HomeMy WebLinkAboutFLOOR PLANFILE COPY
JURISDICTION-- PALM EEACH COUNTY, FL
OCCUPANCY CLASS-- PESIDENTIAL R-3
TYPE OF CONSTRUCTION --V
FIRE SPRINKLER SYSTEM --NOT REQUIRED
FIRE ALARM --NOT REQUIRED
BUILDING CODE: 2017 FLORIDA BUILDING CODE
ASCE 7-10, NEC 2014
EXPOSURE: C
BUILDING DESIGNED AS ENCLOSED
MEAN ROOF HEIGHT: 19 FT
IMPORTANCE FACTOR: 1.0
WIND VELOCITY: Vult=175 Vasd=135
qh=56.57 psf
Kh=.85
Kzt=1.0
Gcp i=.18+/—
GCpf=1.0+, 1.4—
P=0.6w
ROOF MATERIAL: 5V METAL ROOF PER PRODUCT APPROVAL
ROOF DEAD LOAD: 30 PSF
ROOF LIVE LOAD 25 PSF
SOIL BEARING CAPACITY: 2500 PSF
REVIEWED FOR SHEAR WALL REQUIREMENTS : YES
IMPACT PROTECTION: PER PRODUCT APPROVAL --
WINDOWS AND DOORS IMPACT RATED
INTERNAL COEFFIECIENT: 0.18
RISK CATAGORY : II
END ZONE WIDTH FOR 30FT L BUILDING: 3 FT
COMPONENTS AND CLADDING DESIGN WIND PRESSURES
WALL
ROOF
ZONE
Leeward/Windward
Leeward/Windward
TRIBUT.AREA
10sf
1
—36.7 +23.1
ROOF
PERIMETER
2
—63.8 +23.1
ROOF
CORNER
3
—63.8 +23.1
WALL
INFIELD
4
—43.4 +40.1
WALL
CORNER
5
—53.6 +40.1
DESIGN
PRESSURES
FOR OPENINGS (IN
PSF):
WITHIN 3FT FROM CORNERS --SEE ELEVEATIONS
GREATER THAN 3 FT FROM CORNERS: SEE ELEVS.
GARAGE DOOR NOT APPLICABLE
INSULATION: FLOOR NOT APPLICABLE
WALLS R 4.1 MIN OR
WALLS R13 0 6" FRAME EXTERIOR
ROOF R 30 MIN
ROOF NAILING PATTERN
IF REQUIRED
1. 10 D RING SHANK NAILS
AT 4" EDGE AND 6" FIELD
WALL SHEATHING :
1.8"EXTERIOR GRADE PLYWOOD W/ 8D RING
SHANK NAILS 0 4" O.C. AND 6" FIELD
WINDOW AND
DOOR SCHEDULE
NO.
NOMINAL
WIDTH X
SIZE
HT.
TYPE
REMARKS
�1
36" WIDE
X
96"
HIGH
PANEL DOOR
IMPACT
GLASS
W CATEGORY II SAFETY
PER FBC 4 4410.2.3.1.3
(2
26" WIDE
X
63"
HIGH
ALUM. SINGLE HUNG
IMPACT
GLASS
W CATEGORY II SAFETY
PER FBC 4 4410.2.3.1.3
96" WIDE
X
72"
HIGH
ALUM. SINGLE HUNG
IMPACT
GLASS
W CATEGORY II SAFETY
PER FBC 4 4410.2.3.1.3
CONTRACTOR TO VERIFY ROUGH OPENING DIMENSIONS FOR DOORS AND WINDOWS ORDERED PRIOR TO CONSTRUCTION
ALL DOORS AND WINDOWS TO BE LOW E GLASS AND IMPACT
_ y� ADVANCED
ST. LUCIE C UNTY BBUI D G�IVIS ON
REVIEWED FOR COMPL s DESIGN &
REVIEWED BY 3
DATE I
PLANS AND PERMIT M BE KEPT O ]CB SCANNED
BUI
`DI NG
SCANNED3 SITE OR NO INSPECTIONS) WILL BE MADE
StLu � Co
ALL MANUFACTURES LABLES SHOWING ARCHITECTS
U FACTORS AND SHGC COMPLIANCE
WITH FBC ENERGY CODE MUST
REMAIN ON ALL DOORS AND WINDOWS
UNTIL INSPECTIONS ARE APPROVED
THESE PLANS AND ALL PROPOSED WORK GENERAL
