Loading...
HomeMy WebLinkAboutEVALUATION REPORTMEMO I etc. SCANNED Certificate of Authorization #32455 BY 353 Christian Street, Unit #13 ISO St. Lucie County Oxford, CT 06478 (203) 262-9245 i, ENGINEER EVALUATE TEST CONSULT CERTIFY EVALUATION REPORT Polyglass USA, Inc. RECEIVEDEvaluation Report P12060.02.09-R24 1111 West Newport Center Drive FL5259-R28 Deerfield Beach, FL 33442 JUN 2 2 2Q18 Date of Issuance: 02/24/2009 (951 4) 233-1230 Revision 24: 01/24/2018 SCOPE: ST. Lucie County,,.P2rTiltCing. This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of co InIstruction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. fo I use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6` Edition (2017) Florida Buildin Code sections noted herein. Pal —as—sl RT67fi 119n erla menu LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. C61NTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMOietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOietc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. IN Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. TI)is Evaluation Report consists of pages 1 through 14. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 CONCEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE THE OR RECORD . The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 01/24/2018. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1!: NEMO i etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or I, distributing products it evaluates. 21 NEMO i etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. K Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 41i Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5i; This is a building code evaluation. Neither NEMO ietc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was usq&r permitti o esign guidance unless retained � specifically for that purpose. (�) ` 1-0�f ST. LUCIE COUNTY BUILDING D1I)',ISION REVIEWED FOR COMPLIANCE.r . , , to REVIEWE BY rHESE PLANS AND ALL PROPOSED WO DATE I (JJ %RE SUBJECT ANY CORRECTIONS PLANSANDPERMIT MUST BE KEP O U)COPYN 708 ELD INSPECTORS THATFILE SIT E OR NO INSPECTION S VIAY BE NECESSARY IN ORDER TO - OWILL BE MADE ;OMPLY WITH ALL APPLICABLE CODES. i I' OMEMO etc. ROOFING COMPONENT EVALUATION: 1.1 SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6` E Rion 2017 F on a Bui din Co a through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2.. STANDARDS: Section Property Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1507.2.3 / 1507.1.1 Physical Properties ASTM D226 2009 1507.2.4 / 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Enti Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST 5878) Physical Properties PRIO1111 04/08/2002 PRI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-088-02-01 07/29/2009 MTI (TST 2508) Physical Properties JX20H7A 04/01/2008 MTI (TST 2508) Physical Properties RX14E8A 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift P1740.01.07 01/04/2007 ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (TST 6049) Physical Properties P13450.08.09 08/13/2009 ERD (TST 6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD (TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-3 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 MEMO ETC, I.I.C.Evaluation Report P12060.02.09-R24 Certificate of Authofization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 i Page 2 of 14 ONEMOletc. Entity Examination Reference Date ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049). Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD (TST 6049) Wind Uplift P39680.03.13 03/04/2013 ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD (TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD (TST 6049) Wind Uplift 11757.04.01-1-Ri 04/30/2013 ERD (TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013 ERD (TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013 ERD (TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-4 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-6 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (TST 6049) 'Physical Properties P43290.10.14 10/17/2014 ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.04.15 04/03/2015 ERD (TST 6049) Physical Properties P44360.10.14-R1 05/18/2015 ERD (TST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015 ERD (TST 6049) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016 ERD (TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD (TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016 ERD (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 ii ERD (TST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017 ICC-ES (EVL 2396) IBC Compliance ESR-1697 11/01/2014 Miami -Dade (CER 1592) HVHZ Compliance NOA 14-0717.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/L Affidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, LLC. (QUA9625) Quality Control Service Confirmation Exp. 10/,05/2018 4. PRODUCT DESCRIPTION: 4.1 Mechanically fastened Underlayments 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. 41 Self-Adhering'Underlaymentsc 4.2.1 Polystick MTS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/TRI April 2012. 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with -an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. i NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 3 of 14 ONEMOletc. 4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. > 4.2.5 Pol stick TU Max is a nomina 60-milt ick rub erize as ha t water roo an membrane wit a 190 /rna o ester a rI. su ace; meets ASTM D1 70 and FR-Y RI A ri 2012. 4.2.6 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester reinforced, APP'modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Prom is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970. 4.2.8 Polystick Tile Pro"' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3 Mechanically. .Fastened and/or Bonded 'Underlayments: 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen the underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 G and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 5.1 LIMITATIONS: 5.1 This is a building code evaluation. Neither NEM01etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the productis specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization #32455 6T"EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 4 of 14 ONEMOjetc. 