HomeMy WebLinkAboutCONSTRUCTION PLANS PAGE 61-75GENERALNOTES 100. DESIGN CRITERIA 100A DESIGN BUILDING CODE A. FLORIDA BUILDING CODE, 2014 100.2 GRAVITY LOADS: A. ROOF LIVE LOADS: 1. FLAT ROOF 20 PSF 100.3 LATERAL LOADS: A. WIND LOADS (IN ACCORDANCE WITH DESIGN BUILDING CODE PER GENERAL NOTE 100.1): 1. ULTIMATE DESIGN WIND SPEED (3 SECOND GUST), Vult = 161 MPH 2. NOMINAL DESIGN WIND SPEED (3 SECOND GUST), Vasd = 125 MPH 3. RISK CATEGORY = II 4. EXPOSURE CATEGORY = C 5. ENCLOSURE CLASSIFICATION = ENCLOSED 6. INTERNAL PRESSURE COEFFICIENT (GCpi) = +/- 0.18 7. COMPONENTS AND CLADDING PRESSURES: SEE "COMPONENTS AND CLADDING WIND LOADS" TABLE, AND "COMPONENTS AND CLADDING WIND PRESSURE DIAGRAM" 110. GENERAL 110.1 THESE DRAWINGS HAVE BEEN PRODUCED ENTIRELY ON ATLANTIC ENGINEERING SERVICES CADD SYSTEM. ANY OTHER LETTERING, LINES, OR SYMBOLS, OTHER THAN PROFESSIONAL STAMPS AND SIGNATURES, HAVE BEEN MADE WITHOUT THE AUTHORIZATION OF ATLANTIC ENGINEERING SERVICES AND ARE INVALID. 110.2 THE STRUCTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL STRUCTURAL FEATURES, UNLESS NOTED OTHERWISE. THE ARCHITECTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL DIMENSIONS. 110.3 DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS, ONLY DIMENSIONS INDICATED ON DRAWINGS MAY BE USED TO ESTABLISH THE LOCATION AND EXTENT OF STRUCTURAL WORK. IF A REQUIRED DIMENSION IS NOT FURNISHED ON DRAWINGS, THE CONTRACTOR SHALL SUBMIT A REQUEST FOR INFORMATION TO OBTAIN THE DIMENSION. 110.4 THE METHOD AND FREQUENCY OF ATTACHING MECHANICAL EQUIPMENT UNITS, ETC., TO THE STRUCTURAL ELEMENTS SHALL BE SUBJECT TO THE ENGINEER'S REVIEW AND APPROVAL. 110.5 UNLESS OTHERWISE INDICATED, STRUCTURAL COMPONENTS SUPPORTING MECHANICAL EQUIPMENT HAVE NOT BEEN DESIGNED FOR THE VIBRATIONAL EFFECTS OF THE EQUIPMENT. THE CONTRACTOR SHALL PROVIDE VIBRATION ISOLATORS FOR ANY MECHANICAL EQUIPMENT MOUNTED TO THE STRUCTURE IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. 110.6 THE CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION SEQUENCING AND ALL TEMPORARY SHORING AND STABILIZATION THAT IS REQUIRED TO PERFORM THEIR WORK. WHERE REQUIRED, THE CONTRACTOR SHALL RETAIN THE SERVICES OF A REGISTERED PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN THE STATE OF FLORIDA FOR THE DESIGN OF TEMPORARY SHORING AND BRACING. THE CONTRACTOR IS RESPONSIBLE FOR PERFORMING THEIR WORK IN A SAFE AND SATISFACTORY MANNER. 110.7 ALL STRUCTURAL WORK SHALL BE INSPECTED IN ACCORDANCE WITH THE BUILDING CODE AND ALL LOCAL ORDINANCES. THE OWNER SHALL ENGAGE AN EXPERIENCED, QUALIFIED INSPECTION AGENCY, SUBJECT TO THE REVIEW OF THE ARCHITECT, TO PERFORM ALL INSPECTION WORK, AS REQUIRED. 120. SHOP DRAWINGS 120.1 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR REVIEW BY ATLANTIC ENGINEERING SERVICES AND THE PROJECT ARCHITECT. SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL COMPONENTS INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING: A. FABRICATED STRUCTURAL STEEL B. REINFORCING STEEL FOR CONCRETE AND MASONRY C. CONCRETE AND/OR MASONRY POST -INSTALLED ANCHORS D. PRECAST CONCRETE LINTELS (IF USED) E. PREFABRICATED WOOD TRUSSES INCLUDING COLD FORMED METAL FABRICATIONS UTILIZED IN TRUSS -TO -FRAME CONNECTIONS. 120.2 SHOP DRAWINGS TO BE SUBMITTED SHALL PROVIDE COMPLETE INFORMATION FOR THE PRODUCTS OR COMPONENTS TO BE SUPPLIED. SUBMITTAL INFORMATION SHALL INCLUDE, BUT NOT BE LIMITED TO: MEMBER SIZES AND DIMENSIONS; GRADES OF MATERIAL FURNISHED; MATERIAL PREPARATION REQUIRED; MATERIAL FINISH AND MATERIAL COATINGS TO BE FURNISHED; INFORMATION REGARDING CUTS, COPES, AND HOLES REQUIRED FOR OTHER TRADES; END CONNECTIONS; CAMBER AND OTHER DEVIATION FROM LINE; SPECIAL ERECTION AND/OR INSTALLATION PROCEDURES, INCLUDING REQUIREMENTS FOR TEMPORARY STABILIZATION. 120.3 ALL SHOP DRAWING RESUBMITTALS AND RECORD COPY SUBMITTALS SHALL HAVE ALL REVISIONS SUBSEQUENT TO THE PREVIOUS SUBMISSION CLOUDED OR OTHERWISE IDENTIFIED ON THE RESUBMITTED SHEETS. RESUBMITTALS AND RECORD COPY SUBMITTALS WITHOUT IDENTIFICATION OF REVISIONS WILL BE REJECTED WITHOUT REVIEW. 120.4 THE CONTRACTOR SHALL NOT DIRECTLY INCORPORATE THE STRUCTURAL DRAWINGS, OR PORTIONS THEREOF, INTO SHOP DRAWINGS OR ERECTION DRAWINGS TO BE SUBMITTED FOR THIS PROJECT WITHOUT FIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF ATLANTIC ENGINEERING SERVICES. SUBMITTED SHOP DRAWINGS WHICH CONTAIN COPIES OR REPRODUCTIONS OF ANY PORTION OF THE STRUCTURAL DRAWINGS WITHOUT THE EXPRESS WRITTEN PERMISSION OF ATLANTIC ENGINEERING SERVICES WILL BE RETURNED REJECTED. PERMISSION FOR A SPECIFIC CONTRACTOR OR SUB -CONTRACTOR TO USE PORTIONS OF THE STRUCTURAL DRAWINGS IN THEIR PREPARATION OF SHOP DRAWINGS REQUIRES THAT CONTRACTOR OR SUB -CONTRACTOR TO ENTER INTO A WRITTEN AGREEMENT WITH ATLANTIC ENGINEERING SERVICES AND TO PAY A SERVICE FEE. SUCH AGREEMENT IS NON-TRANSFERRABLE AND IS EXTENDED ONLY TO THAT CONTRACTOR FOR THE DURATION OF THIS PROJECT. 120.5 THE CONTRACTOR SHALL SUBMIT ELECTRONIC COPIES OF SHOP DRAWINGS IN LIEU OF PRINTED COPIES. ELECTRONIC COPIES SHALL BE SUBMITTED TO ATLANTIC ENGINEERING SERVICES IN PDF FILE FORMAT, WITH ONE (1) ELECTRONIC FILE PER PACKAGE SUBMISSION. ATLANTIC ENGINEERING SERVICES WILL REVIEW, ANNOTATE, AND RETURN ONE (1) ELECTRONIC PACKAGE TO THE ARCHITECT TO REVIEW AND DISTRIBUTE TO THE CONTRACTOR. 120.6 THE REVIEW OF SHOP DRAWINGS AND OTHER SUBMITTALS FOR THIS PROJECT IS FOR CONFORMANCE WITH THE DESIGN CONCEPT AND FOR GENERAL COMPLIANCE WITH THE INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS. COMMENTS REGARDING THESE SUBMITTALS DO NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR PERFORMING HIS WORK IN A SAFE AND SATISFACTORY MANNER. 200. FOUNDATIONS - GENERAL 200.1 FOUNDATIONS HAVE BEEN DESIGNED AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH CRITERIA ESTABLISHED BY UNIVERSAL ENGINEERING SCIENCES, INC. IN THEIR GEOTECHNICAL REPORT DATED JUNE 13, 2017 (UNIVERSAL PROJECT NO. 0330.1700067.0000). 200.2 THE CONTRACTOR SHALL OBSERVE WATER CONDITIONS AT THE SITE AND TAKE THE NECESSARY PRECAUTIONS TO ENSURE THAT THE FOUNDATION EXCAVATIONS REMAIN DRY DURING CONSTRUCTION. PROVIDE FOR DEWATERING AS NECESSARY. 200.3 THE CONTRACTOR SHALL USE EXTREME CAUTION DURING EXCAVATION. SUCH EXCAVATION SHALL BE PERFORMED IN SUCH A MANNER AS TO MAINTAIN THE STRUCTURAL INTEGRITY OF ALL EXISTING STRUCTURES TO REMAIN. PROVIDE TEMPORARY SHORING AS REQUIRED. 200.4 CONCRETE SLABS ON GRADE HAVE BEEN DESIGNED TO BEAR ON COMPACTED SUBGRADE SOILS OR PROPERLY COMPACTED FILL AS PER THE REPORT REFERENCED IN NOTE 200.1. 210. SHALLOW FOUNDATIONS 210.1 FOUNDATIONS HAVE BEEN DESIGNED AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH CRITERIA ESTABLISHED IN THE GEOTECHNICAL REPORT REFERENCED IN NOTE 200.1. 210.2 SPREAD FOOTINGS HAVE BEEN DESIGNED TO BEAR ON UNDISTURBED SOILS OR PROPERLY COMPACTED FILL HAVING AN ALLOWABLE BEARING CAPACITY OF 2,500 PSF, AS PER THE GEOTECHNICAL REPORT REFERENCED IN NOTE 200.1. 210.3 ELEVATIONS SHOWN ON THE DRAWINGS AT WHICH FOUNDATIONS ARE TO BEAR ARE APPROXIMATE. MATERIAL ON WHICH FOUNDATIONS ARE TO BEAR SHALL HAVE AT LEAST THE ABOVE NOTED CAPACITY. ALL EXTERIOR FOOTINGS SHALL BEAR A MINIMUM OF 18" BELOW FINISHED GRADE. 210.4 STEP FOOTINGS BELOW ALL SANITARY AND WATER LINES. PROVIDE STEPS IN THE FOUNDATIONS IN ACCORDANCE WITH THE TYPICAL DETAILS. COORDINATE THE EXACT LOCATION AND ELEVATION OF THE PLUMBING LINES WITH THE MECHANICAL AND PLUMBING DRAWINGS AND CONTRACTORS. PROVIDE SLEEVES IN THE FOUNDATION WALLS AS REQUIRED FOR PIPE PENETRATIONS. 210.5 THE CONTRACTOR SHALL RETAIN THE SERVICES OF A PROFESSIONAL GEOTECHNICAL ENGINEER, SUBJECT TO THE APPROVAL OF THE ARCHITECT, TO INSPECT THE FOUNDATIONS, BEARING LEVELS, ETC., AND VERIFY THAT THE MATERIAL ON WHICH FOUNDATIONS BEAR HAS AT LEAST THE ABOVE NOTED CAPACITY. 300. REINFORCED CONCRETE 300.1 ALL REINFORCED CONCRETE WORK SHALL BE IN CONFORMANCE WITH THE "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (ACI 318, LATEST EDITION) AND SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301, LATEST EDITION) OF THE AMERICAN CONCRETE INSTITUTE. 300.2 MINIMUM DESIGN COMPRESSION STRENGTH (F'c) REQUIRED AT 28 DAYS: A. FOUNDATIONS 3000 PSI B. SLABS ON GRADE 4000 PSI C. COLUMNS AND BEAMS 4000 PSI 300.3 MAXIMUM WATER TO CEMENTITIOUS MATERIALS RATIO: A. FOUNDATIONS 0.60 B. SLABS ON GRADE 0.45 C. COLUMNS AND BEAMS 0.45 00 CONCRETE SHALL E NORMAL WEIGHT CONCRETE MINIMUM 144 PCF 3 .4 ALL L B WE ( ) WITH ALL CEMENT CONFORMING TO ASTM C150, TYPE I, II OR 1/II. MAXIMUM AGGREGATE SIZE SHALL BE 1-1/2" FOR FOOTINGS AND 3/4" FOR WALLS AND SLABS, CONFORMING TO ASTM C33. 300.5 REINFORCEMENT A. DEFORMED BARS ASTM A615, GRADE 60 B. WELDED WIRE FABRIC ASTM A1064 300.6 MINIMUM COVER FOR CAST -IN -PLACE CONCRETE REINF., UNLESS OTHERWISE SHOWN ON DRAWINGS, SHALL BE AS FOLLOWS: A. FOUNDATIONS 3" B. COLUMNS (OVER VERT. REINF.) 2" C, BEAMS (OVER MAIN REINF.) 2" D. SLABS CAST AGAINST EARTH 2" 300.7 SPLICES IN REINFORCEMENT, WHERE PERMITTED, SHALL BE AS FOLLOWS: A. WELDED WIRE MESH 8" B. ALL OTHERS CLASS "B" TENSION, CASE "1" MINIMUM, UNLESS OTHERWISE NOTED 300.8 CLASS T', CASE -1" TENSION SPLICES IN INCHES, SHALL BE AS FOLLOWS: 3000 PSI 4000 PSI SIZE TOP BARS ALL OTHERS TOP BARS ALL OTHERS #3 (#10) 28 22 24 19 #4 (#13) 37 29 32 25 #5 (#16) 47 36 40 31 #6 (#19) 56 43 48 37 #7 (#22) 81 63 70 54 300.9 SPLICES IN TOP REINFORCEMENT SHALL BE LOCATED AT MIDSPAN AND SPLICES IN BOTTOM REINFORCEMENT SHALL BE LOCATED OVER SUPPORTS, UNLESS NOTED OTHERWISE. 300.10 BARS IN BEAMS SHALL TERMINATE IN A CLASS "B" TENSION SPLICE OR HOOK AT DISCONTINUOUS END. 300.11 PARALLEL REINFORCEMENT PLACED IN TWO OR MORE LAYERS SHALL HAVE A CLEAR DISTANCE BETWEEN LAYERS OF V. UPPER LAYER BARS SHALL BE PLACED DIRECTLY ABOVE BARS IN THE BOTTOM LAYER. 300.12 ALL REINFORCING SHALL BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES DURING PLACEMENT OF CONCRETE. REINFORCING SUPPORTS FOR ALL EXPOSED CONCRETE SHALL BE GALVANIZED WITH PLASTIC COATED FEET. ALL WELDED WIRE MESH SHALL BE CHAIRED IN ACCORDANCE WITH THE DESIGN BUILDING CODE. 300.13 ALL TIES SHALL HAVE 135 DEGREE HOOKS. 300.14 PROVIDE 1/2" PREMOULDED EXPANSION MATERIAL WHERE SLAB ON GRADE IS POURED AROUND COLUMNS AND AGAINST WALLS UNLESS OTHERWISE SHOWN ON DRAWINGS. 300.15 CONTRACTION JOINTS FOR SLABS ON GRADE SHALL BE SPACED NO MORE THAN 12'-0" ON CENTER. PANELS FORMED BY JOINTS OR SLAB EDGES SHALL BE AS SQUARE AS POSSIBLE WITH A LENGTH -TO -WIDTH RATIO NOT TO EXCEED 1.5. 300.16 CONTRACTOR SHALL VERIFY DIMENSIONS AND LOCATIONS OF ALL SLOTS, PIPE SLEEVES, ETC., AS REQUIRED FOR MECHANICAL TRADES BEFORE CONCRETE IS PLACED. 300.17 PIPES OR CONDUITS PLACED IN SLABS SHALL NOT HAVE AN OUTSIDE DIAMETER LARGER THAN 1/3 THE SLAB THICKNESS AND SHALL NOT BE SPACED CLOSER THAN 3 DIAMETERS ON CENTERS. ALUMINUM CONDUITS SHALL NOT BE PLACED IN CONCRETE. NO CONDUITS SHALL BE PLACED IN SLAB WITHIN 12" OF COLUMN FACE OR FACE OF BEARING WALL. NO CONDUITS MAY BE PLACED IN EXTERIOR SLABS. 300.18 PRIOR TO CONCRETE PLACEMENT, THE CONTRACTOR SHALL SUBMIT A CONCRETE MIX DESIGN PREPARED IN ACCORDANCE WITH ACI-318 CHAPTER 5 TO THE STRUCTURAL ENGINEER FOR REVIEW. 350. CONCRETE/MASONRY ANCHORS 350.1 ALL ADHESIVE STUD ANCHORS FOR ANCHORING TO CONCRETE SHALL BE "HILTI HIT-HY 200 ADHESIVE CONCRETE ANCHORS" AS MANUFACTURED BY HILTI FASTENING SYSTEMS, INC. (OR APPROVED EQUIVALENT). 