ARETANY CORRECTIONS CONTRACTORS
REQUIREDUIRED BFIELD FIELD INSPECTORS THAT
-4 15 -4 MAY N NECESSARY IN ORDER TO A ROUND HILL DEVELOPMENT GROUP COMPANY
23
' COMPLY WITH ALL APPLICABLE CODES. 17968 115 TH AVE. NORTH
10 JUPITER, FLORIDA 33478
PH: 561-216-1000
O CELL 561-718-0831
a/C - 319 167TH ST
O 1 CONCEALED FASTENERS OR ATTACHMENTS NO. MI MI BEACH,
0 33162
ARE THE RESPONSIBILITY OF THE WWW.AD VANCED—DESIGN—BUILDING.COM
CONTRACTOR OF RECORD. 1MESE DRAWINGS AND SPECIFICATIONS PR ARE
INSItI IHIESE OF SERVICE AND ARE THE NS ARE
OF
ROUND HILL DEVELOPMENT GROUP. INC./ dbu ADVANCED
DESIGN ! BUILDING THEY ARE NOT TO BE USED ON
D ANY OTHER PROEM OR DM34SONS OF THIS PROJECT
14'—$" 5'-0" 12'-0" EXCEPT BY WRITTEN AGREEMENTS KITH ROUND HILL
U DEVELOPMENT GROUP.
LL NO DESIGN CHANGES WHICH ALTER THE INTENT
2'-B"x8'— OF THESE DRAWINGS OR SPECFICATIONS ARE TO BE MADE
UTILITY WITHOUT OBTAINING WRITTEN PERMISSION FROM
^0 ROUND HILLDEVELOPMENT GROUP.
o ROOM BEDROOM
_I 1 I 0
0 - - _ ARCHITECT: BERNARD
0 0 JONES
I ARCHITECT -Do (:::Ic
5'- 0" LIVING
11, SEAL:% E =0 e
8'-
CLOSET BATH DATE.
FROCH OORONT -4xB-G• A 0
d CLOSET O
O ^
0
CLIENT:
R FORT PIERCE HOUSE
2'-B"x8'-0"
0
0
1 OFFICE 0 KITCHEN BEDROOM
0
9'-0"1 10'-0" 14'-0"
® ® 0 0 ADDRESS:
3'-8"
2
19'-8"
N
GUEST HOUSE
SCALE 1/41NCH
U
15'-4"
RECEIVED
LFFR 0 4 2019
ST. Lucie County, Permitting
FLOOR PLAN
REVISIONS:
DRAWN BY: JMG
CHECKED BY: BVJ
PROJECT #:
SCALE: j INCH
A-2
E =
EXISTING LEGEND
WALL MOUNT
FIRE
SUPPRESSION
AT KITCHEN
HOOD
/0-� CEILING ENDANT LAMP(HEAT)
PENDANT °
I SWITCH LETTER
• • NEW
EXISTING ADDED FIRE
F.SPRINLER SPRINKLER
HEAD HEAD
RECESSED
MAKE UP AIR
LIGHT
CEILING
RETURN AIR GRILLE
SURFACE
Emil
MOUNT
1 X 4
FLUORESCENT
SUPPLY
S . 61-14" REGISTER
2 X 4
FLUORESCENT
CEILING FAN
EXIT SIGN/EMERGENCY
LIGHT COMBO
EF EXHAUST FAN
EXIT ISCONNECT
SIGN
3 - WAY
$ SWITCH SWITCH
PANEL
EMERGENCY LIGHTING
CIRCUIT NO.
GROUND TYPE DUPLEX RECEPTACLE
P❑ FIRE ALARM PULL STATION
12OV-2OAMP INTEGRAL FAULT
aGFI INTERRUPT PROTECTION
CD COMBINATION /VISIBLE
STROBE
GROUND TYPE DUPLEX
RECEPTACLE12OV-2OAMP
WEATHERPROOF TYPE
CD=CANDELA
WP
80"-96" AFF RATING SETTING
GROUND TYPE SINGLE
RECEPTACLE 12OV-2OAMP
+180AFF UNLESS NOTED
OTHERWISE
GROUND TYPE DUPLEX RECEPTACLE
12OV - 20 AMP
GMOUNTED IN CEILING
GROUND TYPE DUPLEX OUTLET
12OV-2OAMP +18"AFF U.N.O.
