St. Lucie Cc FLOR`DA ENERGY I M_ IENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: WYNNE THE GRAND CARLTON
Builder Name: WYNNE BUILDING COPR.
Street: 11 �51p 24p V
Permit Office: ST. LUCIE COUNTY
City, State;IZip: FT. PIERCE, FL,
Permit Number:
Owner: WYNNE BUILDING CROP
Jurisdiction: ST. LUCIE COUNTY
I
Design Location: FL, Fort Pierce
County:: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
9. Wall Types (1442.0 sqft.)
Insulation Area
2. Single family or multiple family Single-family
a. Concrete Block - Ext Insul, Exterior
R=4.1 1250.00 ft2
11
b. Frame - Wood, Adjacent
R=11.0 192.00 ft2
3. Number if units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 2
d. N/A
R= ft2
worst
10. Ceiling Types (1446.0 sqft.)
Insulation Area
5. Is this a case? Yes
11
a. Under Attic (Vented)
R=30.0 1446.00 ft2
6. Conditioned floor area above grade (ft2) 1446
b. N/A
R= ft2
Condition) d floor area below grade (ft2) 0
c. N/A
11. Ducts
R= ft2
R ft2
7. Windows(141.3 sqft.) Description Area
a. Sup: Attic, Ret: Attic, AH: Attic
6 250
a. U-Factor: Sgl, U=0.36 101.25 ft2
SHGC.. SHGC=0.25
b. U-Factor: Sgl, U=0.65 40.00 ft2
12. Cooling systems
kBtu/hr Efficiency
SHGC;: SHGC=0.21
a. Central Unit
34.8 SEER:15.00
c. U-Factor: N/A ft2
SHGC:
13. Heating systems
kBtu/hr Efficiency
d. U-Factor: N/A ft2
a. Electric Heat Pump
34.8 HSPF:8.50
SHGC:
Area Weighted Average Overhang Depth: 3.832 ft.
Area Weighted Average SHGC: 0.239
14. Hot water systems
a. Electric
Cap: 40 gallons
8. Floor Types (1445.5 sqft.) Insulation Area
i
EF: 0.970
a. Slab -On -Grade Edge Insulation R=0.0 1445.50 ft2
b. Conservation features
b. N/A R= ft2
None
c. N/A R= ft2
15. Credits
Pstat
it Total Proposed Modified Loads: 47.17
Glass/Floor Area: 0.098
PASS
Total Baseline Loads: 48.08
u
I hereby certify that the plans and specifications covered by
Review of the plans and
tHE S�,q?�
this calculation are in compliance with the Florida Energy
specifications covered by this
O�
Code. II
calculation indicates compliance
VO
zl:'•`';
with the Florida Energy Code.
PREPARED BY:
DATE:
Before construction is completed
this building will be inspected for
compliance with Section 553.908
r
a
* "'
jl
I hereby certify that this building, as designed, is in compliance
Florida Statutes.
CDD
with the Fllorida Energy Code.
yyE
OWNEWAG T' ► -
BUILDING OFFICIAL:
DATE:
DATE:
- Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope! leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
Ij
I�
I�
4/17/2018 3:41 PM
l
I
EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software
Page 1 of 5
FORM R40542017
PROJECT
Title: WYNNE THE GRAND CARL
Bedrooms: 2
Address Type:
Street Address
Building Type: User
Conditioned Area: 1446
Lot #
Owner Name: WYNNE BUILDING CROP
Total Stories: 1
Block/Subdivision:
# of Units: I 1
Worst Case: Yes
PlatBook:
Builder Name: WYNNE BUILDING COPR.