350.2 THE "HAS ANCHOR ROD" SHALL CONFORM TO ASTM A36 STEEL, THE "HAS SUPER ANCHOR ROD" SHALL CONFORM TO ASTM A193 STEEL, AND THE NUT SHALL CONFORM TO ASTM A563, GRADE A. 350.3 THE SPACING AND MINIMUM EMBEDMENT OF POST -INSTALLED ANCHORS SHALL BE AS INDICATED ON DRAWINGS. THE INSTALLATION OF THE ANCHORS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDED PROCEDURES. 420. MASONRY 420.1 ALL MASONRY WORK SHALL BE IN CONFORMANCE WITH THE LATEST EDITION OF "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (TMS 402/ACI 530/ASCE 5) AND THE "SPECIFICATIONS FOR MASONRY STRUCTURES" (TMS 602/ACI 530.1/ASCE 6) OF THE MASONRY SOCIETY. 420.2 ALL MASONRY WORK TO BE EXECUTED IN COLD WEATHER SHALL BE IN CONFORMANCE WITH THE RECOMMENDATIONS FOR COLD WEATHER CONSTRUCTION OF THE LATEST EDITION OF "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (TMS 402/ACI 530/ASCE 5) AND THE "SPECIFICATIONS FOR MASONRY STRUCTURES" (TMS 602/ACI 530.1/ASCE 6) OF THE MASONRY SOCIETY WITH THE FOLLOWING ADDITION TO THE REQUIREMENTS OF TMS 602/ACI 530.1/ASCE 6, SECTION 1.8•C: FOR ALL CONDITIONS WHEN TEMPERATURES FALL BELOW 40 DEGREES F, THE TEMPERATURE OF THE NEWLY LAID MASONRY OR NEWLY GROUTED MASONRY SHALL BE MAINTAINED ABOVE 32 DEGREES (F) FOR A MINIMUM OF 24 HOURS USING THE METHODS DESCRIBED IN TMS 602/ACI 530.1/ASCE 6. 420.3 MORTAR SHALL CONFORM TO THE PROPORTION SPECIFICATION OF ASTM C270, TYPE S. 420.4 GROUT SHALL CONFORM TO ASTM C476 AND AS FOLLOWS: A. COMPRESSIVE STRENGTH (F'c) OF GROUT = F'm AS INDICATED BELOW BUT NO LESS THAN 3,000 PSI. B. SLUMP OF GROUT SHALL BE 8 TO 11 INCHES AS MEASURED ACCORDING TO ASTM C143. C. MAX. AGGREGATE SIZE SHALL BE 3/8" (AGGREGATE GRADED TO PRODUCE FINE GROUT IN CONFORMANCE WITH ASTM C476 AND C404). 420.5 LIMIT CEMENTITIOUS MATERIALS IN MORTAR TO: PORTLAND CEMENT CONFORMING TO ASTM C150 TYPE I; LIME CONFORMING TO ASTM C207; MORTAR CEMENT CONFORMING TO ASTM C1329; AND MASONRY CEMENT CONFORMING TO ASTM C91. 420.6 PROVIDE SOLID AND HOLLOW LOAD BEARING CONCRETE BLOCK UNITS CONFORMING TO ASTM C90. FURNISH CONCRETE BLOCK WITH NET AREA COMPRESSIVE STRENGTH AS SPECIFIED BY TABLE 2 OF TMS 602/ACI 530.1/ASCE 6, SECTION 1.4 B.2 BASED ON THE UNIT STRENGTH METHOD. 420.7 MINIMUM 28-DAY ULTIMATE COMPRESSIVE STRENGTH OF MASONRY: A. Fm 1500 PSI 420.8 HORIZONTAL JOINT REINFORCING FOR ALL EXTERIOR AND LOAD BEARING WALLS SHALL BE GALVANIZED TRUSS OR LADDER TYPE DUR-O-WAL, OR EQUIVALENT AS APPROVED BY THE ENGINEER WITH 2-9 GAUGE LONGITUDINAL WIRE AND 9 GAUGE CROSS WIRE, SPACED AT 16" CENTER TO CENTER, UNLESS NOTED OTHERWISE. PROVIDE ADDITIONAL LAYERS OF JOINT REINFORCEMENT IN THE FIRST TWO COURSES ABOVE AND BELOW A MASONRY OPENING. PROVIDE LAP AS RECOMMENDED BY MANUFACTURER WITH A MINIMUM OF 6". DISCONTINUE JOINT REINFORCING AT CONTROL JOINTS. PROVIDE "L" SHAPE AND "T" SHAPE DUR-O-WAL AT ALL INTERSECTION CORNERS WITH Bfl MINIMUM LAP. SEE TYPICAL DETAILS. 420.9 PROVIDE "DOVE -TAIL" ANCHORS AT 16" OC VERTICALLY FOR ALL MAOSNRY PLACED ADJACENT TO CAST -IN -PLACE COLUMNS. 420.10 FULL BED AND HEAD JOINTS SHALL BE USED. MASONRY WALLS SHALL BE SECURELY B ED UNTIL FLOOR OR ROOF 420.11 ALL MASORAC SYSTEM HAS BEEN INSTALLED AND HAS BECOME CAPABLE OF STABILIZING THE WALLS. 42 GROUT SOLID ALL CELLS IN MASONRY UNITS INSTALLED BELOW GRADE. 0.12 GR U 420.13 GROUT SOLID ALL CELLS CONTAINING REINFORCING, AND WHERE INDICATED ON PLANS AND SECTIONS. 420.14 PROVIDE FINE GROUT PER ASTM C476 WHEN WIDTH OF GROUT SPACE IS LESS THAN 2". PROVIDE COARSE GROUT FOR GROUT SPACE WIDTHS TOR GREATER. PROVIDE FINE GROUT WHEN REINFORCING HAS LESS THAN 1/2" CLEARANCE. 420.15 PROVIDE CONTROL JOINTS IN MASONRY CONSTRUCTION PER THE TYPICAL DETAILS. THE CONTRACTOR SHALL SUBMIT THE PROPOSED CONTROL JOINT LAYOUT TO THE ARCHITECT FOR REVIEW AND APPROVAL. PROVIDE MASONRY CONTROL JOINTS IN ACCORDANCE WITH THE FOLLOWING GUIDELINES UNLESS OTHERWISE INDICATED ON DRAWINGS: A. CONTROL JOINTS SHALL BE LOCATED AT A MAXIMUM SPACING OF 20 FEET ON CENTER IN THE WALL FIELD AND A MAXIMUM OF 10 FEET FROM BUILDING CORNERS B. LOCATE CONTROL JOINTS AT MAJOR HEIGHT CHANGES, CHANGES IN WALL THICKNESS AND AT WALL OPENINGS. C. CONTROL JOINTS IN PARAPETS SHALL BE SPACED AT 15 FEET ON CENTER MAXIMUM. WHERE JOINTS IN PARAPETS CAN NOT BE ALIGNED WITH JOINTS IN WALL FIELD, PROVIDE CONTROL JOINTS IN THE PARAPET ONLY AT HALF THE WALL FIELD SPACING. D. CONTROL JOINTS SHALL BE A MINIMUM WIDTH OF 3/8" AND SHALL UTILIZE COMPRESSIBLE MATERIAL WITH A MINIMUM EXTENSIBILITY OF 60%. 420.16 PROVIDE CLEAN OUT AND INSPECTION HOLES AT BOTTOM OF MASONRY WALL IN ACCORDANCE WITH MASONRY CODE AT REINFORCING IF HIGH LIFT GROUTING (OVER 4 FEET HIGH) IS USED. 420.17 DEFORMED BAR REINFORCEMENT SHALL CONFORM TO ASTM A615, GRADE 60. PROVIDE LAP SPLICES OF 48 BAR DIAMETERS MINIMUM. PROVIDE BAR SPACERS AS REQUIRED TO PROPERLY LOCATE REINFORCING. 420.18 MASONRY COURSING SHOWN IN SECTION IS APPROXIMATE. REFER TO PLANS AND ELEVATIONS FOR ACTUAL COURSING. COORDINATE ACTUAL COURSING REQUIREMENTS WITH ARCHITECTURAL DRAWINGS. 420.19 ALL ANCHOR BOLTS SHALL CONFORM TO ASTM A307. 510. STRUCTURAL STEEL 510.1 ALL STRUCTURAL STEEL WORK SHALL BE IN ACCORDANCE WITH ANSI/AISC 360-10 -"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS." LOADS, FORCES AND MOMENTS INDICATED ARE SERVICE LEVEL AND ARE INTENDED FOR USE WITH THE ALLOWABLE STRENGTH DESIGN PROVISIONS OF THE CODE. 510.2 GRADE OF STEEL A. STRUCTURAL W SHAPES ASTM A992 B. STRUCTURAL M, S, C, MC, AND L SHAPES ASTM A36 C. STRUCTURAL HP SHAPES ASTM A572, GRADE 50 D. STEEL TUBES (HSS SHAPES) ASTM A500, GRADE B E. STEEL PIPE (ROUND HSS) ASTM A500, GRADE B F. PLATES AND BARS ASTM A36 5103 ALL WELDING SHALL BE IN ACCORDANCE WITH THE STRUCTURAL WELDING CODE, AWS D1.1, LATEST EDITION, OF THE AMERICAN WELDING SOCIETY. ELECTRODES SHALL BE E70XX FOR MANUAL ARC WELDING AND F7X-EXXX FOR SUBMERGED ARC WELDING. 510.4 ALL STRUCTURAL STEEL FRAMES SHALL BE SECURELY BRACED UNTIL ALL FLOOR SLABS, ROOF DECKS, AND SHEAR WALLS HAVE BEEN INSTALLED AND BECOME CAPABLE OF STABILIZING THE FRAMES. 510.5 ALL STRUCTURAL STEEL WORK, EXCEPT PORTIONS OF MEMBERS TO BE WELDED, FIELD BOLTED, GALVANIZED, OR FIREPROOFED, SHALL BE SHOP PAINTED WITH PAINT CONFORMING TO STEEL STRUCTURES PAINTING COUNCIL (SSPC) PAINT 25. APPLY PRIME PAINT ACCORDING TO SSPC PAINT SYSTEM GUIDE NO.7.00 CLEAN STEEL FREE OF LOOSE SCALE, RUST, OIL AND GREASE. ADDITIONAL AREAS SHALL BE FIELD PAINTED AFTER WELDING. 510.6 BOLT AND WELD TESTING: A. ALL SHOP AND FIELD BOLTS SHALL BE TESTED PER AISC REQUIREMENTS. B. ALL WELDS SHOULD BE VISUALLY INSPECTED. 510.7 LEVELING GROUT SHALL BE NON -SHRINK, NON-METALLIC TYPE, FACTORY PRE -MIXED GROUT TESTED IN ACCORDANCE WITH CE-CRD-C621 OR ASTM C109, WITH fc OF NOT LESS THAN 5000 PSI. 510.8 ALL ANCHOR BOLTS SHALL BE ASTM A36 OR ASTM F1554, GRADE 36 AND A MINIMUM 3/4" DIAMETER WITH A MINIMUM CONCRETE EMBEDMENT OF 12" UNLESS NOTED OTHERWISE. 610. STRUCTURALLUMBER 610.1 ALL STRUCTURAL LUMBER WORK SHALL BE IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION" (NDS - LATEST EDITION) PUBLISHED BY THE AMERICAN WOOD COUNCIL. 610.2 ALL STRUCTURAL LUMBER SHALL BE AS A MINIMUM NO.2 GRADE SOUTHERN PINE AND SHALL HAVE AT LEAST THE FOLLOWING MINIMUM ALLOWABLE DESIGN STRESSES (NOT INCORPORATING THE SIZE ADJUSTMENT FACTOR (CF)) AND MODULUS OF ELASTICITY AT A MAXIMUM MOISTURE CONTENT OF 19%: A. Fb.(BENDING) 750 PSI B. Fv.(SHEAR) 175 PSI C. Fc.(COMPRESSION) 1,250 PSI D. Ft.(TENSION) 450 PSI E. E 1,400,000 PSI 610.3 ALL LUMBER SHALL COMPLY WITH PS 20 "AMERICAN SOFTWOOD LUMBER STANDARD" AND WITH THE APPLICABLE RULE OF INSPECTION AGENCIES CERTIFIED BY AMERICAN LUMBER STANDARD. FACTORY -MARK EACH PIECE OF LUMBER WITH GRADE STAMP OF INSPECTION AGENCY EVIDENCING COMPLIANCE WITH GRADING RULE REQUIREMENTS. 610.4 STRUCTURAL STEEL PLATES, ANGLES, ETC., SHALL BE ASTM A36. CONTRACTOR TO SUBMIT SHOP DRAWINGS ON ALL MISCELLANEOUS METALS FOR REVIEW BY STRUCTURAL ENGINEER. 610.5 ALL BOLTS SHALL BE 3/4" DIAMETER ASTM A307 UNLESS NOTED OTHERWISE WITH 2 WASHERS PER BOLT UNLESS OTHERWISE NOTED. 610.6 ALL LUMBER FOR SILL PLATES, TOP PLATES, AND OTHER WOOD WHICH MAY BE EXPOSED TO WEATHER OR EARTH OR IN CONTACT WITH CONCRETE, OR OTHER CEMENTITIOUS AERIAL SHALL BE PRESSURE MASONRY,MT TREATED WITH WATER -BORNE PRESERVATIVES. PRESSURE TREATMENT SHALL COMPLY WITH REQUIREMENTS OF AWPA STANDARDS C2 AND LP-22. 610.7 PROVIDE NAILING PATTERN IN COMPLIANCE WITH THE DESIGN BUILDING CODE'S RECOMMENDED FASTENING SCHEDULE WHEN JOINING TWO OR MORE FRAMING MEMBERS. 610.8 ALTERNATE CONNECTION DETAILS MAY BE USED IF SUCH DETAILS ARE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL. HOWEVER, THE ENGINEER SHALL BE THE SOLE JUDGE OF ACCEPTANCE AND THE CONTRACTOR'S BID SHALL ANTICIPATE THE USE OF THOSE SPECIFIED DETAILS SHOWN ON THE DRAWINGS THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN OF SUCH ALTERNATE DETAILS WHICH HE PROPOSES. 620, STRUCTURAL WOOD PANELSM/OOD SHEATHING 620.1 FURNISH PANELS THAT ARE EACH FACTORY MARKED WITH A CERTIFICATION STAMP EVIDENCING COMPLIANCE WITH GRADE AND SPAN RATING REQUIREMENTS. THE CENTER -TO -CENTER SPACING IN INCHES SHALL NOT EXCEED THE SPAN RATING STAMPED ON THE PANELS. INSTALLATION OF THE PANELS SHALL BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE APA, 620.2 PANELS SHALL COMPLY WITH USDOC PS-1 OR PS-2 AND APA PRP-108 AND SHALL MEET THE FOLLOWING REQUIREMENTS: A. WALL SHEATHING: 1. MIN. THICKNESS = 5/8" 2. BOND CLASSIFICATION = EXPOSURE 1 3. GRADE = APA RATED SHEATHING 4. SPAN RATING = AS REQUIRED TO SUIT STUD SPACING B. ROOF SHEATHING: 1. MIN. THICKNESS = 5/8" 2. BOND CLASSIFICATION = EXPOSURE 1 3. GRADE = APA RATED SHEATHING 4. SPAN RATING = AS REQUIRED TO SUIT JOIST/TRUSS SPACING 620.3 ALL PANELS WHICH HAVE ANY EDGE OR FACE PERMANENTLY EXPOSED TO THE WEATHER SHALL BE CLASSED EXTERIOR, EXCEPT OPEN SOFFITS OR ROOF SHEATHING EXPOSED ON THE UNDERSIDE MAY BE CLASSED EXPOSURE1. 620.4 ALL ROOF PANELS SHALL HAVE THE END JOINTS LOCATED OVER SUPPORTS AND SHALL HAVE THE ROWS STAGGERED ONE HALF PANEL LENGTH FROM ADJACENT PANELS. PROVIDE 1/8" SPACE AT PANEL ENDS AND EDGES. 620.5 ALL WALL PANELS SHALL HAVE THE END JOINTS LOCATED OVER SUPPORTS. 620.6 THE USE OF ORIENTED STRAND BOARD STRUCTURAL PANELS PROHIBITED. 620.7 ALL ROOF STRUCTURAL PANELS SHALL BE NAILED WITH 10d SPIRAL OR RING SHANK NAILS AT 6" OC AT ALL INTERMEDIATE SUPPORTS AND 4" OC AT ALL ENDS AND EDGES. BLOCKING SHALL BE PROVIDED AT ALL UNSUPPORTED PANEL EDGES. 620.8 ALL WALL STRUCTURAL PANELS SHALL BE NAILED TO WOOD SUPPORTS WITH 8d COMMON NAILS AT 6" ON CENTER AT ALL ENDS, EDGES, AND INTERMEDIATE SUPPORTS AND TO COLD -FORMED STEEL SUPPORTS WITH #6 TEK SCREWS AT ALL ENDS, EDGES, AND INTERMEDIATE SUPPORTS. FASTENER SPACING SHALL BE 4" ON CENTER AT CORNERS. 620.9 ALL PLYWOOD PANELS SHALL COMPLY WITH THE WIND UPLIFT REQUIREMENTS OF NM519 FOR FULLY -WIND -RESISTIVE ROOF ASSEMBLIES COMPLYING WITH UL CLASS 90 CLASSIFICATION. 635. WOOD TRUSSES 635.1 WOOD TRUSSES SHALL CONFORM TO THE MOST CURRENT APPLICABLE EDITION OF THE DESIGN SPECIFICATIONS FOR LIGHT METAL PLATE CONNECTED WOOD ROOF TRUSSES, OF THE TRUSS PLATE INSTITUTE, INC. AND THE NATIONAL DESIGN SPECIFICATIONS FOR STRESS GRADE LUMBER AND ITS FASTENING, OF THE NATIONAL FOREST PRODUCTS ASSOCIATION. 635.2 WOOD ROOF TRUSSES SHALL BE DESIGNED TO SUPPORT THE LOADS INDICATED BELOW AT THE SPACING INDICATED ON THE DRAWINGS. A. DEAD LOADS: 1. UNIFORM TOP CHORD DEAD LOAD 15 PSF + MECH EQUIP. 