PLAN REVIEW FORM
,¢
5160 N.W. Milner Drive ; • .. a
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit# R-18-67
Project Name American Concrete Industries BLDG Permit# 1802-0134
Address 350 North Rock Road City Fort. Pierce !�
Contractor RK Davis
Address P.O. Box City Ft Pierce
State FL Zip 34954 Telephone (772) 461-8335
� a
Architect/Engineer Velcon Engineering Telephone (772) 879-0477
Occupancy Type Industrial _ Construction Type IIA Square Feet 10,000
Occupant Load 50 per plans Number of Stories Access Box Access Key'Switch
AFS Permit FA Permit FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on CO is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all Inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper'LIL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be, located'indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
y 9. Automatic fan shutdown Is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012'EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See tieneral (votes Above ana fteauirecl mevislonsLietow
1. No mechanical plans.
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
,inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.
Page) 1 I of 1F Reviewed by Tony Jerger Date 03-09 18