GROUND TYPE DOUBLE DUPLEX
RECEPTACLE 12OV-20AMP MOUNTED
IN TWO GANG OUTLET BOX AT
180AFF UNLESS NOTED OTHERWISE
GROUND TYPE DUPLEX
12OV-2OAMP MOUNT ABOVE
C�3OA 12OV SPECIAL PURPOSE OUTLET
(SUFFIX INDICATES AMPS)
COUNTER OR AT HEIGHT NOTED
00C
$
`CT 22OV
COMMUNICATIONS OUTLET
�OA 3 WIRE 10 OR 4 WIRE 30
SPECIAL PURPOSE OUTLET
(SUFFIX INDICATES AMPS)
J
g SECURITY JUNCTION BOX
SATELLITE
TV OUTLET SRA RADIO
ANTENNA
CONDUIT
PA SECURITY KEY PAD
THRU WALL
MOKE DETECTOR
p PHOTOELECTRIC)
WIRELESS
, TELEPHONE WAP ACCESS
OUTLET POINT
on CM CARBON MONOCIDE
PUBLIC DDRESSANTERCO
EMERGENCY
HCALL/PUSH BUTTON
O SPEAKER (CEILING MOUNT)
°
SUFFIX
(INTEGRATED TO SECURITY SYSTEM)
INDICATES
MICROPHONE OUTLET
(MICROPHONE SYSTEM)
O PUBLIC ADDRESS/INTERCOM
� SPEAKER (WALL MOUNT)
°._SUFFIX
°� SUFFIX
INDICATES
INPUT+OUTPUT
INDICATES
CAM SECURITY CAMERA
SECURITY MOTION SENSOR
[ij THERMOSTAT
POS POINT OF SERVICE
10 BASE T WIRING
a SPEAKERWIRE POINT AT
CEILIN1OB
VC CONTROL SPEAKER VOLUMN
® RESTROOM A/C SUPPLY
® RESTROOM EXHAUST FAN
AIR DIFFUSER
t
GUEST HOUSE ELECTRICAL PLAN
SCALE 1/4 INCH
ADVANCE
DESK-!V &
BUILDING
ARCHITECTS
GENERAL
CONTRACTORS
A ROUND HILL DEVELOPMENT GROUP COMPANY
17968 115 TH AVE. NORTH
JUPITER, FLORIDA 33478
PH: 561-216-1000
CELL 561-718-0831
319 167TH ST
NO. MIAMI BEACH, FL, 33162
305-454-8000
WWW. AD VAN CED-DESIGN-BUI LD I NG. COM
THESE DRAVANGS AND SPECIFICATIONS ARE
INSTRUMENTS OF SERVICE AND ARE THE PROPERTY OF
ROUND HILL DEVELOPMENT GROUP, INC./ Wa ADVANCED
DESIGN h BUILDING. THEY ARE NOT TO BE USED ON
ANY OTHER PROJECTS OR DM34SONS OF THIS PROJECT
EXCEPT BY WRITTEN AGREEMENTS NTH ROUND HILL
DEVELOPMENT GROUP.
NO DESIGN CHANGES WHICH ALTER THE INTENT
OF THESE DRAWINGS OR SPECFICATONS ARE TO BE MADE
WITHOUT OBTAINING WRTIFN PERMISSION FROM
ROUND HILL DEVELOPMENT GROUP.
ARCHITECT: BERNARD
JONES
ARCHITECT
SEAL:
DATE:
CLIENT:
FORT PIERCE HOUSE
ADDRESS:
ELECTRICAL
PLAN
REVISIONS:
DRAWN BY: JMG
CHECKED BY: BVJ
PROJECT it.
