HomeMy WebLinkAboutPROJECT SUMMARY-CHECK LISTII
r Florida Building Code, Fifth. Edition (2014) - Energy Conservation
-EnergyGauge Summit@ Fla/Com-2015, Effective Date: June 30, 2015
IECC 2012 - Total Building Performance Compliance Option
SCANNED
Do an
Checklil""C 2 0 2017 V
BY............ ......
Applications for compliance with the Florida Building Code, Energy Conservation shall include:
This Checklist
The full compliance report generated by the software that contains the project
summary, compliance summary, certifications and detailed component compliance
reports.
The compliance report must include the full input report generated by the software as
contigous part of the compliance report.
Boxes appropriately checked in the Mandatory Section of the complaince report.
T I I E SIE PL.I.N'S AiND AL1. PI 0P0SED VI 0Pc z.�
ARE SIU&JECT TO M-1Y CGS IECi f'IUIS p
'REQUIRED SY FIELD IN'SPE.i",TOES THAT
IY�.'t1Y BE 'NIECESM17 IN ORDER TO
COIOPLY WITH ALL. ,"OP UCABLE CGE)ES".
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 1 of 21
. -�
PROJECT SUMMARY
Short Desc: Tattoo Yachts
Description:
Tattoo Yachts
Owner:
Addressl: 5350 Steel Boulevard
City:
Fort Pierce
Address2:
State:
FL
Zip:
34946
Type: Warehouse
Class:
Renovation to existing building
Jurisdiction: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
Conditioned Area: 1870 SF Conditioned & UnConditioned Area: 1975 SF
No of Stories: 1 Area entered from Plans 1870 SF
Permit No: 0 . Max Tonnage 4.7
If different, write in:
Component
Gross Energy Cost (in $)
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design Criteria Result
529.0 561.0 PASSED
PASSES
PASSES
PASSES
No Entry
No Entry
No Entry
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit@) Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 2 of 21
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code j��
Prepared By: ProCalcs, LLC C 11;,i " 'I'.� Building Official:
Thomas Platania, DigttalysignedbyThomas
,,Platania CACIS15254
Date: CAC1815254 __ -0Se: 017.11.1415:1a:06 Date:
1 certify that this building is in compliance with the FLodda Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy
Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: ProCalcs, LLC Reg No: Cac1815254
Plumbing Designer: Reg No:
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
' Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 3 of 21
I
I�
Project: Tattoo Yachts
Title: Tattoo Yachts
Type: Warehouse
(WEAFile: FL_ST_LUCIE_CO_INTL.tm3)
Building End Uses
I)Proposed
2) Baseline
Total
33.30
42.10
$529
$661
ELECTRICITY(MBtulkWhl$)
33.30
42.10
9758
12346
$529
$661
AREA LIGHTS
6.80
16.50
2000
4824
$108
$258
MISC EQUIPMT
3.90
3.90
1157
1157
$63
$62
PUMPS & MISC
0.10
0.10
25
19
$1
$1
SPACE COOL
14.10
13.80
4127
4052
S224
$217
SPACE HEAT
2.50
0.50
729
151
S40
$8
VENT FANS
5.90
7.30
1720
2143
$93
$115
Credits Applied: None
PASSES
Passing Criteria = 561
Design (including any credits) = 529
Passing requires Proposed Building cost to be at most 85% of
Baseline cost. This Proposed Building is at 80.1%
l
I I
'j
I'
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
` Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 4 of 21
i
;I
I
i
I
Project: Tattoo Yachts
Title: Tattoo Yachts
Type: Warehouse
(WEAFile: FL ST LUCIE CO_INTL.tm3)
External Lighting Compliance
Description Category Tradable? Allowance
Area or Length
ELPA CLP
(W/Unit)
or No. of Units
(W) (W)
(Sgft or ft)
Ext Light 2 Uncovered Parking Areas -- Yes 0.15
1,000.0
150 128
Parking lots and Drives
Tradable Surfaces: 128 (W) Allowance for Tradable: 850 (W)
PASSES
All External Lighting: 128 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
Project: Tattoo Yachts
Title: Tattoo Yachts
Type: Warehouse
(WEA File: FL ST LUCIE CO INTL.tm3)
Lighting Controls Compliance
Acronym Ashrae Description Area
Design
Min
Compli-
ID (sq.ft)
CP
CP
ance
AHU 1 Electrical Mechanical Equipment 20
1
1
PASSES
Room - General
Storage 1 3 Storage & Warehouse - Bulky 533
1
1
PASSES
Active Storage
Stairs 1 4 Stair - Active Traffic 160
1
1
PASSES
Storage 2 3 Storage & Warehouse - Bulky 204
1
1
PASSES
Active Storage
Storage 3 3 Storage & Warehouse - Bulky 524
1
1
PASSES
Active Storage
Stairs 2 4 Stair - Active Traffic 72
1
1
PASSES
Closet 2 Storage & Warehouse - Inactive 18
1
1
PASSES
Storage
Storage 4 3 Storage & Warehouse - Bulky 277
1
1
PASSES
Active Storage
RR 1 6 Toilet and Washroom 63
1
1
PASSES
Warehouse 3 Storage & Warehouse - Bulky 105
1
1
PASSES
Active Storage
PASSES
EnergyGauge Summit® FlalCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 5 of 21
Project: Tattoo Yachts
Title: Tattoo Yachts
Type: Warehouse
(WEA File: FL ST LUCIE CO_INTL.tm3)
System Report Compliance
AHU-1 AHU-1
Constant Volume Air Cooled
No. of Units
Split System < 65000 Btu/hr
I
Component
Category
Capacity
Design Eff Design
IPLV Comp-
Eff Criteria IPLV
Criteria liance
Cooling System
Air Conditioners Air Cooled
56000
14.00 13.00 14.00
PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
30709
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
1750
0.36 0.82
PASSES
System -Supply
Constant Volume
Air Distribution
Not in Check list -
N/A
System (Sup)
Compliance Ignored
Air Distribution
Not in Check list -
N/A
System (Ret)
Compliance Ignored
PASSES
Plant Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV liance
None
l l/14/2017
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 6 of 21
Water Heater Compliance
Description Type Category Design Min
Eff Eff
Design Max Comp
Loss Loss liance
None
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond
[inches] Runout? Temp [Btu-in/hr
[F] SF.F]
Ins Req Ins Compliance
Thick [in] Thick [in]
None
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 7 of 21
Mandatory Requirements (as applicable) Mandatory requirements compiled
by US Department
of Energy and Pacific Northwest National Laboratory.
