Building Dept. SLC FMO Permit # B-18-54.
Project NameMaverick Boat Group Inc BLDG Permit# 1801-0678
Address 4551 St Lucie Bvid City Ft Pierce
Contractor RF Concrete Construction
Address 64 Old Dixie Hwy City Vero Beach
State FL Zip 32962 Telephone (772) 567-3356
Architect/Engineer Wes hardon Telephone
Occupancy Type industrial I Construction Type IB I Square Feet 235,000
Occupant Load 2350 pel plans Number of'Stories Access Box Required Access Key Switch
AFS Permit [Required FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submittedon a CD Is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy mustbe received prior to permitting,
3. The: Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design.. Design criteria shall be submitted with the construction plans,.
7. Firealarm panels shall be located indoors within air conditioned space,
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s'that exceed 2,000 cfm design capacity.
10.. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection'Systems require aseparate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. The Installation or Alteration of Fire Sprinkler, Fire Alarm, Systems require a separate review and permit.
>., Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
nspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detectors)
.hall be tied into the fire alarm system.
AI; exit doors shall swing in the means of egress.
Place exit signs over all exit doors. Emergency lighting is required.
Page 17 of 1❑ Reviewed by Tony Jerger Date 02-14-18