SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW
'p
FORM -
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
x
Telephone: 772-621.3322
fQlgj
Fax: 772-621-3604
Web Address: www.slcfd.com
SCANNEL)
U, y
�1Gic County
FMO Permit # 8-18-60
BLDG Permit# 1712-0535
City Fort Pierce
n-urJacquin and Sons
7348 Commercial Circle city Ft Pierce
FL Zip 34951 Telephone (772) 465-2475 J
Architect/Engineer Architecture and Design Telephone (772) 220-4411,
Occupancy Type Industrial. Construction Type 118 Square Feet 4100
Occupant load 150'per plans Number of Stories Access Box Required Access Key Switch I
u LL��rJ
AFSPerm it Required FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions,: including the electroniccopy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. 'Fhe respective Euilding Department shall schedule all final, inspections through the Fire Marshal's Office.
S. Failod inspection, s require payment of fee prior to rescheduling of further inspections.
6. Pengfrations through rated assemblies shall be of the proper UL design: Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC systemis that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION 15 CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDAVJCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. The Installation or Alteration of Fire Sprinkler, Fire Alarm, Systems require a separate review and permit.
2. Automatic fan shutdown is requ4ed for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. The HVAC shall be tied into the
fire alarm system.
Page 11 of 1l Reviewed by Tony Jerger Date 02-26-18