Adopted with permission
Topic
Section Component
Description
Yes
N/A Exempt
1, To be checkedf by Designer or Engineer
Fenestration
C402.2.7 Envelope
U-factor of opaque doors associated with the
El
El
El
building thermal envelope meets requirements.
Insulation
C402.2.1.1 Envelope
High-albedo roofs satisfy one of the following:
3-year-aged solar reflectance >= 0.55 and thermal
emittance >= 0.75, 3-year-aged solar reflectance
index >= 64.0, initial year solar reflectance >=
0.70 and thermal emittance >= 0.75, or initial year
solar
Wattage
C405.6 Exterior Lighting
Exterior grounds lighting over 100 W provides >60
Im/W unless on motion sensor or fixture is exempt
from scope of code or from external LPD.
Wattage
C405.4 Interior Lighting
Exit signs do not exceed 5 watts per face.
❑
1:1
El
Wattage
C405.2.3 Interior Lighting
Additional interior lighting power allowed for
special functions per the approved lighting plans
and is automatically controlled and separated
from general lighting.
HVAC
C403.2.6 Mechanical
Exhaust air energy recovery on systems meeting
1:1
El
Table C403.2.6
SYSTEM —SPECIFIC
C403.3.1,C403.3.1.1 Mechanical
Air economizers provided where required, meet
00
❑
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM —SPECIFIC
C403.3.1,C403.4.1 Mechanical
Water economizers provided where required,
❑
El
❑
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM —SPECIFIC
C403.4.1.4 Mechanical
Economizer operation will not increase heating
❑
❑
El
energy use during normal operation.
SYSTEM —SPECIFIC
C403.2.10.1 Mechanical
HVAC fan systems at design conditions do not
❑
❑
❑
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM —SPECIFIC
C403.2.10.2 Mechanical
HVAC fan motors not larger than allowable limits.
❑
El
SYSTEM —SPECIFIC
C404.2 Mechanical
Service water heating equipment meets efficiency
❑
❑
El
requirements.
SYSTEM —SPECIFIC
C403.2.3 Mechanical
Centrifugal fan open -circuit cooling towers having
❑
❑
El
combined rated capacity >= 1100 gpm meets
minimum efficiency requirement: >=38.2 gpm/hp.
=2. To be checked by Plan Reviewer ,
Air Leakage
C402.4.7 Envelope
Vestibules are installed on all building entrances.
❑
❑
Doors have self -closing devices.
Insulation
C402.2.6 Envelope
Slab edge insulation depth/length. Slab insulation
❑
❑
El
extending away from building is covered by
pavement or — 10 inches of soil.
Plan Review
C103.2 Envelope
Plans and/or specifications provide all information
❑
❑
❑
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 8 of 21
Plan Review C103.2 Exterior Lighting
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include exterior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
Wattage C405.6.2 Exterior Lighting
Exterior lighting power is consistent with what is
❑
❑
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
-
Plan Review C103.2 Interior Lighting
Plans, specifications, and/or calculations provide
❑
El
El
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include interior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
HVAC C403.2.5.1 Mechanical
Demand control ventilation provided for spaces
❑
El
El
>500 ft2 and >25 people/1000 ft2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow >3,000 cfm.
HVAC C403.2.4.3 Mechanical
Each zone equipped with setback controls using
1:1
El
El
automatic time clock or programmable control
system.
Plan Review C103.2 Mechanical
Plans, specifications, and/or calculations provide
1:1
El
El
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering standards and
handbooks.
Plan Review C103.2 Mechanical
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the service water heating systems
and equipment and document where exceptions
to the standard are claimed. Hot water system
sized per manufacturer's sizing guide.
SYSTEM —SPECIFIC C403.4.5 Mechanical
Zone controls can limit simultaneous heating and
cooling and sequence heating and cooling to each
SYSTEM —SPECIFIC C403.4.3.1 Mechanical
zone.
Three -pipe hydronic systems using a common
return for hot and chilled water are not used.
SYSTEM —SPECIFIC C403.4.3.2 Mechanical
Two -pipe hydronic systems using a common
distribution system have controls to allow a
deadband > 15 OF, allow operation in one mode
for at least 4 hrs before changeover, and have
rest controls to limit heating and cooling supply
temperature to <=30 OF.
SYSTEM —SPECIFIC C403.4.3.3.1 Mechanical
Hydronic heat pump systems connected to a
El
1-1
11
common water loop meet heat rejection and heat
addition requirements.
SYSTEM —SPECIFIC C408.2.2.2 Mechanical
HVAC hydronic heating and cooling coils have
1:1
El
El
means to balance and have pressure test
connections.
SYSTEM —SPECIFIC C403.4.2 Mechanical
VAV fan motors >=7.5 hp to be driven by variable
speed drive, have a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM —SPECIFIC C403.4.2.1 Mechanical
VAV fans have static pressure sensors positioned
so setpoint <=1/3 total design pressure.
SYSTEM —SPECIFIC C403.4.2.2 Mechanical
Reset static pressure setpoint for DDC controlled
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM —SPECIFIC C403.4.5.4 Mechanical
Multiple zone HVAC systems have supply air
1:1
El
El
temperature reset controls.
SYSTEM —SPECIFIC C403.4.3.4 Mechanical
Hydronic systems greater than 300,000 Btu/h
El
El
D
designed for variable fluid flow.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 9 of 21
SYSTEM SPECIFIC C403.4.3.4
SYSTEM_ SPECIFIC C403.4.4
Plan Review C406
I Plan Review
Air Leakage
Air Leakage
Air Leakage
C402.3.2.2
Mechanical
Temperature reset by representative building
loads in pumping systems for chiller and boiler
systems >300,000 Btu/h.