2. UNIFORM BOTTOM CHORD DEAD LOAD 10 PSF 3. BOTTOM CHORD CONCENTRATED LOAD AT ANY LOCATION ON BOTTOM CHORD 300 LBS. B. LIVE LOADS= SEE DESIGN CRITERIA GENERAL NOTES C. LATERAL LOADS = SEE DESIGN CRITERIA GENERAL NOTES 635.3 THE DEFLECTION OF THE FLOOR AND ROOF TRUSSES UNDER THE INDICATED LOADS AND AT THE SPAN AND SPACINGS SHOWN ON THE CONTRACT DRAWINGS SHALL MEET THE FOLLOWING CRITERIA: A. ROOF TRUSSES: THE DEFLECTION DUE TO THE TOTAL ROOF LOAD SHALL NOT EXCEED THE SPAN LENGTH/240. THE DEFLECTION DUE TO THE ROOF LIVE/SNOW LOAD SHALL NOT EXCEED THE SPAN LENGTH/360. DETERMINATION OF THE DEAD LOAD DEFLECTION SHALL UTILIZE A TIME DEPENDENT DEFORMATION (CREEP) FACTOR OF 2.0. 635.4 THE WOOD TRUSS MANUFACTURER SHALL SPECIFY AND PROVIDE ALL BRACING AT TOP AND BOTTOM CHORDS REQUIRED TO STABILIZE THE ROOF STRUCTURE DURING AND AFTER CONSTRUCTION, IN ADDITION TO THE BRACING INDICATED ON THE STRUCTURAL DRAWINGS. 635.5 THE WOOD TRUSS MANUFACTURER SHALL SUBMIT STRUCTURAL CALCULATIONS STAMPED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN THE STATE OF FLORIDA FOR ALL TRUSS TYPES, WHICH INDICATE TRUSS CAPACITIES AND DEFLECTIONS. 635.6 ERECTION SHALL BE IN ACCORDANCE WITH TRUSS PLATE INSTITUTE RECOMMENDATIONS. 635.7 NO SPLICES IN WEBS, CHORDS, OR OTHER LOAD CARRYING MEMBERS MAY BE MADE WITHOUT REVIEW AND APPROVAL ON THE FINAL TRUSS SHOP DRAWINGS WHICH INCLUDE SPECIFIC LOCATIONS AND DETAILS FOR ANY SUCH SPLICE(S). 635.8 TEMPORARY TRUSS BRACING SHALL BE INSTALLED IN ACCORDANCE WITH "RECOMMENDEDSPECIFICATIONS IN DESIGN SPEC IC IONS FOR TEMPORARY BRACING OF METAL PLATE CONNECTED WOOD TRUSSES" (DSB-89) AND "COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLING AND BRACING METAL PLATE CONNECTED WOOD TRUSSES" (HIB-91). INSTALL ALL WEB BRACING REQUIRED BY THE TRUSS DESIGNER. TEMPORARY BOTTOM CHORD WEB BRACING SHALL REMAIN PERMANENTLY IN PLACE. THE BOTTOM CHORD BRACING SHALL NOT EXCEED 10' FOR TRUSSES WHERE NO SHEATHING IS ATTACHED TO THE TRUSS BOTTOM CHORD OR WITH TRUSS BOTTOM FILLER. PROVIDE 2X4 LATERAL BRACING AT 36" ON CENTER UNDER PIGGYBACK TRUSSES. AT TRUSSES REQUIRING WEB BRACING, PROVIDE 2X4 DIAGONAL AT 20' MAX NAILED TO WEBS FROM ROOF TO BOTTOM CHORD. ALL BRACING SHALL BE NAILED WITH 2-16D NAILS TO TRUSSES. FOR TRUSS SPANS EXCEEDING 60'-0" SUBMIT BRACING DRAWINGS SIGNED AND SEALED BY A REGISTERED ENGINEER IN THE STATE OF FLORIDA. 635.9 BOTTOM CHORD BEARING PARALLEL CHORD TRUSSES SHALL BE CLEARLY MARKED IN A MANNER WHICH WILL AVOID INVERTED INSTALLATION IN ACCORDA NCE WITH THE TRUSS PLATE INSTITUTE, "NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS CONSTRUCTION," ANSI/TPI 1 - LATEST EDITION. 635.10 THE WOO D TRUSS MANUFACTURER SHALL DESIGN AND SPECIFY ALL CONNECTIONS AND CONNECTION COMPONENTS FOR TRUSS -TO -TRUSS CONNECTIONS. ALL CONNECTIONS AND CONNECTION COMPONENTS SHALL BE INDICATED ON THE FINAL SHOP DRAWINGS. 635.11 THE WOOD TRUSS MANUFACTURER SHALL REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR COORDINATION OF MECHANICAU ELECTRICAL UNITS AND SPECIAL CONCENTRATED LOADS SUPPORTED BY THE WOOD TRUSSES NOT INDICATED ON THE STRUCTURAL DRAWINGS. 635.12 WHERE MECHANICAL / ELECTRICAL LOADS ARE ATTACHED TO THE WOOD TRUSSES, ATTACHED LOADS SHALL NOT EXCEED THE LOADS INDICATED IN THE NOTES ABOVE. WHERE THE ACTUAL LOADS EXCEED THE LOADS INDICATED ABOVE, THE WOOD TRUSS MANUFACTURER SHALL EITHER PROVIDE ADDITIONAL FRAMING TO DISTRIBUTE THE LOADS TO CONFORM TO THE LOADS INDICATED OR PROVIDE ADDITIONAL LOCALIZED CAPACITY IN THE WOOD TRUSS DESIGN TO SUPPORT THE ACTUAL LOADS. 635.13 WHERE MULTIPLE PIPING LINES RUN PARALLEL, STAGGER THE PIPE SUPPORT HANGERS AS REQUIRED TO COMPLY WITH THE LOADS INDICATED ABOVE. F r a� o_ w 0 w <n O o_ tr a. o_ m w 0 z z Ix w I- o_ z 0 O w O i z w 0 0 0 Ir W X O 0 z a 0 F Q 0_ 0 z 0 O z D: 0 20 ATLANTIC 'oQ� , •, c •• s' ,'�� ENGINEERING * : NO. 6 0*? 6501 Arlington Expressway Building B, Suite 201 Jacksonville, FL 32211 PH: 904.743.4633 FX:904.725.9295 AES #317.107 = '0 -%; TAT OF % O R 1 V P�:,'�.��?;� , R. Wulbern Architect PA AA • 0003433 Ile (904)329.2610 W mbenQwulbem.net 0 <n z 2 En N En a O a LU 0 w It U. w �- H o v � 6 Go Go N W J en W n O 0 _j o 0 1� z w v� z Y W Q� m a m o U v 0 IL V goldco VERTIC L AW V J v+ •e✓ LO Q CD W CD O Yo Z� �o U_ Z W=� Y O =O Li 00 J �OWCO m�z r z 0 W a OW Z J I z a W Z W �^ W J (� 0 z H o H N W W SO 4 r` m PV O 7 6/8" T-8 7/8" Itry]ll 2.33 r- - - WF- 104 — NOTE 8 — 105 O 106 NOTE 8 105 NOTE 2.--WF- -----� --- - - - - - - - - - - - 102 1 r-------- • -- --- -- I l 1 0 15122 i i -- O I I 1 I � - I I r__ -- NOTE 1 1 I I 1 F3 _ _ F4 l F4 - WF2.33 f -II LJ --- -- a —WF233 --J I i I L---— — — — — — — — — — — — — — — ---------------------J I I ._.._.._.._.. 1 - ----- t._.._.._.._.._.._.._..4..—..------ _.._.._.._.._... — F- L------------------L -------------I I I I III c1-------------------------- 1, r------:- i NOTE NOTE 8 001 1 l I I I S 3 Ni i WF2.33 I I I L I I I I I 112 31 I I 1 i I I s s I i i I I F.D. I I I r J L, i — I F8.5 '-1� 1A C1 I I i SLOPE SLAB I 1 I I I 1 I TO DRAIN TYP I I I I 1 1 0 I I I I I I.._.._.. _.._.I — —J _ ._.._.:_.._.._.._.._.._.._.._.._.1._.._.._.._.._.._.._.._.._.._.._.._.._. _.._.._._.._.._.._.._..—.._.._.._.._.._. Ca F3 I r --J I C1 F.D i i i----- - I I I I _ J i I J N __ _-__ L —) r I I 1 NOTE 1 MOP SINK ( 112 I F.D. M I I CONTRACTION/CONSTRUCTION i 1 i i JOINT TYP i I 6" I I I I 1 1 1 i I I I I 103 1 I I I I -- - — - - — - — - I Fq — Fa ............. I I i I i I I I I 1 os I O S-5 r-- HSS5X5X5/16 ON 3/4"X1i"X12" BASE L _ - _ -J I I I I PLATE WITH (4) 3/4"DIA N�jj 1'-0" _ _ _ _ I i 1 I I I ANCHOR BOLTS (3) LOCATIONS � + - I : i I I I 1 3 w I� —) 111 I ij F7 I I I 3zZJL-_ F5 I UU 1 I41/4"UUI F8 a J L L_ Op F.D F.Dii1 1IIr---g oo I 1 , z--------------------- I C3 L-----J C2 I-- a Ct - - --------------- ---- - 1 TD I a I 1 04 1--------------------------- ----------------------------- J r------) r- ---, NOTE r--- I F4 a O a0 1 L-------J --- -- --� M 106 I I F3 F3 F3 v L------- --� r----I r— --1 r---, s4 107 1 1 1 I I I S-5 8I I a I C41 Q I I i I I I NOTE 8 S 6 NOTE 8 7 5/8" 7 5/8" c 44. 7 5/8" CONTINUOUS WALL FOOTING SCHEDULE MARK WIDTH DEPTH LONGITUDINAL REINFORCING TRANSVERSE REINFORCING WF2.0 2'-0" V-4" (2) #5 CONT TOP AND BOTTOM #3 TIES AT 16" OC WF2.33 2'-4" V-4" (2) #5 CONT TOP AND BOTTOM #3 TIES AT 16" OC WF4.0 4'-0" 1'-4" (4) #5 CONT TOP AND BOTTOM #3 TIES AT 16"OC SPREAD FOOTING SCHEDULE MARK WIDTH LENGTH DEPTH REINFORCING F3 T-0" T-0" 1'-4" (4) #5 EACH WAY TOP AND BOTTOM F4 4'-0" 4'-0" V-4" (5) #5 EACH WAY TOP AND BOTTOM F5 5'-0" 5'.0" V-4" (6) #5 EACH WAY TOP AND BOTTOM F7 T-0" 4'.0" 7'-0" V-4" (6) #6 EACH WAY TOP AND BOTTOM F8 8'-0" 1.4. (5) #5 LONG WAY TOP AND BOTTOM 01) #5 SHORT WAY TOP AND BOTTOM F8.5 6'-0" 8'-6" 114" (7) #5 LONG WAY TOP AND BOTTOM (10) #5 SHORT WAY TOP AND BOTTOM FOUNDATION AND SLAB PLAN SCALE: 1/4" = V-0" NOTES: 1. 4" CONCRETE SLAB ON GRADE REINFORCED WITH 6X6-W1.4XW1.4 WWR ON VAPOR RETARDER ON TERMITE TREATED COMPACTED FILL. VERIFY LOCATION OF CONSTRUCTION/CONTRACTION JOINTS WITH ARCHITECT. 2. REFERENCE FINISH FLOOR ELEVATION = 0'-0". COORDINATE FLOOR ELEVATIONS, SLOPES, AND RECESSES WITH ARCHITECTURAL AND CIVIL DRAWINGS. 3. TOP OF EXTERIOR FOOTING ELEVATION = 4-4" UNLESS NOTED OTHERWISE. TOP OF EXTERIOR FOOTINGS SHALL BE MINIMUM 8" BELOW FINISH GRADE UNO. 4. STEP FOOTINGS BELOW WATER AND SANITARY PIPES. SEE TYPICAL DETAILS ON S-8. 5. EXTERIOR MASONRY WALLS SHALL BE REINFORCED WITH (1) #5 VERTICAL CENTERED IN GROUTED CELL AT 2'-8" OC UNO. FILL ALL REINFORCED CELLS SOLID WITH 3000 PSI GROUT. SEE TYPICAL DETAILS ON S-9 FOR ADDITIONAL REQUIRED REINFORCING. 6. CONTINUOUS WALL FOOTINGS SHALL BE TYPE WF2.0 UNO, 7. SEE ARCHITECTURAL DRAWINGS FOR HEIGHT, WIDTH, AND LOCATION OF MASONRY WALLS AND WALL OPENINGS. 8. 3 5/8" STUD FURRING ELEMENT. SEE SECTION 104/S-4 FOR FRAMING. DIMENSION IS TO OUTSIDE FACE OF SHEATHING. PROVIDE MINIMUM 12" DEEP CONCRETE CURB (TOP OF CONCRETE EL = +0'-4") REINFORCED WITH #4 CONTINUOUS AT 12" OC MAX BENEATH STUDS - SEE TYPICAL DETAIL. 9. F.D. - DENOTES FLOOR DRAIN. COORDINATE LOCATION OF ALL FLOOR/HUB DRAINS AND FLOOR SINKS WITH PLUMBING DRAWINGS. PROVIDE 2% SLOPE IN 4'-0" X 4'-0" AREA AROUND FLOOR DRAINS LINO. N (6) #6 VERTICAL u� r` „-:S AT S" OC 6"DIA X 8'-0" STEEL BOLLARD FILLED WITH CONCRETE SEE TYPICAL DETAIL On NOTE 8 � 1 112 108 O ERTICAL AT 8" OC (8) #6 VERTICAL N 0: 1 U #3 TIES AT 8" OC N C2 C3 CONCRETE COLUMN DETAILS ATLANTIC ENGINEERING: 6501 Arlington Expressway Building B, Suite 201 Jacksonville, FL 32211 PH: 904.743.4633 FX:904.725.9295 AEB #317.107 R. Wulbern A «..1. +o..t n e M - 0003433 Ilc (904)329.2510 tal mbertgwulbam.nat N ? N Y U_ � (L w 0 LL IW— a a � o s � Cm Cm � Lu i O N J O z SO w c~� � z a Uj w o :0�00C W 0 0 z 0: 0 H Q D- z 0 J o V) CLR Z w W 2 ITIES AT8"OC o #6 VERTICAL z Q z O 0 z 0 0 z 0 Z a 0 z 0: 0 n g0ldC0. .', "..,.,• VERTIC L V J ''AWA Ln Z Uj t(j Uj rn e a M O Yo ZQ @W O Z�LL F4 � QO A4 O=O W 0 Lon 05 D" J m�z W J H H H W U-I N S-1 DAVID L WEBB PE 47180 104 105 1 TRUSS BASE SUPPORT EL+20'-0" r PARAPET: ZONE 4: +/-97 PSF r ZONE 5: +/-110 PSF EL +18'-0" r—► J12 �► F WALL, ZONE 4: +50 /-54 PSF _ ZONE 5: +50 / -63 PSF H SEE CANOPY SHOP ` DRAWINGS FOR TRUSS BASE REACTIONS ON WOOD SUPPORT EL +10'-0" TRUSSES r-- OVERHANG: f f f f f PSF INTERIOR: 82PSF • TRUSSES AT 24" OC • REFER TO GENERAL NOTES FOR GRAVITY LOADS • WIND PRESSURE/SUCTION INDICATED HERE ARE BASED ON "COMPONENTS AND CLADDING" • WIND PRESSURES ARE ULTIMATE - TYPICAL TOWER TRUSS WIND LOAD DIAGRAM COMPONENTS AND CLADDING WIND PRESSURE DIAGRAM a = 4'-0" m_ V w 101 S-3 m LL O a O N U 0 J w CD m 0 a R U TRUSS BEARING EL+10'-4 1/2" UNO 103 113 TOP OF BEAM EL +13'-0" PRE FAB METAL CANOPY SEE ARCH FURRING AT TOWER ELEMENT SEE WALL PRE FAB METAL CANOPY SEE ARCH FURRING AT TOWER ELEMENT SEE WALL SECTIONS TRUSS BEARING EL+10'4 1/2" UNO 106 PRE FAB METAL CANOPY SEE ARCH PRE-ENGINEERED FURRING AT TOWER WOOD TRUSSES AT ELEMENT SEE WALL 24"OC MAX UNO. SECTIONS SEE ARCH FOR TRUSS PROFILE SECTIONS NOTE9 NOTE9 T SEE ARCH MEN DNOTE EF 2 EF-1_ 2501bs 2501bs ROOF VENT SEE ARCHI I I I I II i I I 1 I I I I I I II I I f l II I I I GIRDER TRUSS — s" - o" I Ill 11 SPA 1 — 7 SPACES AT 2'-0 - 22 SPACES AT 2 0" 18-IJ 1'-3 3/4" 1'-11 1!4" 10 1/2" I I _ I I_ LL� J 1' 11 1/4 '.11 1/4" 2,_0" V-3 1/4" „ " 10 7/8" 11 1/4 11 1/4" 11 1/4' 2'-0' 2'-0" 11 1/4 11 1/4 2'-0" 2'-0" 11 1 / " 2'-0" 2'-0 2'-0" 2 -0' 1 1/2" ! ! _ y - --- ------------ ------1----J-----_==___---------1----11----1--------------4----1=' - _=_=------11---------- IL---- ---------- ---------------------------------------- - �_- I I I �7-77 NOTE 9 — II TRUSS PLACEMENT CRITICAL FOR KITCHEN EXHAUST DUCTS RTU-2I II II N9501bs OTE6 — ----- ---� FURRING AT TOWER ELEMENT SEE WALL SECTIONS -7 108 — --- — — — -- — �i RT�1a (2) 2X8 BETWEEN TRUSSES WITH, - RTU 1 NO 6 9501bs { I III SIMPSON L US28-21FJ�CH END TYP NOTE 6 I I � II I I I I II I I I `NOTE 1' I (2) 2X8 BETWEEN TRUSSES WITH NOTE 8 TYP SIMPSON LUS28-2 EACH END TYPICAL AT ROOF TOP UNITS DRAG TRUSS MIN 2 PLY RTU-4 j PRE-ENGINEERED WOOD TRUSSES AT \l` FORCES =420PLFI 9501bs, 24"OCMAX UNO. _ _--- -'- `__ _, ALLOWABLE_ NOTES ( I__ SEE ARCH FOR __--- ----- - --- ----DRAG -__ - -- n*-=--' --- - ------ r----b� ==-- -- --11----------L---- - -I--- ==-� --- - -------- --- -'---- � _--- TRUSS PROFILE 3/4 1 09 PRE-ENGINEERED WOOD TRUSSES AT 24"OC MAX UNO. SEE ARCH FOR TRUSS PROFILE COMPONENTS AND CLADDING WIND PRESSURES TRIBUTARY AREA (SF) ROOF ZONE WALL ZONE PARAPET ZONE 1 2 3 4 5 4 5 10 +28/-57 +52/-95 +52/-95 +52/-56 +52-69 +461-51 +46/-64 20 +22/-55 +50/-85 +50/-85 +50/-54 +50/-63 +44148 +44/.59 50 +20/-54 +47/-72 +47-72 +47/-51 +47/-59 +41/45 +411-53 100 +19/-52 +44/-62 +44/-62 +44/49 +44/-54 +38/43 1 +38/-48 NOTES: 1. ALL LOADS ARE IN POUNDS PER SQUARE FOOT (PSF). 