SCALE: j INCH
E-2
PROJECT INFORMATION
WIND DESIGN DATA
JURISDICTION-- ST. LUCIE COUNTY, FLORIDA
CLASS. : RESIDENTIAL R-3
TYPE OF CONSTRUCTION --
RISK CATEGORY II — NEW CONSTRUCTION
FIRE SPRINKLER SYSTEM --NOT REQUIRED
FIRE ALARM --NOT REQUIRED
BUILDING CODE: 2017 FLORIDA BUILDING CODE
6TH EDITION, NEC 2014)
ASCE 7-10
EXPOSURE: C
BUILDING DESIGNED AS ENCLOSED
MEAN ROOF HEIGHT: 20.5 FT
IMPORTANCE FACTOR: 1.0
BASIC WIND VELOCITY: 170 MPH
ROOF MATERIAL: ROOFING PER PRODUCT
APPROVAL
5/8 INCH EXT.
PLYWOOD W/ 8D
RING SHANK
NAILS @ 4"
2 X -
EDGE/6" FIELD
STUDS
WITH METAL LATH
AND STUCCO
2X
BLOCK11'
AS
NEEDED
FOR
STORM
PANELS
2 X 12 BAND BOARD
SIMPSON SP1 TOP PLATE
STRAP W/ (6) 10 DS
SINGLE HUNG
WINDOW
OR DOOR
INSTALLED
PER
PRODUCT
APPROVAL
DOUBLE 2 X 6
HEADER
PER FRAMING PLAN
W/ 1 /2" PLYWOOD
SANDWICHED —
SIMPSON SP2 TOP PLATE
STRAP W/ (6) 10 DS
SIMPSON MSTA 18 14-10DS (TYPICAL)
(2) 12D NAILS @
12"O.C.-TYPICAL AT
JACK STUDS
BOTH SIDES
SIMPSON MSTA 12 5 -IODS
HORIZONTAL AND
2 X PT. BOTTOM PLATE
SIMPSON SP1 TOP PLATE l
STRAP W/ (6) 10 DS
.SIMPSON MSTA 18 14 -10DS
AT 16" OC. EACH STUD
2 X 12 BAND BOARD
ROOF DEAD LOAD: 25 PSF
ROOF LIVE LOAD: 30 PSF
FLOOR DEAD LOAD 30 PSF
FLOOR LIVE LOAD 40 PSF
SOIL BEARING CAPACITY: 2500 PSF ASSUMED
REVIEWED FOR SHEAR WALL REQUIREMENTS YES
IMPACT PROTECTION: NOT APPLICABLE
INTERNAL COEFFIECIENT: 0.18
DESIGN PRESSURES FOR OPENINGS (IN PSF):
WITHIN 3FT FROM CORNERS: SEE ELEVATIONS
GREATER THAN 3 FT FROM CORNERS: SEE ELEVS.
GARAGE DOOR:
INSULATION: FLOORS: R-13
WALLS CBS: R-4.1 FOIL
WALLS WOOD: N/A
ROOF: R30 MIN
ROOF NAILING PATTERN: 10 D RING SHANK NAILS
AT 4" EDGE AND FIELD
ROOF SHEATHING: 5/8" EXTERIOR GRADE PLYWJOD
5/8 INCH EXT.
PLYWOOD W/ 8D
NAILS @ 4" 2 X 4 —
EDGE/6" FIELD STUDS
WITH METAL LATH S
at AND STUC16"O.C.
CO
2 X 12 BAND BOARD
SIMPSON SP1 TOP PLATE
STRAP W/ (6) 10 DS
MINIMUM R-11 BATT
INSULATION ALL EXTERIOR
WALLS W/ 1/2 DRWALL
INTERIOR
SIMPSON SP2 TOP PLATE
STRAP W/ (6) 10 DS
SIMPSON MSTA 18
14--10DS (TYPICAL
II
SIMPSON SP1 TOP PLATE
STRAP W/ (6) 10 )S
-SIMPSON MSTA 198 14 -10DS
AT 32" OC. TO
2 X 12 BAND BOARD
ULTIMATE
WIND SPEED:
170
MPH
NOMINAL
(BASIC) WIND SPEED:
132
MPH
RISK CATAGORY:
WIND EXPOSURE:
ENCLOSURE CLASSIFICATION:
INTERNAL PRESSURE COEFFICIENT:
COMPONENTS AND CLADDING:
10
ENCLOSED
0.18+ /_
ROOFING ZONE 1: +23.3 PSF MAX.,
ROOFING ZONE 2
ROOFING ZONE 3:
+23.3 PSF MAX.,
+23.3 PSF MAX.,
ROOFING
AT
ZONE
2
OVERHANGS:
ROOFING
AT
ZONE
3
OVERHANGS:
STUCCO, CLADDING, DOORS AND WINDOWS:
ZONE 4: +40.3 PSF MAX.,
ZONE 5: +40.3 PSF MAX.,
END ZONE WIDTH: 3 FT
O/H GARAGE DOORS:
—37.0 PSF MIN.