Rotate Angle: 180
Street:
Permit Office: ST. LUCIE COUNTY
Cross Ventilation: No
County:
St. Lucie
Jurisdictiori: ST. LUCIE COUNTY
Whole House Fan: No
City, State, Zip:
FT. PIERCE,
Family Type: Single-family
FL,
New/Existing: New (From Plans)
Comment:''
CLIMATE
Design Temp
Int Design Temp Heating
Design Daily Temp
V Design Location TMY Site 97.5 %
2.5 %
Winter
Summer Degree Days Moisture
Range
I FL, Fort Pierce FL VERO_BEACH_MUNI 39
90
70
75 299
62
Low
BLOCKS
Number) Name Area Volume
1 Entire House 1446 11568
SPACES
Number l Name Area
Volume Kitchen Occupants
Bedrooms
Infil ID Finished Cooled
Heated
,j
1 BEDROOM 301
2408 No
0
1
1 Yes
Yes
Yes
2 WIC 63
504 No
0
1 No
Yes
Yes
3 M.BATH 56
448 No
0
1 Yes
Yes
Yes
4 KITCHEN 192
1536 Yes
0
1 No
Yes
Yes
5 BATH 45
360 No
0
1 Yes
Yes
Yes
I
6 BEDROOM 2 204
1632 No
0
1
1 Yes
Yes
Yes
7 ENTRY 55
440 No
0
1 Yes
Yes
Yes
8 LAUNDRY 42
336 No
0
1 Yes
Yes
Yes
9 GREAT/DINING 488
3904 No
0
1 Yes
Yes
Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood
Carpet
11 Slab -On -Grade Edge Insulatio
BEDROOM 52 ft 0
301 ft2
_---
0 1
0
2 Slab -On -Grade Edge Insulatio
I'
WIC 1 ft 0
63 ft2
____
0 1
0
3 Slab -On -Grade Edge Insulatio
M. BATH 8 ft 0
56 ft2
____
0 1
0
,4 Slab -On -Grade Edge Insulatio
KITCHEN 1 ft 0
192 ft2
____
0 1
0
5 Slab -On -Grade Edge Insulatio
BATH 5 ft 0
45 ft2
____
0 1
0
1 6 Slab -On -Grade Edge Insulatio BEDROOM 2 32.2 ft 0
203.5 ft2
____
0 1
0
7 Slab -On -Grade Edge Insulatio
I
ENTRY 7 ft 0
55 ft2
--__
0 1
0
4/17/2018 3:41 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5
FC)P%A Rdn-r;117n17
ii
FLOORS
#� Floor Type Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile
Wood Carpet
81SIab-On-Grade Edge Insulatio LAUNDRY 6 ft
0
42 ft2
---_
0
1
0
9�Slab-On-Grade Edge Insulatio GREAT/DINING 46 ft 0
488 ft2
-__-
0
1
0
i�
ROOF
/ II Roof
Gable
Roof
Solar SA
Emitt
Emitt
Deck
Pitch
# Type Materials Area
Area
Color
Absor. Tested
Tested
Insul.
(deg)
1. Gable or Shed Metal 1524 ft2
i
240 ft2
Light
0.6
No
0.9
No
0
18.4
ATTIC
V #
Type Ventilation
Vent Ratio (1 in)
Area
RBS
IRCC
1 Full attic Vented
150
1446 ft2
N
N
1
�i
CEILING
# Ceiling Type Space
R-Value
Ins Type
Area
Framing Frac Truss Type
Under Attic (Vented) BEDROOM
30
Blown
301 ft2
0.1
Wood
2 Under Attic (Vented) WIC
30
Blown
63 ft2
0.1
Wood
3 Under Attic (Vented) M. BATH
30
Blown
56 ft2
0.1
Wood
4 Under Attic (Vented) KITCHEN
30
Blown
192 ft2
0.1
Wood
5 Under Attic (Vented) BATH
30
Blown
45 ft2
0.1
Wood
16 Under Attic (Vented) BEDROOM 2
30
Blown
204 ft2
0.1
Wood
7 'Under Attic (Vented) ENTRY
30
Blown
55 ft2
0.1
Wood
18 Under Attic (Vented) LAUNDRY
30
Blown
42 ft2
0.1
Wood
'I9 Under Attic (Vented) GREAT/DINING
; f
30
Blown
488 ft2
0.1
Wood
WALLS
Adjacent Cavity Width
Height
Sheathing Framing
Solar
Below
Space
_
_
1 NE -SW Exterior Concrete Block - Ext InsiHEDROOM
4.1 10
0 8
0
80.0 ft2
0
0
0.6
0
2 SW=>NE Exterior Concrete Block - Ext InsiflEDROOM
4.1 28
0 8
0
224.0 ft2
0
0
0.6
0
_ 3 NW=>SE Exterior Concrete Block - Ext InsiflEDROOM
4.1 14
0 8
0
112.0 ft2
0
0
0.6
0
4 SW=>NE Exterior Concrete Block - Ext InsuM. BATH
4.1 8
0 8
0
64.0 ft2
0
0
0.6
0
5 NE=>SW Exterior Concrete Block - Ext Insul BATH
4.1 5
0 8
0
40.0 ft2
0
0
0.6
0
6 NE=>SW Exterior Concrete Block - Ext InEEDROOM 2
4.1 16
0 8
0
128.0 ft2
0
0
0.6
0
li
7 SE=>NW Exterior Concrete Block - Ext ImMDROOM 2
li
4.1 10
0 8
0
80.0 ft2
0
0
0.6
0
8 S=>N Exterior Concrete Block - Ext In&EDROOM 2
4.1 4
3 8
0
34.0 ft2
0
0
0.6
0
I I
9 SW=>NE Exterior Concrete Block - Ext InQEDROOM 2
l
4.1 2
0 8
0