Mechanical
Fan systems with motors >=7.5 hp associated
with heat rejection equipment to have capability to
operate at 2/3 of full -speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
Project
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the additional energy efficiency
package options.
Envelope
Skylights in office, storage, automotive service,
manufacturing, non -refrigerated warehouse, retail
store, and distribution/sorting area have a
measured haze value > 90 percent unless
designed to exclude direct sunlight.
C402.4.1,C402.4.2 Envelope
C402.4.3,C402.4.4 Envelope
C402.4.1.1 Envelope
Air Leakage C402.4.6 Envelope
Air Leakage C402.4.8 Envelope
Fenestration
C303.1.3
Envelope
Fenestration
C303.1.3
Envelope
Insulation
C303.2
Envelope
Insulation
C303.2
Envelope
Insulation
C403.2.7,C408.2.8,C4, Envelope
Insulation
Insulation
Insulation
Insulation
Insulation
Insulation
Insulation
C402.4.2.1 Envelope
C303.2 Envelope
C402.2.1
C303.2
C303.2
C303.1
C303.2.1
Envelope
Envelope
Envelope
Envelope
Envelope
The building envelope contains a continuous air
barrier that is sealed in an approved manner and
either constructed or tested in an approved
manner. Air barrier penetrations are sealed in an
approved manner.
Factory -built fenestration and doors are labeled
as meeting air leakage requirements.
All sources of air leakage in the building thermal
envelope are sealed, caulked, gasketed, weather
stripped or wrapped with moisture
vapor -permeable wrapping material to minimize
air leakage.
Weatherseals installed on all loading dock cargo
doors.
Recessed luminaires in thermal envelope to limit
infiltration and be IC rated and labeled. Seal
between interior finish and luminaire housing.
Fenestration products rated in accordance with
NFRC.
Fenestration products are certified as to
performance labels or certificates provided.
Below -grade wall insulation installed per
manufacturer's instructions.
Slab edge insulation installed per manufacturer's
instructions.
Exterior insulation protected against damage,
sunlight, moisture, wind, landscaping and
equipment maintenance activities.
Roof R-value. For some ceiling systems,
verification may need to occur during Framing
Inspection.
Roof insulation installed per manufacturer's
instructions. Blown or poured loose -fill insulation
is installed only where the roof slope is <=3 in 12.
Skylight curbs are insulated to the level of roofs
with insulation above deck or R-5.
Above -grade wall insulation installed per
manufacturer's instructions.
Floor insulation installed per manufacturer's
instructions.
Building envelope insulation is labeled with
R-value or insulation certificate providing R-value
and other relevant data.
Exterior insulation is protected from damage with
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
W o m
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
I
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 10 of 21
Insulation
C402.2.1
Envelope
Insulation intended to meet the roof insulation
requirements cannot be installed on top of a
suspended ceiling. Mark this requirement
compliant if insulation is installed accordingly.
Controls
C405.2.4
Exterior Lighting
Automatic lighting controls for exterior lighting
installed.
Controls
C405.2.2.1
Interior Lighting
Automatic controls to shut off all building lighting
installed in all buildings.
Controls
C405.2.1.1
Interior Lighting
Independent lighting controls installed per
approved lighting plans and all manual controls
readily accessible and visible to occupants.
Controls
C405.2.1.2
Interior Lighting
Lighting controls installed to uniformly reduce the
El
El
0
lighting load by at least 50%.
Controls
C405.2.2.3
Interior Lighting
Daylight zones provided with individual controls
❑
❑
that control the lights independent of general area
lighting.
Controls
C405.2.3
Interior Lighting
Sleeping units have at least one master switch at
the main entry door that controls wired luminaires
and switched receptacles.
Controls
C405.2.2.2
Interior Lighting
Occupancy sensors installed in required spaces.
❑
❑
El
Controls
C405.2.2.3
Interior Lighting
Primary sidelighted areas are equipped with
❑
El
required lighting controls.
Controls
C405.2.2.3
Interior Lighting
Enclosed spaces with daylight area under
skylights and rooftop monitors are equipped with
required lighting controls.
Controls
C405.2.3
Interior Lighting
Separate lighting control devices for specific uses
installed per approved lighting plans.
Controls
C405.3
Interior Lighting
Fluorescent luminaires within odd numbered lamp
configurations that are with 10 feet center to
center (if recess mounted) or are within 1 foot
edge to edge (if pendant or surface mounted)
shall be tandem wired.
Wattage
C405.5.2
Interior Lighting
Interior installed lamp and fixture lighting power is
❑
❑
❑
consistent with what is shown on the approved
lighting plans, demonstrating proposed watts are
less than or equal to allowed wafts.
HVAC
C403.2.4.5
Mechanical
Freeze protection and snow/ice melting system
❑
❑
El
sensors for future connection to controls.
HVAC
C403.2.3
Mechanical
HVAC equipment efficiency verified.
❑
El
El
Air Leakage
C402.4.5.1
Envelope
Stair and elevator shaft vents have motorized
0
El
❑
dampers that automatically close.
Air Leakage
C402.4.5.2
Envelope
Outdoor air and exhaust systems have motorized
❑
❑
El
dampers that automatically shut when not in use
and meet maximum leakage rates. Check gravity
dampers where allowed.
HVAC
C403.2.8.1
Mechanical
Piping Insulation exposed to weather is protected
❑
❑
El
from damage (due to sun, moisture, wind, etc.).
HVAC
C403.2.7
Mechanical
HVAC ducts and plenums insulated. Where ducts
❑
❑
El
or plenums are installed in or under a slab,
verification may need to occur during Foundation
Inspection.
HVAC
C403.2.8
Mechanical
Thermally ineffective panel surfaces of sensible
heating panels have insulation — R-3.5.
HVAC
C403.2.7
Mechanical
Ducts and plenums sealed based on static
El
El
1:1
pressure and location.
