsteiiation r.'t&4.5... , —
--.-.— , - vV g !G nil-vvolea c;enerators
11
Site Selection and pn" 01fion 0
12
install the generator set, in its
outdoofs where adequate cooltn protective enclosure,
always a„elia�l8 � g and ventilating air Is
Consider these factors:
° The Installation of the
strictly with ICC 1FGC generator must comply68, and NFPA 70 standardsPA 37, NFPA 54, NFPA
° Install the unit where air inlet and outlet openings
will not become obstructed by Issues
etc. If prevailing winds will , grass, snow,
drifting, consider using a windbreak io plrowecgthe
unit.
° rlor
Install the generator on high
nd Where water
levels will not rise and endaerrauThis unit should
not operate In or be subjected to standln
° Allow sufficient room on all sides to dig water.
for maintenance and seMcing. This he generator
installed In accordance with
national codes tar minimumwith any local, state, or
structures. distances from other
° Clearance from t
. must bethe ends and front of the
g generator�
bushes ft (0•91 m)• This includes and frees. Clearance fro
generator must be a he back of h minimum of 1,S m tin (457 mm . s
Clearance at the fop should be a minimum of 5 �
protections f from the well.rom any structure, overhang, or
° DO NOT install under wooden decks or structures
unless there Is at least
above the generator. 5 ft (1.52 m) of clearance
Install the unit where
run-off, landscape irrigatlot� frwa e sprinklers, spouts, roof
sump pump discharge does) not floothe unif or
�4n
spray the enclosure, including any air inlet or outlet
openings, A4.1
° Install the unit where services will not be affected Mee
or obstructed, Includingco Seca
or covered services such as electrical,aled,underground fuel, honeavali
air conditioning,exce
Wdrrd . irrigation. This could ar%ci and
+Y COVer8g6, mane
° Where strong prevailing winds blow from one labors
direction, face the generator air inlet openings to the to
the prevailing winds.
° en
Install the generator as close as NOTE
suppiy to reduce the length of jp n Bible to the fuel 18 In
THAT t:AUfIS OR CODES MAY RECU MEMBER
DISTANCE AND LOCATION. LATE THE of nations
local codes regarding placement orclearance,ce,we agency,
recommend following these guidelines: The crlt
Install the generator as close as possible to the whin th
transfer switch, REMEMBER THAT He
the
kerns ou
CODES MAY REGULATE THE DISTA W8 ANp a en
LOCATION.
— The generator must be Installed on a lev- a—`f s
face- mmhe generator must be level within a 0.5 In
all around.
The generator is typically placed on ea
compacted soil, crashed stone, Ora concrete
gravel, pad. Check local codes fo see what ►squired, if a concrete pad is require all pe is ii-
cable codes should be followed. pp
Installation Guidelines for Sta"ionarYAfr,Cooied
Generators
NFPA 37 is the The National
Assoclatfon,s standard for the Instatlatiolne and use. of
stations co proi'ectlon
►Y combustion engines. Its requirements limit the
Wallspacing of an enclosed generator set from a structure or
,=���:_;�:, �,,;�).
NFPA 37, Section 4.'1.4
Enqlnes znglnes, and their weatherproof ho stnased outdoors;
hat are Installed outdoors shall be locatedg ff provided,
1:52 m) hom openings in walls and at least at least S ft
from structures having combustible wall, Aft (1.52 m)
eparation shalt not be required where minimum
conditions exist the following
1 The adjacent wall of the structure has a fire
resistance rating of at least one hour.
2• The weatherproof enclosure Is constructed of
noncombustible Materials and It
has been
d®monstrated that a fire within the enclosure y�i>t
not Ignite combustible materials outside the
enclosure.
sell A — Expjanatory lWaterial
s of full scale fire fdemonstratingesr bccompliance are b
use of the limited spaces that on procequres.y
able for installation, it has become are frequently
ptlon (2) would be beneflcta( for Many that
commercial instailafions. vitith that to mind the
facturer contracted with an Inds
story tv run full scale fire tests to assuretthat the
sure will not ignite combustible materials outside
closure.
-Southwest Research Institute testis
(4-57 MM) Installation minimum from pproves
`" C)• South -structure
!ly recognized thiwest from Institute is a
Party tang and listing
eria was to determine, the Worst Case fire sCenado
e generator and to determine fhe tside the engine enclosignitabllity of
closure cons at varlous distances.
Materials, and the 9 of non-combustible
s and conc
'**dependent testing lab Indicated that alnyfirres from the
within the
installation Guidelines For80 HzAlr-Cooled Generators
.generator enclosure would not pose an ignition
nearbY comiDustibles or Y 'gnitlon risk to
Service personnel response ctures, with or without fire
Lei BYi SpYynrost R A 37
pnp'°4a't' seq pRtplto,
ADM I
_ ¢ am
NM a
We
MM7inaft
aas�+
�at ,M
Ffgure 3-2. SoufbwestResearch
rr�stittrte lliadd
rig
Based on this testing
S804.1.4,n the ng and the requirements of guidelines for Installation NFPA 37,
listed above are changed io 98 in of generators
backside of the generator to a Stationary7 mll from the
(C)• For adequate maintenance and ailowi Cor learance
the area above the generator should be at least 6 1. S2
m) with a minimum of 3 ft O,g� e'
of the enclosure. ( M) at the front and ends
bushes. This Includes trees, shrubs
Vegetation not In compliance and
clearance parameters could with these
exhaust obstruct air flow. In addition,
growth, fumes from the generator could inhibit plant
See °and the Installation drawing
within the OW �.,.... r .�;
ner's manual for details.
�a m
Automatic start up. Disconnect utlii
render unit inoperable before workln pon wer and
Failure to do so will result in death or se our injury
(000191)
Asphyxiation. Runnln
carbon monoxide, a Colo le See produce
Poisonous as. Carbon monoxide°if not
avoided, wfj result in death orserlaus Injury,
MOTE; l€the (000
generator is not set to OFF, it can crank and
start as soon as the battery cables are connected. k the
utility power supply is not turned off
at the battery pow and cause an a sparking can occur
xplosion.
I'll
lnstalfefloI Guidelines Far 60 A-1`r-Cooled Generators
Site Selectlon and Preparation
"Site PrepaFation
° Locate the mounting area as close the transfer switch and fuel s as possible i
° Leave adequate roc .�PIY
access Cn around the area for service
(check focal code), and place geignhereatoug,to keep rising waterfromreachin the
Choose an openspatethatwill g
and unobstructed airflow provide adequate
° Place the unit so air vents WOO become
with leaves, grass, snow clogged
exhaust furnes will not ante or debris. Verify that
eaves, windows, Ventilation fans wilding through
intakes a:aX a:,:) , or other air
° Select the type of base
to —compacted so11, , Ouch
con-_ but not limited gre
ete
or. as required by local laws or codes.' as desired
local requirements before selecting, verify Your
Material Sufficient for Level installation
° Prepare a rectangular area approximately
mm) deep (A) and approxim51n (127
longer and wider g 6 In ('152 ram
generator. Verify ()than at the the footprint of the
'generator will be Mohunted is coerce where the
and will not erode over time. A concreteed' leveled,
poured if desired or re pad can be
required.
� n
Prgure 3-3 Conrpacied $olf or Grayer Pad
NOTE: if a concrete pad Is required, follow ail
federal, state, or local codes. applicable
13