16.0 ft2
0
0
0.6
0
10 SE=>NW Exterior Concrete Block - Ext Insul ENTRY
4.1 6
0 8
0
48.0 ft2
0
0
0.6
0
_ 11 SW=>NE Exterior Concrete Block - Ext Insul ENTRY
li
4.1 1
0 8
0
8.0 ft2
0
0
0.6
0
12 S IW=>NE Exterior Concrete Block - Ext Insd1AUNDRY
4.1 6
0 8
0
48.0 ft2
0
0
0.6
0
13 NE=>SW Exterior Concrete Block - Ext InsGREAT/DINT
4.1 26
0 8
0
208.0 ft2
0
0
0.6
0
14 NW=>SE Exterior Concrete Block - Ext InsGiREAT/DINI
4.1 20
0 8
0
160.0 ft2
0
0
0.6
0
15 N=>S Garage Frame - Wood KITCHEN
11 24
8
192.0 ft2
0.23
0.6
0
I
4/17/2018 3:41 PM
EnergyGaugeO USA - FlaRes2017 Section R405.4.1 Compliant Software
Page 3 of 5
F(1RAA RAn.p6n17
1
DOORS
#'I Ornt ,
Door Type Space
Storms U-Value Width
Ft In
Height
Ft In
Area
1 SE=>NW
Insulated ENTRY
None .39 3 1
6 8
20.6 ft2
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
/ Wall
v # ,I Ornt ID Frame
Panes NFRC
Overhang
U-Factor SHGC Imp Area Depth Separation Int Shade
Screening
1 NW=>SE 3 Metal
2 !SW=>NE 4 Metal
3 SSE=>NW 7 Metal
4 !NE=>SW13 Metal
5 INW=>SE14 Metal
Low-E Single Yes
Low-E Single Yes
Low-E Single Yes
Low-E Single Yes
Low-E Single Yes
0.36 0.25 N 32.9 ft2 1 ft 0 in 1 ft4 in
0.36 0.25 N 6.9 ft2 1 ft 0 in 1 ft4 in
0.36 0.25 N 24.0 ft2 6 ft 0 in 1 ft4 in
0.36 0.25 N 37.5 ft2 1 ft 0 in 1 ft4 in
0.65 0.21 N 40.0 ft2 8 ft 0 in 1 ft 4 in
Drapes/blinds
None
None
None
Drapes/blinds
Exterior 5
None
None
None
Exterior 5
1
GARAGE
# Floor Area
Ceiling Area
Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 315ft2
315ft2
24ft 8ft
11
INFILTRATION
# Scope Method
SLA
CFM 50 ELA EgLA ACH ACH 50
1 Wholehi use Proposed ACH(50) .000356
1349.6 74.09 139.34 .2598
7
I
HEATING SYSTEM
# System Type
Subtype
Efficiency Capacity
Block
Ducts
1 Electric Heat Pump/ Split
HSPF:8.5 34.8 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type
Subtype
Efficiency Capacity Air Flow
SHR Block
Ducts
11 Central Unit/
Split
SEER: 15 34.8 kBtu/hr cfm
0.8 1
sys#1
HOT WATER SYSTEM
1# System Type
SubType Location
EF Cap Use SetPnt
Conservation
1 Electric
None Garage
0.97 40 gal 60.9 gal 120 deg
None
1
SOLAR HOT WATER SYSTEM
FSEC
�Cert # Company Name
Collector
System Model # Collector Model # Area
Storage
Volume FEF
None None
ft2
,I
4/17/20118 3:41 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5
FORM R405L2017
DUCTS
-- Supply =---
- -- Return ----
Air
CFM 25
CFM25
HVAC #
#1 Location R-Value Area
Location
Area
Leakage
Type
Handler
TOT
OUT
QN
RLF
Heat Cool
1�
Attic
6 250 ftZ
Attic
65 ft2
Default Leakage
Attic
(Default) (Default)
1 1
i
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Coolin Jan
Heating Jan
Feb
XFeb
Mar
Mar
E
Apr
APr f
Ma
May
[X] Jun
]Jun
[X] Jul
j Jul
AuSep
rl Au
il Se
[ ]Oct
[ ]Oct
Nov
Xi Nov
[ ]Dec
H Dec
Ventin Jan
[ Feb
X Mar
[
A r [
Ma
E ]Jun
E j Jul
Aug
Se
[X] Oct
[X Nov
[ ]Dec
Thermostat Schedule:
HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5
6
7
8
9
10
11
12
Cooling (WD)
AM
78
78
78
78
78
78
78
78
80
80
80
80
PM
80
80
78
78
78
78
78
78
78
78
78
78
Cooling (WEH)
AM
78
78
78
78
78
78
78
78
78
78
78
78
PM
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WD)
AM
66
66
66
66
66
68
68
68
68
68
68
68
PM
68
68
68
68
68
68
68
68
68
68
66
66
1
Heating (WEH)
AM
66
66
66
66
66
68
68
68
68
68
68
68
I
PM
68
68
68
68
68
68
68
68
68
68
66
66
4/17/2018 3:41 PM
I
EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software
Page 5 of 5
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
l
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: WYNNE THE GRAND CARLTON Builder Name: WYNNE BUILDING COPR.