HVAC
C408.2.2.1
Mechanical
Air outlets and zone terminal devices have means
for air balancing.
HVAC
C403.2.11
Mechanical
Unenclosed spaces that are heated use only
radiant heat.
HVAC
C403.2.4.1
Mechanical
Heating and cooling to each zone is controlled by
❑
El
❑
a thermostat control.
HVAC
C403.2.4.2
Mechanical
Thermostatic controls have a 5 °F deadband.
HVAC
C403.2.4.2
Mechanical
Temperature controls have setpoint overlap
❑
El
restrictions.
fi EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
I1/14/2017 Page 11 of21
HVAC C403.2.4.3
Mechanical Automatic Controls: Setback to 55'F (heat) and
❑
85°F (cool); 7-day clock, 2-hour occupant
override, 10-hour backup
SYSTEM_SPECIFIC C404.3
Mechanical Temperature controls installed on service water
heating systems (110 OF for dwelling units and
lavatories in public restrooms and 90 OF for other
occupancies.)
SYSTEM_SPECIFIC C404.4
Mechanical Automatic time switches installed to automatically
switch off the recirculating hot-water system or
heat trace.
SYSTEM_SPECIFIC C404.2
Mechanical Heat traps installed on non -circulating storage
0
water tanks.
SYSTEM_SPECIFIC C403.2.3
Mechanical PTAC and PTHP with sleeves 16 in. by 42 in.
11
El
labeled for replacement only as per Footnote b to
Table C403.2.3(3).
SYSTEM_SPECIFIC C403.4.2
Mechanical VAV fan >= 7.5 hp are driven by mechanical or
❑
❑
El
electrical variable speed drive, or driven by
vane -axial with variable speed blades, or operate
with motor demand <=30% design kW at 50%
design flow - calculations required
SYSTEM_SPECIFIC C403.2.8
Mechanical HVAC piping insulation thickness. Where piping
El
❑
El
is installed in or under a slab, verification may
need to occur during Foundation Inspection.
SYSTEM —SPECIFIC C403.2.7.1.3
Mechanical Ductwork operating >3 in. water column requires
air leakage testing.
SYSTEM_SPECIFIC C403.4.3.5
Mechanical Reduce flow in pumping systems >10 hp to
El
El
❑
multiple chillers or boilers when others are shut
down.
SYSTEM_SPECIFIC C403.4.3.3.3
Mechanical Two -position automatic valve interlocked to shut
❑
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM —SPECIFIC C403.4.6
Mechanical Condenser heat recovery system that can heat
1:1
El
water to 85 OF or provide 60% of peak heat
rejection is installed for preheating of service hot
water in 247 facility, water cooled systems reject
>6 MMBtu, SHW load > 1 MMBtu.
SYSTEM_SPECIFIC C403.4.7
Mechanical Hot gas bypass limited to:
❑
❑
El
<=240 kBtu/h — 50%
>240 kBtu/h — 25%
SYSTEM_SPECIFIC C403.2.4.2
Mechanical Heating and cooling to each zone is controlled by
a thermostat control. Minimum one humidity
control device per installed
humidification/dehumidification system.
SYSTEM_SPECIFIC C403.2.4.3.3
Mechanical Systems include optimum start controls.
El
❑
❑
SYSTEM_SPECIFIC C403.2.4.1.1
Mechanical Heat pump controls prevent supplemental electric1:1
El
❑
resistance heat from coming on when not needed.
SYSTEM_SPECIFIC C404.3
Mechanical Public lavatory faucet water temperature <=1 I WE
SYSTEM_SPECIFIC C404.5
Mechanical All piping in circulating system insulated
SYSTEM_SPECIFIC C404.5
Mechanical First 8 ft of outlet piping is insulated
SYSTEM_SPECIFIC C404.5
Mechanical All heat traced or externally heated piping
insulated
SYSTEM_SPECIFIC C404.6
Mechanical Controls are installed that limit the operation of aEl
El
❑
recirculation pump installed to maintain
temperature of a storage tank.
SYSTEM_SPECIFIC C404.7.1
Mechanical Pool heaters are equipped with on/off switch and
1:1
El
no continuously burning pilot light.
SYSTEM_SPECIFIC C404.7.3
Mechanical Vapor retardant pool covers are provided for
El
El
❑
heated pools and permanently installed spas.
SYSTEM —SPECIFIC C404.7.2
Mechanical Time switches are installed on all pool heaters
and pumps.
Testing C408.2.3.2
Mechanical HVAC control systems have been tested to
ensure proper operation, calibration and
adjustment of controls.
'I
i
I, EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 12of21
Mandatory Additional Eff C406
Insulation C402.2.8
Project
Project
Efficient HVAC performance, efficient lighting
system, or on -site supply of renewable energy
consistent with what is shown the approved plans.
Bottom surface of floor structures incorporating
radiant heating insulated to > R-3.5.
El
0
❑
❑
4. To be checked by'Jnspector at Project Completion and, Prior to Issuance of
of Occu�I1Gy
Post Construction C408.3
ExteriorLighting
g g
Lighting systems have been tested to ensure❑❑
proper calibration, adjustment, programming, and
operation.
Post Construction C408.2.5.1
Interior Lighting
Furnished as -built drawings for electric power
systems within 30 days of system acceptance.
Post Construction C303.3,C408.2.5.2
Interior Lighting
Furnished O&M instructions for systems and
equipment to the building owner or designated
representative.
Post Construction C408.3
Interior Lighting
Lighting systems have been tested to ensure
proper calibration, adjustment, programming, and
operation.
Post Construction C408.2.5.1
Mechanical
Furnished HVAC as -built drawings submitted1:1
El
❑
within 90 days of system acceptance.
Post Construction C303.3,C408.2.5.2
Mechanical
Furnished O&M manuals for HVAC systems
within 90 days of system acceptance.
Post Construction C408.2.5.3
Mechanical
An air and/or hydronic system balancing report is
provided for HVAC systems.
Post Construction C408.2.1
Mechanical
Commissioning plan developed by registered
design professional or approved agency.