5.5 Allowable Roof Covers: TABLE ;1: ; ROOF„COVER OPTIONS _ Underiayment Asphalt Shingles Nail -On Tile Foam -On Tile Metal Wood Shakes & Shingles Slate Elastobase Yes Yes (Base Sheet in 2-ply system) Yes (Base Sheet in 2-ply system) Yes Yes Yes Elastobase P Yes Yes (Base Sheet in 2-ply system) Yes (Base Sheet in 2-ply system) Yes Yes Yes Polyglass G2 Base No Yes (Base Sheet in 2-ply system) Yes (Base Sheet in 2-ply system) No No No Polyglass APP Base No Yes (Base Sheet In 2-ply system) Yes (Base Sheet in 2-ply system) No No No Polystick MTS or MTS PLUS Yes Yes No Yes Yes Yes Polystick IR-Xe Yes No No No Yes Yes Polystick TU P No Yes Yes (See 5.5.1) No No No Polystick TU Plus Yes Yes Yes (See 5.5.1) Yes Yes Yes P,o ystc IU Max No es Yes (See 5.5.1) Yes No No Polystick Dual Pro Yes No No Yes Yes Yes Polystick Tile Pro Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick MU-X Yes No No Yes Yes Yes Elastoflex S6 G Yes Yes Yes (See 5.5.1) No Yes Yes Elastoflex S6 G FR Yes Yes No No Yes Yes Elastoflex G TU Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G FR Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 5.5.1) No Yes Yes Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Yes Yes Yes (See 5.5.1) No Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved the adhesives / underlayment combinations. TABLEIA: ALLOWABLE TILE ADHESIVE �'UNDERLAYMENT CONIBINATIONSl. Adhesive Florida Product Underlayments Approval DAP Foam Touch `n Seal Storm Bond Roof Tile Adhesive FL14506 Polystick TU Plus, Polystick TU Max Dow TileBondTM FL22525 Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® AH-160 FL6332 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® RTA-1 FL6276 Elastoflex G TU, Elastoflex S6 G. Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) I I Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization k32455 6' EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 5 of 14 5.6 -> 5.6.1 I 5.6.2 5.6.3 ONEMOletc. Allowable Substrates: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. Bond -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. i' NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization #32455 6i" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 �, Page 6 of 14 f ONEMOjetc 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. => 5.7 [Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. -� Po . sttc M , M S PLUS, TU P, TU P us, TU Max, Dua Pro, Ti 2 Pro or E asto ex G TU s a not e e ex ose or Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. 1ABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRECT -DECK TILE INSTALLATIONS . Underlayment Tile Profile Staging Method Maximum Slope Elastoflex G TU Flat 10-tile stack 7:12 Lugged 8-tile stack (6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Polystick TU Max Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged 6-tile stack (4 over 2) 7:12 Lu a 0-ti a star 612 Polystick TU P Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 Flat or Lugged 10-tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged I6-tile stack (4 over 2) 4:12 NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-1128 I Polyglass Roof Underlayments; (9S4) 233-1230 Revision 24: 01/24/2018 Page 11 of 14 ONEMOletc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). -6.3 Elastobase, Elastobase.P or Mule. Hde,NaiF!Base: . 6.3.1 Non -Tile Applications: Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April 2012 (04-12) Installation Manual. 6 4 Po stie TS, MTS' PLUS, IR=Xe, TU P, TU Plus Max Dual Pro, Tile Pro or MU-X or Polyflex SAP, Polyflex SAPTR, ide SA-AP.P Cap Sheet.or Mule Hide`5A-AP ap Sheet (FR). 6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.4.2 Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) s ould be ackTn7ai lUdIffin selva a ed a seam in accordance wit Po ass Mu e- Hi a ack nai in ul a fines. Nai s s a e corrosion resistant, 11 au a rin -s an a wit a minimum 1-inc iameter meta is or Simp ex- a meta ca nai , at a minimum rate o Ego" Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal -lap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand roller to ensure full contact and adhesion. , For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). , View of Ovelap Seam of Dual Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 12 of 14 li I. IRNEMOjetc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications (not allowed for Polystick Dual Pro, IR Xe or Polystick MU X): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section 5.6.4 herein. 6.4.4 Two (2) Ply Underlayment Systems: Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P. TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Elastoflex G'tU, Elastoflex S6 G or Elastoflex S6 G FR: 6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile i roof systems. I' 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-inch beyond the lap edge. [.6.6 . Polyflex G or Polyflez G FR 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization A32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underla yg yments; (954) 233-1230 Revision 24: 01/24/2018 Page 13 of 14 NNEMOjetc. 6.6.2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. I, 6_7 Tile Staging: 6.7.1 Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment. Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 .(04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail - boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. S. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements. The following plants have qualified products under their respective physical properties specifications. 9' Plant ;,r Specifics#ionProduct s Fernley, NV, Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick MU-X Hazleton, PA M-D 13-0004 Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASTM D1970 & FRSA/TRI April 2012 Polystick TU Plus ASTM D1970 & FRSA/TRI April 2012 Polystick TU Max Tuscaloosa, AL ASTM D4601, Type II Polyglass G2 Base Winter Haven, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM D6509 Polyglass APP Base FRSA/TRI April 2012 Polystick MTS, Polystick MTS PLUS FRSA/TRI April 2012 Polystick TU P FRSA/TRI April 2012 Polyflex SAP, Polyflex SA P FR ASTM D1970 Polystick Dual Pro ASTM D1970 & FRSA/TRI April 2012 Polystick Tile Pro ASTM D6164 Elastoflex S6, Elastoflex S6 G FR ASTM D6222 I Polyflex G, Polyflex G FR QUALITY ASSURANCE ENTITY: UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com NEMO ETC, U.C. Certii icote of Authorization #32455 - END OF EVALUATION REPORT - 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Polyglass Roof Underlayments; (954) 233-1230 Evaluation Report P12060.02.09-R24 FL5259-R28 Revision 24: 01/24/2018 Page 14 of 14