—64.4 PSF MIN.
—95.2 PSF MIN.
—75.1 PSF MIN.
—126.4 PSF MIN.
—43.7 PSF MIN
—54.0 PSF MIN
+38.3 — 45.6
THE NOMINAL WIND SPEED WAS USED TO DETERMINE THESE
COMPONENT AND CLADDING PRESSURES.
ALL EXTERIOR GLAZED OPENINGS SHALL BE PROTECTED FROM
IND BORNE DEBRIS AS PER SECTION 1609.1.2 FBC (INCLUDING
ISTING TO BE COVERED BY PANELS PER PRODUCT APPROVAL)
TH$
SITE OF THIS
BUILDING IS
NOT SUBJECT
TO TOPOGRAPHICAL
WIND
EFFECTS AS
PER SECTION
1609.1.1.1 OF
THE 2014 FBC.
CO PONENT AND CLADDING DESIGN PRESSURES:
TH5 EXTERIOR SHELL OF THIS BUILDINGS ENVELOPE IS DIVIDED INTO
5 IFFERENT ZONES AS SHOWN IN THIS DIAGRAM:
Alm
I
® I
I O
I
\ I
ADVANCED
DESIGN
ARCHITECTS
GENERAL
CONTRACTORS
A ROUND HILL DEVELOPMENT GROUP COMPANY
515 NO. FLAGLER DRIVE, SUITE P-300
WEST PALM BEACH, FL 33401
PH: 561-216-1000 CELL 561-718-0831
319 NE 167TH ST.
N. MIAMI BEACH, FL, 33162
FAX: 305-454-8600
WWW. AD VAN CED-DESIGN-B U I LDI N G. COM
ARCHITECT:BERNARD JONES
ARCHITECT
AR0015193
SEAL:,,, ryAib dg
Mom_ .z
SIGNATURE:'
DATE: t , .:...;+,1. _. / ......... _.
CLIENT:
VEGA
HOMES
ADDRESS:
FORT PIERCE
DETA L
REVISIONS:
DRAWN BY: BVJ
CHECKED BY: BVJ
PROJECT #:
DATE:
D-1
TYPICAL WINDOW REIFORCING I TYPICAL EXTERIOR FRAME WALL
/ram ��r, �r+r• „�r..,, „ • r,\
JURISDICTION-- PALM BEACH COUNTY, FL
OCCUPANCY CLASS-- RESIDENTIAL R-3
TYPE OF CONSTRUCTION --V
FIRE SPRINKLER SYSTEM --NOT REQUIRED
FIRE ALARM --NOT REQUIRED
BUILDING CODE: 2017 FLORIDA BUILDING CODE
ASCE 7-10, NEC 2014
EXPOSURE: C
AS ENCLOSED
19 FT
is 1.0
WIND VELOCITY: Vult=175 Vasd=135
•qh=56.57 psf
Kh=.85
Kzt=1.0
Gcpi=.18+/—
GCpf=1.0+, 1.4—
P=0.6w
ROOF MATERIAL: 5V METAL ROOF PER PRODUCT APPROVAL
ROOF •DLOAD:
ROOF LIVE LOAD
SOIL BEARING■ •• PREVIEWED SF SHEAR WALL REQUIREMENTS
APPROVAL
WINDOWS AND D•O-
INTERNAL COEFFIECIENT: 0.18
RISK CATAGORY : II
END ZONE WIDTH FOR 30FT L BUILDING: 3 FT
COMPONENTS AND CLADDING DESIGN WIND PRESSURES
WALL
ROOF
ZONE Leeward/Windward
Leeward/Windward
TRIBUT.AREA
10sf
1
—36.7 +23.1
ROOF
PERIMETER
2
—63.8 +23.1
ROOF
CORNER
3
—63.8 +23.1
WALL
INFIELD
4 —43.4 +40.1
WALL
CORNER
5 —53.6 +40.1
DESIGN PRESSURES FOR OPENINGS (IN PSF):
WITHIN 3FT FROM CORNERS --SEE ELEVEATIONS
GREATER THAN 3 FT FROM CORNERS: SEE ELEVS.