Street: it Permit Office: ST. LUCIE COUNTY
City, State, Zip: FT. PIERCE, FL, Permit Number:
Owner: WYNNE BUILDING CROP Jurisdiction: ST. LUCIE COUNTY
Design iLocation: FL, Fort Pierce
i
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General 'i
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and an gaps in the air barrier shall be sealed.
Y 9 P
shall be aligned with the air barrier.
i�
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity with
sealed.
a material having a thermal resistance of R-3 per inch
Knee walls shall be sealed.
minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows'skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl. spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
Bs.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
I�
shall be sealed to the drywall.
thermal envelope shall be airtight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
II
installation readily conforms to available space shall
extend behind p*peng and wiring,
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire -wriplilgr cover plates and walls or ceilings
a. In addition, inspection of log walls shall be m accordance with the provisions of ICC-400.
11
4/17/2018 3:41 PM EnergyGauge® USA - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
li
I
FORM R40,5-2017
ENERGY PERFORMANCE LEVEL (EPL)
�I
DISPLAY CARD
ij ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the EnergyPerformance Index, the more efficient the home.
FT. PIERCE, FL,
j
1. New construction or existing
New (From Plans) 9. Wall Types
Insulation
Area
2. Single family or multiple family
Single-family a. Concrete Block - Ext Insul, Exterior
R=4.1
1250.00 ft2
i
b. Frame - Wood, Adjacent
R=11.0
192.00 ft2
3. Number of units, if multiple family
11
1 c. N/A
R=
ft2
4. Number of Bedrooms
2 d. N/A
R=
ft2
.1
5. Is this a worst case?
10. Ceiling Types
Yes
Insulation
Area
a. Under Attic (Vented)
R=30.0
1446.00 ft2
6. Conditioned floor area (ft2)
1446 b. N/A
R=
ft2
7. Windows** Description
Area c.
R=
ft2
a. U-Factor: Sgl, U=0.36
11. Ducts
101.25 ft2 a. Sup: Attic, Ret: Attic, AH: Attic
R ft2
6 250
SHGC: SHGC=0.25
b. U-Factor: Sgl, U=0.65
40.00 ft2
SHGC; SHGC=0.21
12. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: N/A
ft2 a. Central Unit
34.8 SEER:15.00
SHGC:
d. U-Fadi r: N/A
ft2
SHGC;
13. Heating systems
kBtu/hr
Efficiency
Area Weighted Average Overhang Depth:
a. Electric Heat Pump
3.832 ft.
34.8
HSPF:8.50
Area Weighted Average SHGC:
0.239
8. Floor Types
Insulation Area 14. Hot water systems
Cap:
40 gallons
a. Slab -On -Grade Edge Insulation
a. Electric
R=0.0 1445.50 ft2EF:
0.97
b. N/A
R= ft2
c. N/A
R= ft2 b. Conservation features
None
15. Credits
Pstat
I
I certify that this home has complied with the Florida Energy Efficiency Code for Building ZgE Sp
Construction through the above energy saving features which will be installed (or exceeded) ��0� e AT�o
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: �- Date:
Ij
Address of New Home. QQS(p 3� City/FL Zip.
I
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Email EnergyGauge tech support at
techsupport@energygauge.com or see the EnergyGauge web site at energygauge.com for information and a list of
certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building
Commission's support staff.
:I
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
4/17/2018 3:41 PM EnergyGauge® USA - FlaRes2017 - Section R405.4.1 Compliant Software Page 1 of 1
I I
I
- - v►►,Aghtsoftw
317 ST. LUdlE LN., FT. PI
Project Summary ua e:
Entire House By:
QUICK CALCS, INC.
FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUI
i. For: THE GRAND CARLTON
WYNNE DEVELOPMENT, FT. PIERCE, FL
( 5o
Notes:
Desi n Information
Weather: Fort Pierce, FL, US
11
Winter Design Conditions
Outside db 42 OF
Inside db 70 OF
Design TD 28 OF
Heating Summary
Structure 17848 Btuh
Ducts 5654 Btuh
Central vent (0 cfm) 0 Btuh
none
Humidification 0 Btuh
Piping 0 Btuh
Equipment load 23503 Btuh
Infiltration
Method
Construction quality
Fireplaces
Area (ft2)
Volume (fta)
Air changes/hour
Equiv. AVF (cfm)
Simplified
Average
0
He 1446
Cool*
12511
12511
0.45
0.23
94
48
Heating Equipment Summary
'Make Carrier
Trade CARRIER AIR CONDITIONING
,Model 25HBC536A*030
'AHRI ref 7914585
i�Efficiency
Heating input
"Heating output
.iTemperature rise
Actual air flow
Air flow factor
iStatic pressure
(Space thermostat
I, Capacity balance point 32 OF
Backup:
Summer Design Conditions
Outside db
90
OF
Inside db
75
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
61
gr/lb
Sensible Cooling Equipment Load Sizing
Structure
17520
Btuh
Ducts
8536
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
n
Rate/swing multiplier
0.95
Equipment sensible load
24753
Btuh
Latent Cooling Equipment
Load Sizing
Structure
3203
Btuh
Ducts
2318
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Equipment latent load
5521
Btuh
Equipment total load
30274
Btuh
Req. total capacity at 0.70 SHR
2.9
ton
Cooling :Equipment
Summary
Make Carrier
Trade CARRIER AIR CONDITIONING
Cond 25HBC536A*030
Coil FX4DN(B,F)037
AHRI ref 7914585
8.5 HSPF
Efficiency
12.0 EER, 15 SEER
Sensible cooling
24360
Btuh
34600
Btuh @ 470F
Latent cooling
10440
Btuh
27
OF
Total cooling
34800
Btuh
1160
cfm
Actual air flow
1160
cfm
0.049
cfm/Btuh
Air flow factor
0.045
cfm/Btuh
0.50
in H2O
Static pressure
0.50
in H2O
Load sensible heat ratio
0.83
Input = 7 kW, Output = 23009 Btuh, 100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsoft, Right -Suite® Universal Page 1
2017 17.0.14 RSU08101 2017-Apr-11 09:29
ge 1
...uick Calcs\DocumentslTHE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N
- wq,9htsoft° Right-M Worksheet � Date:
Entire House Date:
By.
j QUICK CALCS, INC.
I
317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM
1
Room name
Entire House
BEDROOM
2
wall
156.2 ft
49.0 ft
3
red
red
8.7 ft d
8.0 ft heat/cool
4
Room dimensions
1.0 x 297.0 ft
5
Room area
1445.5 ft2
297.0 ftz
Ty I�
. Construction
U-value
Or
HTM
Area t2)
Load
Area t-)
Load
number
(Btutdit2L°F).
(Btuhlftz)
or perimeter (ft)
(Btuh)
or perimeter. (ft)
(Btuh)
Heat
Cool
Gross
WP/S
Heat
Cool
Gross
WP/S
Heat
Cool
I�
6
1M-4ocs.
' '
0143
0.770
n`
'4.00
21s56
2.55
'.
503
, : ;465
1862..
1184:
72
'
72
`.
289
,:::Q
183.
' '0
4A5-torn-
:ri ..
19.31
38
0
815
:: 730
. 0
0
13A-4ocs
0.143
a
4.00
2.55
128
83
333
212
0
0
0
0
I,
1Aclom
1.270
a
35.56
87.29
24
2
848
2082
0
0
0
0
11
11D0
6.390
a
10.92
11.31
21
21
229
238
0
0
0
0
W 1'
'13A4oc's . :..
a6143
^`se-
4:0Q.
'2i55
-. 34
34
136,,
86
'.. 0
- ,0
. 0
0.
W ��
�G
13A-4ocs
0143
s
4.00
2.55
366
353
1414
_
899
216
216
865
550
1A•clom
1270
s
35.56
34.77
7
7
247
241
0
0
0
0
1111
13A46cs
0149
w
4:00
2.55
310
.237
94.9
603:"-
104
72
288
183'
1A:c1om
4270
w,
35:56
55.21
32
2
1140
: 1770
32
` -..2
1140
1770'
'4A5 tom .
.0.770
.w
21.56
19:31
41
4.1
- 880
. 788
-' 0
. 0
.
P !�
12C-Osw
0.091
-
2.55
1.28
192
192
489
246
0
0
0
0
C
:16A30md
0:032
-
0.90
2.32
. 1446
1446
1295,
3354
297
297
266
689
F
i
I
I
I
22A-tpl
0.989
-
27.69
0.06
1446
156
4325
0
297
49
1357
0
6
it
c)AED eixursion
918
-627
4-lope loss/gain
14961
13349
4204
4003
12
a) Infiltration
2887
791
848
232
li) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
6
1380
3
690
Appliances/other
2000
0
Subtotal (Ines 6 to 13)
17848
17520
5053
4925
Less eMemal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
17848
17520
5053
4925
15
Duct loads
32%
49%
5654
8536
32%
49%
1661
2400
Total room load
23503
26056
1
6653
7326
Air required (cfm)
11601
1160
328
326
-- wrightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101
... uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces:
2017-Apr-11 09:29:38
Page 1
I
I ,
- wr',ghtsoft° Right-J® Worksheet
Ij Enfire House
QUICK CALCS, INC.