Post Construction C408.2.4
Mechanical
Preliminary commissioning report completed and
certified by registered design professional or
approved agency.
Post Construction C408.2.5.4
Mechanical
Final commissioning report due to building owner
within 90 days of receipt of certificate of
occupancy.
Post Construction C408.2.3.1
Mechanical
HVAC equipment has been tested to ensure
proper operation.
Post Construction C408.2.3.3
Mechanical
Economizers have been tested to ensure proper
El
operation.
I'
ii
I I
j, EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
• i Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 13 of 21
Input Data Report
Project Name:
Tattoo Yachts
Address:
5350 Steel Boulevard
Owner:
Building Type:
Warehouse
No.of Stories:
1
Bldg. Rotation:
None
Proiect Information
Project Title: Tattoo Yachts
State: FL
Zip: 34946
Building Classification: Renovation to existing building
GrossArea (SF): 1,975
Zones
No Acronym
Description Type
Area
Multi Total Area
lsfl
Isfl
I ;1 Second Floor
Second Floor CONDITIONED
1870.0
1 1870.0 B
2� Warehouse
�I
Existing Warehouse UNCONDITIONED
104.5
1 104.5
i
i
1
I
i
li
II
I
I[
I
1
I
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 14 of21
I Ii
Spaces
No Acronym
Description
Type
Depth
Width
Height Mult
Total
Total
(ft]
lft]
lft]
Area
Vollct]
lsfl
In Zone: Second Floor
1 AHU
AHU
Electrical Mechanical
4.50
4.50
7.00
1
20.3
141.8
Equipment Room - General
2 Storage 1
Storage 1
Storage & Warehouse- Bulky
18.37
29.00
7.00
1
532.7
3729.1
Active Storage
3 Stairs 1
Stairs 1
Stair - Active Traffic
4.50
35.50
7.00
1
159.8
1118.3
4 Storage 2
Storage 2
Storage & Warehouse- Bulky
18.50
11.00
7.00
1
203.5
1424.5
Active Storage
5 Storage 3
Storage 3
Storage & Warehouse- Bulky
23.00
22.78
10.80
1
523.9
5658.6
Active Storage
6 Stairs 2
Stairs 2
Stair - Active Traffic
4.50
16.00
7.00
1
72.0
504.0
7 Closet
Closet
Storage & Warehouse -
4.50
4.00
7.00
1
18.0
126.0
•
Inactive Storage
.8 Storage 4
Storage 4
Storage & Warehouse - Bulky
16.78
16.50
7.00
1
276.9
1938.1
Active Storage
9 RR 1
RR 1
Toilet and Washroom
10.00
6.30
7.00
1
63.0
441.0
In Zone: Warehouse
1 Warehouse
Warehouse
Storage & Warehouse - Bulky
1.00
104.50
10.80
1
104.5
1128.6
Active Storage
I
i
I
i
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 15 of 21
1
I�
I
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires Luminaire
[W]
Ctrl pts
In Zone: Second Floor
In Space: AHU
18
18
Manual On/Off
1
❑
1 , Compact Fluorescent
General Lighting
1
:In Space: Storage 1
1 Compact Fluorescent
General Lighting
6
24
144
Manual On/Off
1
❑
In Space: Stairs 1
1 % Compact Fluorescent
General Lighting
2
40
80
Manual On/Off
1
❑
In Space: Storage 2
1 Compact Fluorescent
General Lighting
2
24
48
Manual On/Off
1
❑
�In Space: Storage 3
1 Compact Fluorescent
General Lighting
6
24
144
Manual On/Off
1
❑
1. In Space: Stairs 2
1' Compact Fluorescent
General Lighting
1
48
48
Manual On/Off
1
❑
j In Space: Closet
11 Compact Fluorescent
General Lighting
1
10
10
Manual On/Off
1
❑
" In Space: Storage 4
1 Compact Fluorescent
General Lighting
4
24
96
Manual On/Off
1
❑
i In Space: RR 1
1 1 Compact Fluorescent
General Lighting
1
60
60
Manual On/Off
1
❑
In Zone: Warehouse
i In Space: Warehouse
1 Compact Fluorescent
General Lighting
1
5
5
Security (continuous)
1
❑
�i
I
n
'i
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 16 of21
Walls (Walls will be rotated clockwise by building rotation value)
No
Description
Type
Width H (Effec) Multi
Area Orient Cond- Heat Dens.
R-Value
IN [ft] plier
[sfJ ation uctance Capacity [Ib/cf]
[h.sf.F/Btu]
[Btu/h.sfF1 [Btu/sf.F]
In Zone: Second Floor
1
East Wall 1
1/2" Gyp Brd / 2 x 4
60.00 7.00 1
420.0 East 0.0840 1.272 16.25
11.9
❑
w/ R-I I / 1/2" Gyp
Brd
2
East Wall 2
1/2" Gyp Brd / 2 x 4
21.50 10.80 1
232.2 East 0.0840 1.272 16.25
11.9
❑
w/ R-I I / 1/2" Gyp
Brd
3
South Wall
1/2" Gyp Brd / 2 x 4
23.00 7.00 1
161.0 South 0.0840 1.272 16.25
11.9
❑
w/ R-1 I / 1/2" Gyp
Brd
4,
West Wall 1
Metal
60.50 7.00 1
423.5 West 0.0873 1.095 18.82
11.5
❑
siding/2x4@24"
Frame / R-I I
Batt/l/2"Gyp
5,
West Wall 2
Metal
21.00 10.80 1
226.8 West 0.0873 1.095 18.82
11.5
❑
siding/2x4@24"
Frame / R-I I
Batt/l/2"Gyp
6
North Wall
Metal
18.50 7.00 1
129.5 North 0.0873 1.095 18.82
11.5
❑
siding/2x4@24"
Frame / R-I I
II,
Batt/l/2"Gyp
Windows (Windows will be rotated clockwise by building rotation value)
'No
Description
Orientation Shaded
U SHGC
Vis.Tra W H (Effec) Multi Total Area
[Btu/hr sf F]
IN IN plier
Isf]
I
,In Zone: Second Floor
In Wall: West Wall 1
1
West Window
West Yes
0.9000 0.50
0.40 3.00 3.00 8
72.0
❑
In Wall: West Wall 2
1
West Window
West Yes
0.9000 0.50
0.40 3.00 3.00 2
18.0
❑
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 17 of 21
I'
I�
Doors
No Description
Type
Shade?