2. (+) DENOTES PRESSURE, (-) DENOTES SUCTIONS. 3. "a" SHALL BE 10% OF LEAST HORIZ DIMENSION OR 0.4h, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF LEAST HORIZ DIMENSION OR T-0". 4. "h" = MEAN ROOF HEIGHT. �4 IIROOF I I HATCH OP U WALL BETWEEN TRUSSES WITH SIMPSON TOP OF CMU WALL - ------ i, II IIII I I I I II LUS28-2 EACH END EL +10,_0„ 111 — ° S•6 7GIRDER TRUSS DNOTEROOF VENT2X4 X-BRIDGING AT SEE ARCH FOR B IN ! EF-3�! 9 WALL BE --- ------ - ----------- I iIIj II II II II II II 107 110 CB-1, TOP OF BEAM EL +1 V-0" FURRING AT Ti ELEMENT SEE SECTIONS CONCRETE BEAM SCHEDULE MARK WIDTH DEPTH REINFORCING TIES CB-1 7 5/8" Z-0" (6) #5 #3 TIES AT 8" OC CB-2 7 5/8" T-0" (8) #6 #3 TIES AT 8" OC CB-3 7 5/8" 2'-0" (6) #6 #3 TIES AT 8" OC COMPONENTS AND CLADDING OVERHANG LOADS EFFECTIVE OVERHEAD ZONE AREA (FT2) 2 3 10 57/-97 57/-97 20 55/-94 55/-94 50 52/-90 52/-90 100 149/-87 1 49/-87 NOTES 1. TABULATED COMPONENT AND CLADDING PRESSURES (Putt) HAVE BEEN CALCULATED IN ACCORDANCE WITH THE DESIGN BUILDING CODE PER NOTE 100.1 BASED ON ULTIMATE DESIGN WIND SPEED (Vult) PER NOTE 100.3A AND SHOULD BE USED IN CONJUNCTION WITH ASCE 7-10 LOAD COMBINATIONS. TABULATED PRESSURES CAN BE CONVERTED TO NOMINAL VALUES BY MULTIPLYING BY 0.6, PRE-ENGINEERED WOOD V— NOTE 9 TYP TRUSSES AT 2% UNO TRUSS BEARING EL+10'-4 1/2" UNO PRE FAB METAL 106 SIMS 4 CANOPY SEE ARCH ®ROOF FRAMING PLAN SCALE: 1/4"= V-0" NOTES: 1. 5/8" APA RATED EXPOSURE 1, 40/20 SPAN RATING PLYWOOD ROOF SHEATHING. ATTACH PLYWOOD WITH 10d SPIRAL OR RING SHANK NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS AND 4" O.C. AT ALL ENDS AND EDGES. 2. PROVIDE 2X6 MINIMUM BLOCKING AT ALL RIDGES, HIPS, VALLEYS, EAVES, AND UNSUPPORTED PLYWOOD PANEL EDGES. 3. TRUSS MANUFACTURER SHALL PROVIDE ALL BRIDGING AND BLOCKING REQUIRED TO STABILIZE THE TRUSSES. 4. ALL METAL CONNECTORS THAT ARE IN CONTACT WITH PRESSURE TREATED WOOD SHALL BE STAINLESS STEEL OR HOT -DIPPED GALVANIZED. CONTRACTOR SHALL VERIFY COATING REQUIREMENTS AND COMPATIBILITY WITH TREATED WOOD AND METAL CONNECTOR MANUFACTURER. 5. WHERE MULTI -PLY TRUSSES ARE INDICATED, TOP CHORDS SHALL BE FASTENED TOGETHER WITH 1/2"DIA BOLTS AT 48"OC OR AS SPECIFIED BY THE TRUSS MANUFACTURER. 6. DESIGN TRUSSES FOR INDICATED EQUIPMENT WEIGHTS. VERIFY SIZE AND LOCATION OF MECHANICAL EQUIPMENT WITH MECHANICAL DRAWINGS. REFER TO MECHANICAL DRAWINGS FOR SIZE AND LOCATIONS OF ROOF OPENINGS AND PENETRATIONS. ROOF TOP CURBS SHALL BE PROVIDED BY MECHANICAL EQUIPMENT SUPPLIER. 7. DIMENSIONS ARE TO EXTERIOR FACE OF STUD UNLESS NOTED OTHERWISE 8. WOOD BRIDGING. SEE TYPICAL BRIDGING DETAIL ON S-10. NAETWFRAMED ITHXTUDA" O.C. PROVIDE 2X6 SUPPORT BLOCKING BETWEEN TRUSSES AT EACH STUD. SEE DETAIL A/S-10. BILE COPY ENGINEER r VIY�Y � �V - "v I N G 6501 Arlington Expressway C Building B, Suite 201 � Jacksonville, FL 32211 PH: 904.743.4633 FX:904.725.9295 AE• #317.107 rrrgn mtpt P` DAVID L WEBB PE 47180 R. Wulbern Architect PA AA - 0003433 tic (904)320.2510 tal raWrt@wulbam.nat (9 (N ? o_ W V (L LLJW0 LL WIT o � co co J W n CD(1) J O O I%. z "o Z YLLI W d a L)O 0 A 99ldco ... .......... VERTIC L V J N ti o W z W� r r .. 28 O Z�j it Z� MENEM }U- F- Y� W mO 0�=_() C'n 0 V Ln moz�' 0 9.. a � z a � I z L LU LU O z I- O o H W W S S2 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS CONT PT (2) 2X8 TOP PLATE WITH 1/2" DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS TOP OF CMU EL +16'-4" — 3 5/8", 16 GA CFSF STUDS AT 24" OC CONNECT TO WALL WITH 1/4" DIA TAPCON AT 24" OC MAX— CMU WALL VENEER SEE ARCH TOP OF BEAM EL +I X-0" — BLOCKING AND ATTACHMENT PER CANOPY MANUF BOTOTM OF BEAM EL +IU-0" PREFAB METAL CANOPY SEE Al BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE 16" CMU BOND BEAM WITH (4) #5 CONT SIMPSON HETA24 STRAP AT 24" OC WITH 4" EMBED IN WALL AND (9) 10d X 1 1/2" NAILS THROUGH SHEATHING TO RAFTER UPLIFT AND SHEAR CONNECTOR BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO EACH TRUSS WITH (2) #10X4" SCREWS PRE-ENGINEERED WOOD OVERFRAMING TRUSSES AT 24" OC ROOF SHEATHING CONT UNDER OVERFRAMING SLOT AS NEEDED FOR TRUSS TO TRUSS CONNECTION PLYWOOD ROOF SHEATHING a 1 �� 2X8 AT 24-OC PROVIDE 2X8 ;, BLOCKING AT 24"OC SIMPSON LUS26 HANGER EACH END EACH RAFTER ATTACHED WITH (4) 10d NAILS TO NAILER AND RAFTER (1) PT2X8 NAILER TOP WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT 8"X36" CONCRETE BEAM CB-2 EJ CONCRETE BARRIER CURB FINISH GRADE OR PAVEMENT SEE CIVIL m 4. 1 z o (2) # 4 CONT 4. L SIMPSON 11 STRAP AT 24" OI WITH 4" EMBED IN WALL AND (9) 10d X 1 1/2" NAILS THROUGH SHEATHING TO BLOCKING PRE-ENGINEERED WOOD TRUSSES SEE PLAN. 2X4 BLOCKING AT 24" OC (1) PT2X8 NAILER TOP WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT 8"X36" CONCRETE BEAM CB-2 SECTION 101 SCALE: 314" = V-0" S•3 STOREFRONT SYSTEM SEE ARCH (2) #5 CONT #5 DOWELS AT 24" OC CONCRETE SLAB SEE PLAN FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE CONT PT (2) 2X8 TOP PLATE WITH 1/2"DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS TOP OF CMU EL +16'-4" — 3 5/8", 16 GA CFSF STUDS AT 24" OC CONNECT TO WALL WITH 1/4" DIA TAPCON AT 24" OC MAX— CMU WALL VENEER SEE ARCH TOP OF BEAM EL +13'-0" — BLOCKING AND ATTACHMENT PER CANOPY MANUF TRUSS BEARING EL SEE PLAN — BOTOTM OF BEAM EL +10'-0" PREFAB METAL CANOPY SEE Al EJ CONCRETE BARRIER CURB FINISH GRADE OR PAVEMENT SEE CIVIL—\ (2) # 4 CONT f CONNECTOR TYPE 3 SEE SCHEDULE CONNECTOR TYPE 2 SEE SCHEDULE (1) PT2X8 NAILER TOP AND BOTTOM WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT 8"X36" CONCRETE BEAM CB-2 STOREFRONT SYSTEM SEE ARCH (2) #5 CONT #5 DOWELS AT 24" OC CONCRETE SLAB SEE PLAN A - SECTION 102 SCALE: 3/4" = V-0" S-3 FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN 16" CMU BOND BEAM WITH (4) #5 CONT UPLIFT AND SHEAR CONNECTOR BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO EACH TRUSS WITH (2) #10X4" SCREWS ROOF SHEATHING CONT UNDER OVERFRAMING SLOT AS NEEDED FOR TRUSS TO TRUSS CONNECTION PRE-ENGINEERED WOOD OVERFRAMING TRUSSES AT 24" OC PRE-ENGINEERED WOOD TRUSSES SEE PLAN 2X4 BLOCKING AT 24" OC TOP OF BEAM EL +16'-4" — CONT PT2X8 WITH (2) 3/4"DIA ADHESIVE ANCHORS AT 24"OC WITH 6 3/4" EMBED — PLYWOOD ROOF ME -ENGINEERED WOOD OTRUSSES SEE PLAN. SEE ARCH FOR TRUSS PROF11 16" CMU BOND BEAM WITH (4) #5 CONT —� TOP OF BEAM EL+13'-0 TRUSS ATTACHMENT BY TRUSS MANUF , TOP OF BEAM EL +11-0" EL SEE ARCH J CONT PT2X8 WITH (2) 3/4"DIA ADHESIVE ANCHORS AT 24"OC WITH 6 3/4" EMBED BOTTOM OF BEAM EL+9'-0" CONT 2X4 FASCIA ATTACHED TO EACH TRUSS WITH (2) #10 X 3" SCREWS EJ CONCRETE BARRIER CURB FINISH GRADE OR PAVEMENT SEE CIVIL— LIGHT BAND SEE ARCH CONT PT2X8 TOP PLATE WITH 1/2" DIA ADHESIVE ANCHOR BOLTS AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS 24" CMU BOND BEAM WITH (6) #5 CONT CMU WALL PLYWOOD ROOF SHEATHING SIMPSON HETA24 STRAP AT 24" OC WITH 4" EMBED IN WALL AND (9) 10d X 1 1/2" NAILS THROUGH SHEATHING TO BLOCKING PRE-ENGINEERED WOOD LTRUSSES SEE PLAN. 2X4 BLOCKING AT 24" OC (1) PT2X8 NAILER TOP WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" 7 EMBEDMENT 8"X24" CONCRETE BEAM CB-3 STOREFRONT SYSTEM SEE ARCH CMU BLOCK SILL WITH (2) # 5 CONT DOWEL INTO CONCRETE COLUMNS (EACH SIDE) EJ CONCRETE SLAB SEE PLAN °A #5 DOWEL AT 16" OC FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH ° y 3000 PSI GROUT A (2) # 4 CONT ° SECTION 103 SCALE: 3/4" = 1'-0" S-3 CONCRETE FOOTING SEE PLAN PJ` "CL ATLANTIC _ ENGINEERING?* 0.4 6501 Arlington Expressway Building B, Suite 201 = �% •{(/ Jacksonville, FL 32211 o"m: S T OF : PH: 904.743.4633 FX:904.725.9295 y�4�' O R)� P,:,�.��?: AES #317.107 �i �-V-•" ......... �� R. Wulbern Architect PA A • 0003433 Ile (904)329.251D tel mbert@wulbemmet C9 z z O to U N Y x IL � E w p PC—: 00 00 04 NO lij U) O 0 J O 0 I�- z w U 'O Z w— m i a m 0 U OO 0 0- [ I� goldco VERTIC L O V V J ''Aw^ vI N o 1` z � Q � 0) W °) s s CAM O Yo Z� Z LL �0 �» O=° fCL� �S U v�61 05 W5 0) J (Du) now moz ZJ O ih �t � 2S a Z 0 O ' U w U W J t i � o H F- w LU co S-3 TOP OF CMU EL +16'-4" — TOP OF BEAM EL +13'-0" BLOCKING AND ATTACHMENT PER CANOPY MANUF TRUSS BEARING EL SEE PLAN — 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS CONT PT (2) 2X8 TOP PLATE WITH 1/2" DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS 3 5/8", 16 GA CFSF STUDS AT 24" OC CONNECT TO WALL WITH 1/4" DIA TAPCON AT 24" OC MAX - PREFAB METAL CANOPY SEE AI VENEER SEE ARCH 3 5/8", 16 GA TRACK WITH (2) 1/2" DIA TAPCONS AT 24" OC WITH 2" EMBED CONCRETE BARRIER CURB FINISH GRADE OR PAVEMENT SEE CIVIL - (3) # 4 CONT N Eli, 1' 1 _ kjpl I, L, 00 ► i I�I BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE CONNECTORTYPE3 SEE SCHEDULE CONNECTOR TYPE 2 SEE SCHEDULE (1) PT2X8 NAILER TOP AND BOTTOM WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT 32" CMU BOND BEAM WITH (8) #5 CONT CMU WALL SECTION 104 SCALE: 3!4" = 1-01, S-4 EJ CONCRETE SLAB SEE PLAN A FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN 16" CMU BOND BEAM WITH (4) #5 CONT TOP OF CMU UPLIFT AND SHEAR CONNECTOR EL +16'-4" BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO EACH TRUSS WITH (2) #10X4" SCREWS ROOF SHEATHING CONT UNDER OVERFRAMING SLOT AS NEEDED FOR TRUSS TO TRUSS CONNECTION PRE-ENGINEERED WOOD OVERFRAMING TRUSSES AT 24" OC PLYWOOD ROOF SHEATHING PRE-ENGINEERED WOOD TRUSSES SEE PLAN. 2X4 BLOCKING AT 24" OC TOP OF BEAM EL +13'-0" BLOCKING AND ATTACHMENT PER CANOPY MANUF TRUSS BEARING EL SEE PLAN — TOP OF BEAM EL +8'-0" — 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS CONT PT (2) 2X8 TOP PLATE WITH 1/2" DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS 3 5/8", 16 GA CFSF STUDS AT 24" OC CONNECT TO WALL WITH 1/4" DIA TAPCON AT 24" OC MAX - PREFAB METAL CANOPY SEE ARCH VENEER SEE ARCH FUR -OUT ELEMENT BEYOND VENEER SEE ARCH CONCRETE BARRIER CURB FINISH GRADE OR PAVEMENT SEE CIVIL (3) # 4 CONT i BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE CONNECTORTYPE3 SEE SCHEDULE SECTION 105 SCALE: 3/4" = V-0" S4 CONNECTOR TYPE 2 SEE SCHEDULE (1) PT2X8 NAILER TOP AND BOTTOM WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT CMU LINTEL SEE SCHEDULE STOREFRONT SYSTEM SEE ARCH CMU BLOCK SILL WITH (2) # 5 CONT DOWEL INTO CONCRETE COLUMNS (EACH SIDE) EJ CONCRETE SLAB SEE PLAN A FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN 16" CMU BOND BEAM WITH (4) #5 CONT UPLIFT AND SHEAR CONNECTOR BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO EACH TRUSS WITH (2) #10X4" SCREWS ROOF SHEATHING CONT UNDER OVERFRAMING SLOT AS NEEDED FOR TRUSS TO TRUSS CONNECTION PRE-ENGINEERED WOOD OVERFRAMING TRUSSES AT 24" OC PLYWOOD ROOF SHEATHING TOP OF CMU EL +16'-4" CONT PT2X8 WITH (2) 3/4"DIA ADHESIVE ANCHORS AT 24"OC WITH 6 3/4" EMBED — PLYWOOD ROOF SHEATHING OP E-ENGINEERED WOOD 1 TRUSSES SEE PLAN. SEE ARCH FOR TRUSS PROFILE 32" CMU BOND BEAM WITH (8) #5 CONT TRUSS ATTACHMENT BY TRUSS MANUF CONT PT2X8 TOP PLATE WITH 1/2" DIA ADHESIVE ANCHOR BOLTS AT 24" OC WITH 12" EMBEDMENT WITH 3" DIA WASHERS 16" CMU BOND BEAM WITH (4) #5 CONT 24" CMU BOND BEAM WITH (6) #5 CONT AT MANSARD LOCATIONS PLYWOOD ROOF SHEATHING CONNECTORTYPE3 SEE SCHEDULE TRUSS BEARING EL SEE PLAN EL SEE ARCH PRE-ENGINEERED WOOD PRE-ENGINEERED WOOD <' TRUSSES SEE PLAN. TRUSSES SEE PLAN.ZCONT PT2X8 WITH (2) 3/4"DIA ( CONNECTOR TYPE 