GARAGE DOOR NOT APPLICABLE
INSULATION: FLOOR NOT APPLICABLE
WALLS R 4.1 MIN OR
WALLS R13 0 6" FRAME EXTERIOR
ROOF R 30 MIN
ROOF NAILING PATTERN
IF REQUIRED
1. 1C D RING SHANK NAILS
AT 4" EDGE AND 6" FIELD
WALL SHEATHING :
1l"EXTERIOR GRADE PLYWOOD W/ BD RING
SHANK NAILS 0 4" O.C. AND 6" FIELD
WINDOW AND
DOOR SCHEDULE
-NOMINAL
SIZE
N0.
WIDTH X
HT.
TYPE
REMARKS
�1
36" WIDE
X
96"
HIGH
PANEL DOOR
IMPACT
W CATEGORY II SAFETY
GLASS
PER FBC 4 4410.2.3.1.3
0
26" WIDE
X
63"
HIGH
ALUM. SINGLE HUNG
IMPACT
W CATEGORY II SAFETY
GLASS
PER FBC 4 4410.2.3.1.3
[96" WIDE
X
72"
HIGH
ALUM. SINGLE HUNG
IMPACT
W CATEGORY II SAFETY
GLASS
PER FBC 4 4410.2.3.1.3
CONTRACTOR TO VERIFY ROLM OPENING DIMENSIONS FOR DOORS AND WINDOWS ORDERED PRIOR TO CONSTRUCTION
ALL DOORS AND VANDOWS TO BE LOW E-0 4r7,-4VD IMP4V
ADVANCED
DESIGN 8
BUILDING
ARCHITECTS
GENERAL
CONTRACTORS
23 -4 15 -4
"
A ROUND HILL DEVELOPMENT GROUP COMPANY
17968 115 TH AVE. NORTH
JUPITER, FLORIDA 33478
PH: 561-216-1000
O
CELL60631
167TH S 19
NO. MIAMI BEACH, FL, 33162
305-454-8000
WWW.ADVANCED-DESIGN-BU ILDIN G.COM
TWX DRAWINGS AND SPECFlCATIONS ARE
I SIRUMIXR OF S ERMCE AND ARE IRE PROPERTY OF
LD
110 5'-0" 12'-0"
ROUND HILL DEVELOPMENT GROUP. INC./ dito ADVANCED
OESION a SURONO THEY ARE NOT TO DE USED ON
FROECT
r �'
WITHI�,D HLL
DEVELOPMENT OR".
NO DEMON CHAN= W#CH ALTER THE INTENT
2•-8�x8—
UTILITY
It
OF THESE DRAWINGS OR SPEM"TIONS ARE 10 BE MADE
WTHOUT OBTNNNO WRITTEN PERMISSION FROM
ROOM
�j O
ROUND HLLL DEVELOPMENT OR".
BEDROOM -I
I
I
-
.'
O
-
V�V�J��
ARCHITECT: BERNARD
C)y taq o
of
JONES
00
ARCHITECT
5'-0"
- -----
10L
0 8'-0"
SEAL*
CLOSET BATH 0
ol
DATE:
00
FRONT
PROCH O
(z IA 2'
0
ado ;n
d-
Qbc>r CLOSET o 0
m
O
AIM I
ol
R
CLIENT:
N
0 FORT PIERCE HOUSE
o
JOXtox LD )�
co
I
OFFICE b
KITCHEN BEDROOM
o
'-0
9'-0"
�-
10'-0" 14'-0"
®
o 0
®el
ADDRESS:
O �j
O
N
1
3'-8"
15'-4"
GUEST HOUSE
SCALE: ''4INCH FLOOR PLAN
REVISIONS:
DRAWN BY: JMG
CHECKED BY: BVJ
PROJECT f:
SCALE: } INCH
A-2