I
317 ST. LUCIE LN., FT. PIERCE, FL 34946-Phone: 772-466-6799 Fax 772-466-6796
Email: QUICKCALCS@AOL.COM
Job:
Date:
By:
1
Room name
WIC
KrrCHEN.
2
Exposed wall
O ft
Oft
3
Room height
8.0 ft heaUcool
8.0 ft heat/cool
4
. Rodin dimensions
6.0 x 9.0 ft
1.0 x 172.0 ft
5
Room. area
54.0 ftz
172.0 ft'
Ty II
Construction
U-value
Or
HTM
Area (ft')
Load
Area (ft-)
Load
II
number
(Btuh/f6°F)
(MU 2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
I Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat .
Cool
6
I�
.. ,
0
. , 0
:0
i,
.4A52oms .
;
0 0
.. n:
21:56
19:31
.: , . 0
0
0
.0
0
0
0
-: 0
vl�13AAocs
0.143
a
4.00
2.55
0
0
0
.0
0
0
0.
,
0
1Aclom
1.270
a
35.56
87.29
0
0
.0
0
0
0
0
0
-I
11
11DO
0.390
a
10.92
11.31
0
0
0
0
0
0
0
0
W', G.:.13A4ocs
6� 143
se .
:4:00
: " . 2:55
. - .:0
. :. 0.
0:-
.0
.: p
0
.: ,p
0:
V�I
13A-4ccs
0.143
s
4.00
2.55
0
0
0
0
0
0
0
0
GI
1Aclom
1270
s
35.56
34.77
0
0
0
0
0
0
0
0
(�
13A�ocs;
0143
w-
4•`00
2.55
0
0
0-
0,
0
:., 0
:p
' 0
1Ac1om:. ,
'1 270
w`
35;5,6
55;21
p
' 0
p
: 0'
.. 0.
0
p
0
�G
4A5 tom
0.770
w:
21.56
19.31
' 0
0.
0
0
0
0
.6
0
P
12C-Osw
0.091
-
2.55
1.28
0
0
0
0
64
64
163
82
C .I
16A-30md
0032
: -
0.90
2.32
54
54
48
125
172
172
154
. , 399
F I
II -
it
I .
I
II "
.I
II
22Prtpl
0.989
-
27.69
0.00
54
0
0
0
172
0
_
0-
0
6
c)AED excursion
-9
-170
Fsvelope loss/gain
48
117
317
311
12
a) Infiltration
0
0
0
0
0) Room ventilation
0
0
0
0
13
Intemal gains: Occupants @ 230
0
0
0
0
Appliances/other
1
0
2000
n
Subtotal (lines 6 to 13)
48
117
317
2311
Less extemal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
.0
14
Subtotal
48
117
317
2311
15
Duct loads 1
32%
49%
15
57
32%
49%
100
1126
;I
Total room load
I
64
174
418
3437
Air required (cfm)
1
3
8
21
153
Calculations approved bvACCA
4JA- wcightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces:
2017-Apr-'11 09:29:38
Page 2
wrightsoft° Right-J® Worksheet Job:
Entire House By:
QUICK CALCS, INC.
I '
317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-46M799 Fax 772-466-6796 Email: QUICKCALCS a(AOL.COM
1
Room name
BATH
BEDROOM 2
2
F�osed wall
5.0 ft
34.2 ft
3
Room height
8.0 ft heat/cool
8.0 ft heat/cool
4
Room dimensions
9.0 x 5.0 ft
1.0 x 203.5 ft
5
Room area
45.0 ftz
203.5 ft'
Ty I,
Construction
U-value
Or
HTM
Area (ft')
Load
Area (ft')
Load
number
(Btuh/ft2-"F).
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/PIS
Heat
Cool
6
yJ
13A-4ocs
0.143
' n
_4.00.
2.55
40
40
160
, , .102
128
' 128
' 519
326
G;
4A5 tam '
0:770
: n ..
-21,56
'- 19.31
0
0
.0
0
0
A."
0
V�J�G
13A-4ocs
0.143
a
4.00
2.55
0
0
0
0
80
56
225
143
IA-clom
1.270
a
35.56
87.29
0
0
0
0
24
2
848
2082
D
11
11DO
0.390
a
10.92
11'.31
0
0
0
0
0
0
0
0
W` -'f:
::13A4ocs
'0r143'
se.
.400
2.55
0
0.
0.
0
34
:34
136
, 86
W
13AAws
0.143
s
4.00
2.55
0
0
0
0
32
32
128
61
G
1A-clom
1270
s
35.56
34.77
0
0
0
0
0
0
0
0
13A400s `.