Width H (Effec) Multi Area
Cond. Dens. Ht Cap. R
[ft] IN plier [st]
[Btu/h.sf.F] [Ib/cf] [Btu/sf. [h.sf.F/
F] Btu]
In Zone:
In Wall:
Roofs
No Description
Type
Width
H (Effec) Multi Area Tilt
Cond. Heat Cap Dens. R-Value
[ft]
[ft] plier [sf] [deg]
[Btu/h.SE F] [Btu/sE F] [lb/cf] [h.sf.FBtu
In Zone: Second Floor
1 Second Floor Roof
Mtl Bldg Roof/R-5
81.30
23.00 1 1869.9 0.00
0.1398 4.95 43.85 7.2
Insulation
•
Skylights
No Description
Type
U
SHGC Vis.Trans W H (Effec) Multi- Area Total Area
[Btu/hr sf F]
IN IN
plier [Sf] [Sf]
i
In Zvae:
I' In Roof:
I
I
❑
Floors
No Description
Type
Width H (Effec) Multi Area
Cond. Heat Cap. Dens. R-Value
IN IN plier [st] [Btu/h.sf.F [Btu/sf. F] [lb/cf] [h.sf.FBtu
In Zone:
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page 18 of21
I�
Systems
AHU-1 AHU-1
Constant Volume Air Cooled
Split System < 65000 Btu/hr
No. Of Units
1
Component Category
Capacity Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
4 Air Distribution System (Sup)
5 Air Distribution System (Ret)
56000.00 14.00 14.00
30709.00 1.00
1750.00 0.36
❑
❑
❑
❑
❑
Plant
Equipment Category
Size Inst.NoEff.
IPLV
I
Water Heaters
W-Heater Description Capacity Cap.Unit UP Rt. Efficiency
Loss
i
I.
I.
Ext-Lighting
Description Category
No. of Wafts per Area/Len/No Control
Lumin- Lumin- [sVft/No] Type
aires afire
Wattage
[WI
1 Ext Light 2 Uncovered Parking Areas --
Parking lots and Drives
2 64 1000.00 Photo Sensor control 128.00 ❑
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
Page 19 of 21
0
A
IJ
Piping
Operating Insulation
Nomonal pipe
Insulation
Is
No
Type
Temp Conductivity
Diameter
Thickness
Runout.
[F] [ Btu-in/h.sf.F]
[in]
[in]
I
{
Fenestration Used
a
Glass
SHGC
VLT
Nam:
{
Glass Type
No. of
Conductance
I,
Panes
[Btu/h.sEF]
ASHULDb1TntM
User Defined
2 0.9000 0.5000
0.4000
tl-Oth frm
Materials Used
Only RValue
Thick
Cond-
Density
Sp. Heat
Mat No
Acronym
Description
R-Value [h.sf.FBtu]
[ft]
uctivity
[lb/cf]
[Btu/Ib.F]
Used
[Btu/h.ft.F
j187
Matl187
GYP OR PLAS
No 0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1/21N
I' 12
Mat112
3 in. Insulation
No 10.0000
0.2500
0.0250
2.00
0.2000
❑
�i 4
Matl4
Steel siding
No 0.0002
0.0050
26.0000
480.00
0.1000
❑
271•
Mat1271
2x4 r@i 24" oc + RI 1 Batt
No 10.4179
0.2917
0.0280
7.11
0.2000
❑
I; 94
�I
Mat194
BUILT-UP ROOFING, 3/8IN No 0.3366
0.0313
0.0930
70.00
0.3500
❑
I' EnergyGauge Summit@) Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
f; 11/14/2017 Page 20 of 21
I
I
I,
I�
Constructs Used
Simple Massless Conductance Heat Cap
Density
RValue
No. Name
Construct Construct [Btu/h.sf.F] [Btu/sf.F]
jib/el]
[h.sEFBtu]
1046 Mtl Bldg Roof/R-5 Insulation
No No 0.14 4.95
43.85
7.2
Layer Material
Material Thickness
Framing
No.
IN
Factor
1 94
BUILT-UP ROOFING, 3/8IN 0.2000
0.000
❑
II 2 12
3 in. Insulation 0.1250
0.000
❑
,I1
Simple Massless
Conductance Heat Cap
Density
RValue
No Name
Construct Construct
[Btu/h.sf.F] [Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1048 1/2" Gyp Brd / 2 x 4 w/ R-11 / 1/2"
No No
0.08 1.27
16.25
11.9
Gyp Brd
• Layer Material
Material
Thickness
Framing
No.
IN
Factor
1 187
GYP OR PLAS BOARD,1/2IN
0.0417
0.000
❑
2 271
2x4@24" oc + RI Batt
0.3080
0.000
❑
Z 1R7
rWP OR PT.AC ROART) 1/?TM
0.0417
0.000
❑
No Name
Construct Construct
[Btu/h.sEF] [Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1055 Metal siding/2x4@24" Frame / R-11 No No
0.09 1.09
18.82
11.5 ❑
Batt/1/2"Gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
4
Steel siding
0.0050
0.000
❑
• 2
271
2x4@24" oc + RI 1 Batt
0.3080
0.000
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.000
❑
I
I
i
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation IECC 2012 - Total Building Performance Compliance Option
11/14/2017 Page21 of21
ti
Y_ ♦ ,
`�����
Building Analysis
Job: Tattoo Yachts
Digitally signed by Thomas Date: November14,2017
Thomas Platanid plataniacac,8,s2sa
<?
` we are the m'"1.9Plate!