2 2X4 BLOCKING AT 24" OC ADHESIVE ANCHORS AT SEE SCHEDULE 24"OC WITH 6 3/4" EMBED CONT 2X4 FASCIA (1) PT2X8 NAILER TOP AND ATTACHED TO EACH TRUSS BOTTOM WITH (2) 3/4" DIA WITH (2) #10 X 3" SCREWS ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT CMU WALL Y FINISH GRADE 1 EJ OR PAVEMENT ' CONCRETE SLAB SEE CIVIL _ SEE PLAN FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN SECTION 106 SCALE: 3/4" = V-0" S-4 ATLANTIC ENGINEERING'* 6501 Arlington Expressway Building B, Suite 201 Jacksonville, FL 32211 PH: 904.743.4633 FX:904.725.9295 y AEs #317-107 Gi w V) Z O a U a to 3 H U O tL H a z ¢ W w 0 w to 0 a D a w 0 >- O w F- ¢ a z_ O 1 O z w U 0 0 CL w 0 z w V7 D w co z } z a z W z C U z C LL w z Z a z C C C F a c z 2 z a C z a 0: C R. Wulbern Architect PA AA • 0003433 Ilc (904) 3293510 tel mbefowulbemawt w Z z O N rn Y U � � a a LU 0: w 0 LL F o a s � Go Go N NO Uj J w O to _I O o� z Z a Y Uj W w o o a o v UI goldco „Poo VERTIC L O V 4) j AW U) N n z Uj 0) Uj rn s CO O Yo Z�j Z� o YDo wgomo H- U 0ncn0 �l 00 ��W(0 M J rn t� ''^^ VJ C S Z O ) P z I U LU W J Z f— f— W W S N S-4 TOP OF CMU EL +16'-4" CONT PT2X8 WITH (2) 3/4-DIA ADHESIVE ANCHORS AT 24"OC WITH 6 3/4" EMBED PLYWOOD ROOF SHEATHING E-ENGINEERED WOOD OTRUSSES SEE PLAN. SEE ARCH FOR TRUSS PROFIT TRUSS ATTACHMENT BY TRUSS MANUF TOP OF BEAM EL +11-0" CONT PT2X8 TOP PLATE WITH 1/2' DIA ADHESIVE ANCHOR BOLTS AT 24" OC WITH 12" EMBEDMENT WITH 3" DIA WASHERS 24" CMU BOND BEAM WITH (6) #5 CONT 24" CMU BOND BEAM WITH (6) #5 CONT EL SEE ARCH CONNECTOR TYPE 3 SEE SCHEDULE CONT PT2X8 WITH (2) 3/4"DIA I. CONNECTOR TYPE 2 ADHESIVE ANCHORS AT SEE SCHEDULE 24"OC WITH 6 3/4" EMBED (1) PT2X8 NAILER TOP AND CONT 2X4 FASCIA BOTTOM WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC ATTACHED TO EACH TRUSS TOP OF BEAM WITH 6 3/4" EMBEDMENT WITH (2) #10 X 3" SCREWS EL +9'-0" 7 — 8"X24" CONCRETE BEAM CB-1 STOREFRONT SYSTEM SEE ARCH CMU BLOCK SILL WITH (2) # 5 CONT DOWEL INTO CONCRETE COLUMNS (EACH SIDE) PLYWOOD ROOF SHEATHING PRE-ENGINEERED WOOD TRUSSES SEE PLAN. TRUSS BEARING rEL SEE PLAN 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER -------------- SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS CONT PT (2) 2X8 TOP PLATE WITH 1/2"DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS 3 5/8", 16GA TRACK WITH (2) #10 X 3" SCREWS AT EACH TRUSS TOP OF CMU EL +16'4" � 3 5/8", 16 GA CFSF STUDS AT 24" OC WITH BLOCKING AT 48"OC — 16" CMU BOND BEAM WITH (4) #5 CONT TOP OF BEAM EL +13-0" SIMPSON HETA24 STRAP AT 24" OC WITH 4" EMBED IN WALL AND (9) 10d X 1 1/2" NAILS THROUGH SHEATHING TO BLOCKING VENEER SEE ARCH BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL CONT PT2X8 TOP PLATE WITH 1/2" DIA ADHESIVE ANCHOR BOLTS AT UPLIFT CONNECTOR TYPE 1 TOP OF BEAM 24" OC WITH 12" EMBEDMENT WITH SEE SCHEDULE EL +17'-1D" 3" DIA WASHERS 16" CMU BOND BEAM WITH • 8" CMU BOND BEAM (4) #5 CONT WITH (2) #5 CONT OGROUT WALL ABOVE 24" — UPLIFT AND SHEAR CONNECTOR BEAM SOLID BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX CONT PT2X8 WITH (2) 3/4"DIA 24" CMU BOND BEAM WITH ATTACHED THRU SHEATHING TO EACH ADHESIVE ANCHORS AT (6) #5 CONT TRUSS WITH (2) #10X4' SCREWS 24"OC WITH 6 3/4" EMBED ROOF SHEATHING CONT UNDER PLYWOOD ROOF • (1) PT2X8 NAILER TOP WITH (2) ' OVERFRAMING SLOT AS NEEDED SHEATHING 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT FOR TRUSS TO TRUSS CONNECTION E-ENGINEERED WOOD s TRUSSES SEE PLAN. SEE SIMPSON HETA24 STRAP AT 24" OC PRE-ENGINEERED WOOD O ARCH FOR TRUSS PROFILE WITH 4" EMBED IN WALL AND OVERFRAMING TRUSSES AT 24" OC (9) 10d X 1 1/2" NAILS THROUGH PLYWOOD ROOF CMU BOND BEAM ( SHEATHING TO BLOCKING WITH (4) #5 CONT W SHEATHING ROOF TOP OF BEAM SHEATHING EL +1 T-0 s: TRUSS ATTACHMENT BY TRUSS MANUF I PRE-ENGINEERED WOOD EL SEE ARCH 2X4 BLOCKING AT 24" OC TRUSSES SEE PLAN. CONT PT2X8 WITH (2) 3/4-DIA � PRE-ENGINEERED WOOD (1) PT2X8 NAILER TOP WITH (2) ADHESIVE ANCHORS AT TRUSSES SEE PLAN. 3/4" DIA ADHESIVE ANCHORS AT 24"OC WITH 6 3/4" EMBED ZV OC WITH 6 314" EMBEDMENT i 2X4 BLOCKING AT 24" OC CONT 2X4 FASCIA ATTACHED TO EACH TRUSS 8" CMU BOND BEAM WITH 16" CMU BOND BEAM WITH (2) #10 X 3" SCREWS i (2) #5 CONT WITH (4) #5 CONT , CMU WALL CMU WALL 3 5/8", 16 GA TRACK WITH (2) i *'' 1/2" DIA TAPCONS AT 24" OC I THIN BRICK WITH 2" EMBED SEE ARCH CMU WALL I I I CONCRETE O BARRIER CURB EJ EJ E3 FINISH GRADE I FINISH GRADE N I FINISH GRADE OR PAVEMENT OR PAVEMENT CONCRETE SLAB SEE CIVIL CONCRETE SLAB OR PAVEMENT CONCRETE SLAB SEE CIVIL SEE PLAN SEE PLAN SEE CIVIL — • I SEE PLAN g I g I g \Z Z Z " 101" .. 2 g FILL ALL CELLS BELOW FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH FINISH FLOOR SOLID WITH 3000 PSI GROUT 3000 PSI GROUT FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH • �. •, '• 3000 PSI GROUT ;° (3) # 4 CONT a e e ! ^. CONCRETE FOOTING ° ° CONCRETE FOOTING ° CONCRETE FOOTING • • SEE PLAN #4 + HK AT 24"OC ^. ;° •. SEE PLAN ° • • SEE PLAN SECTION 108 SCALE: 3/4" = V-0" S-5 SECTION rl 0 g SCALE: 34' = V-0" S-5 w N z D: J a V U w W W 3 F _V 0 w a z Q 0: w 0 Li V) O 0. X D a Ir w 0 z o: O H o_ z m O 0 •CL ATLANTIC 4 ENGINEERING 6501 Arlington Expressway �•, OL1\� �: 5 Building 8, Suite 201 .• FFF��� Jacksonville, FL 32211'•;°••O R• 1 pP•r ♦; PH:904.743.4633 FX:904.725.9295 %,��s ..I- t%��� AEe #317.107 '0,,/,0,,�yL1„`,.�`, DAVID L WEBB PE 47180 R. Wulbern Architect PA A 0003433 Ne (904)320.2510 tel robert@wulb@mnet 0 1n z Y � 0: w 0: 0 o: w r o � IL CO N J w O CID J O o I� z U �O z r L) LLJ w — om poa [ 1� goldco x VERTIC L V J -F+ U) V CN o ti z m LULO w a a O Yo Zc M� 0 Z �' YD�!no 0 _ Uj�Cn0Z3 W 1Z 1 J 0 rn fi U) a Z O ' U ` a W IJ w J F z Z F_ °o H F- w LU S-5 5/8" PLYWOOD WALL SHEATHING ON VAPOR BARRIER VENEER SEE ARCH —� SIMPSON A34 AT EACH TRUSS ATTACHED WITH (8) 8d X 1 1/2" NAILS CONT PT (2) 2X8 TOP PLATE WITH 1/2" DIA ANCHOR BOLT AT 24" OC (12' EMBEDMENT) WITH 3" DIA WASHERS TOP OF CMU EL +16'-4" — 3 5/8", 16 GA CFSF STUDS AT 24" OC CONNECT TO WALL WITH 1/4" DIA TAPCON AT 24" OC MAX— CMU WALL TOP OF BEAM EL +13'-0" — BLOCKING AND ATTACHMENT PER CANOPY MANUF TOP OF BEAM EL +11'-0" TRUSS BEARING EL SEE PLAN — PREFAB METAL CANOPY SEE Al BOTTOM OF BEAM EL +9'-0" BLOCKING AS REQUIRED AT ROOF VENT 2X BLOCKING FOR SHEATHING ATTACHMENT TYPICAL UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE 16" CMU BOND BEAM WITH (4) #5 CONT SIMPSON HETA24 STRAP AT 24" OC WITH 4" EMBED IN WALL AND (9) 10d X 1 1/2" NAILS THROUGH SHEATHING TO RAFTER UPLIFT AND SHEAR CONNECTOR BY TRUSS MANUF CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO EACH RAFTER WITH (2) #10X4" SCREWS PRE-ENGINEERED WOOD OVERFRAMING TRUSSES AT 24" OC ROOF SHEATHING CONT UNDER OVERFRAMING SLOT AS NEEDED FOR TRUSS TO TRUSS CONNECTION PLYWOOD ROOF SHEATHING 2X4 X-BRIDGING AT 24-OC TO \ 2X8 AT 24"OC 1r r. BRACE WALL v\ I I / PROVIDE 2X8 BLOCKING AT 24"OC I I SIMPSON LUS26 HANGER EACH END EACH RAFTER ATTACHED WITH (4) 10d NAILS TRUSS BEARING TO NAILER AND RAFTER EL SEE PLAN (1) PT2X8 NAILER TOP WITH (2) CONNECTO TYPE 3 « ` 3/4" DIA ADHESIVE ANCHORS SEE SCHEDLE AT 24" OC WITH 6 314" EMBEDMENT CON ECTOR TYPE 3 5/8", 16 GA CFS 3/4" DIA THRU BOLT AT 12" OC IN SEE CHEDULE"' STUDS AT 16" OC VERTICAL SLOTTED HOLES — 16" CMU BOND BEAM WITH (4) #5 CONT 2X4 BLOCKING AT 24" OC MAX CMU LINTEL SEE SCHEDULE 8"X36" CONCRETE BEAM CB-3 (1) PT2X8 NAILER TOP AND v BOTTOM WITH (2) 3/4" DIA ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT — 8"X24" CONCRETE BEAM CB-1 VENEER SEE ARCH STOREFRONT SYSTEM SEE ARCH EJ (1) #5 CONT CONCRETE CONCRETE SLAB SLAB SEE CIVIL CONCRETE SLAB SEE CIV SEE PLAN 4, P FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING �'. SEE PLAN CONCRETE FOOTING BEYOND SECTION gSCALE: 3/4" = V-0" #5 AT 24" OC DRAG TRUSS SEE PLAN PLYWOOD ROOF SHEATHING CONTANCHOR RBOLTSWITH1 CDIA ANCHOR BOLTS AT 24" OC WITH 12" EMBED \ PRE-ENGINEERED WOOD TRUSSES SEE PLAN. CONT (2) PT2X8 TOP PLATE TOP OF CMU EL +10'-0" 16" CMU BOND BEAM WITH (4) #5 CONT SECTION 111 SCALE: 3/4" = V-0" S 6 CMU WALL EJ CONCRETE SLAB SEE PLAN FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN BLOCKING AS REQUIRED 5/8" PLYWOOD WALL AT ROOF VENT SHEATHING ON VAPOR PRE-ENGINEERED WOOD BARRIER OVERFRAMING TRUSSES AT 24" OC SIMPSON A34 AT 2X BLOCKING FOR EACH TRUSS SHEATHING ATTACHMENT ATTACHED WITH (8) TYPICAL 8d X 1 1/2" NAILS-----\ UPLIFT CONNECTOR TYPE 1 SEE SCHEDULE CONT PT (2) 2X8 TOP PLATE WITH 1/2" DIA ANCHOR BOLT AT 24" OC (12" EMBEDMENT) WITH 3" DIA WASHERS TOP OF CMU EL +16'-4" 16" CMU BOND BEAM WITH �(4) #5 CONT I I I, I 3 5/8", 16 GA CFSF STUDS i PRE-ENGINEERED WO( AT 24" OC CONNECT TO i OVERFRAMING TRUSS[ WALL WITH 1/4" DIA AT 24" OC TAPCON AT 24" OC MAX I I ti UPLIFT AND SHEAR I CONNECTOR BY CMU WALL i TRUSS MANUF I I 1 VENEER SEE ARCH i CONT 2X6 SLEEPER AT 24" OC MAX ATTACHED THRU SHEATHING TO TOP OF BEAM EACH TRUSS WITH (2) EL +13'-0" #10X4" SCREWS I I I I. I I BLOCKING AND ATTACHMENT d ` PER CANOPY MANUF SIMPSON HETA24 PROVIDE 2X8 STRAP AT 24" OC WITH BLOCKING AT 24"OC 4" EMBED IN WALL AND i 2X8 AT 24"OC (9) 10d X 1 112" NAILS THROUGH SHEATHING (1) PT2X8 NAILER TOP TO RAFTER WITH (2) 314" DIA I ADHESIVE ANCHORS AT 24" OC WITH 6 3/4" EMBEDMENT BOTOTM OF BEAM EL +10 0 PREFAB METAL CANOPY SEE ARCH 8"X36" CONCRETE BEAM CB-2 EJ CONCRETE WALK SEE CIVIL --\ SECTION SCALE: 3/4" = 1'-0" (1) #5 CONT CONCRETE SLAB SEE PLAN d 3'.. SECTION 112 SCALE: 3/4" = V-0" S-6 6"1S7 FILL ALL CELLS BELOW FINISH FLOOR SOLID WITH 3000 PSI GROUT CONCRETE FOOTING SEE PLAN #5 AT 24" OC I_I w 0 N O 0. D: o_ w O } Z O tl F a z IX O J O i Z W U O 0 CL w ir W, R. Wulbern Architect P_A M •0003433 Ik (904)329.2510 tol roban@wulbem.net U) Z y Y U_ W (L Uj M w 0 IX LL r Q N o 6 � G aD N � O N J O o I-, Z ,0 LU Z Y w o X: m @ [ I� goldco VERTIC l Ame AV' _W .j Cm tN W I� 1A a a I A 0 Yo Z � MONW 6� 3 o O�U LU =) � J � 0 Lb m�z J �5 � a Z O U � Uj W J o Z I— g F- F-• LU LU in ATLANTIC '* ENGINEERING- 6501 Arlington Expressway Building B. Suite 201 Jasksonvilie, FL 32211 PH: 904.743.4633 F%:904.725.9295 '! AES #317.107 %37'01VAL V4 ��nnunu111 Z�c DAVID L WEBB PE 47180 �a� I.V14%,mm I � rvw I 111v ELEVATION 110 SCALE: 1/2" = T-0" S-7 — TOP OF CONCRETE BEAM CB-2 EL +13'-0" K5X5/16 STANDARD 90 DEG HOOK a � d a � d V SCHEDULE O a d W 5 0 = --CONCRETE COLUMN VERTICAL COLUMN REINFORCING DETAIL g SCALE: 3/4" = V-0" SJ BEAM CONCRETE BEAM 8"X7"X5/8" PLATE WITH (4) 5/8" DIA X 6" LONG WELDED HEADED STUDS HSS5X5X5/16 DETAIL q SCALE: 1" = V-0" S-7 0 w x 1n z J U Ii U w a 3 U_ 0 1L a w 0 w 1n 0 a a w O z a 0 w a a z a c LL CTs LL 3 z c C: C a a Lai a R. Wulbern Architect PA AA • D003433 He (904) 3294510 101 robert@Rwulbsm.mt 0 N z z 0 Y Ic U > a a LLI w 0 Q' 11 W r H a a � a � 00 0 N -1 w r O 0 J O o I� Z WY U z W 11 0 0: U O CL Ej ,,,\11111111111r//II ,.�. .F. QP: V � C E ••• ••� 4 ATLANTIC 47 ENGINEERING 6501 Arlington Expressway = "0 Building B, Suite 201 Jacksonville, Fl. 32211 %; AT OF 2: PH: 904.743.4633 FX:904.725.9295 ••. • OR 1V P. • ,: AE8 #317.107 i • •• , �'6ppOgr�.