.0143
4.00
2.55
0`
0
0
0
0
0
.0
0
1Ac1om
1.270
.,w
w
35.56
- 55c21,
. 0
0
0
0
0
0
0
0
4A5 tom
' -0:770
' w
21.56
- 19.31
0
0
.0
. • . 0,
0
'0
0
0
P
12C-0sw
0.091
-
2.55
1.28
0
0
0
0
0
0
0
0
C ,;
16A=30md
0.032
-
0.90
2.32
45
45
40
104
204
204
182
472
F
i
I
22A-tpl
0.989
-
27.69
�
0.00
45
5
138
0
204
34
946
0
6
c)AED a)rursion
-16
-85
Envelope loss/gain
339
190
2978
3106
12
i) Infiltration
87
24
593
162
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
1
230
Appliances/other
01
0
Subtotal (lines 6 to 13)
1425
214
35711
3498
Less e)demal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
425
214
3571
3498
15
Duct loads
32%
49%
135
104
32%
49%
1131
1704
Total room load
560
318
1
4702
5203
Air required (cfm)
28
14
232
232
Calculations approved byACCA to meet all requirements of Manual .J 8th Ed.
-Fid- wrightsoTt- 2017-Apr-11 09:29:38
Right -Suite® Universal 2017 17.0.14 RSU08101
Page 3
.4CGP....uick CalcslDocuments\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N
I�
II
+WHI htsoft°
19
Ij
I�
I
317 ST. LUCIE LN., FT. PIERCE,
Right-JO Worksheet
Entire House
QUICK CALCS, INC.
FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM
Job:
Date:
By:
1
Room name
LAUNDRY
GREAT/DINING
2
E)q3iised wall
6.0 ft
47.0 ft
3
Room height
8.0 ft heat/cool
9.8 ft heat/cool
4
Roam dimensions
7.0 x .6.0 ft
1.0 x 526.0 ft
5
Room area
42.0 ft2
526.0 ft2
Ty it
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ft2--°F)
(Btuhlft2)
or perimeter (ft)
(Btuh)
or perimeter. (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
I
6
°13A flocs -
0143
. n`
4.00
255
0
-: 0
0
, " 0
. 255
217
869
552
4Ar2om
0.770
n:"
21:56
19:31'
0
.. 0
' :0
0
38
• 0
.. 815
:730
13A-4ocs
0.143
a
4.00
2.55
0
0
0
0
0
0
0
0
1Ac1om
1.270
a
35.56
87.29
0
0
0
0
0
0
0
0
11
11DO
0.390
a
10.92
11.31
0
0
0
0
0
0
0
0
4I
W i `.
=13Aocs
0:143
se'
4.00
' 2:55
0
0
0
0`
0
0
' 0
' ^ 0.
II
L-'-G
13A4ocs
0.143
s
4.00
2.55
48
48
192
0
122
0
0
0
0
0
0
0
0
0
11
1Ac1om
13A-0acs ".
1.270
0143
s
w ;
35.56
4.00
34.77
:2:55
0
0
0
0
0
_ 0
206
165
66'1
420
1A�1om .
1 270
w
35:5ti
55:21
.0
0
0
0
0
0
0
0:
r
4A52om<
0.770
w .
2T.56
19.31
0'
0
0
- .
* 4.1
:" 41
_880
788
P �l
12C-0sw
0.091
-
2.55
1.28
56
56
143
72
0
0
0
0
C I
16A-30md
0.032
-
0.90
2.32
42
42
38
97
526
526:
471
. - . -1220
F
I
II
I
I
I
II
I I
I
22A-tpl
0.989
-
27.69
0.00
42
6
166
0
626
-.
47
1.302
0
6
c)AED ecursion
-22
668
Envelope loss/gain
539
270
4997
4379
12
a) Infiltration
104
28
997
273
b) 'Room ventilation
0
0
0
0
13
letemal gains: Occupants@ 230
0
0
2
460
Appliances/other
01
0
Subtotal (lines 6 to 13)
643
298
5994
5112
Less a demal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
ISubt6tal
0
0
0
0
14
643
298
5994
5112
15
IDuctloads
32%
49%
204
145
32%
49%
1899
2490
I
Total room load
846
443
7892
7602
Air required (cfm)
42
20
390
338
FJ4- wrightsoft- Right -Suite@ Universal 2017 17.0.14 RSU08101
..uick Calcs%Documents%THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces:
2017-Apr-11 09:29:38
Page 4
wrightsofV Right-M Worksheet Job:
Entire House Date:
QUICK CALCS, INC. By:
317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM
1
Room name
FOYER
M. BATH
2
3
2red wall
Room height
7.0 ft
8.0 ft heat/cool
8.0 ft
8.0 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 50.0 ft
50.0 ft2
7.0 x 8.0 ft
56.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ft2-°F).
(Btuhlft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
y✓ 'I
�. 'G•
13A-0acs
' . "
0.143
.0.770
n:
,' n
-4.00
21.56
2:55
19:31
8
0
`.. 8.