Second Floor
ProCalcs, LLC
By: Jimmy Conlon
CAC1815254 Date: 2017.11.1415:19:04
osoo 61k
j
II
e
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www ProCalcs. Net License: CAC1815254 RTIN #0105474
'll
ProjectInformation
For:
I
Tattoo Yachts
_ 7 I "7 �y
"
5350 Steel Boulevard, Fort Pierce, FL 34946
DEC 2 0 2017
Design Conditions
Location:
Indoor: ..Heating• Cooling
Fort Pierce, FL, US
Indoor temperature (OF) 70 75
Elevation: 25 ft
Design TD (OF) 28 13
Latitude: 27°N
Relative humidity (%) 40 50
Outdoor:
Heating Cooling
Moisture difference (gr/lb) 23.2 61.5
Dry bulb (OF)
42 88
Infiltration:
Daily range (OF)
- 20
( M) Method Simplified
Wet bulb (OF)
- 78
Construction quality Poor
Wind speed (mph)
15.0 7.5
Component
Btuh/ft2
Btuh
% of load
Walls
2.7
4050
12.9
Glazing
25.2
2722
8.7
Doors
0
0
0
Ceilings
2.9
5419
17.3
Floors
0
0
0
Infiltration
66.7
7206
23.0
Ducts
330
1.1
Piping
0
0
Humidification
5296
16.9
Ventilation
6261
20.0
Adjustments
0
Total
1
1 31284
100.0
Jul 1700 LST
j'Component
Btuh/ft2
Btuh
% of load
;Walls
1.6
2424
6.1
Glazing
86.8
9378
23.7
Doors
0
0
0
Ceilings
4.2
7852
19.9
Floors
0
0
0
Infiltration
23.9
2585
6.5
Ducts
730
1.8
Ventilation
3220
8.1
Internal gains
13322
33.7
Blower
0
0
Adjustments
0
j Total
1
39511
100.0
Latent Cooling Load = 16254 Btuh
Overall U-value = 0.124 Btuh/ft2 °F
I
Data entries checked.
Gains
-�- wrightsoft- 2017-Nov-1415:10:06
�, .µ.• m , Right -Suite® Universal 2018 18.0.04 RSU25375 Page 1
...s\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W
P.O.
Ri ht-Suite® Universal 2018 Short Form Job: Tattoo Yachts
Calm 9 Date: November 14, 2017
!missing plece Second Floor By: Jimmy Conlon
ProCalcs, LLC
Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: vnvatProCalcs.Net License: CAC1815254 RTIN #0105474
For. Tattoo Yachts
5350 Steel Boulevard, Fort Pierce, FL 34946
Htg Clg
side db
(OF)
42 88
side RH
N
- 63
side wb
(OF)
- 78
ly range
(OF)
- 20
sture diff.
(gr/lb)
- 61
Heating Equipment
Make
Carrier
Model
KFC E H2901 N 09
Type
Elec strip
Efficiency
100 EFF
Heating Input
9.0 kW
Hleating Output
30.7 MBtuh
Humidifier
14.0 gpd
Leaving Air Temp
123.5 OF
Actual Heating Fan
i
522 cfm
• f,
Equipment Location
System Type
Fan Motor Heat Type
Fan & Motor Combined Efficiency
I
I
Static Pressure Across Fan
Htg Clg
Inside db
(OF)
70 75
Inside RH
N
- 50
Inside wb
(OF)
- 63
Design TD
(OF)
28 13
Cooling Equipment
Make
Carrier
Model CA14NA0600000A0/FB4CNP060L
Type
Split AC
COP / EER / SEER
14.0
Sensible Cooling
44.8
MBtuh
Latent Cooling
11.2
MBtuh
Total Cooling
56.0
MBtuh
Leaving Air Temp
55.0
OF
Actual Cooling Fan
1750
cfm
Second Floor
PEAKCV
DRAWTHRU
95.0 %
0.6 in H2O
NAME
II
Area
ftz
Heat
Loss
Sensible
Gain
Latent
Gain
Htg
cfm
Clg
cfm
Time
f;
AHU
20
118
35
102
0
0
Jul 1700 LST
Storage 1
537
8608
13709
3956
143
604
Jul 1700 LST
Stairs 1
160
524
137
400
0
0
Jul 1700 LST
,Storage 2
204
3203
5600
1537
53
248
Jul 1700 LST
Storage 3
524
12919
12204
7722
226
536
Jul 1700 LST
Stairs 2
72
1049
1006
300
21
45
Jul 1700 LST
Closet
(Storage
18
105
31
90
0
0
Jul 1700 LST
4
277
4178
6487
1963
67
284
Jul 1700 LST
f RR 1
63
581
712
184
13
34
Jul 1700 LST
Ibecond Floor
1875
31284
39919
16254
522
1750
Jul 1700 LST
I�
wrightsoft. 2017-Nov-14 15:10:06
1"..
Right-Suite® Universal 2018 18.0.04 RSU25375 Page 1
\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W
I I
li
I .
I,
I I
Right-Suite®Universal 2018 Load Summary Job: Tattoo YachtsDate: November14,2017
CS Second Floor By: Jimmy Conlon
We are the missing piece'
fProCalcs, LLC
•P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: vnwaProCalcs.Net License: CAC1815254 RTIN #0105474
For: Tattoo Yachts
5350 Steel Boulevard, Fort Pierce, FL 34946
C_OO.LING_ LOAD_
1.
DESIGN CONDITIONS
at Jul 1700 LST
Inside: 75 OF
Outside: 88 OF
RH: 63 %
MoistDiff: 61.5 gr/lb
2.
SOLAR RADIATION THROUGH GLASS
3.
TRANSMISSION GAINS
Sensible
Walls:
2762
Glass:
1109
Doors:
0
Partitions:
0
Floors:
0
Ceilings:
7546
4.
INTERNAL HEAT GAIN
Sensible
Occupants:
1381
Lights:
8543
Motors:
0
Appliances:
3560
5.
INFILTRATION:
Outside air cfm:
6.
SUBTOTAL: Space load
Sensible
Envelope
35852
Less external
0
Redistribution
0
7.
SUPPLY DUCT
8.
SUBTOTAL: Space load + supply duct
Actual cfm:
1750 at supply TD:
9.
