June 18, 2018
Re: Wharton Roof Re -Roof
651 Hidden River Dr.
Port St. Lucie, FL
f
SCOPE OF WORK:
Remove existing roofing and install new standing seam Metal Roof (Extreme Metal Fabricators
FL # 17022.5) at above referenced residence address over new underlayment and existing
plywood sheathing. '.
DESIGN CRITERIA:
FBC 2017'
ASCE7-10
PROJECT DATA:
BUILDING HIEGHT = 8'
A= 3'
MEAN ROOF HIEGHT = <20'
ROOF ANGLE = 3:12
SHAPE = PITCHED HIP
U%4PROTANCE FACTOR = 1.00
WIND VELOCITY V ult =160 MPH
WIND VELOCITY V asd = 124 MPH
EXPOSURE = C
ENCLOSURE CLASS = ENCLOSED BUILDING
INTERNAL PRESSURE COEFFICIENT = -0.18
APPLIED UPLIFT DESIGN PRESSURES ON SLOPED ROOF (nsf)•
ZONE 1 (Field) = -32.5
ZONE 2 (Perimeter/ Ridge) = -56.6
ZONE 3 (Corners) = -83.7
Paul Welch Inc.
Paul Welch P.E. Reg. No. 29945
June 18, 2018
651 Hidden River Dr. Port St. Lucie, FL 1 of 4
16"
_—� 34"
Panel Profile
16'o.c
Deck .
1&3rorgreater Plywood or
- Mod plank
Snap Lock
Apply Y16- Bead BDS R 915-Sealant
.CorkCrwoksAlong Male Pob Yertnl Ran4e
Fastener
410.1' Mm. per Table'A
PanokeHead Mod Screw
l
(Typical Fastening Pattem Across Width)
METAL ROOFING ATTACHMENT REOUIREMENTS (FL#17022 5)• ,
Metal roofing to be attached'with #10 x V long (minimum 3/16". penetration through plywood
sheathing) pancake head screws spacing as follows:
ZONE 1(Field):
Fasteners through panel strip at 6" O.C.
ZONE 2 (Perimeter/ Ridge):
Fasteners through panel strip at 61' O.C.
ZONE 3 (Corners):
Fasteners through panel strip at 6" O.C.
Zones 1 & 2 Design uplift Pressure: -86 psf
Zone 3 Design uplift Pressure: - 86 psf
r
651 Hidden River Dr. Port St. Lucie, FL 2 of 4
UNDERLAYMENT:
Underlayment shall be Tri-Built Roofing Products FL# 16048.1 "Tri-Built S/A HT TU".
While priming is optional, TRI-BUILT recommends priming the deck if the final roof cover is
not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back
the first 3 ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while
holding the membrane tight. Firmly roll the membrane into place to achieve a bond. Horizontal
seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6inches
and staggered not less than 2-ft from vertical seams in the course below. All over -granule end -
laps shall be sealed using either heat -welding or hot air welding,techniques. For Valleys and
Ridges: Cut underlayment,into 4 to 6 foot lengths. Peel the release paper and center sheet over
valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge
in each direction. For valleys, apply the sheet starting at the lowest point and work upward.
DECK INSTALLATION:
Re -nail all plywood sheathing (19/32" thick minimum) with 8D ring -shank nails at. 6" O.C.
perimeter and 6" O.C. field for all zones.
All work to be in compliance with product approval (FL # 11560.5), (FL# 16048.1),
manufacturer's'specifications, and the Florida Building Code 2017. ,
651 Hidden River Dr. Port St. Lucie, FL
Paul Welch Inc.
Paul Welch. P.E. Reg. No. 29945
June 18, 2018
3 of4
r-0, i 00
Nn'(
A LLu
ROOF ZONE PLAN
A=3
1 ( , 03 = ZONE DESIGNATION (TYPICAL)
NOTE: CONTINUOUS APPROVED LAP SEALANT MUST BE USED AT ALL PANEL
SIDELAPS FOR SLOPES LESS THAN 3:12.
651 Hidden River Dr. Port St. Lucie,, FL
Paul Welch Inc.
Paul Welch P,E. Reg. No. 29945
June 18, 2018
I
4 of 4