0
32
0
20
.0
0
0
: ''0'
0
0
0
0
0
.`,4A5r2om
13AAocs
0.143
a
4.00
2.55
48
27
908
69
0
0
0
0
11
I- G
1A-c1om
11DO
1.270
0.390
a
a
35.56
10.92
87.29
11.31
0
21
0
21
0
229
0
238
0
0
0
0
0
0
0
0
W •', `
W
13A-40cs .
13A4ocs
0:143
0.143
- se
s
4.00
4.00
2:55
2.55
0
0
0
0
0
0
, 0
0
0
64
0
57
. '-.01
228
' ..' - 0
145
�G
1A-c1om
:
1.270
0143
s
. W
35.56
4.'00
34.77
-2.55
0
0
0
0
0
0
0
0
7
0
7
0.
247
'01.
241
0
'VV13A46cs
1Ao1om
1.270
•. w
35.56
55i21
0:
0
0
- 0
- 0
0
0
0
4A5. om '
. .0.770
, w
21:56
` . 19:31
0
6
' 0
0
� 0
0.
0
0
P I
_.
12C-0sw
0.091
-
2.55
1.28
t
72
183
92
0
0
0
0
C
.16A-30md
0.032
-
0.90
2.32
50
50
45
116
56
56
50
130
F
i
I
I
I
22A•tpl
0.989
-
27.69
0.00
50
7
194
0
56
8
222
;.
0
-
6
c)AED excursion
-39
-38
Envelope loss/gain
792
496
747
478
12
a) Infiltration
121
33
138
38
b) Room ventilation
0
0
0
0
13
Intemal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
913
529
885
516
Less extemal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
913
529
885
516
15
Duct loads 132%
49%
289
258
32%
49%
280
251
Total room load
1202
787
1166
768
Air required (cfm)
59
35
581
34
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-F- wrightsoft' 2017-Apr-11 09:29:38
�A Right -Suite® Universal 2017 17.0.14 RSU08101 Page.S
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N
I;
. II
-�+ w�riglitsoft° Duct System Summary
Entire House
I
QUICK CALCS, INC.
.I
317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-46"799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM
For: THE GRAND CARLTON
j WYNNE DEVELOPMENT, FT. PIERCE, FL
it
I
i
Extemal static pressure
Pressure losses .
Available static pressure
Supply'% 'retum available pressure
LowesiOction rate
Actual fair flow
Total effective length (TEL)
11
Heating
0.50 in H2O
0 in H2O
0.50 . in H2O
0.250 / 0.250 in H2O
0.285 in/100ft
1160 cfm
Job:
Date:
By:
Cooling
0.50 in H2O
0 in H2O
0.50 in H2O
0.250 / 0.250 in H2O
0.285 iN100ft
1160 cfm
176 ft
�i
it Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH
h 560
28
14
0.364
4.0
ox0
VIFx
92.4
115.0
st1
BEDROOM 2
h 4702
232
232
0.360
7.0
OxO
VIFx
23.9
115.0
st1
BEDROOM -A
h 3327
164
163
0.300
6.0
OxO
VIFx
31.8
135.0
st2
BEDRI6OM-B
h 3327
164
163
0.285
6.0
OxO
VIFx
40.6
135.0
st2
FOYER
h 1202
59
35
0.505
4.0
Ox0
VIFx
4.0
95.0
GREAT/DINING
h 3946
195
169
0.300
7.0
OxO
VIFx
31.8
135.0
st2
GREAT/DINING-A
h 3946
195
169
0.300
TO
Ox0
.VIFx
31.8
135.0
st2
KITCHEN
c 3431
21
153
0.379
6.0
ox0
VIFx
17.0
115.0
st1
LAUNDRY
h 846
42
20
0.361
4.0'
Ox0
VIFx
23.3.
115.0
st1
M. BATH -A
h 768
58
34
0
0
NO
VIFx
0
0
wlc ilk
c 174
3
8
0.309
4.0
Ox0
VIFx
27.0
135.0
st2
li
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FR
(fpm)
(n)
(in)
Material
Trunk
st2!
Peak AVF
721
672
0.285
918
12.0
0 x 0
VinlFlx
st1
st11l
Peak AVF
1043
1091
0.285
1020
14.0
0 x 0
VinlFlx
II
I I
�iI
I '
�I
-�J-�{_- wri htsoft¢ 2017-Apr-11 09:29:38
' f , 9 • Right -Suite® Universal 2017 17.0.14 RSU08101 Page 1
...uick CalcslDocuments\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N
I
I,
I,
�I
�I
Return
Branch
Detail
Table
Name
Grille
Size (in)
Htg
(cfm)
clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rb1
Ox 0
11.60
1160
0
0
0
0
Ox 0
VIFx
.` wri htsoft° 2017-Apr-11 09:29:38
9 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 2
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N