� �gReb>iso w I 0 goldco " y VERTIC L VW V d J z Z �CD W CD O Yo Zc� cc� 0 Z � � aaa� p W (may' r Y Do A4 o O= U � � V] O? �� W �co coo O W cn W S � CW G I t9 L W w o Z Z w w O V cn S-7 FIELD MOLDED SEALANT CONCRETE SLAB SLAB REINFORCING N ❑ qa'� _ J ❑ .. N VAPOR RETARDER COMPACTED FILL TYPICAL SLAB MIN MIN COMP BACK-UP PREMOLDED INSERT, SAW CUT 1/4" OR TOOLED JOINT. SAW CUT JOINTS WITHIN 4 HOURS OF CONCRETE PLACEMENT. USE TOOLED JOINTS FOR ALL EXTERIOR SLABS CONCRETE SLAB ❑ q TYPICAL CONTRACTION JOINT IN SLAB ON GRADE DETAIL PIPE INTERSECT WITH FOOTING DETAIL SLAB RECESS SEE ARCH SLAB RECESS LESS THAN 311 TD PIPE SOLID WITH tETE ;ETE FOOTING TYPICAL BOLLARD DETAIL POUR FLUSH IN AREAS TO RECEIVE FLOOR COVERING NOTE 1 CONT SHEAR KEY 2" TYPICAL CONSTRUCTION JOINT IN SLAB ON GRADE DETAIL NOTE: 1, ROUT AND SEAL JOINT AT EXPOSED OR EXTERIOR JOINTS ONLY. ❑ d ^ a a BEAM OR FOOTING CORNER BARS TO MATCH SIZE, QUANTITY AND SPACING OF BEAM OR FOOTING REINFORCING (PROVIDE CLASS 'B" TENSION LAP) TYPICAL FOOTING CORNER REINFORCING DETAIL 18 18 Z_ #4 AT 16" OC — CONT CONT SHEAR KEY SLAB RECESS GREATER THAN 3" TYPICAL SLAB RECESS DETAIL EXTERIOR FACE 3 OF SHEATHING -X .I I WALL BEYOND I .I (2) #3 HOOKED TO TURN -DOWN I I EJ MATERIAL I FINISH GRADE OR CONCRETE SLAB STEEL COLUMN SEE CIVIL i CONCRETE SLAB I I III BUMP -OUT TURN -DOWN 6" TO PROVIDE 3" MI 4 9 1/2" NON -SHRINK CONCRETE COVER FOR II GROUT BASE PLATE AND ANCHOR BOLTS - A If CONCRETE FOOTING TYPICAL STEEL COLUMN FOOTING DETAIL CLASS "B" .. CLASS "B" M� < a e' a 1 L REINF BARS SAME SIZE AND NUMBER AS LONGITUDINAL BARS TOP OF FOOTING �(1)#4 ELSEEPLAN— TOP OF FOOTING 04 EL SEE PLAN = a 0 CLASS "B" LAP TIES, SEE SCHEDULE LONGITUDINAL BARS SEE SCHEDULE TYPICAL WALL FOOTING STEP DETAIL r—CONCRETE BEAM OR FOOTING CORNER BARS TO MATCH SIZE, QUANTITY AND SPACING OF BEAM OR FOOTING REINFORCING (PROVIDE CLASS "B" TENSION LAP) TYPICAL FOOTING INTERSECTION REINFORCING DETAIL EXPANSION JOINT MATERIAL EE PLAN & COORDINATE #4AT12" OC WITH EQUIP FURNISHED EW TOP AND (EQUIP SIZE + V-0" MIN) /— PROVIDE ANCHOR BOLTS, BOTTOM LEVELING CHANNELS, ETC AS REQUIRED BY EQUIPMENT i.l FURNISHED SLAB EQUIPMENT PAD TYPICAL BASE PLATE DETAIL (2)#5 CONT FINISH GRADE OR CONCRETE SLAB SEE ARCH. AND CIVIL WHICH EVER GOVERNS TOP OF CONCRETE FOOTING OR PIER * 1/4" PLATE WASHER WITH NUT *-COORDINATE DIMENSION OF THREAD REQUIRED FOR a PLATE AND GROUT THICKNESS. w 3/4"DIA to J 1/4" PLATE WASHER WITH DOUBLE NUTS N TYPICAL ANCHOR BOLT DETAIL CONCRETE SLAB V-0" MIN , TYPICAL TURNDOWN SLAB ,I R. Wulbern Architect PA AA • 0003433 Ile 1904) 3294510 tal mberta"Ibem.not (9 N Z N Y 0- �a U� w p U- W H a c � o 6 n CD N '^ �/ -1 w r� O N J O O I-� Z W U \O LU w 0 W Of w W Z r 0 U Z O F Q 0 w Z Q Z a D: 0 Ln. J `� �e Fe ATLANTIC '� �Q;: ENGINEERING'*; 0.47 6501 Arlington Expressway Building B, Suite 201 = "O • 2 Jacksonville, FL 32211 ;.,• TAT OF • PH: 904.743.4633 FX:904.725.9295 �7 � O R 1 P. ," AES #317.107 i •• ••�§RE"t'iiao 6Drv1P��� goidco VERTIC L V .v .J IY Z N a �Lo wCD ae rCM O Y O O `10o w > Om O W � Ln 0 = ��� �C�W�� m�z J ZO J Co b Q a W N � I Q i J a w J Z F. °o H LLI W S N S 1 u,r��n,-nru,♦. u.n.-.urn•/ IWAI I 1. SEE PLAN AND SCHEDULE FOR REINFORCING REQUIREMENTS 2. SEE ASSOCIATED TYPICAL MASONRY DETAILS 3. PROVIDE MASONRY JOINT REINF AT 16" OC (NOT SHOWN FOR CLARITY) TYPICAL MASONRY WALL REINFORCING ELEVATION P OF WALL CONCRETE TIE BEAM OR MASONRY BOND BEAM VERTICAL REINFORCING HORIZ JOINT REINF DISCONTINUED AT CONTROL JOINT --1 TONGUE & GROOVE BLOCK UNITS--\ SEALANT NOTE 1 PREMOLDED RUBBER OR PVC CONTROL JOINT OPTION #1 RAKE JOINT 3/4" DEEP #2 Z-BAR q HORIZ JOINT REINF �B DISCONTINUED AT CAULKING — LINTEL CONTROL JOINT 4 NOTE SILL REINFORCING OPTION #2 NOTES: 1. REINFORCEMENT PER PLAN & SCHED PROVIDE MIN (1) #5 BAR AT END CELL OF WALL. GROUT CELL SOLID. 2. SUBMIT CONTROL JOINT PLAN TO ARCH FOR REVIEW. TYPICAL MASONRY VERTICAL DOWELS TO MATCH VERTICAL REINFORCING WITH STD 90 DEG HOOK GROUT INSPECTION HOLES IISH FLOOR P OF FOOTING CONTROL JOINT DETAIL NOTE 1 VERTICAL REINFORCEMEP tV EACH FACE REINF NOTE VERTICAL REINFORCEMENT NOTES: 1. VERTICAL BAR POSITIONERS LOCATE AT TOP OF FIRST FILL ALL CELLS BELOW FINISH COURSE, ONE COURSE BELOW TOP OF WALL, AND AT 192 FLOOR SOLID WITH GROUT BAR DIAMETERS WHEN USING HIGH LIFT GROUTING 2. WHERE REINFORCEMENT IN MASONRY WALL SCHEDULE IS DESIGNATED AS INSIDE FACE OR OUTSIDE FACE, INSIDE FACE SHALL REPRESENT BUILDING INTERIOR FACE OF WALL AND OUTSIDE FACE SHALL REPRESENT BUILDING EXTERIOR OR RETAINED SOIL FACE OF WALL. TYPICAL CONCRETE MASONRY WALL REINFORCEMENT DETAIL PROVIDE 2#5 VERTICAL IN 2 CELLS EACH SIDE OF OPENING. BARS TO EXTEND FULL HEIGHT OF STORY IN WHICH OPENING OCCURS. GROUT CELL SOLID. LINTEL BRG ABOVE � MASONRY OPENING LINTEL BRG ABOVE SEE ARCH DWGS FOR LOCATION & DIMENSION PLAN VIEW TYPICAL JAMB REINFORCING FOR OPENING IN LOAD BEARING MASONRY WALL DETAIL TOOTH MASONRY TOGETHER AT EVERY OTHER COURSE REINF W/ (2)#5 GROUT CELL SOLID - INTERSECTING CONC MASONRY WALL CONT CONC MASONRY WALL OPTION #1 11 -1101, STRAP ANCHOR INTERSECTING CONC MASONRY WALL 1 STRAP ANCHOR 1/4"X1 1/2"XZ-6" W/ 3" RIGHT ANGLE BENDS AT EACH END AT 48" OC VERT MAX EMBED BENDS IN CORES FILLED W/ MORTAR OR GROUT OPTION #2 NOTES: 1. TYP AT ENDS AND INTERSECTIONS OF WALLS. 2. GROUT ONLY THOSE CELL CONTAINING VERT REINF UNO. 3. PROVIDE 2'-0" MIN LAP FOR ALL VERT BARS TYP AT ALL FLOORS. 4. FOR MASONRY WALLS NOT SHOWN ON PLAN NO REINF OR GROUTING IS REQ'D EXCEPT AS SHOWN ON TYP DETAILS. 5. USE OPTION #1 AT WALL CORNERS. TYPICAL CORNER AND INTERSECTING MASONRY BEARING WALL DETAILS HORIZ BOND BEAM REINF —1 24 24 (2) #5 CORNER BARS-� BOND BEAM SPLICE TYPICAL BOND BEAM CORNER DETAIL HORIZ BOND BEAM REINF CONTROL JOINT RAKE OUT & CAULK REINF W/ (2) #5 GROUT CELL SOLID TOOTHED MASONRY NOT REQD CONT CONC MASONRY WALL gW p ej ¢ o (2) #5 CORNER BARS ZEn 1�/3zU F Vya 24 24F Q F BOND BEAM TYPICAL BOND BEAM INTERSECTION DETAIL MASONRY LINTEL SCHEDULE WALL DIMENSION AND REINFORCING OPENING = "L" LINTEL MASONRY BLOCK WIDTHS LINTEL PRECAST CONCRETE WIDTHS MASONRY VENEER LINTEL (FT) DEPTH DEPTH 8" WALL 10" WALL 12" WALL W WALL 10" WALL 12" WALL GALV STEEL ANGLE 0'-0" < L < 4'-8" 7 5/8" 244 244 244 8" 244 244 244 L5X3 1/2X1/4 LLH 4'-8" < L < 6'-0" 7 5/8" 245 245 245 8• 244 244 244 L5X3 1/2X5/16 LLH V-0" < L < 7'-4" 15 5/w, 245 245 245 8" 245 245 245 L5X5X5/16 7'-4" < L < 8'-8" 15 5/8" 245 1 245 1 246 8• 245 1 245 1 245 L5X5X5/16 8'-8" < L < 10'-0" 15 5/8" 245 245 246 8" 245 245 246 L5X5X3/8 NOTES: 1. DO NOT USE THIS SCHEDULE IF CONCENTRATED LOADS ARE APPLIED 2. PROVIDE 8" BEARING AT EACH END (MIN) FOR 7 5/8" DEPTH, 16" FOR 15 5/8" DEPTH 3. ALL EXTERIOR LINTEL ANGLES SHALL BE HOT DIP GALVANIZED. 4. AT CAST -IN -PLACE END SUPPORTS, PROVIDE HOOKED DOWELS INTO CONCRETE WALL/COLUMN THAT MATCH SIZE AND QUANTITY OF LINTEL REINFORCEMENT. 5. " fc "FOR PRECAST CONCRETE SHALL BE 4000 psi MIN. 6..MASONRY AND PRECAST LINTEL REINFORCING SHALL BE PLACED AS SHOWN. 7. VERTICAL WALL REINFORCEMENT SHALL EXTEND THROUGH THE LINTEL AT THE BEARING ENDS. 8. ALL WIDTHS ARE NOMINAL DIMENSIONS. FILE COP Y w 0 V) O a cr CL o_ w iE O z Z a Ir O t- a a Z Ir O O i z w U a 0 O CL w D_ 0 W Z a z z O U 0 a w Z O a �— Z � a ,,`tilt„1 n n 11 unnb♦. s'QJ "•• 'c'E " 0% ATLANTIC = Q:'•� ENGINEERING =* •47 6501 Arlington Expressway Building B, Suite 201 Jacksonville, FL 32211 �� PH: 904.743.4633 FX:904.725.9295♦♦ •• . O R• 1.O P' • �: AES #317407 ♦ ♦♦Vs, • `,,,` ♦ /Oil • � ReE�/180 R. Wulbern Architect PA AA.0003433 He (904)3204510 NI robartowul[wm.nat 0 In Z 0 N CAI Y O- G IL X w IY LL W n � H Q V N 0 � o � L co N NO O N J O o I� Z Z Q Y Uj I W w H o o a o 0I goldcoI.F ,..,H., VERTIC L O 0 CD 1.j Vj 0 z Z W W � a a r M Co Y 0 Z� �0 O awU)Z Y O 3 =O 0 = W�Gn0L) A/==g 00J 0w�� Ina 0z J U J_ b Q� S L r W fW/l o Z U C W J z F— g H H W W N S-9 1' WITH SON LUS28-2 IEND D TRUSS WITH OP CHORD 'LAN WITH SON LUS28-2 END TYPICAL ROOF OPENING FRAMING DETAIL NOTE: 1. SEE ARCH/MECH DRAWING FOR SIZE AND LOCATION OF OPENINGS. PLYWOOD WALL SHEATHING 2X6 BETWEEN TRUSSES AT EACH STUD WITH SIMPSON LUS26.2 EACH END PLYWOOD WALL SHEATHING — PRE -FABRICATED WOOD TRUSSES SEE PLAN-! ATTACH LAST STUD TO BLOCKING WITH (2) #10 X 3" SCREWS AT 2'-0"OC 2X4 BLOCKING BETWEEN TRUSSES AT 2'-0"OC VERTICAL 2X4 FRAMING AT 1'-0"OC MAX ATTACH TO BLOCKING BELOW WITH SIMPSON LTP4 SLOTTED THROUGH ROOF SHEATHING DETAIL q SCALE: 3/4" = V-0" S-10 2X8 CONT NAILER 'X' BRIDGING AT 20'-0" OC MAX AND AT EACH END PLYWOOD ROOF SHEATHING LAP HORIZONTAL BRIDGING OVER TWO ADJ TRUSSES 2X4 DIAGONAL BRIDGING CONN WITH (2)16d NAILS. CONN. AT EACH TRUSS W/(2) 16d NAILS (LOCATE BRIDGING CLOSE TO TRUSS PANEL TYPICAL WOOD TRUSSES NOTE TO GENERAL CONTRACTOR: WHERE THE CEILING IS NOT TO BE ATTACHED DIRECTLY TO THE UNDERSIDE OF THE TRUSES, THE TRUSSES SHALL BE LATERALLY BRACED WITH CONTINUOUS 1"X4" MEMBERS NAILED TO THE UPPER SIDE OF THE BOTTOM CHORD AT A MAXIMUM OF 6'-0" ON CENTER WITH TWO(2)-16D COMMON NAILS AT EACH INTERSECTION OR AS SPECIFIED BY TRUSS MANUFACTURER. THIS LATERAL BRACING SHALL BE RESTRAINED AT EACH END AND AT 20'-0". ATTACH DIAGONAL BRIDGING TO NAILER WITH SIMPSON HGA10. TYPICAL BRIDGING DETAIL TRUSS CONNECTOR SCHEDULE TYPE CONNECTOR CAPACITY (LBS) 1 SIMPSON H10A WITH (9)10d UPLIFT = 1340 X 1 112 TO TRUSS AND (9) 10d X 1 1/2 TO PLATE 2 SIMPSON HUS26 WITH (14) UPLIFT = 990 10d X 1 1/2 TO NAILER AND GRAVITY = 2130 (6) 10d TO TRUSS 3 SIMPSON LTT19 WITH 3/4"DIA TENSION = 1310 BOLT TO NAILER/ WALL AND 1(8)10dX1112TOTRUSS NOTES: 1. CONTRACTOR SHALL VERIFY TRUSS REACTIONS DO NOT EXCEED CAPACITIES LISTED. 2. CAPACITIES ARE AT ALLOWABLE LEVEL- NID L . ATLANTIC NO' ENGINEERING- * e \ am \a� 6501 Arlington Expressway • Building B, Suite 201 0' E OF Jacksonville, FL 32211 :� •.•• 4 OR 1• P,: • �?�� PH: 904.743.4633 M904.725.9295 �, .� AES #317.107 '"'S'''0NAL,tt�'` DAVID L WEBB PE 47180 R. Wulbern Architect PA AA - 0003433 lie (904)329.2510 tat mbort@wulbam.rwt 0 U) Z z o N rn Y U a (L LLI W 0 Ix U. w r` H o v � o� 00 ao N O fN J O o I� Z in --^^ Z Q Y w W W H o Cgoldco VERTIC L z Q: Q Lu C) W C) a a O Yo Z cc O LL YO 1:43 C = O U Lj . (0,0 WizLo J Z O u) J_ b Q � s W I Q Z Q � U W J z Z H- F- LU W Cn S-10 o1-- Ld wN� X0w IL P- X X Xww w0�F X_ tw + Of00 h I I I I I I I DIRECT BURY CONCRETE POLE I I I1_ I 5'-0" dl MIN MIN I CONDUIT ENTRANCE --- I CONDUIT DIRECT BURY #8 - GND WIRE TO 3/4" X 10' CU GND ROD 18" #4 PIGTAIL AT POLE BASE AND AT TOP 0 I I a 36" MIN HOLE, BACKFILL WITH I STRUCTURAL FILL & COMPACT TO 95% DENSITY POLE BASE DETAIL (ALTERNATE ® POLE DETAIL NOTES: NO SCALE 1. PROVIDE POLE/LT FIXTURES WITH ALL REQUIRED HARDWARE FOR MTG. 2. PROVIDE/INSTALL CONDUIT, AND PULLSTRING, JEA SHALL PROVIDE/INSTALL CONDUCTORS, POLE, MTG ARM, AND LIGHT FIXTURE. INSTALL ALL PER UTILITY CO REQUIREMENTS. 3. PROVIDE AND INSTALL CONCRETE LIGHT POLE PER MANUFACTURERS RECOMMENDATIONS TO WITHSTAND LOCAL EPA WIND SPEED RATINGS FOR AREA OF INSTALLATION (161 MPH MINIMUM). LIGHT POLE/FIXTURE(S) HAND HOLE 0- W/BLANK COVER POLE BASE COVER �----- 1" CHAMFER 2'-011 °i GROUT AROUND la ANCHOR BOLTS °I ° I aJ L III-1 11= a I ° #8 CU GND - Ell 2'-0' _III- °I ° °I IN 1/2" PVC -III a o I- I -- ------------------------ CONDUIT J1- - - - - - " d i a -d l TRANSITION COUPLING p ° j DIRECT BURY #8 GND WIRE TO 10' X --�---� 3'-0" I I 5/8"'CU GND ROD MIN al (4) #7 REBAR RODS ° W/#3 TIES ® 12" O.C. I a ° y ROUND CONCRETE BASE d a ' BACKFILL AROUND 18„ BASE &COMPACT TO 957. DENSITY POLE/BASE DETAIL NO SCALE DETAIL NOTES: 1. CONSULT CORPORATE CIVIL PLANS FOR OTHER REQUIREMENTS. ALL POLES/FIXTURES SHALL MEET OR EXCEED WIND LOAD REQUIREMENTS GIVEN BY LOCAL CODE. t 1.; 2 CD to D 01 HARDEE RD 01 0`.1 01 AREA OF WORK $-5 $7 65 $ $ J66�65 5 4�6.dJb.3J0.�0. 0�`0 d�6T+6'f ff T 1T2 t2 t-2 t 2-t 2-t2-Q.ft.Tt.T-b7-b7�o-T�Ti- Jc f'b7 tm'0 `UD $o$To- f0 t Tt.Tt.0$.n-t o'Tufi0.0 t.0 +0 + + + .4 +0.5 +0.6 10.7 10.9 1.1 1.1 1.0 1.0 0.8 10.9 1.1 1.4 -1.8 2.1 2.6 3.4 4�9 7. 