VENTILATION:
Make-up air cfm:
10.
RETURNAIRLOAD:
Lighting + plenum (net)
11.
RETURN DUCT
12. TOTAL LOADS ON EQUIPMENT
Peak load at Jul 1600 LST
TD: 13 OF
Mult: 1.0 Ins.wb
Sensible
8617
11417
Latent 13484
930 -
0
163
Latent
7754
0
20
203
2334
35852
740
37012
2907
0
0
39919
63 OF
Latent
930
6824
7754
8500
16254
_ _HEATING LOAD_
13.
DESIGN CONDITIONS Mult:
1.0
Inside: 70 OF Outside: 42 OF TD:
28 OF
14.
TRANSMISSION LOSSES
12190
Walls: 4050
-
Glass: 2722
-
Doors: 0
-
Partitions: 0
-
Floors: 0
-
Ceilings: 5419
-
15.
INFILTRATION: Outside air cfm: 234
7206
i' 16.
SUBTOTAL: Space load
19397
Envelope 19397
-
Less external 0
-
Less transfer 0
-
Redistribution 0
i� 17.
SUPPLYDUCT:
330
18.
VENTILATION: Make-up air cfm: 203
6261
19.
HUMIDIFICATION
5296
Piping
0
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
31284
i
k wrilghtsoftW
2017-Nov 14 1Pa9ge1
• W . -•. Right -Suite® Universal 2018 18.0.04 RSU25375
I..s\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W
i stem Summary Job: Tattoo Yachts
Duct S
` � CaIcs C Y y Date: November 14, 2017
'We are the mWing piece' SeCOnd Floor By: Jimmy Conlon
ProCalcs, LLC
P.O. Box,882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
For: Tattoo Yachts
5350 Steel Boulevard, Fort Pierce, FL 34946
Heating
Cooling
External static pressure
0.60
in H2O
0.60 in H2O
Pressure losses
0.31
in H2O
0.31 in H2O
Available static pressure
0.29
in H2O
0.29 in H2O
Supply / return available pressure
0.145 / 0.145
in H2O
0.145 / 0.145 in H2O
Lowest friction rate
0.123
in/100ft
0.123 in/100ft
Actual air flow
522
cfm
1750 cfm
Totaljeffective length (TEL)
236 ft
I,
I Name
Design
(Btuh)
Htg
(cfm)
Clg
(Cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
i
RRI1
C 712
13
34
0.123
4.0
ox0
ShMt
71.0
165.0
st1C
stairs 2
c 963
21
45
0.186
4.0
14x4
RtFg
61.0
95.0
st1C
Storage 1
C 6394
71
302
0.260
12.0
0x 0
ShMt
6.5
105.0
st1
Storage 1-A
C 6394
71
302
0.245
12.0
Ox 0
ShMt
18.5
100.0
st1
storage 2-A
C 5251
53
248
0.236
10.0
Ox 0
ShMt
33.0
90.0
st1
Storage 3-A
C 5675
113
268
0.190
10.0
0x 0
ShMt
43.0
110.0
st1A
Storage 3-B
C 5675
113
268
0.158
10.0
Ox 0
ShMt
54.0
130.0
st1 B
storage 4
C 6011
67
284
0.130
10.0
Ox 0
ShMt
73.0
150.0
st1 C
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in)
Material
Trunk
st;1C
Peak AVF
101
363
0.123
871
7.9
10 x 6
RectFbg
st1B
SMA
Peak AVF
327
898
0.123
770
7.9
14 x 12
RectFbg
st1
SO
Peak AVF
522
1750
0.123
818
7.9
14 x 22
RectFbg
st1 B
Peak AVF
214
631
0.123
757
7.9
10 x 12
RectFbg
st1A
Bold/italic values have been manually overridden
wrightsoft ° 2017-Nov 14 15:10:06
Right -Suite® Universal 2018 18.0.04 RSU25375 Page 1
-s\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W
Grille
Htg
Clg
TEL
Design
Veloc
Diam
H x W
Stud/Joist
Duct
Name; Size (in)
(cfm)
(cfm)
(ft)
FR
(fpm)
(in)
(in)
Opening (in)
Matl
Trunk
rb1
Ox 0
522
1750
0
0
0
0
Ox 0
VIFx
Wrightsoft 2017-Now1415:10:06
Right -Suite® Universal 2018 18.0.04 RSU25375 Page 2
i s\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W
f I
,y'� �rstatic Pressure and Friction Rate
Job: Tattoo Yachts
q �ii4 �✓���si► Date: November 14, 2017
'We are the missing piece ai► Second Floor By Jimmy Conlon
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: vmwProCalcs.Net License: CAC1815254 RTIN #0105474
iLroject intormation
For: Tattoo Yachts
5350 Steel Boulevard, Fort Pierce, FL 34946
AvailablePressure
Heating
Cooling
i4
(in H2O)
(in H2O)
Extemal static pressure
0.60
0.60
Pressure losses
Coil
0.07
0.07
' Heat exchanger
0
0
Supply diffusers
0.03
0.03
Return grilles
0.03
0.03
Filter
0.15
0.15
Humidifier
0
0
Balancing damper
0.03
0.03
Other device
0
0
Available static pressure
II
0.29
0.29
Total•
Supply
Return
II
(ft)
(ft)
Measured length of run -out
11
0
Measured length of trunk
60
0
Equivalent length of fittings
165
0
Total length
236
0
Total effective length
I
236
I
Friction
li
Heating
Cooling
(in/100ft)
(in/100ft)
Supply Ducts
0.123 OK
0.123 OK
,Return Ducts
0.123 OK
0.123 OK
Supply 4W=35, 2B2=35, 12H1=20, 12H1=20, 12H1=20, 1C=35: TotalEL=165
,Return TotalEL=0
I
i
i
i
W rlghtsc)ft" 2017-Nov-14 15:10:06
Right -Suite® Universal 2018 18.0.04 RSU25375 Page 1
,..s\Finals\Current Docs\Tattoo Yachts - Final.rup Calc = RTS Building Front faces: W