7.8 8 7.8 6.8 5.0 3.4 2.4 1.8 1.3 1.0 1.0 1.1 1.4 1 7 1.9 -1.5- 0,8 +1 0 }1 5 + + + 52+ + ; ,.. + + + - s + + + S;. + ' s +' + .1 3.3 4.6 5.9 7.0 7.3 6.9 6.1 5.0 3.5 2.6 2,1 1.7� �,6 1.7 1.7 1:7 1.7 1.8 2.1 2. 3.0 3.2 4.0 5.0 6.7 7.2 7.2 6.8 5.9 4.5 3.2 2�2 1,6 1.2 1.1 1.1 1.2 1.5% 2.1 2$v3.7 3.7 3,, � 0;9 1:3 ?:0 2.9 +4.1 +5.4 +6.3 +6.5 +6.4 +5.8 +5.4 15.1 +4.0 `3.4 +3.4 2.9 2A ,,2.2 +3,1-+3.6 '3.5 `4.2 15.5-5.9--5.2-" +5:7 -+6.0 U 18.9 +6:8-16.7 +5.7 +4.313:1-12 +1;6 1.3 1.1 }1,2 +1.3 +1:7 2.3 +3.3 +4.8 +6.4 3 0.91.31,92.63.44.45.25.35.2515.46.05.34.75.23.7241.3.3.35.24.85.5+7.88.06.66.17.36.2+7.4}7.47.16.95.64.02.821.11.61.41.31.31.51.92.63.64.76,3 \U\ 10:9-+13 +1.7 12.3 +2.9 +3.6 +4.1 +4.3 +4.3 +4.4 +5.2 +6_.6 +6 7 +6.1 +6 9 +4 2 �2.14 +1.2 10:5 6.2 6.0 6.9 9.4 9.5 ° 4 8.6 ,3.0 11.28.2 8.3 +7.5 5.6 3_9 2.6 2 + + + + 1 + + \ + + + + + + 18,0 �.. + + + + + + + 17 15 1 21 27 37 49 62 0.9 1.2 1.Tf 2.2 2.8 3.2 3.7 3.9 3.9 4 � L 1 2 3 20. 1.8 1 _ ,. '2� 2.4 3.d, 3.5 4.7 5.4\ 0/II 2 0.13 1.7 2.2 2.7 3.0 3.3 3.5 3.6 4 2.2 2. 2.7 3.1 3.8 4.2 4.7 5.2 4.9 4.5 36 1,1 1i4 1.8 2.3 2.6 2.8 3.0 3.0 2. Y 2.7 2.7 0 3.3 3.5 4.1 4.4 4 1 3.9 3.5 2.9 1.9 i \ 3.$ 3. 1 + a y + + 5 �� 26 2. 21'3. I} 3.3 + L BURGER KING 3.3.2 3.4 5 3.8 3.7 3.7 3. 2.5 2.0 1.7 PROPOSED {+3.4 .8 +3.8.7 +3.6 +3.5 +3.3 +3.0 +2.5 '2.' �1 1.8 +. i 2 _ 1+. �4-2. 2.9I3 + �: 3.2`3.4 Q.0+4.2+4.1+3.8+3.5+3.3+3.0+2.5+2.11. -.-. + t + + + 3.1 3.3 .1 4.2 -3 4.2 3.9 3.6 3.1 2.6 2.3` 1,8 1. ;1,9 1.7 15 1.4 +: + µ 12. + '2. + '3. + +13+1. 1416392.22.42. 2.72.82 / ) + + + + + + 2.32.1+1.81.8�1.7). 1.2 1.4 1.6 1:9 2.2 2.4 2.6 2.8 2.9 0 i + + 0 , . .2 +A.5 +4. +4.5 +4.3 +3.8 +3.3 +2.8 \\,_ i 2.3 +2.6 +2.7 +2.6 2.3 2.3, 2.3 2.4 1.3 15 1.8 2.0 3 2. 6 7 2. \` L - 2.9 1 0 4,3 4 4.5 4.3 4.0 3.5 2.9 2.5+ // 2.1 2.3 \ .1.0 13 15 1.8'2.1 2.5 2.7 3.0 3.1 _ 2.5 2. 8 1 4.4 4. 4.6 4.3 4.0 3.6 3.0 2.6 ----� 2.5 2.8 2.9 2.8 2.6 2.7 2.9 3.1 3:6 1 --- \2.0 2.4 2.8 3.0 3.2 3.4 3.3+ + + + + + + } 3 2: c: rr✓ 2: 9 4.2 4.4 4.3 4.1 3.9 3.5 3.0 2.5 2.2 2. .3 2.5 2.9 3.1 3.0 2.8 3.0 3.4 3.7 4.5 5.5 6. 2.1 2.6 2.8 3.0 3.1 3.1 3.0 2.6 2.41.9 1.6 1.4 1.3 1.4 1',8 2.8 4.3 6.2 5.4 5.7 6.4 5.4 5.0 4.3 4.0 3.8 3.4 2.9 2.4/2.1 1.9 1.9 1.9 2.1 2.4 2.8 3.2 3.4 3.7 3.9 3.8 3.7 3.5 3.1 2.6 2.3;2.02.0 .. 2.5 29 32 3.1 2.9 3.2 3.8 4.2 5.1 6.2 7. 2.3 2.7 2.9 3.1 2.6 2.2 1.7 1.5 1.2 1.1 1.2 1.8 2.5 3.4 4.1 3.9 4.2 4.8 4.9 4.5 4.0 3,7 3.4 3.0 2.6 2.1 1.8 1.6 1.5 1.6 1.8 .0 2. .2 3.5 3.6 3.6 3.5 3.2 2.8 2.3 z.1 1.9 1.9 2 2.4 2 9 3 2 3:I 3,p 3.3 3.9 .4.2 5.1 6.3 ��4 2.8 3.1 3.4 3.4 3.1 2.8 2.2 1111111 .8 .4 .2 .0 .0 .3 .7 2.1 2.2., 2.3 2.8 3.3 3.8 4.1 4.1 3.8 3.3 2.9 2.4 +1.9 +1.6 +1.4 +1.3 +1.4 +1.6 +�,.9 2.42.93.33.63.93.73.43.1262.2 +1.9 1.7 +1.82. 2.4 +2.8 3.0 +3.0 +2.8 +3.1 +3.5 +3.9 +4.7 15.8 5.8 6. � + + + + + + + + + + + + + + + + + + + + + } + + + + + + + + + +l < + + + + + + + + }i + + + +,, + + + + + + + + + + + \ i 5.1 3.7 4.1 4.1 3.8 3.0 2.4 1.8 1.3 1.1 9 1 0 1.2 1. 1. 8 .2 3.7 3.1. 2.4 1.8 1.5 1.3 1: 1 3 1 5 18 2.3 .0 3.6 4:2 4.4 4.3 3. 2 5 2 1- .8 1.6 1 A '9 2.2 .8 � 0. 0 9 3 4 �. 2.3 3.0�3.2 4.3 4.4 4 � $ 32- J `'� . , 1. 2.6-2.4 2 2.6 2.8 3.p 3.2 3.9 4.6 5. \3 4.7 4.7 4.2 3.4,2.6`,1.9 14 1.1 0.8 +0. 8 0.8`0.9 1.0 1.2 1. \ \ 1.8`,2.1f/`�\'A+2.4+25.+2\6+3.0+3.3+4. 7 2.3 lA/ \ 5.0 4.9 `4.2 3.4 2.5 2.0 1.6 1.3 1.2 •1.2 1.5,9 2.5 3.3 4.1 4.9 5.1 5.0 4 1 1.6 1.fi \ +5.7 +5.7 5.1 +4.0 +3.0 2.1 +1.6 +1.1 +0.9 + .7 +0.7 +0:8 1.0 +1.2 +118 +2.5 �\ +5.8 +5.b +3.9 +2.9 2.1 +1.5 3 +1.2 +1.$ 1.5 +2.1)` 2.7 +3.7 4.6 5.8 +6.p 5.8 +5.0 1.5 +1.5 1.7 1. +1.9 1.9 1.9, 2,2 +2.4 +2. - 1.0 1.0 •. S2 V86.5 5.6 4. 1.51. 1.5 1- 1 4 1 4n 65 58 4.5 3.3 2. 1.6 1,2 0.9 0.� 0 7 0 8 1.0 1.3 'L8 2 7 3 8 5 5.6 4,$ 0 +1.1 +1.� 3 3 2 2 2 1 7 1 3 1.2 1 3 1 6 2.1 30 4.1 5.5.6.4� S2 2 0.7 �.7' +0. +0. +0.5 `0.5 + . +0. \ 0.4+0.4+0.3+.3+0.3+0A i- }- '�- �-- -i- rt -� -�. ---r-F�+-+- �- }- }- �- -� -I- �- -� -° -t-F-}��- i---+- y- y- �--- r- -�-. r- 4 .2 0.2 0.3 TAM n1 n1 n1 n1 n1 n7 ns na OA 03 n.a OA 09 n1 01 n-1 n-1 0.1 01 0.1 0.1 01 0.1 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.2 0.1 0.1 01 0-1 n1 no--s-+��-,. _..-. -. SITE POLE FIXTURE SCHEDULE KITTERMAN ROAD PHOTOMETRIC SITE PLAN SCALE: 1" = 20'-0" ® PHOTOMETRIC NOTES: 1. SEE ELECTRICAL SITE PLAN FOR CIRCUITING INFORMATION. APPROVED SITE FIXTURE LIGHT LAMP INPUT SYMBOL MFRS. ** MODEL POLE TYPE WATTAGE LIGHTING XLCM-FT-LED SS-CW-HSS SINGLE ON '5SQBO-S21G-23, d:18' POLE *** 193 LED 193 SYSTEMS ±18' POLE + 2' BASE 20'-0" MAX. HEIGHT TO TOP OF ! "S2" » INC. I FIXTURE ADJUST CONC. BASE or I BURIAL DEPTH AS NEEDED. !PAINT TO MATCH SHERWIN WILLIAMS #2103 OR #2206 * PROVIDE ALL "S2" & "S2" FIXTURES WITH EXTERNAL HOUSE SIDE SHIELD IN ADDITION TO INTERNAL HOUSE SIDE SHIELD OPTICS. ** APPROVED MANUFACTURER'S SHALL INCLUDE EQUAL FIXTURES BY, RUDD LIGHTING AND H&L LIGHTING. *** PROVIDE SEPARATE PRICING FOR OWNER OPTION, IN LIEU OF METAL POLE ON 2FT CONCRETE BASE, PROVIDE DIRECT BURY CONCRETE POLE WITH MATCHING DISTANCE ABOVE GRADE. SEE "POLE BASE DETAIL", OR "POLE BASE DETAIL (ALTERNATE)" FOR ADDITIONAL REQUIREMENTS. Schedule Symbol Label Quantity Manufacturer Catalog Number Description Lamp Number Filename Lumens Light Loss Wattage Lamps Per Lamp Factor 8 N 1 LSI INDUSTRIES SWM-2-LED-CW-UE Wall mounted 1' below canopy, LED 1 SWM-2-LED- 4074.796 0.95 41.6 security light CW-UE.IES . 6 LSI INDUSTRIES XPWS3-FT-LED-48-450- Wall mounted at 14', area light LED 1 XPWS3-FT- 6154,666 0.95 72 8 L CW-UE LED-48-450- CW-UE.ies 7 LSI INDUSTRIES XLCM-FT-LED-SS-CW- Area Site Pole. Light, Mounted on Pole LED 1 XLCM-FT-LED- 16556 0.95 181.7 �" S2 INC. HSS Refer to Schedule for Fixture Ht. SS-( HISS.ies Statistics Description Symbol Max Avg Min Max/Min Avg/Min Parking/ Drive + 11.2 fc 3'0 fc 0.2 fc 56.0:1 15.0:1 Property Line + 0.7 fc 0.1 fc 0.0 fc N/A N/A to.0 10.0 ro.0 40 � �� ENTIRE Y REVISED ,A 0 1/4/18 2813E01 POWELL & HINKLE ENGINEERING, P.A. ROBERT L, HINKLE PE 29302 & H 1409 KINGSLEY AVENUE, BLDG 12A GALTON LANE R. C, MOK HINKLE PE 33192 P ORANGE PARK, FLORIDA 32073 PE 48076 (904) 264-5570 FAX:(904) 278--2646 ENGINEERING CORPORATION FLA. REG. EB-4577 THOMAS RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 R. Wulbern Architect PA 6 O AA-0003433 Ilc• N L)(904)329.2510 tel e 0) .0 robert@w lbem.net e Cl C U 2 a •G oCD c m EL > c ca m 0 c C M > ;o a r c 0 d C C°1 Q 0) m w v cc a) Q) d Na C a) c ° or a)N C rn D a � d 'c o m V C °' o d ° c 0 c N M M c mE N U 4 0 L Z Z 0 W Y = z a U (� S2 S2 a Lu Lu E LL tr 0 m m LL UJI F- O O N 2 �' > m w F N a n O 0 O z w U z Y w - x m a X O U OO 0 0_ goldco VERTIC L i1 0 0 4) J U) %%ftoi N Ln ti o Ilm w N z LO tQ N LU dam• ZU co Yo to Z� �� W� IYUO�5 WU [-+=0 Q LI °� O �rl a) J 000Ztocoku U Q W -� w c z O U) lu CL W J � 0 0 p f- w w x E0,ional .. HARDEE ROAD I � 11� \ ------------- -- _ _ TRAF SIGN BUILDING MOUNTED A-13 1 LIGHTS (TYP, SEE I! PROPOSED BURGER KING TELE CABINET �- 5 3-2"PVC TFI F /CARI F ----------- AREA OF WORK A-9,11 _— -.DRIVE-THRU MENU METER, SHUNT BOARD COMM SYSTEM V� I MTS & GEN. (SEE LIGHTING PLAN):TRIP, TAP BOX_§§ E ` RISER DIAGRA\/ �4 SECONDARY , Q• / / PROPOSED / 1 UTIL. CO. TRANS. i ELECTRICAL SITE PLAN SCALE: 1" = 20'-0" PRE -SELL MENU BOARD (SEE LIGHTING PLAN) ® SITE PLAN NOTES: 1. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF PRIMARY SERVICE CONDUIT & CONNECTION POINT PER ELECTRIC UTILITY CO DIRECTION. PROVIDE/VERIFY (2) 4" SCHEDULE 40 PVC CONDUITS W/36" RADIUS ELLS TO UTILITY SERVICE CONNECTION POINT. PROVIDE CONDUIT W/PULLWIRE AND MAINTAIN 42" MINIMUM DEPTH, CALL FOR INSPECTION BEFORE COVERING. PRIMARY AND SECONDARY CONDUIT/FEEDER LOCATIONS ARE CONTINGENT UPON ELEC UTILITY CO APPROVAL. PROVIDE PULLBOX/COND.UIT/PULLWIRES AND GROUND RODS PER ELEC UTILITY CO REQUIREMENTS. SEE 'POWER RISER' FOR COMPLETE REQUIREMENTS. 2. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF SERVICE CONDUITS & CONNECTION POINT PER TELEPHONE UTILITY CO DIRECTION. PROVIDE/VERIFY TELE CO REQUIREMENTS OF (2) 2" SCHEDULE 40 PVC CONDUIT RUN OUT PAST PROPERTY LINE, W/200LB PULLWIRE, SEAL ENDS TO PREVENT GAS/WATER/RODENT INTRUSION, 24" MINIMUM COVER, CALL FOR INSPECTION BEFORE COVERING. SEE ALSO 'TELEPHONE RISER DIAGRAM' FOR COMPLETE REQUIREMENTS. 3. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF SERVICE CONDUITS & CONNECTION POINT PER CABLE UTILITY CO DIRECTION. PROVIDE/VERIFY CABLE CO REQUIREMENTS OF (1) 2" SCHEDULE 40 PVC CONDUIT RUN OUT PAST PROPERTY LINE, W/200LB PULLWIRE, SEAL ENDS TO PREVENT GAS/WATER/RODENT INTRUSION, 24" MINIMUM COVER, CALL FOR INSPECTION BEFORE COVERING. SEE ALSO 'TELEPHONE RISER DIAGRAM' FOR COMPLETE REQUIREMENTS. 4. SERVICE ENTRANCE SECONDARY FROM ELEC UTILITY CO TRANSFORMER, SEE 'ELECTRICAL RISER DIAGRAM' 5. PROVIDE ALL CONDUITS WITH MULTI -STRAND POLY -CORD PULLSTRING (TYPICAL). 6. FIELD VERIFY & COORDINATE EXACT LOCATION OF EQUIPMENT WITH OWNER AND SIGN CONTRACTOR. SEE 'ELEC LIGHTING PLAN' & ELEC POWER PLAN' FOR COMPLETE REQUIREMENTS. UNDERGROUND CONDUIT (TYPICAL) 1/4/18 2813E02 R013ERT L. HINKLE PE 29302 POWELL & HINKLE ENGINEERING, P.A. GALTON C. MOK PE 33192 1409 KINGSLEY AVENUE, BLDG 12A P & H LANE R. HINKLE PE 48076 ORANGE PARK, FLORIDA 32073 (904) 264-5570 FAX:(904) 278-2646 ENGINEERING CORPORATION FLA. REG. EB-4577 THOMAS RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 Ia No.4I STATf R. Wulbern r Architect PA d AA.0003433 Ile WU (904) 329.2510 tel N U robert@wulbern.net Q c EL` c . (a m c � a a c 0) m N � ma 'v N N w o S �m m m W �N d dw m d -0 d� N Nr (m c •No> d c t77 T 'y i4 d 2 a) m U c N L m E c E N U to W Z N r a 0. w F w w 0 Lu � m m LL 0 LL Lu F- o o N 0 0 0 0 4 ti 04 m F to O Co 6I-- Z Y W Z i x a O U OO 0 IL goldco VERTIC L O V J N LO ti o 0) 0Y N z a QN • W It o "' ZU Yo Zo � '" _ LL W= (nz WU®=o 0���W =O W 00 COO Z �aynn r J z Q Z t s W W W W J H a 0 p H H W w x N EO-2 ON 0 ■ ol C LSI PDL6K LED HO WW 120 SECURITY SLSDBXQL L86LEDA30K WH D CREE LRS 10L 30K 120 A DR W/ RC6 12W GU24 -{ LIGHT FIXTURE SCHEDULE MANUFACTURER CATALOG NO. WATTAGE REMARKS NAUTICAL FURNISHINGS BK-CG-A 12W GU24 LED SHAKER PENDANT LIGHT. PENDANTS TO BE CENTERED OVER TABLES PER DECOR DRAWINGS. COORDINATE LOCATION AND QUANTITY WITH DECOR SUPPLIER. LOWEST BOTTOM OF LIGHT: 6'-6" NAUTICAL FURNISHINGS BK-CG-B 3.5w A-19 LED I CAGE PENDANT LIGHT. PENDANTS TO BE CENTERED OVER TABLES PER DECOR DRAWINGS. COORDINATE LOCATION AND QUANTITY WITH DECOR SUPPLIER. - - SEE ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT(S). CREE CR 6 800L 35K 12 GU24 CT6AW RC6 12W GU24 12W GU24 LED — 6" RECESSED LED DOWNLIGHT RECESSED 6" LED DOWNLIGHT 13W 30K LED 6" RECESSED LED DOWNLIGHT 14W 30K LED 11W 30K LED ,t,1r 1 D0, CREE LE6 GU24 RC6 12W GU24 12W GU24 LED E 6" RECESSED LED ADJUSTABLE DOWNLIGHT 8w PAR20 LED 120 VOLT TRACK WITH LED PAR LAMP MOUNT TO CEILING SURFACE ! (VERIFY) PARAPET LIGHT BAND TO BE SUPPLIED & INSTALLED 0.5W/FT LED ' BY LEKTRON, INC, OR D.V.S., OR SIGNSTRUT, INC. COORDINATE LENGTH OF BAND AND ELECTRICAL REQUIREMENTS WITH MANUFACTURER. G.C. TO RUN ' POWER AND PROVIDE FINAL CONNECTIONS TO LIGHT F FIXTURES. FLUXWERX BK GG F PROFILE 100 DN LED LIGHT 38W 40K LED 16" ALUMINUM FINISH F12' LSI GA24 LED HO NW UE P12 57W 40K LED 2'x4' RECESSED LED- LENSED -TO BE USED IN THE KITCHEN SECURITY LJT24 40MLG FSA12 EU C388 41W 40K LED G CREE CR24 40L 40K S 57W 40K LED h Et JUNO LIGHTING BK-CG-G 1OW 30K LED CEILING/RECESSED 2" LED ROUND DOWNLIGHT, O2B 930 F U SSN 2-NCMF SATIN NICKEL BAFFLE FINISH GO- BK-CG-G CEILING/RECESSED 2" LED ROUND DOWNLIGHT, JUNO LIGHTING 1OW 30K LED ® _ 2A 930 F U SN 2-NCMF WITH ADJUSTABLE GIMBAL, SATIN NICKEL BAFFLE FINISH rA G1 LSI SECURITY GA24 LED HO NW UE P12 57W 40K LED 2'x2' RECESSED LED— LENSED LJT24 40MLG FSA12 EU C388 41W 40K LED HCREE CR24 40L 40K S 57W 40K LED LSI XSL2 S LED 50 CW WHT CMT 86W 50K LED RECESSED LED SOFFIT LIGHT I — — —FOR NEW CONSTRUCTION ONLY SECURITY 851/852 LED 60 U W (RETROFIT) 30W SOK LED I � K (VERIFY) (FIXTURE) EKLPU4RW EKAUCW (LAMP) LP208AF3, (2' TRACK) EK1T2, (FEED) EKC261W, (CONNECTOR) EKC231W XPWS3 FT LED 48 450 CW UE MSV 72W 50K LED', WALL MID AT 14FT, LED FLOOD LIGHT -DOWN LIGHT ONLY RWSC 30LED WD PS MT 30W 50K LED RS 30WLED DO SV 120 3OW 53K LED EG3 4 S LED HO CW UE 60W 50K LED LED LINEAR VAPORTIGHT _. -FOR IN AWNINGS AND COOLER/FREEZER SYMBOL LEGEND DETAIL DESCRIPTION TOGGLE SWITCH - SINGLE POLE HUBBELL #1221-1 Q PUSHBUTTON SWITCH DUPLEX 125V-20A-2 POLE-3 WIRE STRAIGHT BLADE RECEPTACLE OUTLET - WALL MID. (24" A.F.F., - U O.N.) qp DUPLEX RECEPTACLE OUTLET WITH USB CHARGING OUTLET LEGRAND_#TM8-USBWCC6 SINGLE 125V 20A-2 POLE-3 WIRE STRAIGHT BLADE RECEPTACLE OUTLET - WALL MTD.(24" A.F.F., U.O.N.) 208V RECEPTACLE HUBBELL 208V 14 - #5352 1 208V, 34 - #8420/#8460 Qj JUNCTION OR GANG BOX 0 TELEPHONE OUTLET WITH BUSHED HOLE COVERPLATE CABLE TELEVISION OUTLET LB! BUZZER / BELL H REAR DOOR ALARM ❑T TRANSFORMER TELEPHONE OUTLET FOR P.O.S. MODEM 0 MOUNTED 96" A.F.F. (ALL OUTLETS HOMERUN IN 3/4" CONDUIT TO TELEPHONE BACKBOARD) SECURITY CAMERA BY "PRIVID-EYE" CONTACT: LARRY SATTLER, 954-581-1756 SECURITY MONITOR BY "PRIVID-EYE" TV PROVIDE DUPLEX RECEPTACLE ® 84" A.F.F. (VERIFY) CONNECT TO P.O.S. CIRCUIT B B BUMP -BAR (3 P.O.S. PRINTER DEVICE P.O.S. REGISTER DEVICE g VIDEO DISPLAY DEVICE (CEILING MTD.) A-3 CONDUIT RUN WITH ARROW DENOTING HOMERUN. SUBSCRIPT INDICATES PANEL AND CIRCUIT NO. GROUND CONDUCTOR REQUIRED IN ALL CONDUITS BUT NOT INDICATED O R WAOLK IN REFRIATER GERATOR/FREEZER KON DVP 182 14 JY 36W 45K LED SWM 2 LED CW UE GBZ 42W 50K LED WALL MTD AT LOFT, LED SECURITY LIGHT WGH 1LU M 41W 50K LED E.WP1X031Z7 27W 40K LED LIGHT FIXTURE SCHED LE NOTES: 1. NOT ALL LIGHT FIXTURE TYPES SHOWN ON SCHEDULE MAY BE USED ON THIS PROJECT. REFER TO LIGHTING PLAN FOR PROJECT SPECIFIC TYPES AND QUANTITIES. LSI XBAL NFL25 LED SS CW UE ELK USF J35AH1 / 23W 40K LED GROUND MOUNTED, LED NARROW FLOOD 2. PENDANT FIXTURES "B2" MUST BE CENTERED OVER TABLE TOPS. COORDINATE WITH -SEAL MOUNTING BOX TO PREVENT DECOR DRAWINGS. SECURITY WATER INTRUSION 3. EXCEPT FOR DROPPED CEILING OPTION, ALL LIGHT FIXTURES IN DINING ROOM AREA AND RESTROOM CORRIDOR ARE TO BE SUPPORTED FROM EXPOSED ROOF TRUSSES. - USE 2x4 BETWEEN BOTTOM CORDS FOR SURFACE MOUNTED FIXTURES. P CREE 4. CONTRACTOR TO NOTIFY LIGHTING SUPPLIER OF THE FOLLOWING: FIXTURE TYPES 'C' AND -- - -- V WILL BE REQUIRED TO BE LENS AT THE LOCATIONS OVER THE SERVICE AREA AND LSI LTEM WH 1OW WHT LED EMERGENCY EGRESS LIGHT OVER THE SELF -SERVE DRINK AREA. FIXTURE TYPE 'G2' WILL REQUIRE A LENS OR TUBE GUARD T THOSE LOCATIONS. SECURITY 5. SYMBOLHALF SHADED' OR 'NL' IS INDICATED, PROVIDE FIXTURE WITH WHERE 'SYMBOL BUILT-IN EMERGENCY BATTERY UNIT FOR EMERGENCY LIGHTING (1100 LUMEN EM22RWH 11W WHT LED MIN. FOR 4FT LAMPS). PROVIDE DOWNLIGHTS WITH FACTORY INSTALLED E M iCREE INTEGRAL PUSH TO TEST BUTTON MOUNTED IN TOP OF FIXTURE REFLECTOR. _ _ _ CONNECT TO OPERATE AS FOLLOWS: LSI LPRX R U LD11 R 2W RED LED EMERGENCY EGRESS LIGHT i HALF SHADED'- CONNECT FIXTURE TO OPERATE WITH SWITCH AND BATTERY UNIT TO OPERATE FIXTURE UPON BRANCH CIRCUIT FAILURE. II SECURITY CCRRC 2W RED LED 'NL'- FIXTURES ARE TO BE CONNECTED AHEAD OF LOCAL SWITCH ES TO ( ) OPERATE AS NIGHT LIGHT, BATTERY UNIT OPERATES LAMPS ON FAILURE OF E MX CREE EXDMBRWH 2W RED LED BRANCH CIRCUIT. FOR SPECIAL LIGHTING PRICING ON THE TOTAL LIGHTING PACKAGE CALL LSI SECURITY LIGHTING CREE/HERMITAGE KONTECHUSA NAUTICAL FURNISHINGS JUNO LIGHTING/ACUITY BRANDS RON LARIMORE ERIC HILLESLAND STEVE FRIEDMAN MIGUEL MARTINEZ MICHAEL HOGLUND SHAWN FENTRESS 800-436-7800 x3375 630-63-8493 262-504-5479 866-236-8701 954-771=1100 904-744-7000 x27 CTORY OF MANUFACTURERS AND SUPPLIERS PHIS LIST IS INTENDED TO ASSIST THE CONTRACTOR IN SOURCING BUILDING MATERIALS AND PRODUCTS. IN MANY CASES APPROVED BURGER KING MATERIALS AND PRODUCTS MAY BE PURCHASED DIRECTLY FROM THESE SOURCES AT A NATIONAL ACCOUNTS PRICE. FOR A COMPLETE LISTING OF APPROVED MANUFACTURERS SEE PLANS AND SPECIFICATIONS. DIVISION 16000 — ELECTRICAL -LSI INDUSTRIES INC. (LIGHTING) -HERMITAGE LIGHTING NAT. ACCOUNTS INTERIOR AND EXTERIOR LIGHTING INTERIOR AND EXTERIOR LIGHTING SURVEYS AND PHOTOMETRICS 500 LAFAYETTE STREET 10000 ALLIANCE ROAD NASHVILLE, TN. 37203 CINCINNATI, OH 45242 BRYAN BIRDWELL, JOE LUTTMAN ANDY STRICKLAND 615-843-3369, 615-843-3368 513-793-3200 -RUUD LIGHTING, INC. -HM ELECTRONICS (DRIVE-THRU SOUND SYSTEM) LIGHTING EQUIPMENT 9201 WASHINGTON AVENUE 6675 MESA RIDGE ROAD RACINE, WI 53406-3772 SAN DIEGO, CA 92121 JEANNE MASCARETTE (800) 909-6604 262-884-3215 (619) 535-6030 -SECURITY LIGHTING -3M SOUND PRODUCTS EXTERIOR SITE / BLDG. LIGHTING (DRIVE-THRU SOUND SYSTEM & 1085 JOHNSON DRIVE SATELITE ANTENNA) BUFFALO GROVE IL 60089 3M CENTER STEVE FRIEDMAN, MIKE KREINER BUILDING 551-lW-01 847-279-0627 ST. PAUL, MN 55144 -TRANE CO. (800) 328-0033 (ENERGY MANAGEMENT PANEL) (612) 733-8027 2550 CORPORATE EXCHANGE DR.#200 COLUMBUS, OH 43231 -AEI MUSIC NETWORK, INC. (800) 872-6330 (SATELITE ANTENNA) 900 EAST PINE STREET -SYLVANIA LIGHTING SERVICES E, WA 98122 (LIGHTING SERVICES) (800) 831-8001 (800) 500 FRANK BURR BOULEVARD TEANECK, NJ 07666 -SUNCOAST ENVIRONMENTAL (800) 579-1514 CONTROLS, INC. -N.C.A. (ELECTRICAL SWITCH GEAR) (MASTER CONTROL SYSTEM) 8655 115TH AVENUE NORTH 4585 140 AVENUE NORTH, SUITE 1009 LARGO, FL 34643 CLEARWATER, FL 33762 (877) 544-6679 (877) 530-0078 -SENSORMATIC/ADT SECURITY SERVICES -GE BURGLAR ALARMS, CCTV, ACCESS (LIGHTING) CONTROL, AND FIRE ALARMS 2700 HUTCHISON-MCDONALD RD ONE TOWN CENTER ROAD CHARLOTTE, NC 28269 BOCA RATON, FL 33486 GREG AUFDERHEIDE KERIANN WORLEY 704-597-6720 EXT 122 954-590-3083 ABBREVIATIONS A.F.F. ABOVE FINISHED FLOOR. GFCI GROUND FAULT CIRCUIT INTERRUPTING P.O.S. POINT OF SALES U, 0. N. UNLESS OTHERWISE NOTED W.P. WEATHERPROOF al i 11/22/17 2813E03 ROBERT L. HINKLE PE 29302 POWELL & HINKLE ENGINEERING, P.A. 1409 KINGSLEY AVENUE, BLDG 12A GALTON C. MOK PE 33192 P & H ORANGE PARK, FLORIDA 32073 LANt R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 ENGINEERING CORPORATION FLA. REG. EB-4577 THOMAS RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 r 0- N'0 .4 076 _ . STATE OF R. Wulbern L 6Architect PA .J O- AA - 0003433 Ile Wt0.1 (904)329-2510 tel. 0) U robart@wulbern.net. y Z w w F N O W U U5 0 12Lu z z a � Y Y 0 Lu IX m m C LL LL w ~ o O \ M N to 0 0 0 a n d > m w H s N � 1,0 O O 8 z 3' w U Z �c w — _ 0 U O 0 (l goldco q VERTI :`L O .FJ Ln ti 0 N z Q Q N .. 0) ILL Ict /z U Y o V1 @0 ro Z� W } 0 C) UL, C) H O Lr) w =OW� °_j pp J mc�z�� p Z W J L 3� Q U F- U J p Z Q w J w F- H w w U) E0iii,,,,,,,31 48"AFF 01 (0) 1 (b) (c) (d) 1-_1i 2 KITCHEN SERVE/ REST DINING CREW ROOMS ROOM 0 0 0 0 0 0 0 0 FLOOR ® SWITCHBANK DETAIL SCALE: N.T.S. ® DETAIL NOTES: 1. AREA LIGHTS SWITCH DESIGNATION, SEE 'ELEC LIGHTING PLAN' FOR CIRCUIT NUMBER. 2. PROVIDE ABOVE FACEPLATE LAMINATED PHENOLIC STRIP 1/16" THICK AND ENGRAVED TO SHOW BLACK LETTERS ON WHITE BACKGROUND WITH NOT LESS THAN 1/4" HIGH LETTERS. 3. PROVIDE 3-WAY SWITCHES AS REQUIRED. �I WP 11 17' I K J EMX K I 27' NING R' IGO A nn- GO I I - -r I I I , M r--- -----� II I I I I M I I � I I L G TO $30 )_ WOMEN F� 0 RED LIGHT BAND FIXTURE "F" POINT OF CONNECTION) FOR RED PARAPET LIGHT. PROVIDE #10 WIRE NOTES: 1. VERIFY POINT OF CONNECTIONS AND CIRCUITING REQUIREMENTS FOR THE LIGHT BAND WITH THE SIGN MANUFACTURER. 2. PARAPET LIGHT BAND DIMENSIONS TO BE VERIFIED IN FIELD BY SIGN MANUFACTURER. 3. LOCATION OF SIGN JUNCTION BOX PER SIGN MANUFACTURERS REQUIREMENTS. RED LIGHT BAND FIXTURE "F" --- 21 0't " 16'-0t J WP J II --. .........r. ----------1 r� ------------------- II I A-25 485-rO" f RED LIGHT BAND FIXTURE "F" ® ELECTRICAL LIGHTING PLAN SCALE: 1/4" ® KEYED NOTES: 1. SWITCH BANK: REFERENCE DETAIL #1, THIS SHEET. 2. WIRE WALL PACKS THROUGH PHOTO CELL AND MASTER CONTACTOR PANEL. ELECTRICAL CONTRACTOR TO PROVIDE "PARAGON" PHOTOCELL CW 201-00 MOUNTED ON ROOF FACING NORTH. MAKE ADJUSTMENTS FOR ANY AMBIENT LIGHT. 3. PROVIDE HARDWARE FOR INSTALLATION IN GYPSUM BOARD CEILINGS. 4. ELECTRICAL CONTRACTOR TO COORDINATE WITH THE DRIVE THROUGH SIGN SUPPLIER FOR EXACT ELECTRICAL REQUIREMENTS. 5. REFER TO 'ELEC POWER PLAN' FOR CONTINUATION OF MENU BOARD DATA, POWER, S°�"° D°"NECTIDNS. LIGHTING FIXTURE NOTES 1. ALL LIGHTING FIXTURES SHALL BE 120 VOLT UNLESS NOTED OTHERWISE. 2. CONTRACTOR SHALL FURNISH AND INSTALL IN -LINE FUSE HOLDER AND FUSES IN ALL BALLASTED LIGHTING FIXTURES. GENERAL NOTES: 3. CONTRACTOR SHALL CHECK AND VERIFY FIXTURE QUANTITY AND MAKE PROPER ADJUSTMENTS FOR ANY CHANGES IN PLAN SHOWN DUE TO ADDITIONAL REQUIREMENTS SUCH AS VESTIBULES, LOCAL A. REFER TO ELECTRICAL LEGEND, SCHEDULES AND DIAGRAMS SHEET FOR LIGHT FIXTURE 4. CODES, ETC. SEE ELEC SITE PLAN FOR AREA LIGHTING POLES SPECIFICATIONS SPECIFICATIONS. AND DETAILS. B. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION AND MOUNTING 5. WHENEVER APPLICABLE, THE INCANDESCENT LIGHTING FIXTURES HEIGHTS OF LIGHT FIXTURES. COORDINATE FIXTURE LOCATIONS WITH DECOR SUPPLIER. SHALL BE FURNISHED WITH ENERGY EFFICIENT, SELF -BALLASTED C. ALL WORK AND MATERIALS SHALL BE BY THE ELECTRICAL CONTRACTOR UNLESS NOTED LED LAMPS. OTHERWISE. 6. PROVIDE DAYLIGHT HARVESTING SENSOR(S) AS REQUIRED BY CODE. D. MC CABLE ONLY PERMITTED FOR LIGHT WHIPS. ALL OTHER TO BE E.M.T CONDUIT IN MOUNT SENSOR(S) 7'-0" (+/- 12") FROM WINDOWS AND CEILING AND WALLS -RIGID CONDUIT UNDER SLAB. CONNECT TO SWITCHED LEG WHICH CONTROLS ALL LIGHT FIXTURES E. PROVIDE JUNCTION BOXES AT LIGHT FIXTURES PER MANUFACTURERS REQUIREMENTS. WITHIN THIS SPACE. ADJUST LIGHT SENSITIVITY TO AUTOMATICALLY (TYPICAL FOR ALL LIGHTING FIXTURES). DIM FIXTURES WHEN SPACE REACHES 50 OR MORE FOOT CANDLES. F. WHERE TRUSSES ARE EXPOSED, RUN ALL ELECTRICAL CONDUITS ABOVE THE BOTTOM VERIFY/PROVIDE CONNED LIGHT FIXTURES WITH COMPATIBLE CHORD OF THE TRUSS. DIMMING CAP LITIEJ (//►� `1 V FILE COPo " ® � V�3/26/18 J` 2813E11 POWELL & HINKLE ENGINEERING, P.A. ROBERT L, HINKLE PE 29302 1409 KINGSLEY AVENUE, BLDG 12A GALTON C, MOK PE 33192 P & H ORANGE PARK, FLORIDA 32073 LANE R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS M. ELDER PE 56121 ENGINEERING CORPORATION FLA. REG. EB-4577 RICHARD A. MATHEWS PE 59418 DAVID R. SPELL JR. PE 54729 II i EMX ` A-27 L] K G EMX 1 SWITCHBIyANK (TYP �,0� 2) N II K 1 _0111 K BELOW CANOPY _. . I K II I I , II , ' K I I DRIVE THRU MENU BOARD (SEE SITE PLAN) A-15 A - ORDER CONFIRI (SEE SI DRIVE THRU — PREVIEW BOARD (SEE SITE PLAN) R. Wulbern Architect PA T6 AA .0003433 Ile . w U (904)329.2510 tel . N 0 robert@wulbern.net a .a .0 O d c a> c m d C c � L N > t= 0, 0 L0) N A C N 0 0 N C 2) CD N � �c M m 00) m N N -0 c rn c �N pl 21,55 �a) a u 2 Q 0 c 0 a c m `w L E c d E "r rn in P_ >W to U W Z N �d cm (L <uj C7 C7 OLu Ow m m IL w ~Q m O O N 0 0 0 1 CC W v^ N m H A M O O o Z cm W F- U Z Y W m UQD O d 0 w x z a LL LL } J U LL w a 3 m U x O U. a rx- x w x 0 ua 0 a w w 0 O z z z 0 U. F- a a z w O J x 3 z 0 w U O Lu O 0 oI to D w m 0 z a 0 z w 0 LL z O U co z O w w x 0 w z z 0 U 0 Q E 1 1